DC Inverter Commercial VRF

Heat Pump Type (JTOH-BS1 series)


Heat Recovery Type (JTOR-BS1 series)
1711-C-JTOH/R-BS1

2018 JOHNSON CONTROLS. INC.


Index
01 YORK® Brand Introduction

YORK® Brand Introduction 03

87
Outdoor Units

Indoor Units

109 Controllers

DC Inverter Commercial VRF


Heat Pump Type (JTOH-BS1 series)
Heat Recovery Type (JTOR-BS1 series)

The leader in VSD technology Inverter-driven


Air-cooled Screw Chiller
Driving innovation
A century of innovation for more than a century
Established in 1874 in York, Pennsylvania, YORK® has helped our
customers meet their temperature control needs for over a
century. Now a Johnson Controls brand, YORK® continues
to benefit customers through research that has gone on
to claim several significant firsts in design and innovation.
Johnson Controls is able to provide our customers with the best
temperature control solutions available around the world today.

Pioneer in inverter technology


Our customers can be assured that they will enjoy the benefits of
the latest technology when they choose a Johnson Controls
product, as YORK® has always been at the forefront of adopting
new technologies for their offerings. From being the first to offer a
low pressure VSD unit in 1979 to introducing the inverter Magnetic Bearing
technology in the 21 st century, YORK® has demonstrated its Variable Speed Centrifugal Chiller
pioneering spirit.

Leader in reliability
When constructing products, YORK ® places our customers’
needs as the top priority of our design process. Our inverter VRF
units are produced using state-of-the-art lean manufacturing
Inverter-driven
techniques, and rigorous quality testing is implemented at every
Water-cooled Screw Chiller
step of the manufacturing process, before they are shipped to
customers.

01 02
Outdoor Units

Outdoor Units
05 Heat Pump (JTOH-BS1 series)
Line-up Overview
Features and Benefits Overview
Design Flexibility
Adaptability
High Efficiency
Specifications

33 Heat Recovery (JTOR-BS1 series)


Line-up Overview
What is Heat Recovery System?
Features and Benefits Overview
Design Flexibility
Adaptability
High Efficiency
Specifications

Options
60 Heat Pump (JTOH-BS1 series)
Piping connection kit
Multi-kit
Drain Boss
Cabinet Cover

70 Heat Recovery (JTOR-BS1 series)


Piping connection kit
Multi-kit
CH-Box
Drain Boss
Cabinet Cover
03 04
Line-up Overview

Line-up Overview

JTOH-BS1 SERIES
Weight (N/W): in case of cabinet for “380V/60Hz”

Single module

1675mm

1675mm
1675mm
1675mm
1675mm

1675mm

5680mm 765mm 6070mm 765mm 6460mm 765mm

765mm 765mm 765mm


1210mm 1600mm 80HP class(224.0kW) : JTOH800VAEFBS1 1309kg 86HP class(241.0kW) : JTOH860VAEFBS1 1363kg 92HP class[258.0kW] : JTOH920VAEFBS1 1458kg
950mm
82HP class(230.0kW) : JTOH820VAEFBS1 1351kg 88HP class(246.0kW) : JTOH880VAEFBS1 1405kg 94HP class[263.0kW] : JTOH940VAEFBS1 1459kg
8HP class(22.4kW) : JTOH080VPEFBS1 190kg 14HP class(40.0kW) : JTOH140VPEFBS1 268kg 20HP class(56.0kW) : JTOH200VPEFBS1 350kg 84HP class(234.0kW) : JTOH840VAEFBS1 1352kg 90HP class(251.0kW) : JTOH900VAEFBS1 1406kg 96HP class[268.0kW] : JTOH960VAEFBS1 1460kg
10HP class(28.0kW) : JTOH100VPEFBS1 190kg 16HP class(45.0kW) : JTOH160VPEFBS1 310kg 22HP class(61.5kW) : JTOH220VPEFBS1 364kg
12HP class(33.5kW) : JTOH120VPEFBS1 210kg 18HP class(50.0kW) : JTOH180VPEFBS1 311kg 24HP class(67.0kW) : JTOH240VPEFBS1 365kg

Combination of single module Summary table


Current
Item Unit JTOH-BS1 series
(JVOH-AQ)

Capacity HP class 8-96 8-54


1675mm

1675mm

1675mm

Nominal Cooling Capacity kW 22.4 - 268.0 22.4 - 150.0

Nominal Heating Capacity kW 25.0 - 305.0 25.0 - 165.0


765mm 2440mm 765mm 2830mm 765mm
2180mm
26HP class(73.0kW) : JTOH260VAEFBS1 478kg 32HP class(90.0kW) : JTOH320VAEFBS1 579kg 38HP class(106.0kW) : JTOH380VAEFBS1 633kg Maximum Connectable Indoor Unit Quantity 64 64
28HP class(77.5kW) : JTOH280VAEFBS1 520kg 34HP class(95.0kW) : JTOH340VAEFBS1 621kg 40HP class(112.0kW) : JTOH400VAEFBS1 675kg
30HP class(85.0kW) : JTOH300VAEFBS1 521kg 36HP class(100.0kW) : JTOH360VAEFBS1 622kg 42HP class(118.0kW) : JTOH420VAEFBS1 676kg
Combination Capacity Ratio Between ODU and IDU % 50-130 50-130

Total Piping Length m (ft.) 1000 (3281) 1000 (3281)


1675mm
1675mm

1675mm

Maximum Piping Length Between ODU and IDU m (ft.) 165 (541) 165 (541)

Maximum Equivalent Piping Length Between ODU and IDU m (ft.) 190 (623) 190 (623)

3220mm 765mm 3670mm 765mm 4060mm 765mm Maximum Piping Length Between 1st Branch and IDU m (ft.) 90 (295) 90 (295)

44HP class(122.0kW) : JTOH440VAEFBS1 728kg 50HP class(140.0kW) : JTOH500VAEFBS1 890kg 56HP class(157.0kW) : JTOH560VAEFBS1 944kg
46HP class(128.0kW) : JTOH460VAEFBS1 729kg 52HP class(145.0kW) : JTOH520VAEFBS1 932kg 58HP class(162.0kW) : JTOH580VAEFBS1 986kg Maximum Height Difference Between ODU and IDU *
m (ft.) 110 (361) 50 (165)
48HP class(136.0kW) : JTOH480VAEFBS1 730kg 54HP class(150.0kW) : JTOH540VAEFBS1 933kg 60HP class(167.0kW) : JTOH600VAEFBS1 987kg (when ODU is higher than IDU)

Maximum Height Difference Between ODU and IDU


m (ft.) 40 (131) 40 (131)
(when IDU is higher than ODU)

Maximum Height Difference Between IDU and IDU m (ft.) 30 (98) 15 (49)
1675mm

-5 to 48 -5 to 43
1675mm

1675mm

Cooling Operation Range ** °C DB (°F)


(23 to 118) (23 to 109)

-20 to 15 -20 to 15
Heating Operation Range ** °C WB (°F)
(–4 to 59) (–4 to 59)
765mm
4450mm 765mm 765mm
4840mm
5290mm * Please consult your distributor or dealer if the height different is over 50m. The maximum piping length for 56 to 96HP class (JTOH-BS1) is 90m.
** For more details, please consult your distributors or dealer, or, refer to technical manuals
62HP class(174.0kW) : JTOH620VAEFBS1 998kg 68HP class(190.0kW) : JTOH680VAEFBS1 1093kg 74HP class(207.0kW) : JTOH740VAEFBS1 1255kg
64HP class(179.0kW) : JTOH640VAEFBS1 1040kg 70HP class(196.0kW) : JTOH700VAEFBS1 1094kg 76HP class(212.0kW) : JTOH760VAEFBS1 1297kg
66HP class(184.0kW) : JTOH660VAEFBS1 1041kg 72HP class(201.0kW) : JTOH720VAEFBS1 1095kg 78HP class(217.0kW) : JTOH780VAEFBS1 1298kg

05 06
Features and Benefits Overview

Features and Benefits Overview

FEATURES ADVANTAGES BENEFITS FEATURES ADVANTAGES BENEFITS


Heat pump VRF systems • Precisely heats or cools multiple zones • Provides extreme system design flexibility • In multiple-unit applications at partial load, outdoor • Optimizes efficiency
Rotational operation units operate alternately so that operating hours are • Extends service life
ODU Compact footprint • Requires less indoor space than conventional systems • Expands options for positioning outdoor units shared equally. • Increases reliability

• Provides flexibility to customize systems to each project’s • Simplifies design process • Allows one outdoor unit to be taken off-line for • Avoids system downtime
Modular components ODU Backup operation function
needs • Allows easy updates as space is reconfigured or expanded maintenance while remaining units keep operating. • Protects occupant comfort

Piping flexibility: with pipe runs up to 1000 • Suitable for short or long runs; accommodates nearly all Efficiency optimized for part-
• Allows design freedom System • APF cooling among industry’s highest for VRF systems • Saves energy
meter projects load operation

• Leads to both less piping length and lower installation cost • Heat pump systems deliver simultaneous heating and • Efficient heating/cooling
• Provides more options for outdoor units to be installed Optimum individualized comfort
Higher ESP: up to 80 Pa • Better efficiency cooling • Maximizes occupant comfort
inside building by using ducts
• Better visual aesthetics compared to outdoor installment
• Extremely quiet (24.5-28 dB for indoor units)
Noise reduction preference • Let users choose from three settings for a “not to
• Cooling Operation: [JTOH-BS1] -5°C to 48°C • Ideal where outdoor units are positioned on side of
Temperature Range • Allows design freedom mode exceed” sound level
Heating Operation: [JTOH-BS1] -20°C to 15°C building or in locations where there are noise restrictions
ARCHITECT
&
Silent Mode • Lower sound power/sound pressure level by Three steps • Meet the local limitations to sound level • Among industry’s most efficient VRF systems:
SYSTEM
DC inverter-driven scroll • Engineered to deliver the optimum efficiency at normal • Highest EER
DESIGNER
• Ultimate in design flexibility • Reduces system costs compressor load conditions • Highest APF
Non-ducted systems • Highest COP in low and high heating modes
• Reduces clearance between building floors • Ideal for historic renovations
Compressor
• Accommodates retrofits by making use of existing duct Newly introduced compressor
• New cover can shield up the compressor sound • Lower sound pressure level
infrastructure shield cover
Ducted systems • Reduces overall construction costs
• Suits unique buildings that include ducted and non-ducted
areas Compressor modulation in 0.1 Hz • Smoothly delivers only the exact amount of refrigerant • Allows fine control for optimum comfort
increments needed for the load • Saves energy
• Up to 130% for Combination Capacity [JTOH-BS1(8-54HP
Connectable IDU/ODU capacity ratio Up • Reduces system costs • Users can select from a wide variety of power settings
class)] • Limits electric demand charges
Demand control from 100% to 60% and program “not to exceed” a given • Limits equipment wear and tear
VRF Selection Software • Intuitive functionality that simplifies and speeds designs • Allows confident selection and right-sizing of systems power level • Reduces noise

H-LINK: original communication system to Corrosion-resistance improved /


• No connection boundary among RAC, PAC and VRF • Allows design freedom Protection layer of "Phosphoric • More reliable cabinet • Life of cabinet extended
control multiple ODUs and IDUs from one
• Flexible wiring routes • Reduces system costs acid chromate treatment" added
control point.

Smooth Drive: new compressor • Saves energy


• Controls compressor more efficiently
control operation system • Constant room temperature
BUILDING Outdoor Units
OWNER • Allows programming to turn units on/off in rotation at • Saves energy
Load shedding
10- to 20-minute intervals • Limits demand charges
FEATURES ADVANTAGES BENEFITS
• Ease of transportation leads to time/cost saving in • Improved compressor cover
Compact footprint • Requires less indoor space than conventional systems Low noise operation • More quiet operation
installation • Improved Fan + Fan-inlet structure

• [JTOH-BS1]9% lighter cabinet on average compared to • Ease of transportation leads to time/cost saving in • Heat exchange are increased by more than 10 % (single • Greater heat exchange rate
Lighter cabinet New Heat Exchanger (Σ shape!)
Current Model (JVOH-AQ) installation module) • More efficient operation

New Package of ODU • Easy to understand for craning • Reduces installation time and cost • Longer fan blades increase airflow quantity by 25%, • Operates more efficiently
New long blade propeller fan
resulting in higher static pressure • Extends motor life
•O
 utdoor unit piping can be connected from front, back or
underneath. As high as 200Pa static pressure • Offers adjustable speeds to match the static pressure
Installation simplicity • Reduces installation time and cost • Flexibility to accommodate long or short ductwork runs
•S
 mall and light indoor units are easy to handle without in ducted systems requirement
heavy equipment
Indoor Units Widest range of line-up • Meets any of your indoor requirement • keeps aesthetic
MECHANICAL
CONTRACTOR Comprehensive training •M
 odules tailored to specific job functions • Enables professional, high-quality, timely installation
Optional motion and radiant • Sets back temperature when space is unoccupied,
& • Saves energy
• Ensures correct components are delivered to job sites on • Enhances installation efficiency sensors increasing efficiency even further
INSTALLER Consistent, reliable product delivery
time • Allows efficient labor scheduling
• Controls multiple indoor and outdoor units from one
• Maximizes indoor comfort
• The upper panel (on the side of an electric box) control point
"H-LINK" Protocol • Saves energy
independently detached from the lower panel (on the • Adds versatility to connect various central control
• Improves system management
compressor chamber side) options
• All PCB visible and easily accessible including 7-segment
• Speeds up time spent on maintenance, repair, and Controls • Adjusts in 0.5/1 degree C increments • Auto-adjusts for daylight saving time
Easy maintenance access display Temperature control
troubleshooting • Adjustable fan speeds • Provides options to satisfy multiple projects/buildings
• More Space in lower section, easy access to compressors
and each valve
• Refrigerant evacuation: Enforced operation to open ODU • Enables control of VRF systems by way of a building • Optimizes comfort
H-LINK BACnet adapter for
EVO/EVB, IDU EVI, and Hi/Low pressure Bi-pass SVB management system (e.g. Metasys®) for almost unlimited • Saves energy
integration into BMS
control in a building of campus enterprise. • Unified interface for all HVAC systems
Improved Strength •R
 igidity ratio increased by 36.7% • Extends service life
Wide controllers line-up /
• Better management achieved thanks to our advanced
variety of individual controllers & • Meets any requirement for your application
controllers
centralized controllers

07 08
Design Flexibility

Design Flexibility

COMPACT EASY TRANSPORTATION

Smaller Lighter
JTOH-BS1 Can be transported in an
elevator by pallet jack Lift Crane
Combination comparison of outdoor unit up to... 800

JTOH-BS1:18HP class New


HP class 8 to 18 20 to 24 26 to 36 38 to 48 50 to 54 56 to 96
(50.0kW) New package
design to be
Current Model
- craned more
(JVOH-AQ)
easily
Single Module Two Units Two Units Three Units

New
New Model Three Units / 1210
(JTOH-BS1) Four Units

Single Module Single Module Two Units Two Units Three Units 765
1350

Single Module Capacity Expanded ! New Line-up up to 96HP!

New
Footprint Weight
-5.8%
on average
Current -9.2%
on average IMPROVED EXTERNAL STATIC PRESSURE
Current Current
New Model
model
New Model
model
High static pressure for outdoor units: can handle up to 80Pa

1,210mm(47 5/8inch) 1,600mm(63inch) Current Model New Model


1,920mm(75 3/5inch) 2,180mm(85 4/5inch) 4 Options
0Pa 60Pa available 0Pa 30Pa 60Pa 80Pa
Wall Wall Wall Wall

Duct (Field Supplied) Duct (Field Supplied) Duct (Field Supplied) Duct (Field Supplied)

offers more options for


Space the indoor installation of
24HP class
Current Current 38HP class
-27%
del New Model Current
New Model the outdoor unit
model model model
• Less piping length
5/8inch) 1,600mm(63inch) Weight 2,830mm(111 2/5inch) • Lower installation cost
mm(75 3/5inch) 2,180mm(85 4/5inch)

2 2
-28% 3,150mm(124inch) • Visual aesthetics

Space:1.67m 1.22m
Space:2.41m2 2.16m2
Weight:504kg 365kg Space Weight
Weight:743kg 633kg
-10% -15% Wall Outdoor
Wall Unit Outdoor Unit Wall WallOutdoor Unit Outdoor Unit

* Please refer to the technical catalogue for more details.


Current
New Model
model
Current
New Model
model
3,670mm(144 2/5inch)
4,380mm(172 11/25inch)
2,830mm(111 2/5inch)
3,150mm(124inch)

Current
New Model
model

3,670mm(144
09 2/5inch) 10
4,380mm(172 11/25inch)
Design Flexibility
WB

15°C

0
PIPING CONNECTION WORKABILITY OPERATION TEMPERATURE RANGE -20°C

-20°C
Improvement of restrictions on piping construction Expansion of scope of outdoor operating temperature
JTOH-BS1 series
Total piping length 1000m NOTES:
*Refer to the technical catalog for the detail. DB WB
Longest length actual (Equivalent) 165m (190m)

52°C
Longest length after first branch 90m
48°C

Up to 110m*
Higher ODU Standard 50m Optional 110m(*)
Level difference between ODU and IDU
Lower ODU 40m

Level difference between IDUs 30m

* Please consult your distributor or dealer if the height difference is over 50m.
* Longer piping (up to 110m) is available for 8 to 54HP models only.
Maximum piping length for 56-96HP(JTOH-BS1) is 90m. 15°C

• Suitable for a high- 30m

-5°C 0

0
-5°C
rise building or complex
facilities.
• Leads to cost/time saving -20°C

-20°C
for designers, with more 90m
efficient design. 165m
(Actual)

Cooling Heating

DB

Piping direction

52°C
The pipes can be installed in three directions (front, rear or bottom side) from the bottom base. IDU COMBINATIONS RANGE 48°C

Up to
Expansion of number of connectable indoor units 130%
For Piping from Front cover For Piping from Bottom base to Left, Right and Rear side
JTOH-BS1 series

Control Wiring
Cover gaps
with packings. Transition Wiring
(field-supplied) Liquid Pipe
Power Source 38HP class(106.0kW) 64 units at maximum
Wiring

-5°C 0
Gas Pipe
-5°C
Piping Cover Control Wiring Outdoor Unit Capacity_HP class 8 10 12 14 16, 18 20 22 24 26 28 30 32 34 36 38-54 56-96

Range of
Combination Capacity 50-130%: Standard Type (JTOH-BS1)
Transition
Wiring
Power Source Connectable Indoor Units Q'ty 13 16 19 23 26 33 36 40 43 47 50 53 56 59 64 64
Wiring Liquid Pipe Gas Pipe Cover gaps with
packings.
Recommended Connectable
(field-supplied) 8 10 16 18 20 26 32 38 38
Indoor Units Q'ty

NOTES:
1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity.
2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and
For more operating limit in overload operation.
3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit capacity is available up to 130% against the outdoor unit capacity.
service space 4. W hen operating the outdoor unit in cold areas with temperatures of -10°C, or under the high heating load conditions, the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping length
should be less than 300m.
in front. 5. The air flow volume for indoor units of 0.8 and 1.0HP is set higher than that for indoor units of 1.5HP or more. Make sure to select appropriate indoor units when installing indoor units where cold draft may occur during heating
operation. If installing indoor units in such places, refer to the recommended number of connectable indoor units.
6. For connecting Tempclean Indoor Unit and Outdoor Air Processing Air Conditioner, the number of the indoor units should be within recommended connectable indoor units number.
7. If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the possibility of insufficient capacity of 130% combination ratio. Refer to the technical catalog for the detail. If combination capacity exceed
130% contact your distributer or dealer.
image: front image: bottom 8. C ontact your distributer or dealer if the capacity of combination ratio exceed 130% . The system configuration exceed combination ratio of 130% without consultation with distributer or dealer is not acceptable. It may cause activation
of alarm and operation failure.

11 12
Adaptability

Adaptability

LOW NOISE OPERATION DEFROSTING


Thanks to below 2 design changes
Sound Power Level dB(A) Prevention More efficient defrosting
JTOH-BS1 series
Our VRF outdoor unit has “heat exchanger” in the lower part of the Thanks to original sensing function for heat-exchanger status, the
HP Class 8 10 12 14 16 20 22 24
heat exchanger which puts down the frost and ice formation in there, system for detecting the frost amount has improved very much, which
ODU capacity
Cooling (kW) 22.4 28.0 33.5 40.0 45.0 56.0 61.5 67.0 by running mid-temperature refrigerant (5-20°C) (before decreasing leads to the greatly efficient defrosting.
Sound Power Level (dB(A)) New model 80 82 82 85 85 86 84 86 the pressure). First, the maximum defrosting interval has been increased by more
than 200 %, from 120 mins (current) to 250mins (new).
Compressor: Air blower:
image It undertakes defrosting more efficiently, rather than unnecessary
The model is louder than conventional models due to the utilization The air blower has a new structure where it is placed above the
defrosting every two hours.
of a compact high-speed compressor, but it can reduce the level heat exchanger, meaning that the noise on the reverse side can be
And also, it leads to the more comfortable indoor environment by
of the sound pressure by up to 2dB(A) due to the utilization of new suppressed.
keeping more constant room temperature thanks to the longer heating
compressor covers.
duration.

New New
Cover Model cold frosting
warm

No Frost!
New Model hot

New Cover

SILENT MODE IMPROVED STRENGTH


The user can set a (three-step) nighttime low-noise schedule using Rigidity ratio (measured value) in the front and back direction :
Current Model (image) New Model (image)
the control unit remote controller**. The user can set a schedule for increased by 36.7%
operation that takes the ambient environment into account. Unstable Temperature More constant Temperature
More efficient
Setting example and

Heating
Power

Room
Temperature
Day Night Day comfortable
Heating Defrosting
Sound
on
Power
Level

Rigidity
86dB(A) 72.5dB(A) 86dB(A)
Nominal Step2 Nominal improved !
Heating duration
86dB(A) Nominal 72.5dB(A) Step2 more than 200%
longer
dB(A)
Improved!
14HP class[40.0kW] 42HP class(118.0kW) Time Time
Noise Reduction
Sound Power Level Sound Power Level on off on off on
mode
No cold air flow to Indoor
Nominal 86 89
Step1 82.5 86
thanks to automatic IDU stop
Step 2 77.5 81
image
Step3 72.5 76

*The range of performance and operation is limited, since the rotation frequency of
the compressor and ODU fan are forcibly decreased.
** in use of JCWB10NEWS and limited indoor units only. Please consult the dealer in inquiry.

13 14
Adaptability

TO PREVENT FAILURE AND EMERGENCY OPERATION IN CASE OF FAILURE MAINTENANCE EASE


Totally
To prevent failure Back up function Total structure change New!
Standardize the running time of the individual outdoor units Full introduction of backup operation function. If one outdoor unit
and distribute the load by rotating the order of operation of the should fail, the model can continue to operate using the remaining
compressors of the outdoor units. outdoor units, thereby preventing total system failure.
New Structure:
In upper section, all PCB visible and
easily accessible

Combined ODU
off on on
Newly adopted window for
7-segment display:
Adopting access door to the
electrical box in the upper panel,
which leads to easy access to
7-segment display, PSW & DSW
and so on.

open

Rotation
on on off on off on

New Panel:
The upper panel (on the
side of an electric box) can New DSW setting for
be independently detached Refrigerant evacuation:
from the lower panel (on the New Structure:
Enforced operation to open
compressor chamber side) More Space in lower section,
ODU EVO/EVB, IDU EVI, and
easy access to compressors or
Hi/Low pressure Bi-pass SVB
valves

CORROSION RESISTANCE (image)


See "Page 86: Resistance to Salt Damage"
Life-expectancy comparison
In salty-air-location After DSW4-4 On
New! Simplify
Corrosion-resistance improved Heat Exchanger
“refrigerant recovery
2 times
& evacuation work”
longer!
and “air tight test”
Hydrophilic ilm during servicing
Corrosion-resistant ilm fully opening the expansion valves
of outdoor unit (EVO, EVB) and
Phosphoric acid chromate treatment PSW4 ( ) the expansion valve of indoor unit
Aluminum fin 2 times (EVI), and opening the solenoid
for 3 seconds
longer! valve of outdoor unit (SVA)
Mechanical
Phosphoric acid chromate treatment
Contractor &
Corrosion-resistant ilm Installer
Hydrophilic ilm

Current : 2 Layers protection New : 3 Layers protection! Standard Anti-corrosive


Treatment
Heavy anti-
corrosive
Custom Order Treatment
*Considered JRA9002: Criteria and Testing of Corrosion-proof for Refrigeration and Air Conditioning Equipment against Salty Air Custom Order
*Please consult distributors for more details
*Both "Anti-corrosive treatment" and "Heavy anti-corrosive treatment" are by custom order

15 16
High Efficiency

High Efficiency

EFFICIENCY RATIO IMPROVED FAN POWER

Expansion of air outlets


JTOH-BS1
Current model New model
APF: Annual Performance Factor
APF
6.0 5.9 6.0
5.7 5.6 Twin-fan
5.5 5.5 5.5
5.2 5.4 5.4 5.3 5.5 5.2
5.5
5.1 5.0 4.9 5.1
High Efficiency of
4.5 Overall lineup,
with APF improved by
3.0
7 % on average.

