ORO OXYGEN CORPORATION

website: www.prycegas.com

MONTALBAN, RIZAL
INSULATION RESISTANCE AND CONTINUITY TEST REPORT
24-July-18
INSULATION RESISTANCE TEST ON MOTOR CONTROL AND PANELS INSTALLED ON THE PLANT

CONTINUITY TEST
INSULATION TEST (MEGA OHMS)
(MEGA OHMS)
value must be 0 to 10 MΩ ( ideally = 0 ) value must be greater than 5MΩ
LOCATION CIRCUIT BREAKER WIRE USED L1 TO L2 L2 TO L3 L3 TO L1 L1 TO GRND L2 TO GRND L3 TO GRND
MAIN BREAKER 200 AT 60.00 mm ² 0 0 0 --------- --------- ---------
SUB MAIN 100 AT 38 mm ² 0 0 0 0.05 MΩ 0.08 MΩ 0.07 MΩ
AIR COMPRESSOR 60 AT 14 mm ² 0 0 0 54 MΩ 55 MΩ 55 MΩ
LPG PUMP 1 60 AT 14 mm ² 0 0.01 0.003 377 MΩ 372 MΩ 374 MΩ
LPG PUMP 2 60 AT 14 mm ² 0 0 0 175 MΩ 173 MΩ 175 MΩ
GAS COMPRESSOR 60 AT 14 mm ² 0 0 0 34 MΩ 35 MΩ 34 MΩ
ALL READINGS DONE WERE HOLD FOR AT LEAST 2 MINUTES DURATION AND AT A TEST VOLTAGE OF 250V.
ORO OXYGEN
Testing Company License No. 65652
CORP.
SANWA
Testing Instrument INSULATION Date 7/24/2018
TESTER MG1000
Test Method Direct Method Time 12nn to 2pm
PREPARED BY:
LESTER L. MUSCA
CORP. TSD ELECTRICAL
CHECKED BY; MARIO A. MACATOL
CORP. TSD HEAD

18TH Floor Pryce Center, 1179 Don Chino Roces Avenue cor. Bagtikan Street, Makati City, Philippines Tel. Nos. (02) 8994401