1.5

6.07
0.0
6.00 6.00
5.44
8.0
5.10 5.04
10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
5.12 HP class Air outlets area
4.93 4.94 1211mm 1210mm
5.00 22.4 28.0 33.5
4.77 40.0 45.0 50.0 5.00
56.0 61.5 67.0 kW

4.00
NOTES:
4.55
4.174.10 4.11
4.00
Current New
4.32
4.09 3.96 Air volume area : 4403cm2 Air volume area : 6334cm2
+ 40%
3.58
APF (As Reference in the Japanese seasonal performance benchmark for VRF)
APF
3.00is meant for cooling/heating capacity per 1kW of operating power consumption under certain
3.00conditions throughout the year.
APF = Accumulated cooling/heating loads (kWh) / Accumulated power input in cooling/heating (kWh)
2.00 2.00
5.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 5.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 Improvement in bell-mouth
14.0 16.0 22.4 28.0 33.5 40.0 45.0 50.0 16.0 18.0 25.0 31.5 37.5 45.0 50.0 56.0

Current model New model

EER: Energy Efficiency Ratio COP: Coefficient Of Performance

5.21 5.34
5.11 4.94
5.00 4.76 4.90 5.00 Smoother
4.46
4.21 Narrower
4.15
3.93 4.10 4.09 3.92 3.84
air flow
4.00 3.70 3.75 4.00
3.55 3.43
3.00 3.00

Longer
2.00 2.00
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 HP class 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 HP class
22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 kW 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 77.5 kW

NOTES:
1. The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor units.
Less short
2. EER = Energy efficiency ratio = Cooling capacity or Heating capacity ÷ Power consumption of an air conditioner circuit !!
3. COP = Coefficient of performance of an air conditioner = Output KW (cooling capacity) ÷ Input KW (power consumption)

WHAT'S IMPROVED? • Improvement of airflow volume by 23% (single module)


• Energy consumption in the driving shaft has decreased by 20% on average
1) FAN 2) Heat Exchanger 3) Compressor 4) Compressor Control

17 18
High Efficiency

IMPROVED HEAT EXCHANGER IMPROVED COMPRESSOR

New shape New design compressor

Current model (single module) New single medium & Large cabinet

Fixed Scroll
Split left-right
heat exchanger
Pressure bypass valve The 13 colored parts are new!
Σ shape !
Orbiting Scroll
Oldham’s Coupling
Main Bearing
Thrust Bearing

Frame Seal Compressor performance


Crankshaft +4.6% improved
Counterweight APF
9.6
104.6%
Motor Rotor 9.4
9.2
Motor Stator 100.0%
New angle 9.0
8.8
8.6 8.98 9.39
Current model (single module) New single medium & Large cabinet Sub Bearing 8.4
8.2
8.0

Oil Pump Current model New model


Improved angle of
the curve

Greater capacity control Current model* New model*

The highly improved performance as well as


greater energy saving is achieved by adopting 100% 100% 15Hz ~ 100Hz 100% 100% 11Hz ~ 110Hz
newly developed high efficiency DC inverter 85 Steps 990 Steps
(by 1Hz) (by 0.1Hz)

Inverter Compressor

Inverter Compressor
compressor, with outstandingly precise control

Inverter Compressor

Inverter Compressor

Control Capacity

Control Capacity
Control Capacity

Control Capacity
technology of 0.1Hz increments inverter
frequency. Another feature is the dramatically
extended working range, enabled by expanding DC DC DC DC
the compressor’s operating frequency band, InverterInverter InverterInverter
Compressor
Compressor Compressor
Compressor
both upwards and downwards. 20% 20% 10% 10%
Max. Max. Load Load Min.
Cooling Cooling Min.
Max. Max. Cooling Cooling
Load Load Min. Min.
• The heat exchange area has been increased by more than 10% (single module)
*Example at 12HP class[33.5kW]
• Greater heat exchange efficiency

19 20
High Efficiency

IMPROVED COMPRESSOR CONTROL FOR BOTH YOU AND THE EARTH

Smooth drive Concept


Charge proper amount
Significant reduction of CO2 emissions
The model calculates the appropriate amount of refrigerant By reducing power consumption, we have CO2 emissions (for a 10HP class [28.0kW] equivalent system)
of coolant supplied by the outdoor units on significantly reduced CO 2 emissions and
the basis of information about the required Calculation of proper Refrigerant flow reduced the environmental impact. (Reduction 15 years ago Model JTOH-BS1 series About 4,982
About kg/year
5,188 kg/year
Piping
load from the individual indoor units. The refrigerant amount amount)
model employs smooth operation control New Model About 2,523 kg/year

to control the number of revolutions of the Reduction


inverter compressor. The model supplies the About 2,665 kg/year
appropriate amount of coolant to the indoor
All Inverter NOTE:
units according to the required load. The compressor IDU IDU 1. CO2 emissions are a trial calculation value based on JIS B 8616: 2015 (Tokyo office). The CO2 emissions coefficient is 0.534 kg-CO2/kWh.
2. Based on the end-use intensity of CO2 emissions (actual emission coefficient in FY 2014) specified by the Federation of Electric Power Companies.
model increases energy-saving efficiency 3. As reference in Japanese domestic model

by operating smoothly while controlling the Transmit Transmit


load load
switching on and off of the compressor at low- information information

load operation. ODU

Transmission Wire

Significant reduction of power consumption


By increasing the performance of air Comparison of seasonal power consumption (for a system equivalent to 10HP class [28.0kW])
blowers, heat exchangers and compressors
Actual example of the new compressor control
and improving compressor control, we 15 years ago Model JTOH-BS1 series 9,331 kWh/year

have significantly reduced annual power


Current model New model
consumption. (Comparison of power New Model 4,537 kWh/year

consumption during a specific period) Reduced by


Original! about 51
%

Room 30 Room 30
Temp Temp 0 1,000 2,000 3,000 4,000 5,000 6,000 7,000 8,000 9,000 10,000
(°C) (°C) (kWh/year)
25 25
NOTE:
Unstable Temperature Constant Room Temperature 1. Seasonal power consumption is a calculated value based on JIS B 8616: 2015 (Tokyo office), and it may vary depending on the area or usage conditions.
20 2. As reference in Japanese domestic model
20

15 15

10 10
Energy Consumption Loss
5 5 Smoother operation
Power
(kW) Power
0 (kW) 0
60 Time(mm) 120 180 60 120 180
Time(mm)

Room Temperature(°C)
Room Temperature(°C)
Power(kW)
Power(kW)

due to frequent switching on/off -40%


Going green saves money and the planet
operation energy consumption

21 22
Specifications

HP class 8 10 12 14 16 18

Model JTOH080VPE(U,F,R)BS1 JTOH100VPE(U,F,R)BS1 JTOH120VPE(U,F,R)BS1 JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1

Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 22.4 28.0 33.5 40.0 45.0 50.0

Nominal Heating Capacity kW 25.0 31.5 37.5 45.0 50.0 56.0

Color Munsell Code Natural Gray (1.0Y 8.5/0.5)


Cabinet
Outer Dimensions H*W*D mm 1,675 x 950 x 765 1,675 x 950 x 765 1,675 x 950 x 765 1,675 x 1,210 x 765 1,675 x 1,210 x 765 1,675 x 1,210 x 765

Sound Power Level dB(A) 80 82 82 85 85 86


Sound Level
Sound Pressure Level dB(A) 58 60 59 63 63 65

460V/60Hz kg 195 195 215 273 315 316

Net Weight 380V/60Hz kg 190 190 210 268 310 311

220V/60Hz kg 185 185 205 263 305 306


Weight
460V/60Hz kg 211 211 231 291 333 334

Gross Weight 380V/60Hz kg 206 206 226 286 328 329

220V/60Hz kg 201 201 221 281 323 324

Type R410A

Refrigerant Flow Control Micro-Computer Control Expansion Valve

Charge (before Shipment) kg 5.0 5.0 7.2 8.9 9.9 10.7

Type Hermetic (Scroll)

Specifications
AA50PHD + AA50PHD +
Model AA50PHD AA50PHD DC80PHD DC80PHD AA50PHD AA50PHD
Compressor
Quantity 1 1 1 1 2 2

Motor Output Pole kW 3.3 (6) 4.3 (6) 5.4 (6) 8.0 (6) 4.5 (6) x 2 5.0 (6) x 2

Type FVC68D
Refrigeration Oil
NOTES: Charge L/Unit 6.0 6.0 6.0 6.9 7.9 7.9
The cooling and heating performances are the values when combined with our
specified indoor units.
Cooling Operation Heating Operation Heat Exchanger Multi-Pass Cross-Finned Tube
Conditions Conditions
Indoor Air Inlet Temperature: Indoor Air Inlet Temperature:
o o o o
27 C DB (80 F DB) / 19.0 C WB (66.2 F WB) 20oC DB (68oF DB) Type Propeller Fan
Outdoor Air Inlet Temperature: Outdoor Air Inlet Temperature:
1 o o
35 C DB (95 F DB) 7oC DB (45oF DB) / 6oC WB (43oF WB) Quantity 1 1 1 2 2 2
Piping Length: 7.5 Meters(JTOH080~180VPE(U,F,R)BS1), 10.0 Meters Condenser Fan
(JTOH200~240VPE(U,F,R)BS1, JTOH260~300VAE(U,F,R)BS1), 12.5 Meters Air Flow Rate 3
m /min. 165 170 190 239 256 256
(JTOH320~440VAE(U,F,R)BS1), 15.0 Meters (JTOH460~560VAE(U,F,R)BS1), 17.5
Meters (JTOH580~720VAE(U,F,R)BS1), 20.0 Meters(JTOH740~840VAE(U,F,R)BS1),
22.5 Meters (JTOH860~960VAE(U,F,R)BS1) Motor Output Pole kW 0.26 (8) 0.28 (8) 0.42 (8) 0.33 (8) x 2 0.39 (8) x 2 0.39 (8) x 2
Piping Lift: 0 Meter
The sound pressure is based on the following conditions. Main Refrigerant Liquid Line mm (in.) φ9.52 (3/8) φ9.52 (3/8) φ12.7 (1/2) φ12.7 (1/2) φ12.7 (1/2) φ15.88 (5/8)
1 Meter from the unit service cover surface, and 1.5 Meters from floor level. Piping
The above data is based on the cooling mode. In case of heating mode, the sound
2
pressure level increases by approximately 1~2 dB. Heat Pump System Gas Line mm (in.) φ19.05 (3/4) φ22.2 (7/8) φ25.4 (1) φ25.4 (1) φ28.58 (1-1/8) φ28.58 (1-1/8)
The above data was measured in an anechoic chamber so that reflected sound (2 Pipes)
should be taken into consideration in the field.
Except for the specified combination in the table (26~96HP), there is no other
3 Dimensions H*W*D mm 1,800 x 1,030 x 810 1,800 x 1,030 x 810 1,800 x 1,030 x 810 1,800 x 1,290 x 810 1,800 x 1,290 x 810 1,800 x 1,290 x 810
combination of the base unit.
Package
The width of outer dimension, it is the value when each distance between the base
4
outdoor units is specified to 20mm. Measurement m3 1.5 1.5 1.5 1.9 1.9 1.9
The 11th digit of the model name indicate the power supply of each unit.
*T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

23 24
Specifications

HP class 20 22 24 HP class 26 28 30 32 34 36

Model JTOH200VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 Model JTOH260VAE(U,F,R)BS1 JTOH280VAE(U,F,R)BS1 JTOH300VAE(U,F,R)BS1 JTOH320VAE(U,F,R)BS1 JTOH340VAE(U,F,R)BS1 JTOH360VAE(U,F,R)BS1

Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz JTOH120VPE(U,F,R)BS1 JTOH120VPE(U,F,R)BS1 JTOH120VPE(U,F,R)BS1 JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
Combination of Base Unit JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
Nominal Cooling Capacity kW 56.0 61.5 67.0 Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Heating Capacity kW 63.0 69.0 77.5 Nominal Cooling Capacity kW 73.0 77.5 85.0 90.0 95.0 100.0

Color Munsell Code Natural Gray (1.0Y 8.5/0.5) Nominal Heating Capacity kW 82.5 90.0 95.0 100.0 106.0 112.0
Cabinet
Outer Dimensions H*W*D mm 1,675 x 1,600 x 765 1,675 x 1,600 x 765 1,675 x 1,600 x 765 Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet
Sound Power Level dB(A) 86 84 86 Outer Dimensions H*W*D mm 1,675 x 2,180 x 765 1,675 x 2,180 x 765 1,675 x 2,180 x 765 1,675 x 2,440 x 765 1,675 x 2,440 x 765 1,675 x 2,440 x 765
Sound Level
Sound Pressure Level dB(A) 65 64 66 Sound Power Level dB(A) 87 87 87 89 89 89
Sound Level
460V/60Hz kg 355 369 370 Sound Pressure Level dB(A) 64.5 64.5 66 67 67 68

Net Weight 380V/60Hz kg 350 364 365 460V/60Hz kg 215 + 273 215 + 315 215 + 316 273 + 316 315 + 316 316 + 316

220V/60Hz kg 345 359 360 Net Weight 380V/60Hz kg 210 + 268 210 + 310 210 + 311 268 + 311 310 + 311 311 + 311
Weight
460V/60Hz kg 375 389 390 220V/60Hz kg 205 + 263 205 + 305 205 + 306 263 + 306 305 + 306 306 + 306
Weight
Gross Weight 380V/60Hz kg 370 384 385 460V/60Hz kg 231 + 291 231 + 333 231 + 334 291 + 334 333 + 334 334 + 334

220V/60Hz kg 365 379 380 Gross Weight 380V/60Hz kg 226 + 286 226 + 328 226 + 329 286 + 329 328 + 329 329 + 329

Type R410A 220V/60Hz kg 221 + 281 221 + 323 221 + 324 281 + 324 323 + 324 324 + 324

Refrigerant Flow Control Micro-Computer Control Expansion Valve Type R410A

Charge (before Shipment) kg 11.3 11.3 11.6 Refrigerant Flow Control Micro-Computer Control Expansion Valve

Type Hermetic (Scroll) Charge (before Shipment) kg 16.1 17.1 17.9 19.6 20.6 21.4

Model AA50PHD + AA50PHD DC80PHD + DC80PHD DC80PHD + DC80PHD Type Hermetic (Scroll)
Compressor
AA50PHD + AA50PHD +
Quantity 2 2 2 DC80PHD + DC80PHD + DC80PHD +
DC80PHD + AA50PHD + AA50PHD +
Model AA50PHD + AA50PHD + AA50PHD +
DC80PHD AA50PHD + AA50PHD +
Motor Output Pole kW 5.5 (6) x 2 6.7 (6) x 2 7.1 (6) x 2 Compressor AA50PHD AA50PHD AA50PHD AA50PHD AA50PHD

Type FVC68D Quantity 2 3 3 3 4 4


Refrigeration Oil 5.4 (6) x 1 + 8.0 (6) 5.4 (6) x 1 + 4.5 (6) 5.4 (6) x 1 + 5.0 (6) 8.0 (6) x 1 + 5.0 (6) 4.5 (6) x 2 + 5.0 (6) 5.0 (6) x 2 + 5.0 (6)
Charge L/Unit 8.4 8.4 8.4 Motor Output Pole kW x1 x2 x2 x2 x2 x2
Type FVC68D
Heat Exchanger Multi-Pass Cross-Finned Tube Refrigeration Oil
Charge L/Unit 12.9 13.9 13.9 14.8 15.8 15.8
Type Propeller Fan
Heat Exchanger Multi-Pass Cross-Finned Tube
Quantity 2 2 2
Condenser Fan
Air Flow Rate m3/min. 329 329 348 Type Propeller Fan

Motor Output Pole kW 0.48 (8) x 2 0.48 (8) x 2 0.56 (8) x 2 Quantity 3 3 3 4 4 4
Condenser Fan
3
Main Refrigerant φ15.88 (5/8) φ15.88 (5/8) φ15.88 (5/8) Air Flow Rate m /min. 190 + 239 190 + 256 190 + 256 239 + 256 256 x 2 256 x 2
Liquid Line mm (in.)
Piping
0.42 (8) + 0.33 (8) x 0.42 (8) + 0.39 (8) x 0.42 (8) + 0.39 (8) x 0.33 (8) x 2 + 0.39 0.39 (8) x 2 + 0.39 0.39 (8) x 2 + 0.39
Motor Output Pole kW 2 2 2 (8) x 2 (8) x 2 (8) x 2
Heat Pump System Gas Line mm (in.) φ28.58 (1-1/8) φ28.58 (1-1/8) φ28.58 (1-1/8)
(2 Pipes)
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4)
Piping
Dimensions H*W*D mm 1,800 x 1,680 x 810 1,800 x 1,680 x 810 1,800 x 1,680 x 810
Package Heat Pump System Gas Line φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ38.1 (1-1/2)
mm (in.)
Measurement m3 2.4 2.4 2.4 (2 Pipes)

* The 11th digit of the model name indicates the power supply of each unit *T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

25 26
Specifications

HP class 38 40 42 44 46 48 HP class 50 52 54

Model JTOH380VAE(U,F,R)BS1 JTOH400VAE(U,F,R)BS1 JTOH420VAE(U,F,R)BS1 JTOH440VAE(U,F,R)BS1 JTOH460VAE(U,F,R)BS1 JTOH480VAE(U,F,R)BS1 Model JTOH500VAE(U,F,R)BS1 JTOH520VAE(U,F,R)BS1 JTOH540VAE(U,F,R)BS1
JTOH140VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
Combination of Base Unit Combination of Base Unit JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
JTOH240VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz
Nominal Cooling Capacity kW 106.0 112.0 118.0 122.0 128.0 136.0
Nominal Cooling Capacity kW 140.0 145.0 150.0
Nominal Heating Capacity kW 118.0 125.0 132.0 140.0 145.0 150.0
Nominal Heating Capacity kW 155.0 160.0 165.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Outer Dimensions H*W*D mm 1,675 x 2,830 x 765 1,675 x 2,830 x 765 1,675 x 2,830 x 765 1,675 x 3,220 x 765 1,675 x 3,220 x 765 1,675 x 3,220 x 765 Cabinet
Outer Dimensions H*W*D mm 1,675 x 3,670 x 765 1,675 x 3,670 x 765 1,675 x 3,670 x 765
Sound Power Level dB(A) 89 88 89 87 88 89
Sound Level Sound Power Level dB(A) 90 90 91
Sound Pressure Level dB(A) 68 67.5 68.5 67 68 69 Sound Level
Sound Pressure Level dB(A) 69 69 70
460V/60Hz kg 273 + 370 316 + 369 316 + 370 369 + 369 369 + 370 370 + 370
460V/60Hz kg 273 + 316 + 316 315 + 316 + 316 316 + 316 + 316
Net Weight 380V/60Hz kg 268 + 365 311 + 364 311 + 365 364 + 364 364 + 365 365 + 365
Net Weight 380V/60Hz kg 268 + 311 + 311 310 + 311 + 311 311 + 311 + 311
220V/60Hz kg 263 + 360 306 + 359 306 + 360 359 + 359 359 + 360 360 + 360
Weight 220V/60Hz kg 263 + 306 + 306 305 + 306 + 306 306 + 306 + 306
460V/60Hz kg 291 + 390 339 + 389 334 + 390 389 + 389 389 + 390 390 + 390 Weight
460V/60Hz kg 291 + 334 + 334 333 + 334 + 334 334 + 334 + 334
Gross Weight 380V/60Hz kg 286 + 385 329 + 384 329 + 385 384 + 384 384 + 385 385 + 385
Gross Weight 380V/60Hz kg 286 + 329 + 329 328 + 329 + 329 329 + 329 + 329
220V/60Hz kg 281 + 380 324 + 379 324 + 380 379 + 379 379 + 380 380 + 380
220V/60Hz kg 281 + 324 + 324 323 + 324 + 324 324 + 324 + 324
Type R410A
Type R410A
Refrigerant Flow Control Micro-Computer Control Expansion Valve
Refrigerant Flow Control Micro-Computer Control Expansion Valve
Charge (before Shipment) kg 20.5 22.0 22.3 22.6 22.9 23.2
Charge (before Shipment) kg 30.3 31.3 32.1
Type Hermetic (Scroll)
Type Hermetic (Scroll)
AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD +
DC80PHD + DC80PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD +
AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD + Model
Model DC80PHD + AA50PHD + AA50PHD AA50PHD + AA50PHD + AA50PHD AA50PHD + AA50PHD + AA50PHD
DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD +
Compressor DC80PHD Compressor
DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD
Quantity 5 6 6
Quantity 3 4 4 4 4 4
8.0 (6) x 1 + 7.1 (6) 5.0 (6) x 2 + 6.7 (6) 5.0 (6) x 2 + 7.1 (6) 6.7 (6) x 2 + 6.7 (6) 6.7 (6) x 2 + 7.1 (6) x 7.1 (6) x 2 + 7.1 (6) x Motor Output Pole kW 8.0 (6) x 1 + 5.0 (6) x 2 + 5.0 (6) x 2 4.5 (6) x 2 + 5.0 (6) x 2 + 5.0 (6) x 2 5.0 (6) x 2 + 5.0 (6) x 2 + 5.0 (6) x 2
Motor Output Pole kW x2 x2 x2 x2 2 2
Type FVC68D
Type FVC68D Refrigeration Oil
Refrigeration Oil Charge L/Unit 22.7 23.7 23.7
Charge L/Unit 15.3 16.3 16.3 16.8 16.8 16.8

Heat Exchanger Multi-Pass Cross-Finned Tube


Heat Exchanger Multi-Pass Cross-Finned Tube

Type Propeller Fan


Type Propeller Fan
Quantity 6 6 6
Quantity 4 4 4 4 4 4 Condenser Fan
Condenser Fan Air Flow Rate m3/min. 239 + 256 x 2 256 x 3 256 x 3
Air Flow Rate m3/min. 239 + 348 256 + 329 256 + 348 329 x 2 329 + 348 348 x 2
0.33 (8) x 2 + 0.56 0.39 (8) x 2 + 0.48 0.39 (8) x 2 + 0.56 0.48 (8) x 2 +0.48 0.48 (8) x 2 + 0.56 0.56 (8) x 2 + 0.56 Motor Output Pole kW 0.33 (8) x 2 + 0.39 (8) x 2 + 0.39 (8) x 2 0.39 (8) x 2 + 0.39 (8) x 2 + 0.39 (8) x 2 0.39 (8) x 2 + 0.39 (8) x 2 + 0.39 (8) x 2
Motor Output Pole kW (8) x 2 (8) x 2 (8) x 2 (8) x 2 (8) x 2 (8) x 2
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4)
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) Piping
Piping
Heat Pump System Gas Line mm (in.) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2)
Heat Pump System Gas Line (2 Pipes)
mm (in.) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2)
(2 Pipes)
*T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
* The 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

27 28
Specifications

HP class 56 58 60 62 64 66 HP class 68 70 72 74 76 78
Model JTOH680VAE(U,F,R)BS1 JTOH700VAE(U,F,R)BS1 JTOH720VAE(U,F,R)BS1 JTOH740VAE(U,F,R)BS1 JTOH760VAE(U,F,R)BS1 JTOH780VAE(U,F,R)BS1
Model JTOH560VAE(U,F,R)BS1 JTOH580VAE(U,F,R)BS1 JTOH600VAE(U,F,R)BS1 JTOH620VAE(U,F,R)BS1 JTOH640VAE(U,F,R)BS1 JTOH660VAE(U,F,R)BS1
JTOH140VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
JTOH140VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH140VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
Combination of Base Unit JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 Combination of Base Unit JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1
JTOH240VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 157.0 162.0 167.0 174.0 179.0 184.0 Nominal Cooling Capacity kW 190.0 196.0 201.0 207.0 212.0 217.0
Nominal Heating Capacity kW 213.0 220.0 225.0 232.0 237.0 244.0
Nominal Heating Capacity kW 176.0 181.0 188.0 196.0 202.0 207.0
Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Color Munsell Code Natural Gray (1.0Y 8.5/0.5) Cabinet
Cabinet Outer Dimensions H*W*D mm 1,675 x 4,840 x 765 1,675 x 4,840 x 765 1,675 x 4,840 x 765 1,675 x 5,290 x 765 1,675 x 5,290 x 765 1,675 x 5,290 x 765
Outer Dimensions H*W*D mm 1,675 x 4,060 x 765 1,675 x 4,060 x 765 1,675 x 4,060 x 765 1,675 x 4,450 x 765 1,675 x 4,450 x 765 1,675 x 4,450 x 765
Sound Power Level dB(A) 90 90 91 92 92 92
Sound Power Level dB(A) 90 90 91 90 90 91 Sound Level
Sound Level Sound Pressure Level dB(A) 69.5 70 71 71 71 71.5
Sound Pressure Level dB(A) 69.5 69.5 70 70 70 70.5 273 + 316 + 316 + 316 + 316 + 316 + 316 + 316 + 316 +
460V/60Hz kg 369 + 369 + 370 369 + 370 + 370 370 + 370 + 370
370 369 370
460V/60Hz kg 273 + 316 + 370 316 + 316 + 369 316 + 316 + 370 273 + 370 + 370 316 + 369 + 370 316 + 370 + 370 268 + 311 + 311 + 311 + 311 + 311 + 311 + 311 + 311 +
Net Weight 380V/60Hz kg 364 + 364 + 365 364 + 365 + 365 365 + 365 + 365 365 364 365
Net Weight 380V/60Hz kg 268 + 311 + 365 311 + 311 + 364 311 + 311 + 365 268 + 365 + 365 311 + 364 + 365 311 + 365 + 365 263 + 306 + 306 + 306 + 306 + 306 + 306 + 306 + 306 +
220V/60Hz kg 359 + 359 + 360 359 + 360 + 360 360 + 360 + 360 360 359 360
Weight
220V/60Hz kg 263 + 306 + 360 306 + 306 + 359 306 + 306 + 360 263 + 360 + 360 306 + 359 + 360 306 + 360 + 360 291 + 334 + 334 + 334 + 334 + 334 + 334 + 334 + 334 +
460V/60Hz kg 389 + 389 + 390 389 + 395 + 390 390 + 390 + 390
Weight 390 389 390
460V/60Hz kg 291 + 334 + 390 334 + 334 + 389 334 + 334 + 390 291 + 390 + 390 334 + 379 + 390 334 + 390 + 390 286 + 329 + 329 + 329 + 329 + 329 + 329 + 329 + 329 +
Gross Weight 380V/60Hz kg 384 + 384 + 385 384 + 385 + 385 385 + 385 + 385 385 384 385
Gross Weight 380V/60Hz kg 286 + 329 + 385 329 + 329 + 384 329 + 329 + 385 286 + 385 + 385 329 + 384 + 385 329 + 385 + 385 281 + 324 + 324 + 324 + 324 + 324 + 324 + 324 + 324 +
220V/60Hz kg 379 + 379 + 380 379 + 380 + 380 380 + 380 + 380 380 379 380
220V/60Hz kg 281 + 324 + 380 324 + 324 + 379 324 + 324 + 380 281 + 380 + 380 324 + 379 + 380 324 + 380 + 380 Type R410A
Refrigerant Flow Control Micro-Computer Control Expansion Valve
Type R410A
Charge (before Shipment) kg 34.2 34.5 34.8 41.9 43.4 43.7
Refrigerant Flow Control Micro-Computer Control Expansion Valve
Type Hermetic (Scroll)
Charge (before Shipment) kg 31.2 32.7 33.0 32.1 33.6 33.9 AA50PHD + AA50PHD +
DC80PHD +
DC80PHD + DC80PHD + DC80PHD + AA50PHD + AA50PHD +
Type Hermetic (Scroll) AA50PHD +
DC80PHD + DC80PHD + DC80PHD + AA50PHD + AA50PHD +
AA50PHD +
DC80PHD + DC80PHD + DC80PHD + AA50PHD + AA50PHD +
AA50PHD + AA50PHD + AA50PHD + AA50PHD + Model AA50PHD +
DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + AA50PHD + AA50PHD +
AA50PHD + AA50PHD + AA50PHD + AA50PHD + Compressor AA50PHD +
AA50PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + AA50PHD + AA50PHD +
AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD +
Model AA50PHD + DC80PHD + DC80PHD DC80PHD DC80PHD DC80PHD + DC80PHD +
AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD DC80PHD DC80PHD
Compressor DC80PHD + DC80PHD +
DC80PHD + DC80PHD + DC80PHD + DC80PHD +
DC80PHD DC80PHD
DC80PHD DC80PHD DC80PHD DC80PHD Quantity 6 6 6 7 8 8
Quantity 5 6 6 5 6 6 (6.7 (6) x 2) x 2+ 7.1 6.7 (6) x 2 + (7.1 (6) 8.0 (6) + (5.0 (6) x (5.0 (6) x 2) x 3 + (5.0 (6) x 2) x 3 + 7.1
Motor Output Pole kW (7.1 (6) x 2) x 3
(6) x 2 x 2) x 2 2) x 2 + 7.1 (6) x 2 6.7 (6) x 2 (6) x 2
8.0 (6) x 5.0 (6) x 2 (5.0 (6) x 2) x 2 + (5.0 (6) x 2) x 2 + 8.0 (6) + (7.1 (6) x 2) 5.0 (6) x 2 + 6.7 (6) 5.0 (6) x 2 + (7.1 (6)
Motor Output Pole kW + 7.1 (6) x 2 6.7 (6) x 2 7.1 (6) x 2 x2 x 2 + 7.1 (6) x 2 x 2) x 2 Type FVC68D
Refrigeration Oil
Type FVC68D
Charge L/Unit 25.2 25.2 25.2 31.1 32.1 32.1
Refrigeration Oil
Charge L/Unit 23.2 24.2 24.2 23.7 24.7 24.7
Heat Exchanger Multi-Pass Cross-Finned Tube
Heat Exchanger Multi-Pass Cross-Finned Tube
Type Propeller Fan
Type Propeller Fan
Quantity 6 6 6 8 8 8
Quantity 6 6 6 6 6 6 Condenser Fan 3
Air Flow Rate m /min. 329 + 329 + 348 329 + 348 x 2 348 x 3 239 + 256 x 2 + 348 256 x 3 + 329 256 x 3 + 348
Condenser Fan
Air Flow Rate m3/min. 239 + 256 + 348 256 + 256 + 329 256 + 256 + 348 239 + 348 + 348 256 + 329 + 348 256 + 348 + 348 0.33(8) x 2 + (0.39
(0.48 (8) x 2) x 2 + 0.48 (8) x 2 + (0.56 (0.39 (8) x 2) x 3 + (0.39 (8) x 2) x 3 +
Motor Output Pole kW (0.56 (8) x 2) x 3 (8) x 2) x 2 + 0.56
0.33 (8) x 2 + 0.39 (0.39 (8) x 2) x 2 + (0.39 (8) x 2) x 2 + 0.33 (8) x 2 + (0.56 0.39 (8) x 2 + 0.48 0.39 (8) x 2 + (0.56 0.56 (8) x 2 (8) x 2) x 2 0.48 (8) x 2 0.56 (8) x 2
Motor Output Pole kW (8) x 2
(8) x 2 + 0.56 (8) x 2 0.48 (8) x 2 0.56 (8) x 2 (8) x 2) x 2 (8) x 2 + 0.56 (8) x 2 (8) x 2) x 2
Main Refrigerant Liquid Line mm (in.) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4)
Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) Piping
Piping
Heat Pump System Gas Line mm (in.) φ44.45 (1-3/4) φ44.45 (1-3/4) φ44.45 (1-3/4) φ50.8 (2) φ50.8 (2) φ50.8 (2)
Heat Pump System Gas Line mm (in.) φ44.45 (1-3/4) φ44.45 (1-3/4) φ44.45 (1-3/4) φ44.45 (1-3/4) φ44.45 (1-3/4) φ44.45 (1-3/4) (2 Pipes)
(2 Pipes)
*T
 he 11th digit of the model name indicates the power supply of each unit
* The 11th digit of the model name indicates the power supply of each unit U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

29 30
Specifications

HP class 80 82 84 86 88 90 HP class 92 94 96
Model JTOH800VAE(U,F,R)BS1 JTOH820VAE(U,F,R)BS1 JTOH840VAE(U,F,R)BS1 JTOH860VAE(U,F,R)BS1 JTOH880VAE(U,F,R)BS1 JTOH900VAE(U,F,R)BS1 Model JTOH920VAE(U,F,R)BS1 JTOH940VAE(U,F,R)BS1 JTOH960VAE(U,F,R)BS1
JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH140VPE(U,F,R)BS1 JTOH160VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH220VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH180VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
Combination of Base Unit Combination of Base Unit
JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1 JTOH240VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 224.0 230.0 234.0 241.0 246.0 251.0 Nominal Cooling Capacity kW 258.0 263.0 268.0
Nominal Heating Capacity kW 254.0 261.0 267.0 275.0 282.0 287.0 Nominal Heating Capacity kW 293.0 299.0 305.0

Color Munsell Code Natural Gray (1.0Y 8.5/0.5) Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Cabinet
Outer Dimensions H*W*D mm 1,675 x 5,680 x 765 1,675 x 5,680 x 765 1,675 x 5,680 x 765 1,675 x 6,070 x 765 1,675 x 6,070 x 765 1,675 x 6,070 x 765 Outer Dimensions H*W*D mm 1,675 x 6,460 x 765 1,675 x 6,460 x 765 1,675 x 6,460 x 765

Sound Power Level dB(A) 92 92 92 92 92 92 Sound Power Level dB(A) 92 92 92


Sound Level Sound Level
Sound Pressure Level dB(A) 71 71 71.5 71.5 71.5 72 Sound Pressure Level dB(A) 72 71.5 72
273 + 316 + 370 + 315 + 316 + 370 + 316 + 316 + 370 + 273 + 370 + 370 + 315 + 370 + 370 + 316 + 370 + 370 + 460V/60Hz kg 369 + 369 + 370 + 370 369 + 370 + 370 + 370 370 + 370 + 370 + 370
460V/60Hz kg
370 370 370 370 370 370
268 + 311 + 365 + 310 + 311 + 365 + 311 + 311 + 365 + 268 + 365 + 365 + 310 + 365 + 365 + 311 + 365 + 365 + Net Weight 380V/60Hz kg 364 + 364 + 365 + 365 364 + 365 + 365 + 365 365 + 365 + 365 + 365
Net Weight 380V/60Hz kg 365 365 365 365 365 365
263 + 306 + 360+ 305 + 306 + 360+ 306 + 306 + 360+ 263 + 360 + 360 + 305 + 360 + 360 + 306 + 360 + 360 + 220V/60Hz kg 359 + 359 + 360 + 360 359 + 360 + 360 + 360 360 + 360 + 360 + 360
220V/60Hz kg Weight
360 360 360 360 360 360 460V/60Hz kg 389 + 389 + 390 + 390 389 + 390 + 390 + 390 390 + 390 + 390 + 390
Weight
291 + 334 + 390 + 333 + 334 + 390 + 334 + 334 + 390 + 291 + 390 + 390 + 333 + 390 + 390 + 334 + 390 + 390 +
460V/60Hz kg 390 390 390 390 390 390 Gross Weight 380V/60Hz kg 384 + 384 + 385 + 385 384 + 385 + 385 + 385 385 + 385 + 385 + 385
286 + 329 + 385 + 328 + 329 + 385 + 329 + 329 + 385 + 286 + 385 + 385 + 328 + 385 + 385 + 329 + 385 + 385 +
Gross Weight 380V/60Hz kg 220V/60Hz kg 379 + 379 + 380 + 380 379 + 380 + 380 + 380 380 + 380 + 380 + 380
385 385 385 385 385 385
281 + 324 + 380 + 323 + 324 + 380 + 324 + 324 + 380 + 281 + 380 + 380 + 323 + 380 + 380 + 324 + 380 + 380 + Type R410A
220V/60Hz kg 380 380 380 380 380 380
Type R410A Refrigerant Flow Control Micro-Computer Control Expansion Valve

Refrigerant Flow Control Micro-Computer Control Expansion Valve Charge (before Shipment) kg 45.8 46.1 46.4

Charge (before Shipment) kg 42.8 43.8 44.6 43.7 44.7 45.5 Type Hermetic (Scroll)
DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD +
Type Hermetic (Scroll) Model DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD +
AA50PHD + AA50PHD + AA50PHD + AA50PHD + Compressor DC80PHD + DC80PHD DC80PHD + DC80PHD DC80PHD + DC80PHD
DC80PHD + DC80PHD +
AA50PHD + AA50PHD + AA50PHD + AA50PHD + Quantity 8 8 8
AA50PHD + DC80PHD +
AA50PHD + AA50PHD + DC80PHD + DC80PHD +
AA50PHD + DC80PHD +
AA50PHD + AA50PHD + DC80PHD + DC80PHD +
Model DC80PHD + DC80PHD + Motor Output Pole kW (6.7 (6) x 2) x 2 + (7.1 (6) x 2) x 2 6.7 (6) x 2 + (7.1 (6) x 2) x 3 (7.1 (6) x 2) x 4
DC80PHD + DC80PHD + DC80PHD + DC80PHD +
Compressor DC80PHD + DC80PHD +
DC80PHD + DC80PHD + DC80PHD + DC80PHD +
DC80PHD + DC80PHD +
DC80PHD + DC80PHD + DC80PHD + DC80PHD + Type FVC68D
DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD Refrigeration Oil
Quantity 7 8 8 7 8 8 Charge L/Unit 33.6 33.6 33.6

8.0 (6) + 5.0 (6) x 2 4.5 (6) x 2 + 5.0 (6) (5.0 (6) x 2) x 2 + 8.0 (6) + (7.1 (6) x 2) 4.5 (6) x 2 + (7.1 (6) 5.0 (6) x 2 + (7.1 (6)
Motor Output Pole kW Heat Exchanger Multi-Pass Cross-Finned Tube
+ (7.1 (6) x 2) x 2 x 2 + (7.1 (6) x 2) x 2 (7.1 (6) x 2) x 2 x3 x 2) x 3 x 2) x 3
Type FVC68D
Refrigeration Oil Type Propeller Fan
Charge L/Unit 31.6 32.6 32.6 32.1 33.1 33.1
Quantity 8 8 8
Condenser Fan
Heat Exchanger Multi-Pass Cross-Finned Tube Air Flow Rate 3
m /min. 329 x 2 + 348 x 2 329 + 348 x 3 348 x 4

Type Propeller Fan Motor Output Pole kW (0.48 (8) x 2) x 2 + (0.56 (8) x 2) x 2 0.48 (8) x 2 + (0.56 (8) x 2) x 3 (0.56 (8) x 2) x 4

Quantity 8 8 8 8 8 8 Main Refrigerant Liquid Line mm (in.) φ25.4 (1) φ25.4 (1) φ25.4 (1)
Piping
Condenser Fan 3
Air Flow Rate m /min. 239 + 256 + 348 x 2 256 + 256 + 348 x 2 256 x 2 + 348 x 2 239 + 348 x 3 256 + 348 x 3 256 + 348 x 3 Heat Pump System Gas Line mm (in.) φ50.8 (2) φ50.8 (2) φ50.8 (2)
0.33 (8) x 2 + 0.39 0.39 (8) x 2 + 0.39 (2 Pipes)
(0.39 (8) x 2) x 2 + 0.33 (8) x 2 + (0.56 0.39 (8) x 2 + (0.56 0.39 (8) x 2 + (0.56
Motor Output Pole kW (8) x 2 + (0.56 (8) x (8) x 2 + (0.56 (8) x (0.56 (8) x 2) x 2 (8) x 2) x 3 (8) x 2) x 3 (8) x 2) x 3
2) x 2 2) x 2 *T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz
Main Refrigerant Liquid Line mm (in.) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ22.2 (3/4) φ25.4 (1)
Piping

Heat Pump System Gas Line mm (in.) φ50.8 (2) φ50.8 (2) φ50.8 (2) φ50.8 (2) φ50.8 (2) φ50.8 (2)
(2 Pipes)

* The 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

31 32
Line-up Overview

Line-up Overview

JTOR-BS1 SERIES Summary table

Weight (N/W): in case of cabinet for “380V/60Hz” New Current


Item Unit
JTOR-BS1 series (JVOR-AQ)

Single module Capacity HP class 8-54 8-54

Nominal cooling capacity kW 22.4 - 150.0 22.4 - 150.0

1675mm
Nominal heating capacity kW 25.0 - 165.0 25.0 - 165.0
1675mm

1675mm

Maximum connectable indoor unit quantity 64 64

765mm 765mm 765mm


950mm 1210mm 1600mm Combination capacity ratio between ODU and IDU % 50-130 50-130

8HP class(22.4kW) : JTOR080VPEFBS1 195kg 14HP class(40.0kW) : JTOR140VPEFBS1 271kg 20HP class(56.0kW) : JTOR200VPEFBS1 355kg
10HP class(28.0kW) : JTOR100VPEFBS1 195kg 16HP class(45.0kW) : JTOR160VPEFBS1 314kg 22HP class(61.5kW) : JTOR220VPEFBS1 369kg
12HP class(33.5kW) : JTOR120VPEFBS1 215kg 18HP class(50.0kW) : JTOR180VPEFBS1 315kg 24HP class(67.0kW) : JTOR240VPEFBS1 370kg Total piping length m (ft.) 1000 (3281) 1000 (3281)

Combination of single module


Maximum piping length between ODU and IDU m (ft.) 165 (541) 165 (541)

Maximum equivalent piping length between ODU and IDU m (ft.) 190 (623) 190 (623)
1675mm

1675mm

1675mm

Maximum piping length between 1st branch and IDU m (ft.) 90 (295) 90 (295)

765mm 2440mm 765mm 2830mm 765mm


2180mm Maximum height difference between ODU and IDU *
m (ft.) 110 (361) 50 (165)
26HP class(73.0kW) : JTOR260VAEFBS1 486kg 32HP class(90.0kW) : JTOR320VAEFBS1 586kg 38HP class(106.0kW) : JTOR380VAEFBS1 641kg (when ODU is higher than IDU)
28HP class(77.5kW) : JTOR280VAEFBS1 529kg 34HP class(95.0kW) : JTOR340VAEFBS1 629kg 40HP class(112.0kW) : JTOR400VAEFBS1 684kg
30HP class(85.0kW) : JTOR300VAEFBS1 530kg 36HP class(100.0kW) : JTOR360VAEFBS1 630kg 42HP class(118.0kW) : JTOR420VAEFBS1 685kg
Maximum height difference between ODU and IDU
m (ft.) 40 (131) 40 (131)
(when IDU is higher than ODU)

Maximum height difference between IDU and IDU m (ft.) 15 (49) 15 (49)
1675mm

1675mm

-5 to 48 -5 to 43
Cooling Operation Range ** °C DB (°F)
(23 to 118) (23 to 109)

-20 to 15 -20 to 15
765mm 765mm Heating Operation Range ** °C WB (°F)
3220mm 3670mm (–4 to 59) (–4 to 59)

44HP class(122.0kW) : JTOR440VAEFBS1 738kg 50HP class(140.0kW) : JTOR500VAEFBS1 901kg


46HP class(128.0kW) : JTOR460VAEFBS1 739kg 52HP class(145.0kW) : JTOR520VAEFBS1 944kg -5 to 24°C DB -5 to 24°C DB
48HP class(136.0kW) : JTOR480VAEFBS1 740kg 54HP class(150.0kW) : JTOR540VAEFBS1 945kg Simultaneous cooling and heating operation range *** °C
-6 to 15°C WB -6 to 15°C WB

* Please consult your distributor or dealer if the height different is over 50m.
** For more details, please consult your distributors or dealer, or, refer to technical manuals.
*** Upper: mainly cooling / Lower: mainly heating for more details, please consult your distributors or dealer, or, refer to technical manuals.

33 34
What is Heat Recovery System ?

What is Heat Recovery System ? RECOMMENDED APPLICATIONS

Heat Pump system and Heat Recovery system Nursing home in all season

Heat Pump VRF systems are two-pipe systems


Multi CH
that enable design for non-ducted or ducted
applications. Precise heating or cooling is

2
Single-Port
Merit 1: Waste
delivered to multiple zones. pipe CH-Box
Heat utilization
system Cooling Heating

Heat Pump system


corridor

Heat Recovery system able to individual


heating and cooling simultaneously along
each room's requirement.

Restaurant in shoulder season

Heat recovery VRF systems are three-pipe systems that also Merit 2: Auto cool / Heat operation in IDU
enable design for non-ducted or ducted applications. Precise

3
heating and cooling is delivered with an extra measure of
pipe flexibility, since the system can provide simultaneous heating
Single CH Single CH Single CH Single CH

system and cooling while transferring any excess heat or cooling


Heat Recovery system from one zone to another. Cooling Heating Cooling

In AUTO mode, by thermistor built in IDU air


inlet or RCS, IDU check the gap between the
Merits in Heat Recovery system current temperature and set-point, which
leads to the great comfortability and energy
saving as well.
Refrigeration room

Multi-Port CH-Box
3 With or Without
CH-Box
In one heat recovery system,
Office in winter season
cooling-only IDU is also utilized
1 Waste Heat by without going though CH-Box.
utilization
Heat Recovery system can Single CH Single CH
transfer the excess heating/
cooling from one zone to
another, which leads to higher Merit 3: Annual
energy efficiency.
Cooling cooling installed Heating Heating
in Heat recovery

2 Auto Cool/Heat system


operation in IDU Cooling-only IDU is also utilized in the
With a remote controller in a
zone, constant desired zone heating recovery system, which is useful for
temperature can be achieved small server room for offices.
by switching between heating Heating Heating Heating Cooling Cooling
and cooling automatically. Server room

35 36
Features and Benefits Overview

Features and Benefits Overview

FEATURES ADVANTAGES BENEFITS FEATURES ADVANTAGES BENEFITS


• Allows simultaneous heating/cooling • Maximizes comfort and efficiency • In multiple-unit applications at partial load, outdoor • Optimizes efficiency
Heat recovery systems • Allows transfer of excess heat/cooling from one zone to another • Maximizes design flexibility Rotational operation units operate alternately so that operating hours are • Extends service life
• Cooling only IDU can be included • Increases occupant comfort to specified zones shared equally. • Increases reliability
• Multi-Port CH-Box (up to 16 ports)
• Allows one outdoor unit to be taken off-line for • Avoids system downtime
• Liquid-piping built-in design Backup operation function
maintenance while remaining units keep operating. • Protects occupant comfort
• No drain-piping needed • Allows design freedom
New CH-Box
• Top-in-class compact body • Reduces system costs
Efficiency optimized for part-
• Top-in-class lightweight unit • APF cooling among industry’s highest for VRF systems • Saves energy
load operation
• Height difference between CH-Box to IDU extended up to 40m
System
ODU Compact footprint • Requires less indoor space than conventional systems • Expands options for positioning outdoor units • Heat recovery systems deliver simultaneous heating • Efficient heating/cooling
Optimum individualized comfort
and cooling • Maximizes occupant comfort
• Simplifies design process
Modular components ODU • Provides flexibility to customize systems to each project’s needs
• Allows easy updates as space is reconfigured or expanded • Extremely quiet (sound ratings as low as 50 dB for outdoor
Noise reduction preference • Let users choose from three settings for a “not to units; 24.5-28 dB for indoor units)
Piping flexibility: with pipe runs up to • Suitable for short or long runs; accommodates nearly all
• Allows design freedom mode exceed” sound level • Ideal where outdoor units are positioned on side of building
1000 meter projects
or in locations where there are noise restrictions
ARCHITECT • Leads to both less piping length and lower installation cost
& • Provides more options for outdoor units to be installed • Quieter operation sound • Lower sound pressure level
Higher ESP: up to 80 Pa • Better efficiency New CH-Box
SYSTEM inside building by using ducts • less expansion valve and no drain-piping • Maintenance Ease
• Better visual aesthetics compared to outdoor installment
DESIGNER
• Operates from -20℃ DB to 48℃ DB (JTOR-BS1 series) • Among industry’s most efficient VRF systems:
Temperature Range • Allows design freedom
• Heat Recovery Operates available: -5℃ DB to 24℃ DB DC inverter-driven scroll • Engineered to deliver the optimum efficiency at normal • Highest EER
compressor load conditions • Highest APF
Night Quiet Mode • Lower sound power/sound pressure level by Three steps • Meet the local limitations to sound level • Highest COP in low and high heating modes
• Ultimate in design flexibility • Reduces system costs Compressor
Non-ducted systems Newly introduced compressor
• Reduces clearance between building floors • Ideal for historic renovations • New cover can shield up the compressor sound • Lower sound pressure level
shield cover
•A ccommodates retrofits by making use of existing duct
Ducted systems infrastructure • Reduces overall construction costs Compressor modulation in 0.1 Hz • Smoothly delivers only the exact amount of refrigerant • Allows fine control for optimum comfort
• Suits unique buildings that include ducted and non-ducted areas increments needed for the load • Saves energy

Connectable IDU/ODU capacity ratio Up • Up to 130% for Combination Capacity (JTOR-BS1 series) • Reduces system costs • Users can select from a wide variety of power settings • Limits electric demand charges
VRF Selection Software • Intuitive functionality that simplifies and speeds designs • Allows confident selection and right-sizing of systems Demand control from 100% to 60% and program “not to exceed” a given • Limits equipment wear and tear
power level • Reduces noise
H-LINK: original communication system to
• No connection boundary among RAC, PAC and VRF • Allows design freedom Corrosion-resistance improved /
control multiple ODUs and IDUs from one BUILDING
• Flexible wiring routes • Reduces system costs Protection layer of "Phosphoric • More reliable cabinet • Life of cabinet extended
control point. OWNER
acid chromate treatment" added

Smooth Drive: new compressor • Saves energy


• Controls compressor more efficiently
control operation system • Constant room temperature
FEATURES ADVANTAGES BENEFITS
Outdoor Units
Compact footprint • Requires less indoor space than conventional systems • Ease of transportation leads to time/cost saving in installation • Allows programming to turn units on/off in rotation at • Saves energy
Load shedding
10- to 20-minute intervals • Limits demand charges
• Multi-Port CH-Box (up to 16 ports)
• Liquid-piping built-in design • Improved compressor cover
• No drain-piping needed • Ease of transportation Low noise operation • More quiet operation
New CH-Box • Improved Fan + Fan-inlet structure
• Top-in-class compact body • Time/cost saving in installation
• Top-in-class lightweight unit • Heat exchange are increased by more than 10 % • Greater heat exchange rate
• Less expansion valve (Single-Port) New Heat Exchanger (Σ shape!)
(compared to current model) • More efficient operation
• [JTOR-BS1]15% lighter cabinet on average compared to Current • Ease of transportation leads to time/cost saving in
Lighter cabinet • Longer fan blades increase airflow quantity by 25%, • Operates more efficiently
Model (JVOR-AQ) installation New long blade propeller fan
resulting in higher static pressure • Extends motor life
New Package of ODU • Easy to understand for craning • Reduces installation time and cost
As high as 200 Pa static pressure • Offers adjustable speeds to match the static pressure
• Flexibility to accommodate long or short ductwork runs
•O
 utdoor unit piping can be connected from front, back or in ducted systems requirement
underneath.
MECHANICAL Installation simplicity • Reduces installation time and cost
•S
 mall and light indoor units are easy to handle without Indoor Units Widest range of line-up • meets any of your indoor requirement • keeps aesthetic
CONTRACTOR heavy equipment
&
Optional motion and radiant • Sets back temperature when space is unoccupied,
INSTALLER • Saves energy
Comprehensive training • Modules tailored to specific job functions • Enables professional, high-quality, timely installation sensors increasing efficiency even further

• Controls multiple indoor and outdoor units from one


• Enhances installation efficiency • Maximizes indoor comfort
Consistent, reliable product delivery • Ensures correct components are delivered to job sites on time control point
• Allows efficient labor scheduling "H-LINK" Protocol • Saves energy
• Adds versatility to connect various central control
• Improves system management
•T he upper panel (on the side of an electric box) options
independently detached from the lower panel (on the
compressor chamber side) Controls • Adjusts in 0.5/1 ℃ increments • Auto-adjusts for daylight saving time
Temperature control
• All PCB visible and easily accessible including 7-segment display • Speeds up time spent on maintenance, repair, and • Adjustable fan speeds • Provides options to satisfy multiple projects/buildings
Easy maintenance access
•M ore Space in lower section, easy access to compressors troubleshooting
and each valve • Enables control of VRF systems by way of a building • Optimizes comfort
H-LINK BACnet adapter for
•R efrigerant evacuation: Enforced operation to open ODU management system (e.g. Metasys®) for almost • Saves energy
integration into BMS
EVO/EVB, IDU EVI, and Hi/Low pressure Bi-pass SVB unlimited control in a building of campus enterprise. • Unified interface for all HVAC systems

Improved Strength • Rigidity ratio increased by 36.7% • Extends service life Wide controllers line-up /
• Better management achieved thanks to our advanced
variety of individual controllers & • Meets any requirement for your application
controllers
centralized controllers

37 38
Design Flexibility

Design Flexibility

NEW CH-BOX (CHANGE-OVER BOX) Which is better?

Wider line-up ”Long narrow building” application

Type Single-Port Multi-Port Single-Port Multi-Port

Model Name JCH-AP160SSX JCH-AP280SSX JCH-AP04MSSX JCH-AP08MSSX JCH-AP12MSSX JCH-AP16MSSX


Much less copper
New New New New New New tube piping !!

Corridor
Corridor
Images

Room
Room
Dimensions (H*W*D) (mm) 191 × 301 × 214 191 × 301 × 214 260 × 303 × 352 260 × 543 × 352 260 × 783 × 352 260 × 1023 × 352

N/W (kg) 6 6 14 25 36 47

Power Supply 1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz


Single-Port Item Multi-port
Electrical
Power Input (W) 5 5 11.2 22.4 33.6 44.8 58m Total piping Length 136m
Details
Current (A) 0.1 0.1 0.2 0.4 0.6 0.8 6 Needed multi-kit sets 0
92 points (Brazing: 57 / Flare: 32) Connection Points 34 points (Brazing: 6 / Flare: 28)
Maximum Total Capacity Index (kW) 16 28 44.8 85 85 85
14 Hanging Rods for CH-Box 4
Number of port (for IDU) 1 1 4 8 12 16 14 pieces Total Ceiling Access Panel 8 pieces

Maximum Connectable IDUs per Port 7 8 6 6 6 6

Maximum
Total piping length between ”Central CH-Box location” application
CH-Box and each indoor unit 40m
Piping length
per branch
Single-Port Multi-Port
between CH-Box 15m
Maximum
Height Between CH-Box and IDU 15m Easier Installation !!!
difference - Less connection
between IDUs connecting to - Less hanging rods
4m
same CH-Box - Less ceiling access panel

System configuration
Single-Port Multi-Port
High/Low Pressure Gas

High/Low Pressure Gas

Multi-Port Single-Port Item Multi-Port


Low Pressure Gas

Low Pressure Gas

Single-Port Single-Port Single-Port Single-Port 60m Total piping Length 63m


6 Needed multi-kit sets 1
Liquid Gas

Liquid Gas

92 points (Brazing: 57 / Flare: 32) Connection Points 40 points (Brazing: 12 / Flare: 28)
14 Hanging Rods for CH-Box 8
14 locations Total Ceiling Access Panel 9 locations

Cooling Heating Cooling Heating


Cooling Heating Cooling Heating CH-Box merit

Multi-kit Flare Connection Brazing Connection Top-in-class compact body No drain connection needed
Top-in-class light-weight unit

More Design Flexibility Easier Installation

39 40
Design Flexibility

COMPACT EASY TRANSPORTATION

JTOR-BS1 Smaller Lighter


Can be transported in an
Combination comparison of outdoor unit elevator by pallet jack up Lift Crane
800
HP class 8 to 18 20 to 24 26 to 36 38 to 48 50 to 54 to...
JTOR-BS1:14HP class New
(40.0kW) New package
Current Model
(JVOR-AQ)
design to be
craned more
Single Module Two Units Two Units Three Units Three Units
easily

New
New Model
(JTOR-BS1)
1210
Single Module Single Module Two Units Two Units Three Units

765
1350
Single Module Capacity Expanded !

New
Footprint Weight
-5.8%
on average
Current -8.6%
on average
New Model
Current
model
New Model
Current
model IMPROVED EXTERNAL STATIC PRESSURE
1,210mm 1,600mm(63inch) High static pressure for outdoor units: can handle up to 80Pa
1,920mm 2,180mm(85 4/5inch)

Current Model New Model

4 Options
0Pa 60Pa available 0Pa 30Pa 60Pa 80Pa
Wall Wall Wall Wall

Space
24HP class
Current Current 38HP class Duct (Field Supplied) Duct (Field Supplied) Duct (Field Supplied) Duct (Field Supplied)
del
model
New Model
model
-27% New Model
Current
model offers more options for
mm 1,600mm(63inch) Weight the indoor installation of
2,830mm(111 2/5inch)
1,920mm 2,180mm(85 4/5inch)
-25% 3,150mm(124inch)
the outdoor unit
• Less piping length
Space:1.67m2 1.22m2
• Lower installation cost
Weight:505kg 379kg Space:2.41m2 2.16m2
Space • Visual aesthetics
Weight:752kg 641kg
Weight
-10% -15%
Current
New Model Wall Outdoor
Wall Unit Outdoor Unit Wall WallOutdoor Unit Outdoor Unit
Current model
New Model
model * Please refer to the technical catalogue for more details.
3,670mm(144 2/5inch)
2,830mm(111 2/5inch) 4,380mm(172 11/25inch)
3,150mm(124inch)

Current
New Model
model

3,670mm(144 2/5inch)
4,380mm(172 11/25inch)

41 42
Design Flexibility

WB

15°C

0
BETTER PIPING LIMIT Outdoor Outdoor Outdoor OPERATION TEMPERATURE RANGE
Unit A Unit B Unit C
-20°C

-20°C
Improvement of restrictions on piping construction Expansion of scope of outdoor operating temperature
Piping JTOR-BS1 series
Connection Kit H1
Example Length (m) Lc (DB) WB (heating main) (WB)
La Lb
DB WB WB
Total piping length - 1000 1st Branch

52°C
52°C
Multi Kit
Refrigerant piping length L1 165 (190) 48°C
Multi Kit
Between Piping connection kit and each ODU La, Lb, Lc 10
Maximum CH-Box
Piping Length
Between "1st branch Multi-kit" and the farthest IDU L2 90

Between "Multi-kit" and each IDU L3 40 15°C 15°C

L3 CH-Box
Total piping length Between CH-Box and IDU - 40
H6

0
-5°C 0

0
-5°C -6°C
H4 H2

-5°C
L1
Example Height (m)
Multi Kit
-20°C
Between ODUs (combination of base units) H1 0.1

-20°C
L2

ODU is higher than IDU ≤ 110 (*) H3


Between ODUs and IDUs H2
Maximum IDU is higher than ODU 40 CH-Box Cooling Cooling & Heating Heating
Height Simultaneous operation
DB
Difference Between IDUs H3 15
NOTES:

52°C
1. Cooling operation at maximum 48oC DB (for standard type) and 52oC DB (for high efficiency type) should be available only if the outdoor air inlet temperature increase temporarily according to the installation condition.
Between CH-Box H4 15 2. If install the units to the place where exceed ambient temperature 48oC continuously, the 48combination
°C ratio must be lower 130% and not to operate all of the indoor unit simultaneously.
H5 3. The cooling capacity is deteriorated at high ambient temperature. Select the larger capacity outdoor unit than compatible building heat load.
Between IDUs connecting to one CH-Box H5 4 4. The appropriate amount (100%) of refrigerant must be charged. Excessive charging of refrigerant is forbidden.
5. It must be avoided to install the units where affected by direct sunlight reflection and short circuit. There may be the possibility to activate protection control and alarm system if install the units to inappropriate place.
Between IDU and CH-Box H6 ≤ 15 Also the life time of the products and parts must be considerably shortened.
6. Periodic maintenance (1/certain month) must be applied to the heat exchanger fin to avoid adhesion of dirt and clogging of sand to the outdoor unit heat exchanger.
7. Refer to the technical catalog for the detail.
(*) Custom Order: up to 110m / Standard: up to 50m 8. operation temperature range in simultaneous heating & cooling varies depending on whether mainly heating or mainly cooling, Refer to technical catalogue for more detail.

Piping direction
IDU COMBINATIONS RANGE

-5°C 0
-5°C

The pipes can be installed in three directions (front, rear or bottom side) from the bottom base.
Up to
Expansion of number of connectable indoor units 130%
For Piping from Front cover For Piping from Bottom base to Left, Right and Rear side JTOR-BS1 series

Control Wiring Liquid Pipe


Cover gaps with packings (field-supplied). Cover gaps with packings (field-supplied).
Install accessory rubber bushes to the wiring outlets. High/Low Install accessory rubber bushes to the wiring outlets.
Transition Wiring
Pressure Gas Pipe 38HP class(106.0kW) 64 units at maximum
Control Wiring Power Source Control Wiring
Piping Cover Wiring Low Pressure Piping Cover
Gas Pipe
Transition Wiring Outdoor Unit Capacity_HP class 8 10 12
Transition14
Wiring 16 18 20 22 24 26 28 30 32 34 36 38-54

Cooling Capacity_kW 22.4 28.0 33.5 40.0 45.0 50.0 56.0 61.5 67.0 73.0 77.5 85.0 90.0 95.0 100.0 106.0-150.0
Low Pressure Low Pressure
Gas Pipe Gas Pipe
Power Source Power Source
Wiring Wiring
Range of
High/Low Pressure Cover gaps with packings (field-supplied).
Combination Capacity High/Low Pressure 50-130%: Standard Type (JTOR-BS1)
Gas Pipe Install accessory rubber bushes to the Liquid Pipe Gas Pipe
Liquid Pipe
wiring outlets.
Maximum Connectable
13 16 19 23 26 26 33 36 40 43 47 50 53 56 59 64
IDU Quantity

Recommended Connectable
8 10 10 16 16 16 18 20 26 26 32 32 32 32 32 38
IDU Quantity

NOTES:
For more 1. The connectable indoor unit capacity ratio can be calculated as follows.
Connectable Indoor Unit Capacity Ratio = Total Indoor Unit Capacity / Total Outdoor Unit Capacity.
service space 2. For the system under which all the indoor units are supposed to operate simultaneously, the total indoor unit capacity should be less than outdoor unit capacity. Otherwise, it may cause a decrease of operating performance and
operating limit in overload operation.
in front. 3. For the system under which all the indoor units are not supposed to operate simultaneously, the total indoor unit capacity is available up to 130% against the outdoor unit capacity.
4. W hen operating the outdoor unit in cold areas with temperatures of -10oC, or under the high heating load conditions, the total indoor unit capacity should be less than 100% against the outdoor unit capacity and the total piping length
should be less than 300m.
5. T
 he air flow volume for indoor units of 0.8 and 1.0HP is set higher than that for indoor units of 1.5HP or more. Make sure to select appropriate indoor units when installing indoor units where cold draft may occur during heating
operation. If installing indoor units in such places, refer to the recommended number of connectable indoor units.
image: front image: bottom 6. For connecting Tempclean Indoor Unit and Outdoor Air Processing Air Conditioner, the number of the indoor units should be within recommended connectable indoor units number.
7. If combination capacity of indoor units exceed 100% of outdoor unit capacity, there might be the possibility of insufficient capacity of 130% combination ratio. Refer to the technical catalog for the detail. If combination capacity exceed
130% contact your distributer or dealer.
8. C ontact your distributer or dealer if the capacity of combination ratio exceed 130% . The system configuration exceed combination ratio of 130% without consultation with distributer or dealer is not acceptable. It may cause activation
of alarm and operation failure.

43 44
Adaptability

Adaptability

Totally
AUTOMATIC COOLING / HEATING OPERATION MAINTENANCE EASE New!

Auto changeover
Total structure change
Just operate in AUTO mode and it can keep the room temperature
New Structure:
as constant as possible with “Automatic heating / cooling operation” In upper section, all PCB visible
and easily accessible
which makes the most of Heating Recovery system, leading to great
comfortability the energy savings as well. Newly adopted window for
7-segment display:
Adopting access door to the
Temperature Cooling electrical box in the upper panel,
which leads to easy access to
7-segment display, PSW & DSW
and so on.
open
+ T

Temperature
Set-point Cooling Heating
Sensing the indoor temperature New DSW setting for
can be by either Indoor unit Refrigerant evacuation:
Enforced operation to open
built-in thermostat, or, Individual New Panel: ODU EVO/EVB, IDU EVI, and
- T remote controller The upper panel (on the Hi/Low pressure Bi-pass SVB
side of an electric box) can New Structure:
be independently detached
More Space in lower section, easy
Time from the lower panel (on the
access to compressors or valves
compressor chamber side)
Cooling Fan Mode Heating Fan Mode Cooling

Indoor Temperature

After DSW4-4 On
Simplify
“refrigerant recovery &
evacuation work” and
SILENT MODE IMPROVED STRENGTH “air tight test” during
servicing
The user can set a (three-step) nighttime low-noise schedule using Rigidity ratio (measured value) in the front and back direction : fully opening the expansion valves
of outdoor unit (EVO, EVB) and
the control unit remote controller**. The user can set a schedule for increased by 36.7% PSW4 ( ) the expansion valve of indoor unit
(EVI), and opening the solenoid
operation that takes the ambient environment into account. for 3 seconds
valve of outdoor unit (SVA)
Mechanical
Setting example Contractor &
Installer
Day Night Day
Sound
Power
Level

Rigidity
86dB(A) 72.5dB(A) 86dB(A)
Nominal Step2 Nominal improved !

86dB(A) Nominal 72.5dB(A) Step2


TO PREVENT FAILURE AND EMERGENCY OPERATION IN CASE OF FAILURE
dB(A)
Improved! To prevent failure off on on
Back up function Combined ODU
JTOR-BS1 series 18HP class(50.0kW) 42HP class(118.0kW)

Noise Reduction
Standardize the running time Full introduction of backup
Sound Power Level Sound Power Level
mode of the individual outdoor operation function. If one outdoor
Nominal 86 89
units and distribute the load unit should fail, the model can
Step1 82.5 86 Rotation
by rotating the order of on on off on off on continue to operate using the
Step 2 77.5 81 image
operation of the compressors remaining outdoor units, thereby
Step3 72.5 76
of the outdoor units. preventing total system failure.
*The range of performance and operation is limited, since the rotation frequency of
the compressor and ODU fan are forcibly decreased.
** in use of JCWB10NEWS and limited indoor units only. Please consult the dealer in inquiry.

45 46
Adaptability

DEFROSTING LOW NOISE OPERATION

Prevention More efficient defrosting Thanks to below 2 design changes


Our VRF outdoor unit has “heat exchanger” in the lower part of the Thanks to original sensing function for heat-exchanger status, the Sound Power Level dB(A)
heat exchanger which puts down the frost and ice formation in there, system for detecting the frost amount has improved very much, which JTOR-BS1 series
by running mid-temperature refrigerant (5-20°C) (before decreasing leads to the greatly efficient defrosting.
HP Class 8 10 12 14 16
the pressure). First, the maximum defrosting interval has been increased by more ODU capacity
than 200 %, from 120 mins (current) to 250mins (new). Cooling (kW) 22.4 28.0 33.5 40.0 45.0

image It undertakes defrosting more efficiently, rather than unnecessary Sound Power Level (dB(A)) New model 80 82 82 85 85
defrosting every two hours.
And also, it leads to the more comfortable indoor environment by
Compressor: Air blower:
keeping more constant room temperature thanks to the longer heating
The model is louder than conventional models due to the utilization The air blower has a new structure where it is placed above the
duration.
of a compact high-speed compressor, but it can reduce the level heat exchanger, meaning that the noise on the reverse side can be
of the sound pressure by up to 2dB(A) due to the utilization of new suppressed.
cold frosting compressor covers.
warm
New New
No Frost! Cover Model
hot

Current Model (image) New Model (image) New Cover New Model

Unstable Temperature More constant Temperature


More efficient
and
CORROSION RESISTANCE
Room
Temperature
Heating
Power

comfortable (image)
Heating Defrosting See "Page 86: Resistance to Salt Damage"
on
Life-expectancy comparison
In salty-air-location
New!
Corrosion-resistance improved Heat Exchanger
2 times
Heating duration
longer!
more than 200%
longer Hydrophilic ilm
Corrosion-resistant ilm
Phosphoric acid chromate treatment
Time Time 2 times
Aluminum fin
on off on off on longer!
No cold air flow to Indoor Phosphoric acid chromate treatment
thanks to automatic IDU stop Corrosion-resistant ilm
Hydrophilic ilm

Current : 2 Layers protection New : 3 Layers protection! Standard Anti-corrosive


Treatment
Heavy anti-
corrosive
Custom Order Treatment
*Considered JRA9002: Criteria and Testing of Corrosion-proof for Refrigeration and Air Conditioning Equipment against Salty Air Custom Order
*Please consult distributors for more details
*Both "Anti-corrosive treatment" and "Heavy anti-corrosive treatment" are by custom order

47 48
High Efficiency

6.07
6.00 6.00
5.44
5.10 5.04 5.12
4.93 4.94
5.00 4.77 5.00

High Efficiency
4.55
4.17 4.10 4.11 4.32
4.09 3.96
4.00 3.58 4.00

3.00 3.00

2.00 2.00
5.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0 5.0 6.0 8.0 10.0 12.0 14.0 16.0 18.0
EFFICIENCY
14.0 RATIO
16.0 22.4 28.0 33.5 40.0 45.0 50.0 16.0 18.0 25.0 31.5 37.5 IMPROVED
45.0 50.0 FAN
56.0 POWER

Expansion of air outlets


JTOR-BS1
Current model New model
EER: Energy Efficiency Ratio
6.07
6.00 5.21 5.34
5.44 5.11 4.94
5.00 4.76 4.90 5.00
5.12 Twin-fan
4.93 4.46 4.94
5.00 4.15 4.21
3.93 4.10 4.09 3.92
4.00 4.32
3.70 3.75 4.00 3.84
4.09 3.55
3.96 3.43
4.00
3.00 3.00
3.00
2.00 2.00
2.00 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 HP class 8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0
5.0
22.4 6.0
28.0 33.58.0 40.010.0 45.0 12.050.0 14.0
56.0 16.0
61.5 18.0 kW
67.0 25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 77.5
16.0 18.0 25.0 31.5 37.5 45.0 50.0 56.0
1211mm Air outlets area
1210mm

Air volume area : 4403cm2 Air volume area : 6334cm2


+ 40%

COP: Coefficient of Performance

5.34 Improvement in bell-mouth


5.11 4.94
5.00 Current model New model

3.93 4.10 4.09 3.92


4.00 3.84
3.43
3.00
Smoother
Narrower
air flow
2.00
8.0 10.0 12.0 14.0 16.0 18.0 20.0 22.0 24.0 HP class
25.0 31.5 37.5 45.0 50.0 56.0 63.0 69.0 77.5 kW
Longer

Less short
circuit !!

NOTES:
1. The above values indicate the EER/COP per outdoor unit when it is combined with specified indoor units.
2. EER = Energy efficiency ratio = Cooling capacity or Heating capacity ÷ Power consumption of an air conditioner
3. COP = Coefficient of performance of an air conditioner = Output kW (cooling capacity) ÷ Input kW (power consumption)

WHAT'S IMPROVED? • Improvement of airflow volume by 23% (single module)


• Energy consumption in the driving shaft has decreased by 20% on average
1) FAN 2) Heat Exchanger 3) Compressor 4) Compressor Control

49 50
High Efficiency

IMPROVED HEAT EXCHANGER IMPROVED COMPRESSOR

New shape New design compressor

Current model (single module) New single medium & Large cabinet

Fixed Scroll
Split left-right
heat exchanger
Pressure bypass valve The 13 colored parts are new!
Σ shape !
Orbiting Scroll
Oldham’s Coupling
Main Bearing
Thrust Bearing

Frame Seal Compressor performance


Crankshaft +4.6% improved
APF
Counterweight
9.6
104.6%
Motor Rotor 9.4
9.2
100.0%
Motor Stator 9.0
New angle 8.8
8.6 8.98 9.39
Current model (single module) New single medium & Large cabinet Sub Bearing 8.4
8.2
8.0

Current model New model


Oil Pump
Improved angle of
the curve

Greater capacity control Current model* New model*

The highly improved performance as well


as greater energy saving is achieved by 100% 100% 15Hz ~ 100Hz 100% 100% 11Hz ~ 110Hz
adopting newly developed high efficiency 85 Steps 990 Steps
(by 1Hz) (by 0.1Hz)

Inverter Compressor

Inverter Compressor
DC inverter compressor, with outstandingly

Inverter Compressor

Inverter Compressor

Control Capacity

Control Capacity
Control Capacity

Control Capacity
precise control technology of 0.1Hz
increments inverter frequency. Another
feature is the dramatically extended
DC DC DC DC
working range, enabled by expanding the InverterInverter InverterInverter
Compressor
Compressor Compressor
Compressor
compressor’s operating frequency band, 20% 20% 10% 10%
both upwards and downwards. Max. Max.
Max. Max. CoolingCooling Load Load Min.
CoolingCooling Min.
Load Load Min. Min.
• The heat exchange area has been increased by more than 10% (single module)
*Example at 12HP class (33.5kW)
• Greater heat exchange efficiency

51 52
High Efficiency

IMPROVED COMPRESSOR CONTROL

Smooth drive Concept


Charge proper amount
The model calculates the appropriate of refrigerant
amount of coolant supplied by the outdoor
units on the basis of information about the Calculation of proper Refrigerant flow
Piping
required load from the individual indoor refrigerant amount
units. The model employs smooth operation
control to control the number of revolutions
of the inverter compressor. The model
supplies the appropriate amount of coolant
All Inverter
to the indoor units according to the required compressor IDU IDU

load. The model increases energy-saving


efficiency by operating smoothly while Transmit Transmit
load load
controlling the switching on and off of the information information

compressor at low-load operation. ODU

Transmission Wire

Actual example of the new compressor control

Current model New model

Room 30 Room 30
Temp
Original!
Specifications
Temp
(°C) (°C)
25 25
Unstable Temperature Constant Room Temperature
20 20 NOTES:
The cooling and heating performances are the values when combined with our
15 15 specified indoor units.
Cooling Operation Heating Operation
Conditions Conditions
10 10 Indoor Air Inlet Temperature:
o o o o
Indoor Air Inlet Temperature:
27 C DB (80 F DB) / 19.0 C WB (66.2 F WB) 20oC DB (68oF DB)
Energy Consumption Loss 1
Outdoor Air Inlet Temperature: Outdoor Air Inlet Temperature:
5 5 Smoother operation o o
35 C DB (95 F DB) 7oC DB (45oF DB) / 6oC WB (43oF WB)
Piping Length: 7.5 Meters(JTOR080~180VPE(U,F,R)BS1), 10.0 Meters
Power Power (JTOR200~240VPE(U,F,R)BS1, JTOR260~300VAE(U,F,R)BS1), 12.5 Meters
(kW) (kW)
0 0 (JTOR320~440VAE(U,F,R)BS1), 15.0 Meters (JTOR460~540VAE(U,F,R)BS1)
60 Time(mm) 120 180 60 Time(mm) 120 180 Piping Lift: 0 Meter
The sound pressure is based on the following conditions.
1 Meter from the unit service cover surface, and 1.5 Meters from floor level.
Room Temperature(°C) Room Temperature(°C) 2
The above data is based on the cooling mode. In case of heating mode, the sound
pressure level increases by approximately 1~2 dB.
Power(kW) Power(kW) The above data was measured in an anechoic chamber so that reflected sound
should be taken into consideration in the field.
Except for the specified combination in the table (26~54HP), there is no other
3
combination of the base unit.
due to frequent switching -40% 4
The width of outer dimension, it is the value when each distance between the base
outdoor units is specified to 20mm.
on/off operation energy consumption The 11th digit of the model name indicate the power supply of each unit.
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

53 54
Specifications

HP class 8 10 12 14 16 18 HP class 20 22 24

Model JTOR080VPE(U,F,R)BS1 JTOR100VPE(U,F,R)BS1 JTOR120VPE(U,F,R)BS1 JTOR140VPE(U,F,R)BS1 JTOR160VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 Model JTOR200VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1

Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 22.4 28.0 33.5 40.0 45.0 50.0 Nominal Cooling Capacity kW 56.0 61.5 67.0

Nominal Heating Capacity kW 25.0 31.5 37.5 45.0 50.0 56.0 Nominal Heating Capacity kW 63.0 69.0 77.5

Color Munsell Code Natural Gray (1.0Y 8.5/0.5) Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Cabinet
Outer Dimensions H*W*D mm 1,675 × 950 × 765 1,675 × 950 × 765 1,675 × 950 × 765 1,675 × 1,210 × 765 1,675 × 1,210 × 765 1,675 × 1,210 × 765 Outer Dimensions H*W*D mm 1,675 × 1,600 × 765 1,675 × 1,600 × 765 1,675 × 1,600 × 765

Sound Power Level dB(A) 80 82 82 85 85 86 Sound Power Level dB(A) 86 84 86


Sound Level Sound Level
Sound Pressure Level dB(A) 58 60 59 63 63 65 Sound Pressure Level dB(A) 65 64 66

460V/60Hz kg 200 200 220 276 319 320 460V/60Hz kg 360 374 375

Net Weight 380V/60Hz kg 195 195 215 271 314 315 Net Weight 380V/60Hz kg 355 369 370

220V/60Hz kg 190 190 210 266 309 310 220V/60Hz kg 350 364 365
Weight Weight
460V/60Hz kg 216 216 236 294 337 338 460V/60Hz kg 380 394 395

Gross Weight 380V/60Hz kg 211 211 231 289 332 333 Gross Weight 380V/60Hz kg 375 389 390

220V/60Hz kg 206 206 226 284 327 328 220V/60Hz kg 370 384 385

Type R410A Type R410A

Refrigerant Flow Control Micro-Computer Control Expansion Valve Refrigerant Flow Control Micro-Computer Control Expansion Valve

Charge (before Shipment) kg 5.0 5.0 7.2 8.9 9.9 10.7 Charge (before Shipment) kg 11.3 11.3 11.6

Type Hermetic (Scroll) Type Hermetic (Scroll)


AA50PHD + AA50PHD +
Model AA50PHD AA50PHD DC80PHD DC80PHD Model AA50PHD + AA50PHD DC80PHD + DC80PHD DC80PHD + DC80PHD
AA50PHD AA50PHD
Compressor Compressor
Quantity 1 1 1 1 2 2 Quantity 2 2 2

Motor Output Pole kW 3.3 (6) 4.3 (6) 5.4 (6) 8.0 (6) 4.5 (6) × 2 5.0 (6) × 2 Motor Output Pole kW 5.5 (6) × 2 6.7 (6) × 2 7.1 (6) × 2

Type FVC68D Type FVC68D


Refrigeration Oil Refrigeration Oil
Charge L/Unit 6.0 6.0 6.0 6.9 7.9 7.9 Charge L/Unit 8.4 8.4 8.4

Heat Exchanger Multi-Pass Cross-Finned Tube Heat Exchanger Multi-Pass Cross-Finned Tube

Type Propeller Fan Type Propeller Fan

Quantity 1 1 1 2 2 2 Quantity 2 2 2
Condenser Fan Condenser Fan
Air Flow Rate m3/min. 165 170 190 239 256 256 Air Flow Rate m3/min. 329 329 348

Motor Output Pole kW 0.26 (8) 0.28 (8) 0.42 (8) 0.33 (8) × 2 0.39 (8) × 2 0.39 (8) × 2 Motor Output Pole kW 0.48 (8) × 2 0.48 (8) × 2 0.56 (8) × 2

Main Refrigerant Liquid Line mm (in.) φ9.52 (3/8) φ9.52 (3/8) φ12.7 (1/2) φ12.7 (1/2) φ12.7 (1/2) φ15.88 (5/8) Main Refrigerant Liquid Line mm (in.) φ15.88 (5/8) φ15.88 (5/8) φ15.88 (5/8)
Piping Piping
Low Pressure mm (in.) φ19.05 (3/4) φ22.2 (7/8) φ25.4 (1) φ25.4 (1) φ28.58 (1-1/8) φ28.58 (1-1/8) Low Pressure mm (in.) φ28.58 (1-1/8) φ28.58 (1-1/8) φ28.58 (1-1/8)
Heat Recovery Gas Line Heat Recovery Gas Line
System (3 Pipes) High/Low Pressure mm (in.) φ15.88 (5/8) φ19.05 (3/4) φ22.2 (7/8) φ22.2 (7/8) φ22.2 (7/8) φ22.2 (7/8) System (3 Pipes) High/Low Pressure mm (in.) φ22.2 (7/8) φ25.4 (1) φ25.4 (1)

Dimensions H*W*D mm 1,800 × 1,030 × 810 1,800 × 1,030 × 810 1,800 × 1,030 × 810 1,800 × 1,290 × 810 1,800 × 1,290 × 810 1,800 × 1,290 × 810 Dimensions H*W*D mm 1,800 × 1,680 × 810 1,800 × 1,680 × 810 1,800 × 1,680 × 810
Package Package
Measurement m3 1.5 1.5 1.5 1.9 1.9 1.9 Measurement m3 2.4 2.4 2.4

*T
 he 11th digit of the model name indicates the power supply of each unit *T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

55 56
Specifications

HP class 26 28 30 32 34 36 HP class 38 40 42 44 46 48

Model JTOR260VAE(U,F,R)BS1 JTOR280VAE(U,F,R)BS1 JTOR300VAE(U,F,R)BS1 JTOR320VAE(U,F,R)BS1 JTOR340VAE(U,F,R)BS1 JTOR360VAE(U,F,R)BS1 Model JTOR380VAE(U,F,R)BS1 JTOR400VAE(U,F,R)BS1 JTOR420VAE(U,F,R)BS1 JTOR440VAE(U,F,R)BS1 JTOR460VAE(U,F,R)BS1 JTOR480VAE(U,F,R)BS1
JTOR120VPE(U,F,R)BS1 JTOR120VPE(U,F,R)BS1 JTOR120VPE(U,F,R)BS1 JTOR140VPE(U,F,R)BS1 JTOR160VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR140VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1
Combination of Base Unit Combination of Base Unit
JTOR140VPE(U,F,R)BS1 JTOR160VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1 JTOR220VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1 JTOR240VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 73.0 77.5 85.0 90.0 95.0 100.0 Nominal Cooling Capacity kW 106.0 112.0 118.0 122.0 128.0 136.0

Nominal Heating Capacity kW 82.5 90.0 95.0 100.0 106.0 112.0 Nominal Heating Capacity kW 118.0 125.0 132.0 140.0 145.0 150.0

Color Munsell Code Natural Gray (1.0Y 8.5/0.5) Color Munsell Code Natural Gray (1.0Y 8.5/0.5)
Cabinet Cabinet
Outer Dimensions H*W*D mm 1,675 × 2,180 × 765 1,675 × 2,180 × 765 1,675 × 2,180 × 765 1,675 × 2,440 × 765 1,675 × 2,440 × 765 1,675 × 2,440 × 765 Outer Dimensions H*W*D mm 1,675 × 2,830 × 765 1,675 × 2,830 × 765 1,675 × 2,830 × 765 1,675 × 3,220 × 765 1,675 × 3,220 × 765 1,675 × 3,220 × 765

Sound Power Level dB(A) 87 87 87 89 89 89 Sound Power Level dB(A) 89 88 89 87 88 89


Sound Level Sound Level
Sound Pressure Level dB(A) 64.5 64.5 66 67 67 68 Sound Pressure Level dB(A) 68 67.5 68.5 67 68 69

460V/60Hz kg 220 + 276 220 + 319 220 + 320 276 + 320 319 + 320 320 + 320 460V/60Hz kg 276 + 375 320 + 374 320 + 375 374 + 374 374 + 375 375 + 375

Net Weight 380V/60Hz kg 215 + 271 215 + 314 215 + 315 271 + 315 314 + 315 315 + 315 Net Weight 380V/60Hz kg 271 + 370 315 + 369 315 + 370 369 + 369 369 + 370 370 + 370

220V/60Hz kg 210 + 266 210 + 309 210 + 310 266 + 310 309 + 310 310 + 310 220V/60Hz kg 266 + 365 310 + 364 310 + 365 364 + 364 364 + 365 365 + 365
Weight Weight
460V/60Hz kg 236 + 294 236 + 337 236 + 338 294 + 338 337 + 338 338 + 338 460V/60Hz kg 294 + 395 338 + 394 338 + 395 394 + 394 394 + 395 395 + 395

Gross Weight 380V/60Hz kg 231 + 289 231 + 332 231 + 333 289 + 333 332 + 333 333 + 333 Gross Weight 380V/60Hz kg 289 + 390 333 + 389 333 + 390 389 + 389 389 + 390 390 + 390

220V/60Hz kg 226 + 284 226 + 327 226 + 328 284 + 328 327 + 328 328 + 328 220V/60Hz kg 284 + 385 328 + 384 328 + 385 384 + 384 384 + 385 385 + 385

Type R410A Type R410A

Refrigerant Flow Control Micro-Computer Control Expansion Valve Refrigerant Flow Control Micro-Computer Control Expansion Valve

Charge (before Shipment) kg 16.1 17.1 17.9 19.6 20.6 21.4 Charge (before Shipment) kg 20.5 22.0 22.3 22.6 22.9 23.2

Type Hermetic (Scroll) Type Hermetic (Scroll)


AA50PHD + AA50PHD + AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD +
DC80PHD + DC80PHD + DC80PHD + DC80PHD +
DC80PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD +
Model AA50PHD + AA50PHD + AA50PHD + Model DC80PHD +
DC80PHD AA50PHD + AA50PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD + DC80PHD +
Compressor AA50PHD AA50PHD AA50PHD Compressor DC80PHD
AA50PHD AA50PHD DC80PHD DC80PHD DC80PHD DC80PHD DC80PHD
Quantity 2 3 3 3 4 4 Quantity 3 4 4 4 4 4
5.4 (6) × 1 + 8.0 (6) 5.4 (6) × 1 + 4.5 (6) × 5.4 (6) × 1 + 5.0 (6) 8.0 (6) × 1 + 5.0 (6) 4.5 (6) × 2 + 5.0 (6) 5.0 (6) × 2 + 5.0 (6) 8.0 (6) × 1 + 7.1 (6) 5.0 (6) × 2 + 6.7 (6) 5.0 (6) × 2 + 7.1 (6) 6.7 (6) × 2 + 6.7 (6) 6.7 (6) × 2 + 7.1 (6) × 7.1 (6) × 2 + 7.1 (6) ×
Motor Output Pole kW Motor Output Pole kW
×1 2 × 2 × 2 × 2 × 2 ×2 ×2 × 2 × 2 2 2
Type FVC68D Type FVC68D
Refrigeration Oil Refrigeration Oil
Charge L/Unit 12.9 13.9 13.9 14.8 15.8 15.8 Charge L/Unit 15.3 16.3 16.3 16.8 16.8 16.8

Heat Exchanger Multi-Pass Cross-Finned Tube Heat Exchanger Multi-Pass Cross-Finned Tube

Type Propeller Fan Type Propeller Fan

Quantity 3 3 3 4 4 4 Quantity 4 4 4 4 4 4
Condenser Fan Condenser Fan
Air Flow Rate m3/min. 190 + 239 190 + 256 190 + 256 239 + 256 256 × 2 256 × 2 Air Flow Rate m3/min. 239 + 348 256 + 329 256 + 348 329 × 2 329 + 348 348 × 2
0.42 (8) + 0.33 (8) × 0.42 (8) + 0.39 (8) × 0.42 (8) + 0.39 (8) × 0.33 (8) × 2 + 0.39 0.39 (8) × 2 + 0.39 0.39 (8) × 2 + 0.39 0.33 (8) × 2 + 0.56 0.39 (8) × 2 + 0.48 0.39 (8) × 2 + 0.56 0.48 (8) × 2 +0.48 0.48 (8) × 2 + 0.56 0.56 (8) × 2 + 0.56
Motor Output Pole kW Motor Output Pole kW
2 2 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2 (8) × 2

Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4)
Piping Piping
Low Pressure mm (in.) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ38.1 (1-1/2) Low Pressure mm (in.) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2)
Heat Recovery Gas Line Heat Recovery Gas Line
System (3 Pipes) High/Low Pressure mm (in.) φ25.4 (1) φ28.58 (1-1/8) φ28.58 (1-1/8) φ28.58 (1-1/8) φ28.58 (1-1/8) φ28.58 (1-1/8) System (3 Pipes) High/Low Pressure mm (in.) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4)

*T
 he 11th digit of the model name indicates the power supply of each unit *T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

57 58
Specifications

HP class 50 52 54

Model JTOR500VAE(U,F,R)BS1 JTOR520VAE(U,F,R)BS1 JTOR540VAE(U,F,R)BS1


JTOR140VPE(U,F,R)BS1 JTOR160VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1
Combination of Base Unit JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1
JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1 JTOR180VPE(U,F,R)BS1
Power Supply 3~,460V/60Hz, 3~/N,380V/60Hz, 3~,220V/60Hz

Nominal Cooling Capacity kW 140.0 145.0 150.0

Nominal Heating Capacity kW 155.0 160.0 165.0

Color Munsell Code Natural Gray (1.0Y 8.5/0.5)


Cabinet
Outer Dimensions H*W*D mm 1,675 × 3,670 × 765 1,675 × 3,670 × 765 1,675 × 3,670 × 765

Sound Power Level dB(A) 90 90 91


Sound Level
Sound Pressure Level dB(A) 69 69 70

Net Weight
460V/60Hz

380V/60Hz
kg

kg
276 + 320 + 320

271 + 315 + 315


319 + 320 + 320

314 + 315 + 315


320 + 320 + 320

315 + 315 + 315


Options
220V/60Hz kg 266 + 310 + 310 309 + 310 + 310 310 + 310 + 310
Weight

Gross Weight
460V/60Hz

380V/60Hz
kg

kg
294 + 338 + 338

289 + 333+ 333


337 + 338 + 338

332 + 333 + 333


338 + 338 + 338

333 + 333 + 333


Heat Pump JTOH-BS1 series
220V/60Hz kg 284 + 328 + 328 327 + 328 + 328 328 + 328 + 328

Type R410A

Refrigerant Flow Control Micro-Computer Control Expansion Valve

Charge (before Shipment) kg 30.3 31.3 32.1

Type Hermetic (Scroll)


DC80PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD + AA50PHD +
Model AA50PHD + AA50PHD AA50PHD + AA50PHD + AA50PHD AA50PHD + AA50PHD + AA50PHD
Compressor
Quantity 5 6 6

Motor Output Pole kW 8.0 (6) × 1 + 5.0 (6) × 2 + 5.0 (6) × 2 4.5 (6) × 2 + 5.0 (6) × 2 + 5.0 (6) × 2 5.0 (6) × 2 + 5.0 (6) × 2 + 5.0 (6) × 2

Type FVC68D
Refrigeration Oil
Charge L/Unit 22.7 23.7 23.7

Heat Exchanger Multi-Pass Cross-Finned Tube

Type Propeller Fan

Quantity 6 6 6
Condenser Fan
Air Flow Rate m3/min. 239 + 256 × 2 256 × 3 256 × 3

Motor Output Pole kW 0.33 (8) × 2 + 0.39 (8) × 2 + 0.39 (8) × 2 0.39 (8) × 2 + 0.39 (8) × 2 + 0.39 (8) × 2 0.39 (8) × 2 + 0.39 (8) × 2 + 0.39 (8) × 2

Main Refrigerant Liquid Line mm (in.) φ19.05 (3/4) φ19.05 (3/4) φ19.05 (3/4)
Piping
Low Pressure mm (in.) φ38.1 (1-1/2) φ38.1 (1-1/2) φ38.1 (1-1/2)
Heat Recovery Gas Line
System (3 Pipes) High/Low Pressure mm (in.) φ31.75 (1-1/4) φ31.75 (1-1/4) φ31.75 (1-1/4)

*T
 he 11th digit of the model name indicates the power supply of each unit
U: 460V/60Hz F: 380V/60Hz R: 220V/60Hz

59 60
Options

1. PIPING CONNECTION KIT


Piping connection kit for the divergence between outdoor units 3 units combination image
Applicable Outdoor Unit Accessory Pipe
(Z-Shape) -Perform the piping connection between outdoor units
Model HP class Connectivity Remarks Base
according to this figure.
Number (Field-Supplied) Outdoor Unit A
JTOH-BS1 series
-Refer to “Installation & Maintenance Manual” of the
for Gas: 1 outdoor unit for the dimension and distance between
MC-NP21SA 26-48 2
for Liquid: 1 outdoor units and between piping connection kits.
Accessory Pipe
for Gas: 2 (Z-Shape)
MC-NP30SA 50-54 3
for Liquid: 2
Gas Piping Outdoor Unit B
for Gas: 2
MC-NP31SA 56-72 3 (Field-Supplied)
for Liquid: 2 Outdoor Unit C
for Gas: 3 Liquid Piping
MC-NP40SA 74-96 4
for Liquid: 3 (Field-Supplied)

NOTE:The old model (MC-TTA1) is not available.


Piping Connection
Kit 1 (Liquid)

Piping Connection
Kit 1 (Gas) Gas Piping
images:MC-NP30SA (Field-Supplied)

GAS Side Liquid Side Reducer Accessory Pipe Piping Connection


(L-Shape) Kit 2 (Liquid)

Piping Connection
Accessory Pipe
Kit 2 (Gas)
(L-Shape)

*Perform the piping connection between outdoor units according to this figure.
*Refer to the Installation & Maintenance Manual of the outdoor unit for the dimensions Liquid Piping Gas Piping
and distance between outdoor units and between piping connection kits.
(Field-Supplied) (Field-Supplied)

4 units combination image


Piping Connection Kit 1
(Liquid)

Liquid Piping Piping Connection Kit 2


(Field-Supplied) (Liquid)
Liquid Piping
(Field-Supplied) Outdoor Unit A
Accessory
Pipe 4 Accessory
Pipe 7
(L Shape) Outdoor Unit B
Accessory
Pipe 10 Accessory
Pipe 2 Base
Liquid Piping
(Z Shape) (Field-Supplied)
(Field-Supplied)
Piping Connection Kit 3
(Liquid)

Accessory Outdoor Unit C


Accessory Pipe 11
Pipe 1 (L Shape)
Outdoor Unit D

Accessory Liquid Piping


Pipe 3 (Field-Supplied)
Piping Connection
Kit 1 (Gas)

Gas Piping Accessory


(Field-Supplied) Pipe 6
(Z Shape)

Accessory
Piping Connection Gas Piping Pipe 10
Kit 2 (Gas) (Field-Supplied)
Gas Piping
(Field-Supplied) Accessory Accessory
Pipe 5 Pipe 10
(L Shape) Gas Piping
Accessory Accessory (Field-Supplied)
Piping Connection
Pipe 8 Pipe 9
Kit 3 (Gas)
(L Shape) (Z Shape)

61 62
Options

NP31SA

Dimensions NP31SA
NP31SA
NP31SA
MC-NP31SA IDU
IDU NP31SA ODU IDU IDU
ODU ODU ODU
GAS Side
597 GAS Side 345 Liquid Side Liquid Side
378
499 IDU
IDU
IDU
IDU
IDU
IDU ID31.75 ODU
ODU
ODU IDU
IDU
IDU ID15.88
IDU
IDU
IDU IDU ID9.52
MC-NP21SA IDU ODU ID31.75
IDU ID25.4 ODU
ODU
ODU IDU
ID19.05 ODU
ODU
ODU ODU
ODU
ODU
ID38.1597
597 ODU ID12.7 378
378
378 ODU
ID50.8 597 ID38.1 ID28.58 499 345 ODU
345
345
GAS Side Liquid Side
597
499
499
499 ID19.05 345
ID15.88
ID15.88 ID15.88 378
ID54.0 ID41.28 ID31.75
ID31.75
ID31.75 ID15.88 ID9.52
ID9.52
ID9.52
ID31.75 ID41.28 ID31.75 ID31.75
ID31.75
ID31.75 ID25.4
ID25.4
ID25.4 ID15.88 ID19.05 ID9.52
ID31.75 ID25.4 ID22.2 ID19.05
ID19.05
ID19.05 ID12.7
ID12.7
ID12.7
ID50.8
ID50.8
ID50.8 ID38.1
ID38.1
ID38.1 ID19.05 ID12.7
469 469 378 378 ID50.8 ID38.1 ID38.1
ID38.1
ID38.1 ID28.58
ID28.58
ID28.58
ID38.1 ID28.58 ID19.05
ID19.05
ID19.05 ID15.88
ID15.88
ID15.88

130
ID41.28
ID41.28

80
ID54.0
ID54.0
ID54.0 ID41.28 ID19.05 ID15.88

130
80
ID22.2 ID22.2 ID9.52 ID9.52 ID54.0 ID41.28 ID41.28
ID41.28
ID41.28 ID31.75
ID31.75
ID31.75 ID19.05
ID19.05
ID19.05
378 ID22.2
ID22.2

141
469 ID22.2

158
211
ID41.28 ID31.75

95
ID31.75 ID25.4 ID22.2 ID19.05
ID31.75 ODU ID25.4 ODU ID15.88 ID12.7ID15.88 ID12.7 ID25.4 Insulation
ID22.2 ID9.52 ODU
ID38.1 ID28.58
ID38.1 ID28.58 ID19.05 ID15.88 ID19.05 ODU

130
80
ID15.88

130
80
61

130
80

130
80
ID31.75 ID25.4 ID15.88 ID12.7 Insulation

130
ODU

80
ID15.88

130
Insulation

80
141

158
211
141

158
211

95
83

95
ID38.1 ID28.58 ODU ID41.28 Insulation

141
ID19.05 ID15.88

158
211
ID19.05

95
ID28.58 ID25.4
ID25.4
ID25.4 61 ID19.05 Insulation
Insulation
Insulation
489 97 409 ID25.4
315 Insulation
303 61
61
61
158 158

80 80

130 130
95

158

Insulation
Insulation
Insulation

80

130
ID15.88
95

IDU IDU Insulation


Insulation
Insulation ID15.88
ID15.88 61
Insulation ID41.28
ID41.28 Insulation
Insulation
Insulation ID28.58 83
83
83 Insulation ID15.88 ODU
ID41.28
ODU ODU
ID28.58
ID28.58 83 ID19.05
ID19.05
ODU
ID19.05 61
61 ID19.05
ID19.05
ID19.05
ID41.28 Insulation ID28.58 ID19.05 61
95

IDU 97
97
97 61 ID19.05
489
489
489 97 409
409
409 315
315
315 303
303
303
Insulation Insulation
ID28.58 ID28.58 83 ID19.05 Insulation 61 61 489 409 315 303
382 83 Insulation ID19.05 ODU
ODU ODU
ODU ODU
ODU
ODU
382 ODU ODU ODU
ODU
ODU ODU
Insulation 303 ID19.05 ODU
303 61 ODU ODU ODU ODU
IDU IDU ID28.58
382
ODU 83 ODU Insulation Reducer
303 ODU Reducer Reducer Reducer
IDU ODU OD28.58 Reducer OD19.05
Reducer ID38.1 ID31.75
OD28.58 OD19.05
OD28.58 OD19.05 OD50.8
Reducer ID41.28 Reducer
Reducer
Reducer Reducer
Reducer
Reducer
OD28.58 OD28.58 Reducer Reducer OD28.58 OD19.05
OD19.05
OD19.05 Reducer
Reducer
Reducer
ID22.2 OD28.58 ID22.2 OD19.05 OD28.58
OD28.58 Reducer
Reducer
ReducerOD19.05 Reducer
Reducer
Reducer ID38.1
ID38.1
ID38.1 ID31.75
ID31.75
ID31.75 OD28.58 Reducer
OD28.58 Reducer Reducer Reducer Reducer ID38.1 ID31.75
ID25.4 ID25.4 Reducer Reducer OD50.8
OD50.8
OD50.8 OD41.28
ID22.2 OD50.8 ID41.28
ID41.28
ID41.28 ID28.58 ID15.88
ID28.58 ID28.58 Reducer ID41.28
ID28.58 ID28.58
Reducer
ID15.88 ID15.88 OD41.28
ID25.4 ID12.7
ID25.4 ID25.4
ID28.58 ID28.58 ID25.4
ID12.7 OD41.28
OD41.28
OD41.28
ID15.88 ID12.7 ID44.45 OD41.28 ID31.75 ID28.58 ID9.52 ID15.88
ID15.88
ID15.88
ID22.2 ID28.58
ID28.58 ID15.88
Reducer Reducer ID25.4 ID22.2 ID28.58
ID9.52
ID12.7 ID9.52 ID41.28 OD41.28
OD41.28
OD41.28 ID22.2
OD28.58 Reducer ID28.58 OD41.28 ID25.4
ID25.4
ID25.4 ID12.7
ID12.7
ID12.7
Reducer ID22.2 ID25.4 ID12.7
ID9.52 ID44.45
ID44.45
ID44.45 ID31.75
ID31.75
ID31.75 ID9.52
ID9.52
ID44.45 ID28.58 ID31.75 ID9.52
ID9.52
ID41.28
ID41.28
ID41.28 OD28.58
OD28.58
OD28.58 ID25.4 ID28.58
ID28.58
ID28.58 ID22.2
ID22.2
ID22.2
ID41.28 OD28.58 Reducer
Reducer
Reducer ID28.58 ID22.2
Reducer
NP40SA NP40SA ID28.58
ID28.58
ID28.58
ID28.58
ID25.4
ID25.4
ID25.4
ID25.4
IDU IDU
NP40SA
IDU IDU ODU ODU IDU IDU IDU IDU
NP40SA
597 597
ODU ODU ODU ODU
378
ODU
378
ODU
NP40SA
345 345
NP40SA
NP40SA
MC-NP40SA 499 499
NP40SA
NP40SA ID31.75 ID31.75 ID15.88 ID15.88 ID9.52 ID9.52
NP40SA
MC-NP30SA ID31.75 ID31.75 ID25.4 ID25.4 IDUIDU
IDUIDUGAS SideID38.1 ID38.1 ODU IDUIDUSide
GAS ID19.05
IDU
Liquid Side ID19.05 Liquid ID12.7
Side ID12.7
ID50.8 ID50.8 ODU
ID38.1 ID38.1 ID28.58 ID28.58 ODU IDU ODU
ODU ID19.05 ID19.05 ODUODU IDU IDU ID15.88
IDU
ID15.88 ODU
GAS Side Liquid Side IDU IDU ID54.0
ID54.0
IDU ID41.28597597ID41.28 ODU ODU
ODU IDU IDU IDUIDU IDU 345345 IDU 378378
IDU
ID41.28 ID31.75
ID41.28 499499ID31.75 IDU ODU
IDU ODU
IDU ODU ODU IDU IDU
ODU ID22.2 ID22.2 ODU
ODU ODU ID19.05 ID19.05 ODU
ODU
472 IDU ODU
597 597 ID31.75 IDU ODU IDU ID15.88
345 345
ID15.88 378 ID9.52
378 ODU 378
ODU
472 378 IDU ODU IDU 597 ID31.75 IDU ID31.75 499 499 499ID25.4 ODU 345 ODU ID9.52
378 597 ID31.75 ID25.4 345 ID19.05ODU ODU 378
ID25.4 597
ID50.8 ID38.1 ID31.75 ODU
ID31.75 499 ODU 345 ID15.88
378ID15.88
ID15.88
ID19.05 378 ID12.7
ID9.52 ID9.52
ID12.7
ID9.52

130
ID9.52

80

80
ID25.4 ID31.75
ID38.1 499

130

130
597 ID38.1 ID28.58

80

80
472 378 ID9.52 ID50.8 ID31.75
ID31.75 345
ID31.75
ID38.1 ID25.4
ID25.4
ID28.58ID25.4 ID15.88 ID9.52 ID15.88
ID31.75 ID28.58 ID31.75499 ID15.88 ID19.05

141

141
ID19.05 ID9.52

158

158
211

211
ID31.75 ID19.05 ID12.7ID12.7
ID15.88

95

95
ID31.75 ID25.4 ID28.58 ID15.88 ID12.7 ID54.0
ID50.8 ID50.8 ID41.28
ID38.1ID38.1
ID38.1 ID31.75 ID15.88 ID25.4ID31.75 ID19.05
ID9.52 ID12.7
ID38.1 ID31.75 ODU ID15.88
ID9.52 ID12.7 ID31.75 ID50.8 ID54.0 ID41.28 ID31.75 ID41.28
ID38.1
ID38.1 ID25.4
ID38.1 ID28.58
ID28.58 ID28.58 ID19.05ID22.2 ID19.05
ID12.7
ID38.1 ID31.75 ODU ID19.05 ID15.88 ODU ID50.8 ID31.75ID38.1 ID25.4 ID41.28 ID31.75 ID25.4
ID19.05 ID25.4
ID19.05 ID19.05 Insulation ID12.7 Insulation
ID19.05
ID15.88
ID15.88 ID15.88
ID31.75 ID28.58 ID19.05 ID15.88 ODU ID50.8 ID54.0 ID38.1
ID54.0 ID41.28 ID41.28 ID38.1 ID19.05 ID28.58 ID19.05
ID12.7 ID22.2
ID15.88 ID12.7 ID50.8 ID38.1 ID54.0 ID41.28 ID38.1 ID41.28 ID28.58
ID41.28 ID31.75
ID31.75 ID31.75 ID19.05 ID15.88 61 61
ODU ID54.0Insulation ID41.28
ID38.1 ID28.58 ID41.28 InsulationID22.2
ID19.05 Insulation
ID22.2 ID22.2 ID15.88 ID15.88 ID19.05
ID19.05
ID15.88ID19.05
ID38.1 ID31.75 ODU Insulation
ID54.0 ID41.28 ID41.28 ID31.75 83 83 ID15.88

130 130
ID19.05

80 80
ID19.05 ID15.88 Insulation Insulation ID19.05

130 130
ID41.28 ID41.28

80 80
ID41.28 ID31.75 ID22.2
ID19.05 ID19.05

130 80
ID54.0 ID41.28 ID28.58 ID28.58 ID19.05

130
ID19.05 ID19.05

130 80
ID41.28 ID31.75 ID22.2 61 61

95 141 141

158 158
211 211
ID19.05

95 95
141
ID22.2

158
211

95
97 97

80
130
158

80

130
95

130

80
80
489 489 409 409 315 ID25.4 315 303Insulation303

130
130
158

80
IDU
80
95

80
211141
IDU ID25.4 Insulation

158
211

15895

80
141

130
158
158 211

80
95

130
80
ODU ODU ODU ODU ODU ODU 61 61

130
141
ODU ODU

80
130

Insulation
158

95
80

130
ID25.4 ID15.88 Insulation
95

80
ID25.4 Insulation

141

158
211
Insulation

95
IDU Insulation 83 83 ID25.4 Insulation Insulation
ID15.88
141

Insulation
211

61 ID41.28
ID41.28 Insulation ID28.58 ID25.4
ID25.4 ID19.05 Insulation
Insulation ID19.05 61 61
61
Insulation 83 Insulation ID19.05 61 ID28.58 Insulation
Insulation ID19.05
Insulation 61 61 ID15.88
ID15.88 ID19.05
ID28.58
Insulation 83 Insulation ID19.05 Insulation
Insulation
Insulation 97 97 ID25.4Insulation 83 83 Insulation ID15.88 61
ID28.58 Insulation 489489
ID41.28
ID41.28 ID41.28 Insulation
Insulation 409 83 Insulation ID19.05
Insulation 315ID19.05 ID15.88 303303 61
382 ODU 83 303 ODU61 Insulation Insulation Insulation 409 ID28.58
ID28.58
ID28.58 83 ID19.05 315 61 6161 61 ID15.88 ID19.05
ID19.05 ID19.05
Insulation 382 ODU Insulation ID19.05 303 ODU Insulation ID41.28
ID41.28 97 Insulation ID28.58 83 ID19.05
ID15.88 ID19.05
ID28.58 489 489 ODU 97
97
83 ID28.58409 409 ODU ID19.05 315 315 ODU 61 ID19.05 303 303 303 ODU
IDU
ID41.28
489
489
Insulation ID28.58 ODU 97 ID19.05409 61ODU ID19.05
315 61
ODU ODU
IDU 382 ODU 303 ODU 489 97 409
409 315
315 303
303
97 ODU
ID31.75 ODU ID31.75 ODU ODU
ODU ODU ODU ODU ODU
ODU
489 409Reducer ODU Reducer 315 303 ODU ODU
IDU ODU ODU ODU ODU
ODU OD28.58 OD28.58 Reducer ODU ODUOD19.05 OD19.05Reducer
Reducer
Reducer ODU ODU
Reducer ID31.75
ID31.75
OD28.58
OD28.58 OD19.05 ODU ID38.1
ODU ID38.1
OD19.05
Reducer ID41.28 ID41.28 Reducer Reducer
ID31.75 OD28.58 Reducer ID38.1 ReducerID41.28
ID41.28 ID44.45 ID44.45
OD19.05 ID38.1 Reducer Reducer Reducer Reducer
Reducer Reducer ID31.75
ID31.75 OD41.28 OD41.28 ID28.58
Reducer Reducer Reducer ID38.1 ID38.1 Reducer
OD31.75 Reducer
ID38.1 OD28.58 OD19.05 Reducer
Reducer
OD31.75 ID28.58 ID31.75 ID31.75 Reducer Reducer ID31.75
ID38.1
ID31.75 ID31.75 OD28.58 Reducer
Reducer OD19.05
Reducer ID28.58 ID15.88 Reducer ID38.1 ID15.88 ID15.88
ID25.4 ID25.4 ID15.88 OD31.75
Reducer OD31.75 ID31.75
Reducer ID31.75 ID28.58 ID28.58 OD19.05 OD19.05 Reducer
Reducer Reducer Reducer
OD31.75 ID25.4 ID25.4 ID12.7 Reducer ID41.28
ID38.1ID38.1 OD28.58
OD28.58 OD28.58 Reducer
Reducer ReducerOD19.05 Reducer
ID28.58 Reducer Reducer ID31.75 ID41.28
ID41.28
ID38.1
ID41.28
OD28.58 Reducer OD19.05
OD19.05 ID12.7
Reducer
Reducer
ID12.7 ID44.45
OD50.8 ID44.45OD50.8 ID38.1 ID38.1 OD31.75 OD31.75 OD25.4 OI
ID28.58 ID22.2 ID15.88 ID12.7
OD31.75 Reducer Reducer ReducerID38.1
ID38.1 OD28.58
Reducer ID25.4 ID25.4
Reducer Reducer
Reducer Reducer
OD28.58 ID25.4 ID28.58
ID25.4 ID22.2 ID9.52 ID38.1
OD28.58 OD19.05
ID41.28
ID41.28 ID41.28 Reducer
Reducer
Reducer OD41.28 Reducer
OD28.58 ID9.52 ID38.1 ID38.1
ID41.28 ID41.28
ID41.28 Reducer
ID28.58 ID28.58 ID44.45
ID44.45 ID44.45 ID31.75 OD41.28 ID31.75 ID28.58 ID28.58
ID12.7 Reducer ID41.28 ID9.52 ID9.52 ID41.28 Reducer
ID41.28
Reducer Reducer Reducer Reducer
Reducer
ID28.58 ID41.28
ID31.75 ID38.1 ID41.28 ID44.45 OD41.28 OD41.28 Reducer Reducer IDID
OD28.58 Reducer ID22.2
ID9.52 OD15.88 Reducer
Reducer ID41.28 ID41.28ID38.1
ID38.1
ID31.75 ID25.4 ID25.4 ID22.2 ID28.58 ID22.2 Reducer ID15.88 ID44.45 OD41.28 Reducer Reducer
Reducer OD15.88 ID41.28 ID38.1 ID44.45 ID28.58 ID15.88 OD41.28 Reducer Reducer ID28.58
ID28.58
OD28.58ID38.1 OD28.58
ID31.75 ID31.75 Reducer Reducer OD41.28
ID28.58
Reducer ID38.1 ID31.75 ID28.58 ID15.88 ID15.88
ID12.7
ID15.88 OD41.28 OD50.8 ID38.1 OD31.75 OD2
Reducer OD15.88 ID31.75 Reducer ID28.58
ID28.58 ID25.4 ID12.7 OD50.8 ID38.1 OD31.75 O
ID31.75 Reducer ID28.58 ID25.4 ID15.88
ID15.88
ID19.05 ID31.75 ID28.58 ID28.58 ID12.7
ID9.52 ID41.28 ID31.75
ID38.1 ID38.1 ID28.58
OD31.75
OD31.75
OD31.75
ID19.05 ID15.88
ID28.58 ID25.4 ID25.4 ID12.7
ID12.7 ID9.52 OD50.8
OD50.8 OD50.8
ID41.28 ID38.1 ID31.75 ID28.58 OD2
OD25
ID28.58 Reducer Reducer
Reducer ID25.4 ID12.7 ID38.1 OD31.75
ID25.4
ID28.58 ID25.4 ID22.2 ID12.7 OD50.8
OD50.8 ID38.1 ID31.75 ID31.75 OD31.75 ID28.58 OD25.4
ID28.58
OD25.4
ID19.05 Reducer
Reducer ID28.58
ID28.58 ID25.4 ID25.4 ID22.2 ID9.52ID9.52
ID9.52 ID41.28
OD31.75
ID41.28 ID41.28 ID31.75 ID28.58
OD28.58 ID25.4 ID28.58 ID12.7 OD50.8 ID38.1 OD25.4 ID31.75 Reducer ID28.58
Reducer OD28.58 ID28.58 ID25.4ID25.4 ID9.52 ID41.28 ID31.75 ID28.58
ID25.4 ID22.2ID22.2
ID22.2 ID9.52 ID31.75 ID41.28 ID28.58
ID28.58 OD28.58OD28.58 ID25.4 ID9.52 ID22.2 ID41.28
OD28.58 ID25.4 ID22.2
ID25.4 OD28.58
OD28.58 ID22.2
OD28.58

63 64
Options

365 main piping


ID25.4 ID28.58 77
ID22.2 ID28.58

2. MULTI-KIT 365
ODU
main piping
262
ID25.4 ID28.58 77 ID9.52

251
ID22.2 ID28.58

219
ID22.2 ID12.7 ID12.7
Branching for indoor and outdoor connecting pipes Insulation
ID19.05
ID15.88
Line branch MW-NP452A3
ODU
ID12.7 ID12.7
290 IDU
Pipe diameter after the first branch and multi-kit

251
ID9.52
First branching pipes GAS Side Liquid Side Reducer

219
ID22.2 ID6.35
Insulation Insulation
365 365 main piping main piping ID25.4
Outdoor Unit HP Model 262 262 main piping main piping ID19.05
Diameter (mm) OD28.58 ID15.88 ID9.52
ID25.4 ID25.4 ID28.58 ID28.58 77 ID15.88 173 IDU
Total Indoor Unit HP Model 77 ID9.52 56
ID9.52 56
8 - 10 MW-NP282A3 Gas Pipe Liquid Pipe ID22.2 ID22.2ID28.58 ID28.58 ID12.7 ID12.7
ID12.7 ID12.7 ID12.7
ODU
290 IDU ID12.7 OD6.35
12 - 16 MW-NP452A3 <6 Φ 15.88 Φ 9.52 Reducer ID22.2 ID19.05 Reducer
18 - 24 MW-NP692A3 6 - 8.99 Φ 19.05 Φ 9.52 MW-NP282A3 ODU ODU
ID25.4 main piping
365
ID12.7 ID12.7 OD28.58

163

163
26 - 54 MW-NP902A3 Φ 22.2 Φ 9.52
ID15.88 ID9.52

139

139
9 - 11.99 ID22.2 ID28.58 77 I

251

251
ID9.52 ID9.52
ID25.4

219

219
56 - 96 MW-NP2682A3 12 - 15.99 Φ 25.4 Φ 12.7
ID22.2 ID22.2 ID6.35 ID6.35
Insulation Insulation Insulation Insulation ID12.7 ID28.58
MW-NP452A3 OD6.35
ID19.05
16 - 17.99 Φ 28.58 Φ 12.7 ID19.05 Reducer ID22.2 ID19.05 Reducer
ID15.88 ID15.88 173 IDU
173 IDU
18 - 25.99 Φ 28.58 Φ 15.88 MW-NP692A3 ID12.7 ID12.7
ODU ODU
26 - 35.99 Φ 31.75 Φ 19.05 290 290 IDU IDU
OD

251
MW-NP902A3

219
Insulation ID22.2
36 - 55.99 Φ 38.1 Φ 19.05
ID25.4 ID25.4
ODU ID19.05
56 - 67.99 Φ 44.45 Φ 19.05 OD28.58
MW-NP692A3OD28.58 ID15.88 ID15.88 ID9.52 ID9.52
ID15.88
68 - 72 Φ 44.45 Φ 22.2 ID12.7
MW-NP2682A3 GAS Side ID12.7 ID12.7
OD6.35 OD6.35 Liquid Side Reducer 290 IDU
74 - 88 Φ 50.8 Φ 22.2 Reducer Reducer
ID22.2 ID19.05
ID22.2 ID19.05 Reducer Reducer
365 main piping 387 main piping
< 90 Φ 50.8 Φ 25.4 365 main piping 387 main piping
ID22.2 ID28.58 ID25.4
ID22.2 ID28.58 77 77 ID15.88 ID15.88 ID12.7 67
ID12.7 67
ID25.4 ID19.05 OD28.58 ID15.88
ID25.4 ID19.05 ID15.88 ID15.88 ID9.52
ID28.58 ID28.58 ID22.2 ID22.2
ID12.7 OD6.35
Reducer ID22.2 ID19.05 Reducer
ID9.52 ID9.52
main piping

219
ODU

219
ODU 477

219251

251

191

191
ID15.88

219
Insulation Insulation
ID22.2 ID15.88 ID31.75 87 ID
images:MW-NP282A3 ID22.2 Insulation Insulation
ID12.7 ID12.7 ID38.1 ID38.1
ODU ODUID19.05 ID19.05 ID9.52 ID9.52
ID15.88 ID15.88 ID6.35 ID6.35
GAS Side Liquid Side Reducer ID12.7 ID12.7
251 ID34.92
290 290 IDU IDU 251 IDU IDU

257
main piping ID31.75

220
477 429
Insulation
ID31.75 87 ID15.88 ID12.7 O
ID25.4 ID25.4 ODU
ID38.1 ID38.1 ID19.05 ID19.05
OD28.58
MW-NP902A3 OD28.58ID15.88 ID15.88 ID9.52 ID28.58 ID22.2 ID22.2
ID9.52
308 IDU
GAS Side ID12.7 ID12.7
OD6.35 OD6.35 Liquid Side Reducer
ID34.92 ID15.88
Reducer ID22.2 Reducer
ID19.05ID22.2 ID19.05 Reducer Reducer

257
main piping ID31.75 ID9.52

220
426 256 main
main piping
piping OD28.58 Insulation OD6.35
477 429 Insulation ID22.2
477 429 ID25.4 ID15.88
ID15.88 ID15.88 67 ID6.35
ID31.75 50 87 ID15.88 ID12.7piping main piping ID28.58 ODU ID9.52
ID15.88
ID31.75 87 ID15.88 ID12.7 main ODU
ID19.05 ID19.05 ID38.1 ID38.1 ID19.05 ID19.05 ID9.52 ID12.7
ID22.2 ID9.52
ID38.1 ID9.52 ID38.1 ID19.05 ID19.05 67 ID28.58 ID12.7
ID22.2 ID22.2
ID22.2
ID22.2
ID22.2 67
699
ID6.35
308 OD31.75
IDU ID25.4 Reducer ID22.2 ID19.05 IDU
Reducer
251
ID50.8 Reducer ID54.0 ID50.8
ID12.7 ID34.92 ID15.88 ID54.0 main piping

220 122
ID34.92 ID15.88
main piping

100

257

240
Insulation ID31.75 ID9.52

257
206

220
OD28.58 OD6.35

240
ODU ID31.75 Insulation
ID9.52

212
Insulation ID22.2

212
ID19.05 ID9.52 Insulation
Dimensions Insulation ID28.58 ID25.4 ID15.88 ID9.52
178

ID6.35 ODU ODU ID15.88


ID15.88 ODU ID15.88 ODU
Insulation ODU ID9.52 ID12.7
ID12.7 170 IDU ID28.58 ID9.52 ID12.7 ID12.7
ID28.58 ID6.35
MW-NP282A3 ID6.35 OD31.75 ID25.4 Reducer ID22.2 ID19.05 Reducer

376
ODU 308
308
IDU
IDU
IDU
251
IDU Insulation Insulation
251 Reducer ID44.45
251 IDU
GAS Side Liquid Side Reducer ID41.28
ID38.1
ID22.2 OD28.58 OD6.35
ID22.2 ID28.58 OD28.58 OD6.35 527
ID25.4 ID15.88 ID9.52 IDU
426 256 main piping ID9.52 ID28.58 ID25.4 ID15.88 ID9.52 ODU
ID15.88 426 256 main piping
ID15.88 ID15.88 67 ID6.35 50 MW-NP2682A3 ID12.7
ID19.05 ID15.88
ID19.05 67 ID6.35 50 ID12.7
ID19.05
ID22.2 ID19.05 ID9.52 ID9.52 OD6.35 OD31.75
OD31.75 ID25.4 Reducer ID22.2 ID19.05 Reducer
ID22.2 ID9.52 ID9.52 ID25.4 Reducer ID22.2 ID19.05 Reducer
ID22.2 ID22.2 Reducer GAS SideReducer Reducer Liquid Side Reducer
OD50.8 ID44.45 ID28.58
699
ID12.7 699 425 ID41.28 OD50.8 ID41.28 ID31.75
ID12.7
122

425
main piping
100

122

ID50.8 ID54.0 ID50.8 ID19.05


Insulation
206

main piping
100

ID54.0 ID50.8 ID19.05


ODU Insulation
ID50.8
206

ODU ID54.0 main piping ID22.2


ID19.05 ID9.52 ID54.0 main piping ID22.2
ID9.52
178

ID19.05 ID6.35 ID25.4


ID25.4 ID44.45 Reducer Reducer ID38.1 OD38.1 Reducer
178

ID15.88 ID25.4 main piping


Insulation ID15.88 ID6.35 ID25.4 main piping
Insulation
ID12.7 170 IDU ID22.2 ID19.05
ID12.7 170 IDU ID25.4 ID15.88 OD19.05
ID15.88
ODU ID12.7
ODU ODU
ODU
251 IDU
251 IDU ID22.2

189
OD28.58 ID12.7 Reducer ID9.52 ID6.35
ID22.2 Reducer

376

189
Insulation Insulation ID25.4 ID19.05

376
Insulation Insulation ID25.4 ID19.05
ID44.45 ID22.2 ID28.58
ID44.45 ID22.2
ID9.52 ID41.28 ID19.05
ID9.52 ID41.28 ID19.05
IDU OD6.35 ID9.52
ID38.1 275
275 IDU OD25.4
ID38.1 Reducer
OD6.35 527 Reducer
OD6.35
Reducer 527 IDU
Reducer ODU
ODU
IDU

65 66

OD50.8 ID44.45 ID28.58


Options

3. DRAIN BOSS
The drain boss is for the drain pipe connection in order to use the bottom base of the outdoor unit as a drain pan.
Header branch
Total Indoor Unit HP class No. of Header Branches Model
Model name Quantity
5-8 4 JMH-NP224A
Name Model Applicable Outdoor Unit HP
5 - 10 8 JMH-NP288A Q'ty
Drain Boss DBS-TP10A JTOH-BS1 series
8-18 1
20-36 2
38, 40 3
42-48 4

images:JMH-NP224A 50-54 3
56-60 4
62-66 5
GAS Side Liquid Side Reducer 68-72 6
74-78 5
80-84 6
86-90 7
92-96 8

images:DBS-TP10A Dimensions
ID19.05
Insulation 55 Drain Boss + Rubber Cap Drain Cap + Rubber Cap Drain Boss×2 Drain Cap×2
ID15.88
To close the drain hall
OD6.35 ID9.52
109

Dimensions Ø32 Ø32 Ø32 Ø32


60 ID15.88
3×60=180 ID12.7
JMH-NP224A
400

43

43

43

43
30

30

30

30
GAS Side Liquid Side Reducer
Insulation
ID19.05 ID19.05 55 Ø20 Ø20
Insulation 55 Insulation
ID15.88 ID15.88 Ø25 Ø25 Ø25 Ø25
81

OD6.35 OD6.35 ID9.52


ID9.52
109
109

60
3×60=180 Drain water treatment
60 60 375 ID15.88
ID15.88 install Drain
install
cap Drain cap
Drain water is discharged during heating and defrosting operation. (247) (247)
Ø32(Rain waterØ32
is also discharged.) Pay attention to the following.
3×60=180
ID6.35 ID12.7
3×60=180 ID12.7 Insulation 2 points 2 points
Ø32
400 Ø32
400 80 55
ID19.05
ID9.52 ID22.2 ID9.52
1. Choose a location where well drainage is available, or provide a drain ditch.
85

ID15.88 Insulation
2. Do not install the unit over a walkway, as condensation water may drip onto people. (90) (90)

43

43
Insulation OD15.88 ID19.05 OD6.35 ID9.52

43

43
Insulation

30

30
30

30
In the case of installing the unit in such a location, provide an additional drain pan. back back
111

3. Do not use the drain boss in a cold area. The drain water in the
Ø20drain pipe may freeze, and the drain pipe may crack.
81

Ø20

42

42
81

ID15.88 Ø25 Ø25 Ø25


Ø25

90

90
ID12.7
60 60
60
3×60=1807×60=420

(48)

(48)
3×60=180 Drain piping
Drain piping bottom bas
bo
JMH-NP288A 375 375 615
How to use field-supplied
field-supplied install Drain
install
boll Drain
2 points
boll 2 points
ID6.35 ODU rear ODUside rear side
ID6.35 Insulation Drain bossDrain boss Drain cap Drain cap
GAS Side Insulation Liquid Side Reducer Bottom view Side view
Insulation
install Drain cap install Drain cap
ID9.52 80 55ID9.52 (247) (247)
ID9.52 ID9.52 2 points 2 points
85

ID19.05 ID22.2 80 55
85

ID15.88 Insulation ID19.05 ID22.2


OD15.88 ID19.05 OD6.35 ID9.52
84

ID15.88 Insulation
OD15.88 ID19.05 OD6.35 ID9.52 (90)
(90)
111

60
7×60=420 back front
111

back front
ID15.88 685

42
ID15.88

42
ID12.7 ID6.35
60 Insulation
ID9.52 ID12.7

90
7×60=420 60

90
ID9.52
ID12.7
85

615 7×60=420

(48)
Drain piping bottom base

(48)
615 Drain piping install Drain boll 2 points bottom base
field-supplied field-supplied install Drain boll 2 points
Insulation ODU rear side ODU rear side
Drain boss Drain boss Drain cap Drain cap
Insulation
84

84

67 60 68
7×60=420
60
685 7×60=420
685
Options

4. CABINET COVER

Air inlet grille Protection net


HP class (kW) Air Inlet Grille HP class (kW) Protection Net
JTOH-BS1 series Rear Right Left JTOH-BS1 series Rear Right Left
8 - 12 (22.4 - 33.5) PSN-TP20BA PSN-TP20R PSN-TP20L 8 - 12 (22.4 - 33.5) PN-TP20BA PN-TP20R PN-TP20L
14 - 18 (40.0 - 50.0) PSN-TP20BB PSN-TP20R × 2 14 - 18 (40.0 - 50.0) PN-TP20BB PN-TP20R × 2
20 - 24 (56.0 - 67.0) PSN-TP20BC PSN-TP20R × 2 20 - 24 (56.0 - 67.0) PN-TP20BC PN-TP20R × 2

image:Air inlet grille image:Protection net

Left Side Left Side

Right Side Rear Side Right Side Rear Side

Options
Heat Recovery JTOR-BS1 series

69 70
Options

1. PIPING CONNECTION KIT ODU ODU


ODU ODU ODU
ODU
469 469 484 484 484
469
ID22.2 ID22.2
ID22.2 ID19.05ID19.05
ID19.05
ID31.75ID31.75 ID25.4 ID25.4 ID25.4 ID25.4
ID25.4
ID22.2 ID22.2
ID31.75 ID25.4 ID22.2 ID
Piping connection kit for the divergence between outdoor units Dimensions ID28.58ID28.58
ID38.1 ID38.1
ID38.1 ID28.58
ID28.58ID28.58
ID28.58
ID25.4 ID25.4
ID25.4 I
ID31.75ID31.75
ID31.75

158
95

158

158
158
Applicable Outdoor Unit

95

95
95

158
158
95
95
Model HP class Connectivity Remarks ID28.58ID28.58 ID28.58ID28.58
ID28.58 ID28.58
89 89
89 89
JTOR-BS1 series Number 383 383383 402 402 89
89
ODU ODU
ODU 402 IDU
IDU IDU IDU IDU ODU ODU
for Low Pressure Gas: 1 MC-NP21SX IDU IDU ODU
MC-NP21SX 26-48 2 for High/Low Pressure Gas: 1
for Liquid: 1 Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side Reducer
for Low Pressure Gas: 2 ODU
ODU OD28.58
ODU
ODU ODU
ODU ODU OD28.58OD28.58 OD28.58
OD28.58 OD19.05OD19.05
MC-NP30SX 50-54 3 for High/Low Pressure Gas: 2 469
469 ODU 484
484 ODU 378
378 OD28.58 ID22.2 ID22.2 OD19.05
469 484 378 ID22.2
for Liquid: 2 ID22.2
ID22.2 ID19.05
ID19.05 ID9.52
ID9.52 ID25.4 ID25.4
ID22.2 ID25.4 ID22.2
ID25.4 ID19.05 ID9.52 ID25.4
ID31.75
ID31.75
ID31.75
ID25.4
ID25.4
ID25.4 ID25.4 ID22.2
ID22.2 ID15.88
ID15.88 ID12.7
ID12.7 ID28.58ID28.58
ID28.58
ID15.88ID15.88
ID15.88
ID28.58 ID25.4
ID28.58 ID15.88 ID12.7
NOTE:The old model (MC-TTA1) is not available. ID38.1
ID38.1
ID28.58
ID38.1 ID28.58
ID28.58 ID28.58ID25.4
ID25.4 ID19.05
ID19.05 ID15.88
ID15.88 ID28.58ID28.58
ID28.58 ID12.7 ID12.7
ID12.7
ID31.75
ID31.75 ID19.05 ID15.88 OD25.4OD25.4
ID31.75 OD25.4 ID25.4 ID25.4
ID25.4 ID9.52 ID9.52
ID9.52
ID22.2 ID22.2

158
158

130
130
ID22.2

80
80
95
95

158
158
158

95
95

130
80
95
ID22.2 ID22.2

158
ID22.2

95
ID25.4 ID25.4
ID25.4ID19.05 ID19.05
images:MC-NP30SX ID28.58
ID28.58
ID28.58 8989
ID28.58
ID28.58
ID28.58
ID19.05
ID19.05
ID19.05 6767
ID19.05
ID19.05ID19.05
8989 303
303 67 ID19.05
383
383 89 402
402 89 303 ID25.4 ID25.4
383 ODU
ODU 402 ID25.4
IDU
IDU ODU IDU
IDU ODU
ODU IDU
IDU ODU
ODU
IDU IDU ODU IDU ODU
Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side Reducer ID22.2 ID22.2
ID22.2
ID25.4 ID25.4
ID25.4OD25.4 OD25.4
OD25.4
IDU ODU ODU
OD28.58
OD28.58 OD28.58
OD28.58 OD19.05
OD19.05 472 457
OD28.58 OD28.58 OD19.05
ID22.2
ID22.2 ID25.4 ID22.2 ID19.05
ID22.2 ID31.75
ID25.4
ID25.4 ID28.58 ID25.4 ID22.2
ID25.4 ID15.88
ID15.88
ID28.58
ID28.58 ID15.88 ID38.1 ID31.75 ID28.58 ID25.4
ID28.58
ID28.58
ID28.58 ID12.7
ID12.7
OD25.4
OD25.4 ID28.58 ID12.7
OD25.4 ID25.4
ID25.4 ID9.52
ID9.52
ID25.4

138
ID9.52

84
158
95
ID22.2
ID22.2
ID22.2
ID22.2
ID22.2
ID25.4
ID25.4 ID22.2
ID19.05
ID25.4 ID19.05 ID28.58 83
ID19.05 ID25.4 77
ID19.05
ID19.05 382 ODU 366 ODU
ID19.05
ID25.4
ID25.4
ID25.4 IDU
MC-NP30SX
ID22.2
ID22.2
Low Pressure Gas Side High/Low
ID25.4 Pressure
ID25.4 Gas Side
ID22.2 Liquid Side Reducer
ID25.4 OD25.4
OD25.4
OD25.4
IDU
IDUIDU ODU
ODU
ODU ODU
ODU
ODU ODU
ODU
ODU OD19.05
472
472472 457
457457 378
378378 ID31.75 OD28.58
ID25.4
ID25.4 ID22.2
ID22.2 ID25.4
ID31.75
ID31.75 ID25.4 ID19.05
ID22.2 ID19.05
ID19.05 ID9.52
ID9.52
ID9.52 ID15.88 ID19.05
ID31.75
ID28.58
ID28.58
ID28.58 ID25.4
ID25.4
ID25.4 ID22.2
ID22.2
ID22.2 ID15.88
ID15.88
ID15.88 ID12.7
ID12.7
ID12.7 ID28.58 ID12.7 ID25.4
ID38.1
ID38.1 ID31.75
ID38.1 ID31.75
ID31.75 ID28.58
ID28.58 ID25.4
ID25.4
ID28.58 ID25.4 ID19.05
ID19.05 ID15.88
ID15.88
ID19.05 ID15.88 OD31.75 OD28.58 ID28.58 ID25.4 ID9.52 OD25.4
ID22.2
ID25.4

138
138
84
84

138
84
158
158

130
130
158

130
80
80
95
95

80
95
ID28.58 OD25.4 OD25.4
ID22.2
For piping from bottom base - Perform the piping connection between
ID28.58
ID28.58
ID28.58 83
83 83 ID25.4
ID25.4
ID25.4 77
77 77 ID19.05
ID19.05
ID19.05
61
61 61
ID25.4 ID19.05
ID25.4
ID22.2
OD28.58 ID25.4
382
382382 ODU
ODU
ODU 366
366366 ODU
ODU
ODU 303
303303 ID25.4 ID28.58
outdoor units according to this figure. ID22.2
IDU
IDUIDU ODU
ODU
ODU OD28.58 ID22.2 OD15.88
Outdoor Unit A IDU
IDUIDU ID19.05 ID38.1
Piping Connection Kit 1 - Refer to “Installation & Maintenance Manual”
(Liquid) Accessory Pipe of the outdoor unit for the dimension and OD31.75 ID19.05
(Z-Shape) Piping Connection Kit 2 distance between outdoor units and between
(Liquid) piping connection kits.
Liquid Piping ID31.75
ID31.75
ID31.75
OD19.05
OD19.05
OD19.05
OD28.58
OD28.58
OD28.58
(Field-Supplied) ID25.4
ID25.4
ID25.4
ID19.05
ID19.05
ID15.88
ID15.88
ID15.88 ID19.05
ID28.58
ID28.58
ID28.58 ID12.7
ID12.7
ID12.7 ID25.4
ID25.4
ID25.4
Accessory Pipe OD31.75
OD31.75 ID28.58
ID28.58
ID28.58 ID25.4
ID25.4
ID25.4
OD28.58
OD31.75 OD28.58OD28.58 ID9.52
ID9.52
ID9.52 OD25.4
OD25.4
OD25.4
(Z-Shape) ID22.2
ID22.2ID22.2
ID25.4
ID25.4
ID25.4
High/Low Pressure Gas Piping ID28.58
ID28.58 OD25.4
OD25.4
ID28.58 OD25.4 OD25.4OD25.4OD25.4
(Field-Supplied) Outdoor Unit B ID25.4
ID25.4 ID22.2
ID22.2
ID22.2
Base ID25.4 ID19.05
ID19.05
ID19.05 ID22.2
ID22.2
ID22.2
(Field-Supplied) ID25.4
ID25.4
ID25.4 OD28.58 ID25.4
OD28.58
OD28.58 ID25.4
ID25.4
ID25.4
ID25.4
ID25.4 ID22.2
ID22.2 ID28.58
ID28.58
ID28.58
Low Pressure Gas Piping ID22.2
OD28.58
OD28.58
OD28.58 ID22.2
ID22.2
ID22.2 OD15.88
OD15.88
OD15.88
ID19.05
ID19.05
ID19.05 ID38.1
ID38.1
ID38.1
(Field-Supplied)
OD31.75
OD31.75
OD31.75 ID19.05
ID19.05
ID19.05
Piping Connection Kit 1
(High/Low Pressure Gas)

Accessory Pipe
Piping Connection Kit 1 (L-Shape)
(Low Pressure Gas)
Piping Connection Kit 2
(High/Low Pressure Gas)
Accessory Pipe
(L-Shape)
Piping Connection Kit 2 Outdoor Unit C
(Low Pressure Gas) High/Low Pressure
Liquid Piping Gas Piping Low Pressure Gas Piping
(Field-Supplied) (Field-Supplied) (Field-Supplied)

*Perform the piping connection between outdoor units according to this figure.
*Refer to the Installation & Maintenance Manual of the outdoor unit for the dimensions and distance between outdoor units and between piping connection kits.

71 72
Options

426

2. MULTI-KIT ID15.88 ID15.88 67


ID19.05 ID19.05
ID
ID22.2 ID22.2

Branching for indoor and outdoor connecting pipes ID12.7


main piping
Insulat

206
ODU
Line branch Dimensions for "After first branch_2 pipes portion" ID19.05

178
Insulation ID15.88
ID12.7
(First branch) ODU
MW-NP282A3 251 IDU
ODU Capacity
Multi-kit Model
HP class kW GAS Side Liquid Side Reducer
MW-NP282X3 8 - 10 22.4 - 28.0 426 426 256 256 main piping main piping ID9.52
ID15.88 ID15.88ID15.88 ID15.88 67 67 ID6.35 ID6.35
50 50
MW-NP452X3 12 - 16 33.5 - 45.0 ID19.05 ID19.05ID19.05 ID19.05
ID9.52 ID9.52
ID9.52 ID9.52 OD6.35
ID22.2 ID22.2ID22.2 ID22.2
Reducer
MW-NP562X3 18 - 20 50.0 - 56.0
365 main pip
MW-NP692X3 22 - 24 61.5 - 67.0 ID12.7 ID12.7 ID25.4 ID28.58 77

122

122
MW-NP902X3 26 - 54 73.0 - 150.0 main piping main piping ID22.2 ID28.58

100

100
Insulation Insulation

178 206

206
ODU ODU
ID19.05 ID19.05 ID9.52 ID9.52

178
(After first branch) Insulation ID15.88
Insulation ID15.88
ID6.35
170
ID6.35
IDU
170 IDU ODU
ID12.7 ID12.7 main piping
365 262
ODU ODU
3 pipes portion 2 pipes portion ID25.4 ID28.58 77 ID
251 251 IDU IDU

219
ID22.2 ID28.58 ID22.2 ID12.7 ID1
Insulation
Diameter (mm) Diameter (mm)
Multi-kit Model Total IDU HP Remarks ID19.05
Multi-kit Model Total IDU HP High/Low Remarks
Gas Pipe Liquid Pipe ODU ID15.88
Gas Pipe Liquid Pipe MW-NP452A3 ID9.52 ID9.52
Pressure Gas Pipe ID12.7
<6 φ15.88 φ9.52
MW-NP142X3 <6 φ15.88 φ12.7 φ9.52 290 IDU

251
GAS Side OD6.35 OD6.35 Liquid Side Reducer
φ19.05 φ9.52

219
MW-NP282A3 6 - 8.99 ID22.2
6 - 8.99 φ19.05 φ15.88 φ9.52 Reducer Reducer
main piping main piping Insulation Insulation
365 365 main piping
MW-NP282X3 9 - 11.99 φ22.2 φ9.52 262 262 main piping
ID19.05
ID25.4
9 - 11.99 φ22.2 φ19.05 φ9.52 ID25.4 ID25.4 ID28.58 ID28.58
77 77 ID9.52 ID9.52
56 56 OD28.58 ID15.88 ID9.52
ID15.88 173
12 - 15.99 φ25.4 φ12.7 ID22.2 ID22.2
ID28.58 ID28.58 ID12.7 ID12.7
ID12.7 ID12.7
12 - 15.99 φ25.4 φ22.2 φ12.7 MW-NP452A3 For 2 pipes ID12.7
MW-NP452X3 ODU
16 - 17.99 φ28.58 φ12.7 290 IDU ID12.7 OD6.35
16 - 17.99 φ28.58 φ22.2 φ12.7 For 3 pipes Reducer ID22.2 ID19.05 Reducer
MW-NP692A3 18 - 25.99 φ28.58 φ15.88 ODU ODU
MW-NP562X3 18 - 21.99 φ28.58 φ22.2 φ15.88 ID25.4 365 main piping
ID12.7

163
ID12.7

163
26 - 35.99 φ31.75 φ19.05

139
139
MW-NP692X3 22 - 25.99 φ28.58 φ25.4 φ15.88 OD28.58 ID15.88 ID22.2 ID9.52 ID28.58 77

251
251
MW-NP902A3 ID9.52 ID9.52
< 36

219
219
ID22.2 ID25.4
φ38.1 φ19.05 ID22.2
Insulation ID6.35 ID6.35
26 - 35.99 φ31.75 φ28.58 φ19.05 Insulation Insulation Insulation ID28.58
MW-NP902X3 ID19.05 ID19.05 ID12.7 OD6.35
< 36 φ38.1 φ 31.75 φ19.05 Reducer ID22.2 ID19.05 Reducer
ID15.88 ID15.88 173 IDU173 IDU
ID12.7 ID12.7
ODU ODU
290 290 IDU IDU
images:MW-NP282X3

251
219
Insulation ID22.2
ID25.4 ID25.4
Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side Reducer OD28.58 ID15.88 ODU ID19.05
OD28.58 ID15.88 ID9.52 ID9.52
MW-NP692A3 ID15.88
ID12.7 ID12.7
ID12.7 OD6.35 OD6.35
GAS Side Liquid Side Reducer 290 IDU
Reducer ID22.2 Reducer
ID19.05 ID22.2 ID19.05 Reducer Reducer
365 365 main piping main piping 387 387 main piping main piping
ID25.4
ID22.2 ID22.2 ID28.58 ID28.5877 77 ID15.88 ID15.88 ID12.7 ID12.7
67 67
ID25.4 ID25.4 ID19.05 ID19.05 ID15.88 ID15.88 OD28.58 ID15.88 ID9.52
ID28.58 ID28.58 ID22.2 ID22.2
ID12.7 OD6.35
Reducer ID22.2 ID19.05 Reducer
ID9.52 ID9.52 main piping
477

219

219
ODU ODU ID31.75 87

251

251

191

191
ID15.88 ID15.88

219

219
Insulation Insulation
ID22.2 ID22.2 ID38.1 ID38.1
Insulation Insulation
ID12.7 ID12.7
Header branch ODU ODUID19.05 ID19.05
ID9.52 ID9.52
ID15.88 ID15.88 ID6.35 ID6.35
ID34.92
Multi-Kit Model Total IDU HP No. of Header branches Remarks ID12.7 ID12.7

257
main piping ID31.75
251 251 IDU IDU

220
290 290 IDU IDU 477 429
JMH-NP288X 5 - 10 8 For 3 pipes ID31.75 Insulation 87 ID15.88 ID12
ID38.1 ODU
ID38.1 ID19.05 ID19.05
JMH-NP224A 5-8 4 ID25.4 ID25.4 ID28.58 ID22.2 ID22.2
For 2 pipes OD28.58 OD28.58
ID15.88 ID15.88
JMH-NP288A 5 - 10 8 MW-NP902A3 ID9.52 ID9.52 308 IDU

ID34.92 ID15
GAS Side ID12.7 ID12.7
OD6.35 OD6.35 Liquid Side Reducer

257
ID31.75
images:JMH-NP224A

220
Reducer ID22.2 Reducer
ID19.05ID22.2 ID19.05 Reducermain pipingReducer Insulation
477main piping 429 Insulation ID22.2 OD28.58 OD6.35
477 429
ID15.88 ID12.7 main piping ID28.58 ID25.4 ID15.88
ODU ID15.
ID9.5
ID31.75 87 ODU
ID15.88 main piping
ID31.75 ID38.1 ID38.187 ID19.05ID12.7 ID19.05 ID9.52 ID12.
GAS Side Liquid Side Reducer ID38.1 ID38.1 ID19.05 ID19.05
ID22.2 ID22.2 67
67 ID28.58 ID12.7ID6.35
ID22.2 ID22.2 308 IDU
OD31.75 ID25.4 Reducer ID22.2 ID19.05251 IDU
Reducer
Reducer
ID34.92 ID15.88
ID34.92 ID15.88

257

240
ID31.75 ID9.52
220
OD28.58 OD6.35
257
Insulation ID9.52

212
ID22.2

240
ID31.75
220

Insulation Insulation ID25.4 ID15.88

212
ID28.58 ID9.52
Insulation ODU ID15.88
ODU ODU ID15.88
ODU ID9.52 ID12.7 ID12.7
ID28.58 ID9.52 ID12.7
ID28.58 ID6.35 OD31.75
308 IDU ID6.35 IDU
ID25.4 Reducer ID22.2 ID19.05 Reducer
308 IDU 251
IDU Reducer
251

ID22.2 OD28.58 OD6.35


73 ID22.2 ID28.58 OD28.58 ID25.4 OD6.35
ID15.88 74
ID25.4 ID15.88 ID9.52
ID28.58 ID9.52
ID12.7
ID12.7
Options

ODU main piping


365
ID25.4 ID28.58 77
main piping
426 main piping
ID28.58
ID15.88 ID15.88 262 main piping 256

ID19.05 ID19.05 ID9.52 ID6.35


50
67 56
ID22.2 ID22.2 ID12.7 ID12.7 ID9.52 ID9.52

main
ODU main piping ID22.2 426

219
365 ID15.88 ID15.88

251
ID12.7 ID19.05

122
77

100
ID12.7 ID25.4 ID28.58

163
ID19.05 ID19.05
Dimensions for "First branch & After first branch_3 pipes portion" ID15.88

206

139
ID9.52
ID28.58

178
ID6.35 ID22.2 ID12.7ID22.2 ID22.2
ID9.52
ID19.05 ID12.7 IDU
173 ID6.35
ID15.88 290 IDU
IDU 170 ID1
MW-NP142X3 ODU ODU MW-NP562X3
ODU
251 IDU ID22.2

219
Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side Reducer Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side ReducerID19.05

251
ID19.05
main
mainpiping
mainpiping
piping main
mainmain
piping piping
piping ODUODUODU main piping
mainmain piping
piping ID15.88 ID12.7
main
main
main piping
piping
piping ID15.88 ID25.4
426
426
426 ODUODUODU main
main
piping
piping
main piping 426426 426 387 387ID12.7
387
ID22.2 ODU
ID15.88
ID15.88
ID15.88 ID15.88
ID15.88
ID15.88 262
262
262 main
mainpiping
main piping
piping 256
256
256 365 365 365 OD28.58 ID15.88 O
ID15.88
ID15.88 ID15.88 ID15.88
ID15.88 ID15.88 ID15.88 ID15.88
ID15.88 ID9.52 ID9.52
ID9.52
ID6.35
ID6.35
ID6.35 77 77 77 67 67 67 67 67 67 251 IDU
ID19.05
ID19.05
ID19.05 ID19.05
ID19.05
ID19.05 ID9.52
ID9.52
ID9.52 505050 ID25.4 ID25.4
ID25.4 ID28.58 ID28.58
ID28.58
676767 565656 ID19.05
ID19.05 ID19.05 ID19.05
ID19.05 ID19.05 ID19.05 ID19.05
ID19.05 ID12.7 ID12.7
ID12.7
290 IDU
ID22.2
ID22.2
ID22.2 ID22.2
ID22.2
ID22.2 ID12.7
ID12.7
ID12.7 ID12.7
ID12.7
ID12.7 ID9.52
ID9.52
ID9.52 ID9.52
ID9.52
ID9.52 ID28.58
ID28.58
ID28.58
OD6.35 ID9.52 ID22.2
ID22.2 ID22.2 ID22.2
ID22.2 ID22.2 ID22.2 ID22.2
ID22.2 ID15.88 ID15.88
ID15.88
ODU main piping
ID12.7
365
ID22.2 ID19.05
ID12.7
ID12.7
ID12.7 ID12.7 ID12.7
ID12.7 ID22.2

122
122
122
100
100
100
ID12.7
ID12.7
ID12.7
163
163
163
main piping main piping ID25.4 ID25.4 ID28.58 77
206
206
206

139
139
139

ID9.52
ID9.52
ID9.52 ID15.88 ID15.88
ID15.88
426 426 main piping
178
178
178

ID22.2 ID22.2
ID22.2

178
178
178

191
191
191
ID6.35
ID6.35
ID6.35 OD28.58 ID15.88 ID28.58
OD6.35

219
219
219
ID15.88 ID15.88 ID15.88 256

206
206
206
67 ID15.88 67 ID19.05
ID19.05 ID19.05

219
219
219
ID9.52
ID9.52
ID9.52 ID12.7 ID12.7
ID12.7 ID9.52

251
251
251
ID19.05
ID19.05
ID19.05 ID19.05 ID19.05
ID19.05
ID12.7
ID12.7
ID12.7 IDUID19.05
IDU
IDU ID19.05 ID19.05 ID19.05 ID15.88 ID15.88
ID15.88 ID12.7 ID12.7
ID12.7
173173
173 ID6.35
ID6.35
ID6.35 ID15.88 ID15.88
ID15.88 ID9.52 ID6.35 ID9.52
ID9.52
ID9.52
ID15.88
ID15.88
ID15.88
ID22.2 ID22.2 ID22.2 ID22.2 ID22.2 ID22.2ID12.7
ID22.2 ID12.7
ID12.7 ODUODUODU ID9.52 50
IDU IDU
IDU 170170
170
ODU
ODU
ODU ODU
ODU
ODU ID6.35 ID6.35
ID6.35
251 251 251 IDU IDU IDU ID12.7
ODU
ODU
ODU ODU main piping ODU
251
251
251 IDU
IDU
IDU 251 251 251 IDU IDU IDU

251
290290 290 IDU IDU IDU ID22.2 ID19.05

219
365 365
ID22.2

122
ID22.2 ID22.2

100
ID12.7 ID12.7 ID19.05

206

206
ID25.4 ID28.58 77 ID25.4 ID2

178

178
ID15.88
ID9.52
ID28.58 ID12.7 ID28.58
ID19.05 ID12.7 ID19.05 ID12.7 ID6.35
ID15.88 ID15.88 ID25.4
ID25.4
ID25.4 290 IDU
170
OD6.35
OD6.35
OD6.35 ID9.52
ID9.52
ID9.52 OD28.58
OD28.58
OD28.58 ID15.88
ID15.88
ID15.88 OD6.35
OD6.35
OD6.35
ODU ODU ID9.52
ID9.52
ID9.52
MW-NP282X3 MW-NP692X3 ODU IDU
251 IDU 251 IDU

251
219
Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side Reducer Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side ID22.2
Reducer ID22.2
ID12.7
ID12.7
ID12.7
main
main
main piping
piping
piping main
main
mainpiping
piping
piping ODU
ODU ODU main
mainpiping
main piping
piping ODU
ODU ODU main
mainpiping
main piping
piping ID19.05 ID19.05
ODU
ODU ODU main
mainpiping
main piping
piping ID25.4
426
426
426 426
426
426 main
main
main piping
piping
piping ID22.2
ID22.2
365ID22.2
365 ID19.05
365 ID19.05
ID19.05 365
365 365 387
387 387ID15.88 OD28.58 ID15.88
OD6.35
ID15.88
ID15.88
ID15.88
ID15.88 ID15.88
ID15.88
ID15.88 676767 ID15.88
ID15.88
ID15.88 ID15.88
ID15.88
ID15.88 676767 256
256
256
ID22.2
ID22.2ID22.2 ID22.2
ID22.2ID22.2 ID12.7
ID9.52
ID9.52ID9.52 ID12.7
ID19.05
ID19.05
ID19.05 ID19.05
ID19.05
ID19.05 ID19.05
ID19.05
ID19.05 ID19.05
ID19.05
ID19.05 ID9.52
ID9.52
ID9.52 ID6.35
ID6.35
ID6.35 ID15.88 ID15.88
ID15.88
ID25.4
ID25.4ID25.4 ID28.58 ID28.58
ID28.58 7777 77 ID25.4
ID25.4ID25.4 ID28.58 ID28.58
ID28.58 7777 77 290
ID12.7
ID12.7ID12.7 IDU ID12.7 290
ID22.2
ID22.2
ID22.2 ID22.2
ID22.2
ID22.2 ID22.2
ID22.2
ID22.2 ID22.2
ID22.2
ID22.2 ID9.52
ID9.52
ID9.52 50
5050 ID19.05 ID19.05
ID19.05 6767 67
OD6.35 ID9.52 ID28.58
ID28.58
ID28.58 ID28.58 ID28.58
ID28.58 ID15.88 ID15.88
ID15.88 ID19.05
ID22.2
ID22.2ID22.2
main piping ODU main piping
426 main piping ID22.2
ODU main piping 477
262
122
122
122

365 ID15.88 ID15.88


100
100
100

ID12.7
ID12.7
ID12.7 ID12.7
ID12.7
ID12.7 ID31.75 ID38.1 87
206
206
206

206
206
206

ID25.4 ID28.58 77 ID9.52 56


ID19.05 ID19.05 67 ID25.4

219
219

219
ID38.1 ID34.92
178
178
178

178
178
178

251
251

251

251
251

251

191
191

191
ID12.7 ID12.7

219
219

219

219
219

219
ID9.52
ID9.52
ID9.52 ID28.58 ID22.2 ID22.2 OD6.35
ID22.2ID22.2
ID22.2 ID22.2
ID22.2ID22.2 ID15.88
ID15.88 OD28.58
ID15.88 ID15.88 ID9.52
ODU
ID19.05
ID19.05
ID19.05 ID12.7
ID12.7
ID12.7 ID19.05
ID19.05
ID19.05 ID12.7
ID12.7
ID12.7 ID6.35
ID6.35
ID6.35 ODU main piping
ID19.05 ID19.05
ID19.05 ID19.05 ID19.05
ID19.05 ID12.7
ID12.7ID12.7
ID15.88
ID15.88
ID15.88 ID15.88
ID15.88
ID15.88 365
170
170
170 ID9.52
ID9.52ID9.52 477 ID12.7
ID15.88
ID15.88
ID15.88 ID15.88 ID15.88
ID15.88
ODU
ODU
ODU ODU
ODU
ODU ID31.75 ID38.1 87 ID22.2
ODU
ODU
ODU IDU
IDUIDU ID22.2 ID6.35
ID6.35ID6.35

163
ID12.7
ID12.7ID12.7 ID12.7 ID12.7
ID12.7ID12.7 ID19.05 ODU

139
ID25.4 ID28.5

257
ODU main piping

206
251
251
251 IDUIDU
IDU 251
251
251 IDUIDU
IDU 251 ID38.1
251 251 IDU
IDU IDU ID34.92

220
main 290
290 290 IDU
IDU IDU 290
290 290 IDU
IDU IDU 365

178
251
ID22.2 piping ID22.2 ODU ID28.58
ID12.7 477
219

426 ID19.05 main piping ODU main piping


ODU main piping ID19.05 ID22.2 ID31.75
ID9.52 ID31.75 ID38.1 87 365
365 ID15.88 ID15.88 ID15.88 ID12.7 262 477 main piping
ID15.88 ID6.35 ID31.75 ID38.1 ID34.92
ID38.1 87 ID22.2 ID25.4 ID28.58 ID28.58
ID25.4 ID28.58 77 ID9.52 56 main piping 77
ID12.7 ID19.05 ID19.05 67 ODU ID28.58
ID12.7 ID12.7 173 IDU ID25.4 308 ID28.58 IDU
ID28.58 ID22.2 ID22.2 ID38.1 ID34.92
251 IDU

257
ODU ID28.58 77 ID22.2

220
290 IDU ID25.4
ID25.4ID25.4 ID19.05
OD6.35
OD6.35
OD6.35 OD6.35
OD6.35OD6.35 ID31.75
ID9.52
ID9.52
ID9.52 OD28.58
OD28.58
OD28.58 ID15.88
ID15.88
ID15.88 ID15.88
MW-NP452X3 MW-NP902X3 ID9.52
ID9.52ID9.52

257
ID22.2

163
ID12.7 ID28.58 ID22.2

251
ID12.7

220
139

219
206
ID12.7
ID12.7ID12.7
Low Pressure Gas Side High/Low Pressure Gas Side Liquid Side ID22.2 Reducer Low Pressure Gas Side High/Low Pressure Gas Side LiquidID31.75
Side 308 Reducer
ID22.2ID19.05

257
178
251

IDU

251
290

220
main piping ID12.7

219
219

426 main
main piping
piping ID19.05 main piping
ID19.05 ID19.05
ID19.05
ID19.05
ID9.52
ODUODU
ODU ID19.05ID15.88
ODU main piping ODUODU ODU mainmain
piping
piping
main piping ID31.75 mainmain
piping
main
piping
piping ID28.58 ID25.4 ID25
426426 mainmain piping
piping ID25.4 ID15.88 ID12.7 ID28.58 ID15.88 ID12.7
ODU
ODU 365 main piping
main piping ID15.88 ID15.88 262
ID15.88 ID22.2
ID22.2ID22.2 365 365365
OD28.58 477 477477 ID6.35 429 429429 OD31.75 ID22.2 ID28.58
262262 ID15.88 OD6.35 308
ID28.58 IDU
ID25.4365365 ID28.58 77
ID15.88
ID15.88
ID19.05
ID15.88
ID15.88
ID19.05 67
ID9.52
ID12.7 56 ODU ID9.52
ID31.75 ID31.75
ID31.75 ID38.1 ID38.1
ID38.1 173
87 87 87 IDU ID22.2 ID22.2
ID22.2 ID12.7
290 IDU
ID25.4
ID25.4 ID28.58 ID28.58
ID28.58 ID9.52
ID9.52 56 56 mainmain
piping
main
piping
piping ID15.88
ID15.88
ID15.88 ID15.88
ID15.88
ID15.88
77 77 ID19.05ID22.2
ID19.05 ID19.05
ID19.05
ID22.2 67 67 ID12.7 ID12.7 251 IDU ID25.4 ID25.4
ID25.4 ID28.58
ID28.58 ID28.58 308 IDU
ID28.58
ID28.58 ID12.7
ID12.7 ID12.7
ID12.7 ID38.1 ID38.1
ID38.1 ID34.92
ID34.92 ODU
ID34.92 ID19.05
ID19.05
ID19.05 ID19.05
ID19.05
ID19.05 67 67 67 290 IDU
ID22.2
ID22.2 ID22.2
ID22.2 290 IDU ID28.58 ID28.58
ID28.58 77 77 77
ID22.2
ID22.2
ID22.2 ID22.2
ID22.2
ID22.2
ID12.7 ID28.58 ID25.4 ID25.4 ID22.2
ID22.2 ID19.05 OD31.75 ID22.2 ID28.58 ID19.05 OD28.
ID22.2
163

ID12.7
139

ID22.2
ID22.2 ID15.88
163
163
206

ID12.7
ID12.7
139
139
178
251

206
206

ID22.2 ID12.7 ID12.7


ID12.7
ID12.7

257

257
257
ID22.2
ID22.2 ID22.2 ID28.58 ID25.4 ID25.4 ID22.2
219

240

240
240
251

251
251
ID12.7
178
178
251
251

220

220
ID22.2
ID22.2 ID19.05 220

219

219
219
ID12.7
ID12.7 ID15.88
ID15.88
ID15.88

212

212
212
ID19.05 ID31
219
219

ID19.05
ID19.05 ID9.52 ID25.4 ID19.05
ID19.05 ID19.05 OD31.75 ID22.2 ID28.58
ID9.52
ID9.52
ID9.52 ID19.05 OD28.58
ID19.05
ID19.05 ID15.88 ID12.7 ID28.58 ID25.4 ID25.4 ID22.2
ID15.88 ID9.52
ID9.52
OD28.58ID6.35 ID15.88 ID31.75
ID31.75
ID31.75 ID12.7
ID12.7
ID12.7 ID15.88
ID15.88
ID15.88 ID12.7
ID12.7 OD6.35 ID15.88
ID15.88 ID15.88 OD31.75 ID22.2 ID28.58 ID19.05
ID15.88
ID15.88 ID9.52 ID9.52
ID9.52
ID9.52 OD28.58
ID12.7 ODU ID6.35
ID6.35 ID15.88 ID12.7
173 IDU ID28.58 ID28.58
ID28.58 ID12.7
ID12.7 ID12.7 ID6.35ID6.35
ID6.35
ID12.7
ID12.7 ODU ODU ID31.75
251 IDU 173173
ODU IDUIDU ID9
308 308308 IDU IDUIDU 251 251251 IDU IDUIDU ID12.7 OD6.35
290 IDU 251251 IDUIDU ODU
ODU 290 290290 IDU IDUIDU
ID31.75
290290 IDUIDU ID12.7 ODUODU
ODU
ID22.2 ID19.05 ID9.52
OD6.35
ID9.52
OD6.35

ID25.4
ID25.4
ID25.4 ID28.58
ID28.58
ID28.58
ID25.4
ID25.4
ID25.4 ID25.4
ID25.4
ID25.4
ID22.2ID22.2
ID22.2
75 OD28.58 ID15.88 OD6.35 76
OD28.58
OD28.58 ID15.88
ID15.88 OD6.35
OD6.35 ID9.52 OD31.75
OD31.75
OD31.75 ID22.2
ID22.2
ID22.2 ID28.58 ID28.58 ID19.05
ID28.58 ID19.05
ID19.05 OD28.58
OD28.58
OD28.58
ID9.52
ID9.52 ID15.88
ID15.88
ID15.88
Options

80 55

ODU OD15.88 ID19.05 OD6.35 ID9.52

111
ID15.88 ID22.2 for Low Pressure Gas piping for Liquid piping
ID19.05 ID15.88

ID12.7
IDU 90 90
60
7×60=420
615 OD12.7 ID9.52 OD15.88 ID12.7
for High Pressure Gas piping for High Pressure Gas piping

3. CH-BOX
ODU

111
ID15.88 ID22.2

ID19.05
ID15.88 Specifications
Dimensions for "Header branch" ID12.7
IDU
60
7×60=420 Type Single-Port
615
Model Name JCH-AP160SSX
JMH-NP288X

Low Pressure Gas Side Liquid


80 Side 55
80 55
Reducer
Images
ODU OD15.88 ID19.05 OD6.35 ID9.52 80 55
ODU
111 111

ID15.88 ID22.2 OD15.88


for Low Pressure GasID19.05
piping OD6.35 ID9.52
for Liquid piping

84
ID19.05
ID15.88 ID15.88
ID22.2 ODU
for Low Pressure Gas piping for Liquid piping OD15.88 ID19.05 OD6.35 ID9.52
ID19.05 ID15.88 Dimensions (H*W*D) (mm) 191 × 301 × 214

111
ID12.7 ID15.88 ID22.2 for Low Pressure Gas piping for Liquid piping
90 60 90
IDU ID19.05 ID15.88 7×60=420 80 55
ID12.7 60
7×60=420
IDU 90 685 90
60
80 55 N/W (kg) 6
615 ID12.7
7×60=420 ODUOD12.7 ID9.52 IDUOD15.88 ID12.7 90 90
IDU OD15.88 ID19.05 OD6.35 ID9.52
60
615 ODU ID15.88 forOD12.7 ID22.2 Gas ID9.52
High Pressure piping forOD15.88
7×60=420 High ID12.7
Pressure Gas pipingID19.05 Power Supply 1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz

111
ID6.35 OD15.88 for Low Pressure Gas
OD6.35 piping
ID9.52 for Liquid piping
ID9.52
for High Pressure Gas piping 615 for High
forPressure Gas piping OD12.7
for Liquid piping ID9.52 OD15.88 ID12.7
111
ID15.88 ID22.2 ID19.05 ID15.88 Low Pressure Gas piping
80 55
Electrical Details Power Input (W) 5
ID19.05 ID15.88 ID9.53
ID12.7 ID12.7 for High Pressure Gas piping for High Pressure Gas piping
High Pressure Gas Side

85
IDU 90 90
ID12.7 60 Current (A) 0.1
ODU IDU 7×60=420 OD15.88 90 ID19.05 OD6.3590 ID9.52
60
7×60=420 615 OD12.7
for Liquid pipingID9.52 OD15.88 Maximum
ID12.7 Total Capacity Index (kW) 16
111

ID15.88 ID22.2 ODU for Low Pressure Gas piping


ODU ID19.05 ID15.88 615 OD12.7 ID9.52 OD15.88 ID12.7
for High Pressure Gas piping for High Pressure Gas piping
Number of Port (for IDU) 1
111 111

ID15.88
ODU ID22.2
ID12.7 for High Pressure Gas piping for High Pressure Gas piping
ID15.88 ID15.88
ID22.2 IDU 90 90
ID19.05 60 ODU
ID15.88 Maximum Connectable IDUs per Port 7
7×60=420

111
ID19.05 ID12.7 ID15.88 ID22.2
IDU 615ID19.05 ID15.88 OD12.7 ID9.52 OD15.88 ID12.7
ID12.7 60 ID19.05 Insulation 55 Maximum Piping Total piping length between CH-Box and each
7×60=420
IDU ID15.88
317S154178 40m
60 ID12.7 for High Pressure Gas piping for High Pressure Gas piping length indoor unit per branch
615
7×60=420 DIMENSIONAL DRAWING OF SINGLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
ODU IDU
615 60 OD6.35 ID9.52
ODU ID15.88 ID22.21 7×60=420
2 3 111
4 5 6 Between
7 CH-Boxes 8 15m
109

615
111

ID15.88 ID22.2 ID15.88


ID19.05
ID15.88 ID12.7 Maximum Height
ID19.05 Between CH-Box and IDU 15m
A IDU Suspension Bracket difference
Specifications A
ID12.7 60 60 ID15.88 (JCH-AP160SSX)
IDU 7×60=420 2-(11×34) Slotted Hole Model CH-AP160SSX
ODU 60 2-Suspension Bolts M10 or W3/8
3×60=180 615 ID12.7 Between IDUs
AC P connecting
m ` Q O O to
| Qsame
S O uCH-Box 4m
JMH-NP224A 7×60=420 (Field-Supplied) C T O g @ P m ` Q Q O u C U O g
111

ID15.88 ID22.2 Upper Side 23 330 Power Supply


400 Min.70 AC P m ` Q R O u C T O g @ P ` Q Q O u C U O g
ID15.88 615 (For Suspension Bolt)
84 84

ID19.05 Input [W] 5


GAS Side Liquid Side Reducer

40
ID12.7 Refrigerant R410A 317S154178
100

60 IDU
Insulation Net Weight [kg] 6
84

60 ID19.05 DIMENSIONAL DRAWING OF SINGLE BRANCH TYPE COOL


ID19.05 7×60=420 7×60=420 Electrical Box 55
317S154178
60 Insulation 55 Insulation Connectable Indoor Unit
685
7×60=420 ID15.88 615 Total Capacity 6.0HP
DIMENSIONAL DRAWING OForSINGLE
less BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
ID15.88 1 2 3
685 IDU 60 Number of Connectable
OD6.35
B
ID9.52
7×60=420
Min.300 Min.300 OD6.35 ID9.52 Dimensions
1 Indoor Unit 2 7 3 B 4 5 6 Service
7 Space 8
81

IDU 685 Min.70


ID6.35
84

ID9.52
109

A
109

ID6.35 IDU Bottom Side


ID9.52
84

ID9.53 60 Service Access Door A A


ID12.7 Refrigerant Gas Pipe Suspension Bracket Specifications 2-Suspension Bolts M10 or W3/8
85 85

ID9.53 ID9.52 ID6.35 60 (□450)


3×60=180 376 (JCH-AP160SSX)
Connection (Field-Supplied)
ID12.7 7×60=420 Electrical Box or W3/8 (Ø15.88 Flare Nut)
2-(11×34) Slotted Hole Model CH-AP160SSXUpper Side Min.70
60 ID15.88 60 60 375 ID15.88 2-Suspension Bolts M10
7×60=420 ID9.53 685 (Available for both sides)
(Field-Supplied) 23 330 AC P m ` Q O O | Q S O u C T O g @ P m ` Q Q O u C U O
317S154178
ID12.7 3×60=180 38 301 38 Upper Side Power Supply
ID12.7
85

3×60=180 ID12.7 685 ID6.35 Min.70 AC P m ` Q R O u C T O g @ P ` Q DIMENSIONAL


Q O u C U ODRAWING
g OF
ODU IDU Insulation (For Suspension Bolt)
84

400 Input [W] 5

100
400 Ground Terminal (M5)
ODU IDU 80 55

40
ID9.52 ID6.35 214 Refrigerant Gas(Low Pressure) (in Electrical Box) Refrigerant
Electrical Box R410A 1 2

100
ID19.05 ID9.52ID22.2 ID9.52 Pipe Connection
ID6.35 60 ODUC 89 C Net Weight [kg] 6
85

ID9.52 ID9.53 (Ø19.05 Flare Nut)


Insulation Electrical Box
ID15.88
7×60=420 Insulation
Insulation OD15.88 ID19.05 OD6.35 ID9.52

191
ID12.7 Connectable Indoor Unit
180
85

ID9.53 685 B
Total Capacity 6.0HP or less
Min.300 Min.300
ID12.7 Refrigerant Gas(High/Low Pressure) A
85
39

Pipe Connection Number of Connectable Min.70


IDU B Min.300 Min.300 7 B
Indoor Unit
111

(Ø15.88 Flare Nut) 2-Suspension Bolts M10


Bottom or W3/8
Side
ODU Min.70 (Field-Supplied)
81

ID6.35 Upper Side


81

ID9.52 82 301 89 Service Access Door Min.70

25
ODU Bottom
111 Side (□450)
ID15.88
ID9.53 Control Wiring 40 221 Service Access Door
20

ID12.7 ID12.7 Power Supply Wiring Refrigerant Gas Pipe


60 Connection(Ø20) (□450)
85

60 40 54 Connection(Ø20) Indoor Unit Connecting Side 376 Connection


60

100
3×60=180 Electrical Box (Ø15.88 Flare Nut)
3×60=180 7×60=420 (Available for both sides)
JMH-NP288A 151 63 Electrical Box
38

D 375 D 38 301 38
375 615 <NOTES>
ODU 214 Refrigerant Gas(Low Pressure)
ID6.35 ID6.35 1)Change-Over(CH)Boxis composedof mechanical parts such as electronic expansion Ground Terminal (M5) Pipe Connection
GAS Side Insulation Liquid Side Insulation
Outdoor Unit Connecting Side Reducer 214
valves for switching cooling/heating Refrigerant
operation. Gas(Low
Therefore,make surePressure)
to install (in Electrical Box)
C B Min.300
(Ø19.05 Flare Nut) Min
Insulation C the service access doors on the electrical box Pipe Connection
side and indoor unit connecting side.
89 C Min.70
ID9.52 ID9.52 ID9.52 80 55 ID9.52 (Ø19.05 Flare Nut)
2)Operating soundand refrigerant flow soundmaybe heard from the CH-Box Refrigerant Gas(High/Low Pressure)
Bottom Side
85

191

39
85

180
ID19.05 ID22.2 80 55 when the electronic expansion valves in the CH-Boxare activated for RUN/STOP, Pipe Connection
Service Access Door
ID15.88 Insulation ID19.05 ID22.2 Thermo-ON/OFF,defrosting or switching operation. Refrigerant Gas(High/Low Pressure)
Therefore,install (Ø15.88 Flare Nut)
(□450)
39

OD15.88 ID19.05 OD6.35 ID9.52 Pipe Connection


84

ID15.88 Accessories Insulation the CH-Boxin the ceiling of corridor so the refrigerant flowNut)
(Ø15.88 Flare soundmay
OD15.88 ID19.05 OD6.35 ID9.52 not heard in the room.Asfor the ceiling material,select a material like
No. Accessory Figure Qty. Purpose Control Wiring
82 301 89

25

20
a plaster board(at least 9mm)whichminimizes operation sound. 11140 Connection(Ø20
111

E 54
E 160 Reducer 7×60=420 1 For refrigerant gas(low pressure) pipe onoutdoorunit side 3)Do not install the CH-Boxin a place near bed roomor hospital roomssince the Control Wiring 40 221
Ó P X D O T ¨ Ó P T D W W
20

Power Supply Wiring


111

refrigerant flow sound


40 maybe54heard from the CH-Boxwhenswitching Connection(Ø20) 214 Refrigerant Gas(Low
685 Connection(Ø20) Indoor Unit Connecting Side
ID15.88 2 AccessoryPipe(for Flare Nut) 2 For refrigerant gas(high/low pressure) pipe onoutdoorunit side
between cooling/heating operation. D C
151 63 Pipe Connection
Ó P T D W W ¨ h D c D Ó P Q D V For refrigerant gas pipe onindoor unit side (Ø19.05 Flare Nut)
ID12.7 ID15.88 4)Makesure the liquid pipe is correctly installed to the appropriate unit.
151 63

38
60 ID6.35 AccessoryPipe(for Flare Nut) Insulation D D
ID9.52 ID12.7 3 1 For refrigerant gas(low pressure) pipe onoutdoorunit side <NOTES> Outdoor Unit Connecting Side
Ó P X D O T ¨ h D c D Ó P X D R
7×60=420 60 DATE REVD. CHKD. APPD. 1)Change-Over(CH)Boxis composedof mechanical parts such as electronic expansion Refrigerant Gas(Hig

39
ID9.52 4 For refrigerant gas(high/low pressure) pipe onoutdoorunit side Outdoor Unit Connecting
SYM. Side Pipe Connection
ID12.7 Ø16iD 2
85

615 7×60=420 For refrigerant gas pipe onindoor unit side REVISIONS valves for switching cooling/heating operation. Therefore,make sure to install (Ø15.88 Flare Nut)
5 Ø20iD
615 1 For refrigerant gas(low pressure) pipe onoutdoorunit side REMARKS TITLE PROJECTION SCALE the service access doors on the electrical box side and indoor unit connecting side.
Insulation
DIMENSIONAL 2)Operating soundand refrigerant flow soundmaybe heard from the CH-Box
6 Material Ø38iD 2
For refrigerant
For refrigerant
gas(high/low pressure) pipe onoutdoorunit side
gas pipe onindoor unit side DRAWING NTS when the electronic expansion valves in the CH-Boxare activated for RUN/STOP,
Insulation Accessories

20
F 7 Ø43iD Insulation
1 For refrigerant gas(low pressure) pipe onoutdoorunit side DWN.
Y.KAGEYAMA 19- 04
- 2017 SHIMIZU DWG. NO. REV. REGD. F
SH. Thermo-ON/OFF,defrosting or switching operation. Therefore,install 40 54
Accessories No. so the
the CH-Boxin the ceiling of corridor Accessory
refrigerant flow soundFigure
may Qty. Purpose
8 Cable Clamp 6 - CHKD.A.Fukasawa19- 04
- 2017
No. 317S154178 not heard in the room.Asfor
E the 1 Reducer
ceiling material,select a material like
APPD. - 2017Accessory
19- 04 Figure Qty. Purpose
Ó P X Doperation
a plaster board(at least 9mm)whichminimizes
D
O T ¨ Ó sound.
P T D W W 1 For
151 refrigerant
63 gas(low pressure) pipe
84

This drawing is E
1 2 3 4 E under license by Johnson Controls-Hitachi Air Conditioning Technology(Hongted
1 Reducer
Kong)Limi
CAD
1 For refrigerant gas(low pressure) pipe onoutdoorunit side 2 Accessory
3)Do not install the CH-Boxin a place Pipe(for
near bed room Flare Nut)
or hospital roomssince the For refrigerant gas(high/low pressure
84

77 Ó P X D O T ¨ Ó P T D W W
refrigerant flow soundmaybe heard fromÓ P the
T DCH-Box
W Wwhen¨ hswitching
D c D Ó P Q D V 2
Outdoor Unit Connecting Side 78
For refrigerant gas pipe onindoor unit
60 2 AccessoryPipe(for Flare Nut) 2 For refrigerant gas(high/low pressure) pipe onoutdoorunit side
3 AccessoryPipe(for Flare Nut)
between cooling/heating operation.
7×60=420 Ó P T D W W ¨ h D c D Ó P Q D V For refrigerant gas pipe onindoor unit side 1 For refrigerant gas(low pressure) pipe
60 4)Makesure the liquid pipe is correctlyÓ installed
P X D O to T the
¨ h appropriate
D c D Ó Punit.X D R
7×60=420
CH-Box

Specifications Specifications

Type Single-Port Type 317S154182 Multi-Port


DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
Model Name JCH-AP280SSX Model Name JCH-AP04MSSX
1 2 3 4 5 6

(JCH-AP04MSSX)
A
Images Images Indoor Unit Connecting Side Refrigerant Liquid Pipe
Connections
67 60×3=180 (4×Ø9.52 Flare Nuts)
Service
Access Door 60
(□450) 4-Suspension Bolts A D C B

60
317S154182
Dimensions (H*W*D) (mm) M10
260 × or
303W3/8
× 352
Dimensions (H*W*D) (mm) 191 × 301 × 214 DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX (Field-Supplied)

155
N/W (kg) 14
N/W (kg) 1 6 2 3 4 5 6 7 8 Upper Side Min.100
Power Supply 50 1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz Refrigerant Gas Pipe

100
Power Supply 1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz B Connection
(JCH-AP04MSSX) Electrical Details Power Input (W) 11.2 (4×Ø15.88 Flare Nuts)
A 20 340
Indoor Unit Connecting Side Refrigerant Liquid Pipe
Electrical Details Power Input (W) 5 Connections Current (A) 0.2
Electrical Box (For Suspension Bolt)
67 60×3=180 (4×Ø9.52 Flare Nuts)
Service Min.100 Min.500
Current (A) 0.1 Access Door 60
Maximum Total Capacity Index (kW) 44.8 198

100
(□450) 4-Suspension Bolts A D C B
Number of Port (for IDU) 4 Min.100 110

60
Maximum Total Capacity Index (kW) 28 M10 or W3/8 Service Bottom Side

30
(Field-Supplied)

155
Maximum Connectable IDUs per Port A Access Door 6
Number of Port (for IDU) 1 (□450)
Upper Side Min.100 Maximum Piping Total piping length between CH-Box and each indoor unit
Refrigerant Gas length C 40m
View from A
per branch Min.300

(For Suspension Bolt)


50 Pipe
Maximum Connectable IDUs per Port 8
100

B Connection
(4×Ø15.88 Flare Nuts)

256
Between CH-Boxes 15m
Maximum Piping Total piping length between CH-Box and each 20 340
40m 551
length indoor unit per branch Electrical Box (For Suspension Bolt) Maximum Height
Min.100 Min.500 Between CH-Box and IDU 15m
198 difference 199 352 Suspension Bracket
100

Between CH-Boxes 15m 4-(12×32) Slotted Hole Refrigerant Gas


6 7 8 Min.100 (High/Low Pressure)
Service
110 Between IDUs connecting to same CH-Box 86 67 4m 540 Pipe Connection
Bottom Side (I.D.Ø22.36)

30
Maximum Height A Access Door 38 303 38
Between CH-Box and IDU 15m
difference A
(□450) D Electrical Box
317S154182
Specifications C View from A
Min.300 DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX

(For Suspension Bolt)


Model Between IDUs connecting to same CH-Box
CH-AP280SSX 4m Ground Terminal (M5)
(in Electrical Box)

260
AC P m ` Q O O | Q S O u C T O g @ P m ` Q Q O u C U O g

256
Power Supply 1 2 3 4 5 6 7 8
AC P m ` Q R O u C T O g @ P ` Q Q O u C U O g
Dimensions

156
Input [W] 5 551

60
Refrigerant R410A (JCH-AP04MSSX)
317S154179 317S154179
Suspension Bracket A Power Supply Wiring Control Wiring Connection
199 352 Refrigerant Gas Refrigerant Liquid Pipe Connection(Ø26) 35 176
Net Weight [kg] 6 4-(12×32)DIMENSIONAL
Slotted Hole DRAWING OF SINGLE BRANCH TYPE COOLING/HEATING CHANGE-OVER Indoor Unit Connecting Side (Ø26)
BOX

42
DIMENSIONAL DRAWING OF SINGLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX (High/Low Pressure) Refrigerant Liquid Connections
Connectable Indoor Unit 67 60×3=180
Total Capacity 6.1HP to 10.0HP 86 67 540 Pipe Connection Pipe Connection (4×Ø9.52 Flare Nuts)
5 Service Refrigerant Gas
Dimensions
1
Number of Connectable
2
8
3
B
4 5 6
Service
1
Space
7 2 8
38
3
303 38
4 (I.D.Ø22.36)
Access Door
(□450)
6 (I.D.Ø12.9) E7 60
8
(Low Pressure)
Pipe Connection

34
Indoor Unit D Electrical Box 4-Suspension Bolts A D C B
(I.D.Ø25.6)

60
M10 or W3/8
A (Field-Supplied) A

155
A Suspension Bracket Ground Terminal (M5) A Suspension Bracket
Refrigerant Gas Pipe (JCH-AP280SSX) 2-(11×34) Slotted Hole Specifications (JCH-AP280SSX) 2-(11×34) Slotted Hole Specifications
(in Electrical Box)
260

2-Suspension Bolts M10 or W3/8 Connection 2-Suspension


Model Bolts M10 or W3/8CH-AP280SSX Upper Side Upper Side Min.100 Model CH-AP280SSX
Electrical Box Upper Side 23 330 (Field-Supplied) 23 330
(Field-Supplied) (Ø19.05 Flare Nut)
Min.70 Min.70

156
(Available for both sides) AC P m ` Q O O | Q S O u C T O g
317S154179 @ P m ` Q Q O u C U(For O Suspension
g Bolt) 50 Power Supply AC P m ` Q O O | Q S O u Refrigerant
C T O g Gas @ Pipe
P m ` Q Q O u C U O g
(For Suspension Bolt) Power Supply

100
AC P m ` Q R O u C T O g @ P ` Q Q O u C U O g B AC P m ` Q R O u C T O g Connection
@ P ` Q Q O u C U O g

60
DIMENSIONAL DRAWING OF SINGLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX (4×Ø15.88 Flare Nuts)
Input [W] 5 Input [W] 5

40
Power Supply Wiring
40

(M5) Control Wiring Connection 20 340R410A


Connection(Ø26) 35 176 50
100

(Ø26) Refrigerant
100

Refrigerant 1R410A 2 3 4 5 6 7 8

42
Electrical Box Electrical Box Electrical Box F (For Suspension 6Bolt) 317S154182
C Net Weight [kg] 6 180 Net Weight [kg] DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HE
Refrigerant Gas Min.100 Min.500
E Connectable Indoor Unit Connectable Indoor Unit 198
191

(Low Pressure) 6.1HP to 10.0HP

100
Total Capacity 6.1HP to 10.0HP 244 Total Capacity
Min.400 Min.400 A Min.400 Min.400 Pipe Connection A
34

Min.100
Suspension Bracket 1 2 3 is under license by Johnson C4
B BNumber of Connectable B (I.D.Ø25.6)
(JCH-AP280SSX) Number
2-(11×34) of Connectable
Slotted Hole Specifications1 110 B This drawing
8 Service 8 2 3 4
Min.70 Indoor Unit 2-Suspension Bolts M10 or Min.70
W3/8 Outdoor Unit ConnectingBottom Indoor
Side Unit
Side Model CH-AP280SSX

30
Upper Side 23 Access Door 330
(Field-Supplied)
Bottom Side Min.70 A
Service Access111
Door Bottom Side Service Access Door (□450)
(For Suspension Bolt) Power Supply AC P m ` Q O O | Q S O u C T O g @ P m ` Q Q O u C U O g
Service Space (JCH-AP04MS
25

(□450) (□450) AC P m ` Q R O u C T O g A @ P ` Q Q O u C U O g
Refrigerant Gas Pipe C View from A Refrigerant Gas Pipe Indo
Min.300 Input [W] 5

(For Suspension Bolt)


376

40
on 376 Connection Connection
Electrical Box Electrical Box (Ø19.05 Flare Nut) 67
100

Indoor Unit Connecting Side (Ø19.05 Flare Nut) Refrigerant R410A Service
(Available for both sides) (Available for both sides)

256
38 301 38 Electrical Box 38 301 38 Net Weight [kg] 6 Access Door
D (□450) 4-Suspension Bolts
<NOTES> 551Ground Terminal (M5) Connectable Indoor Unit
6.1HP to 10.0HP

60
F Ground Terminal (M5) 214 Total Capacity M10 or W3/8
214 parts such as electronic expansion
-Over(CH)Boxis composedof mechanical Min.400 Min.400 (in Electrical Box)
Refrigerant Gas(Low Pressure) (in Electrical Box) Refrigerant Gas(Low Pressure) (Field-Supplied)

155
for switching cooling/heating operation. Therefore,make sure to install B Pipe Connection Suspension Bracket Number of Connectable B
C Pipe Connection C C 199 352 C 8
Refrigerant Gas
(Ø19.05 Flare Nut) 89 (Ø19.05 Flare Nut) 89Min.70 4-(12×32) Slotted Hole Indoor Unit
vice access doors on the electrical box side and indoor unit connecting side. (High/Low Pressure) Refrigerant Liquid Upper Side Min.100

191
180
191
180

ng soundand refrigerant flow soundmaybe heard from the CH-Box 1 2 3 4


Service Access Door Bottom Side This drawing is under license by Johnson 86 Controls-Hitachi Air67 Conditioning Technology(Hongted Kong)Limi 540 Pipe Connection Pipe Connection
CAD 50
e electronic expansion valves in the CH-Boxare activated for RUN/STOP, (□450) (I.D.Ø22.36) (I.D.Ø12.9)

100
39
39

Refrigerant Gas(High/Low Pressure) 38 303 38 Refrigerant Gas Pipe B


Refrigerant Gas(High/Low Pressure)
-ON/OFF,defrosting or switching operation. Therefore,install 376 Connection
Pipe Connection D Electrical Box
-Boxin the ceiling of corridor so the refrigerant Pipe
flow Connection
soundmay (Ø15.88 Flare Nut)
Electrical Box (Ø19.05 Flare Nut) 20
(Ø15.88 Flare Nut) 82 301 96 82 301 96 (Available
111 for both sides)
ard in the room.Asfor the ceiling material,select a material like 111

25
38 301 38
25

Ground Terminal (M5) Electrical Box (F


er board(at least 9mm)whichminimizes operation sound. Min.100 Min.500
E (in Electrical Box)
20

40 221 Power Supply Wiring Connection


20

40 221 Power Supply Wiring Connection


260

nstall the CH-Boxin40a place near


54 bed room or hospital rooms since the 40 54 Ground Terminal (M5)

100
(Ø20) Indoor Unit Connecting Side 214 (Ø20) Indoor Unit Connecting Side
ant flow soundmaybe heard from the CH-Boxwhenswitching Refrigerant Gas(Low Pressure) (in Electrical Box) Min.100

156
n cooling/heating operation. 151 C
151 63 Pipe Connection C
63 89 Service

60
D (Ø19.05 Flare Nut) Bottom Side
38

reD the liquid pipe is correctly installed to the appropriate unit. Control Wiring Connection D
38

30
Control Wiring Connection <NOTES> Access Door

191
180

<NOTES> Power Supply Wiring Control Wiring Connection A


Outdoor Unit Connecting Side
(Ø20) 1)Change-Over(CH)Boxis composedof mechanical
Outdoor Unitparts such as electronic
Connecting Side expansion (Ø20) 1)Change-Over(CH)Box Connection(Ø26)
is composedof mechanical parts 35 such as electronic
176 expansion
(Ø26) (□450)50

42
39

DATE REVD. CHKD. APPD. valves for switching cooling/heating operation. Therefore,make sure to install valves for switching cooling/heating operation. Therefore,make sure to install View from A
SYM. Refrigerant Gas(High/Low Pressure) C 180
Min.300

(For Suspension Bolt)


REVISIONS the service access doors on the electrical box side and indoor unit connecting side. Pipe Connection the service access doors on the electrical box side and indoor unit connecting side. Refrigerant Gas
TITLE PROJECTION SCALE 2)Operating soundand refrigerant flow soundmaybe heard from the CH-Box (Ø15.88 Flare Nut) E 82 301 2)Operating 96soundand refrigerant flow soundmaybe heard from the CH-Box (Low Pressure) 244
111

25
Pipe Connection

34

256
DIMENSIONAL when the electronic expansion valves in the CH-Boxare activated for RUN/STOP, when the electronic expansion valves in the CH-Boxare activated for RUN/STOP,
DRAWING NTS Thermo-ON/OFF,defrosting orConnection
switching operation. Therefore,install (I.D.Ø25.6)
Thermo-ON/OFF,defrosting or switching operation. Therefore,install
20

40 54 40 221 Power Supply Wiring Outdoor Unit Connecting Side551


4 2017 Accessories SHIMIZU DWG. NO. SH. REV. REGD. F Accessories
the CH-Boxin the ceiling of corridor so the refrigerant flow soundmay the CH-Box in
(Ø20) the ceiling of corridor so the refrigerant flow sound may Indoor Unit Connecting Side
4 2017 No. Accessory Figure Qty. Purpose not heard in the room.As for the ceiling
No. material,select aFigure
Accessory material like Qty. Purpose not heard in the room.Asfor the ceiling material,select a material like Suspension Bracket
151 63 a plaster board(at least 9mm)whichminimizes operation sound. 199 352
317S154179 a plaster board(at least 9mm)which minimizes operation
D Nut) sound. 4-(12×32) Slotted Hole
38

D
4 2017 1 AccessoryPipe(for Flare Nut)
E by Johnson 2 For ted
refrigerant gas(low pressure) pipe onoutdoorunit side 1 inAccessory
E CH-Box
3)Do not install the a place
Pipe(for Flare
near 2 E gas(low pressure) pipe
For refrigerant Control Wiring unit
onoutdoor Connection
side 3)Do not install the CH-Boxin a place near bed roomor hospital rooms <NOTES>
since the
E
ense Ó79P Controls-Hitachi
X D O T ¨ h DAirc Conditioning
D Ó Q Q DTechnology(Hong
S Kong)Limi Ó P X D O bed
T ¨ room
h Dorc hospital
D Ó Q Q rooms
D Ssince the
CAD refrigerant flow soundmayAccessory
be heard from the CH-Box whenswitching Outdoor Unit Connecting Side
(Ø20) 1)Change-Over(CH)Box is composed
refrigerant flow soundmaybe heard from the CH-Boxwhenswitching of mechanical parts such as electronic expansion 86 67 80
For refrigerant gas(high/low pressure) pipe onoutdoorunit side Pipe(for Flare Nut) For refrigerant gas(high/low pressure) pipe on outdoor unit side
2 AccessoryPipe(for Flare Nut) 2 between cooling/heating2 operation.
Ó P X D O T ¨ h D c D Ó P X D R 2 For refrigerant gas pipe onindoor unit side between cooling/heating operation. valves for switching cooling/heating operation. Therefore,make sure to install 38
Ó P X D O T ¨ h D c D Ó P X D R For refrigerant gas pipe onindoor unit side the service access doors on the electrical box side and indoor unit connecting side.
4)Makesure the liquid pipe isAccessory
correctlyPipe(for
installed 4)Makesure the liquid pipe is correctly installed to the appropriate unit. D
AccessoryPipe(for Flare Nut) FlaretoNut)
the appropriate unit. Electrical Box
CH-Box

Specifications Specifications

Type 317S154183 Multi-Port Type Multi-Port


DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
Model Name JCH-AP08MSSX Model Name JCH-AP12MSSX
1 2 3 4 5 6 7 8

317S154184
Service Access Door DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
(□450) Service (JCH-AP08MSSX)
Images Images
Access Door
(□450) Indoor Unit Connecting Side 1 2 3 4 5 6
4-Suspension Bolts Refrigerant Liquid
M10 or W3/8 67 60×7=420 Pipe Connections (JCH-AP12MSSX)
(Field-Supplied) (8×Ø9.52 Flare Nuts)
Dimensions (H*W*D) (mm) 260 × 543 × 352 60 Dimensions (H*W*D) (mm) 260 × 783 × 352 Indoor Unit Connecting Side
6 7 8 Min.100 Service Access Door Service
Upper Side (□450) Access Door
N/W (kg) 25 Refrigerant Gas A D C B F E I H G
N/W (kg) (□450) 36 Refrigerant Liquid Pipe Connections

60
317S154184
50 50 Pipe Connection
DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX (12×Ø9.52 Flare Nuts)

156
(8×Ø15.88 Flare Nuts)
100

100

Power Supply 1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz Power Supply 1~, 208/230V/60Hz, 220V/60Hz,
4-Suspension 1~/N, 220V/60Hz, 220-240V/50Hz
Bolts
M10 or W3/8 67 60×11=660
Electrical Details Power Input (W) Electrical Box 1 22.4 2 3 4 5 6 Details
Electrical 7 (W)
Power Input 8 (Field-Supplied)33.6
60
Min.500 Upper Side Min.100
Refrigerant Liquid Current (A) Min.400 0.4 Current (A) 0.6
(JCH-AP12MSSX)
A C B D E F G H I J L K
50 50

60
100

Pipe Connections Bottom Side Min.100 20 580

156
A

100
(8×Ø9.52 FlareMaximum
Nuts) Total Capacity Index (kW) 85 Indoor Unit Connecting Side Maximum Total Capacity Index (kW) 85

100
Service Service Access Door Service (For Suspension Bolt)
(□450)
Access Door Access Door
Number of Port (for IDU) A 8 A (□450)
View from 198 Number of Port (for IDU) Electrical Box 12
Refrigerant Gas (□450) Refrigerant Liquid Pipe Connections Min.400
(12×Ø9.52 Flare Nuts) Min.500
Pipe Connection
Maximum Connectable IDUs per Port 6 Maximum Connectable IDUs per Port 6

100
(8×Ø15.88 Flare Nuts) Min.300 4-Suspension Bolts 110 Bottom Side Refrigerant Gas Pipe Connections

30
M10 or W3/8 67 60×11=660 Service Min.100 (12×Ø15.88 Flare Nuts)
Maximum Piping Total piping length between CH-Box and each indoor unit (Field-Supplied) Maximum Piping Total piping length between CH-Box and each indoor unit
A
40m 60 Access Door 40m 20 820
length per branch Upper Side Min.100 length per branch (□450) View from A
Min.300 (For Suspension Bolt)

(For Suspension Bolt)


A C B D E F G H I J L K
50 50

60
Between CH-Boxes 15m Between CH-Boxes 15m 198

156
256
100

100

B 110
Maximum Height Maximum Height

30
98 Between CH-Box and IDU Electrical Box 15mMin.400 Between CH-Box and IDU 15m
difference 551 Min.500 difference
Suspension Bracket
4-(12×32) Slotted Hole Refrigerant Gas
100

Refrigerant Gas Pipe Connections Refrigerant Liquid

(For Suspension Bolt)


199 352 Bottom Side (High/Low Pressure)
Between IDUs connecting to same CH-Box 4m
Service Min.100 780 (12×Ø15.88 Flare Nuts) Pipe Connection PipeBetween IDUs connecting to same CH-Box
Connection 4m
A

256
317S154183 Access Door 20 820 (I.D.Ø22.36) (I.D.Ø12.9)
DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING 86
CHANGE-OVER BOX 67 (□450) 38 from A
View 543 38
D Min.300 (For Suspension Bolt) 551
Suspension Bracket Refrigerant Gas
Electrical Box 198 4-(12×32) Slotted Hole (High/Low Pressure)
1 2 3 4 5 6 7 8 199 352 Pipe Connection
Dimensions Ground Terminal (M5) 1020
(I.D.Ø25.6)
260

110
30
(in Electrical Box) C 86 67 38 783 38

156
317S154184
Service Access Door D COOLING/HEATING CHANGE-OVER BOX
DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE
(□450) Refrigerant Gas (JCH-AP08MSSX) Electrical Box

60
Service
(For Suspension Bolt)

Refrigerant Liquid
(High/Low Pressure)
Pipe Connection
Access Door
Pipe Connection
Power Supply Wiring Control Wiring Connection Dimensions
50 Ground Terminal (M5)
256

260
(□450) Indoor Unit Connecting Side 35 176 240

42
Connection(Ø26) (2×Ø26) 1 2 3 4 5 (in 6Electrical Box) 7 8
(I.D.Ø22.36) (I.D.Ø12.9)
38 4-Suspension Bolts 180

156
Refrigerant Liquid 551

60
M10 or W3/8 67 60×7=420 Pipe Connections Suspension Bracket Refrigerant Gas
(Field-Supplied) E Refrigerant Gas (JCH-AP12MSSX)
(8×Ø9.52 Flare Nuts) 4-(12×32) Slotted Hole (Low Pressure) 244 Pressure)
(High/Low Refrigerant Liquid
60 199 352 Pipe Connection Power Supply Wiring 35 176 240 240 Control Wiring
A Connection
Min.100 1020 Pipe Connection Pipe Connection Indoor Unit Connecting Side
Upper Side (I.D.Ø28.75) Service Access Door Service Connection(Ø26) (3×Ø26)
(I.D.Ø25.6) (I.D.Ø16.1)
34

Refrigerant Outdoor
(□450) Unit Connecting Side Access Door Refrigerant
86Gas
A D C B F E I H G
67 38 783 38
60

Pipe Connection (□450) Refrigerant Liquid Pipe Connections (Low Press


50 50 D D
156

(12×Ø9.52 Flare Nuts) Pipe Conne


156

(8×Ø15.88 Flare Nuts)


100

100

Electrical Box (I.D.Ø28.75


60

4-Suspension Bolts E
Ground Terminal (M5) M10 or W3/8 67 60×11=660

34
Electrical Box
trol Wiring Connection 50
260

(in Electrical Box) (Field-Supplied)


42

Ø26) Min.500 60
Min.100

156
Min.400 180 Upper Side

60
Refrigerant Gas
100

A C B D E F G H I J L K
Bottom Side Min.100 50 50

60
20 580
(Low Pressure) 244 50

156
F Power Supply Wiring Control Wiring Connection
100
35 176 240 240

42
(For Suspension Bolt)

100
Pipe ConnectionService Connection(Ø26) (3×Ø26)
A (I.D.Ø28.75) Access Door 180 B
View fromSide
Outdoor Unit Connecting A 198 Refrigerant Gas
(□450)
317S154183317S154183 Electrical Box
DIMENSIONAL DRAWING OF
DIMENSIONAL MULTIPLE
DRAWING OF BRANCH
MULTIPLETYPE COOLING/HEATING
BRANCH CHANGE-OVER
TYPE COOLING/HEATING BOX
CHANGE-OVER (Low
BOX Pressure) Min.400 244 Min.500 317S154184
110 Pipe Connection
This drawing is under license by Johnson Controls-Hitachi Air Conditioning Technology(HongtedKong)Limi
Min.300 1 2 3 4 CAD E Refrigerant Gas Pipe Connections
317S154184 DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLIN

100
E (I.D.Ø28.75) Bottom Side DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATIN
30

Service1 Space 2 3 4 5 6 Unit Connecting 7


Min.100 (12×Ø15.88 Flare
8 Nuts) 8
34

1 2 3 4 A 5 Outdoor
Service 6 Side F7
Access Door 20 820 1 2 3
(□450) View from A 1 2 3 4
(For Suspension Bolt)

Service Access Door


Service Access Door
Min.300
(JCH-AP08MSSX)
(For Suspension Bolt)
Service Space This drawing is under license by Johnson(JCH-
Con
256

(□450) (□450) Service Service (JCH-AP08MSSX) 1 2 198 3 4 (JCH-AP12MS


Access DoorAccess Door
(□450) (□450) Indoor UnitIndoor
Connecting Side Service Access Door Service Ind
Unit Connecting Side 110 Service Access Service Access Door
(□450)Door

30
551 Access Door C
Suspension Bracket 4-Suspension Bolts
4-Suspension Bolts Refrigerant Refrigerant
Liquid (□450) (□450)
Refrigerant Gas M10 or W3/8 67 60×7=420 Liquid (□450) Re
drawing is under license by Johnson Controls-Hitachi 4-(12×32)
Air Conditioning Slotted Hole
Technology(Hong ted
Kong)Limi Refrigerant Liquid M10 or W3/8 67 60×7=420 Pipe Connections
199 352 CAD (High/Low Pressure) (Field-Supplied) Pipe Connections (12
(Field-Supplied)

(For Suspension Bolt)


780 Pipe Connection Pipe Connection 60 (8×Ø9.52 Flare Nuts) Flare Nuts)
(8×Ø9.52 4-Suspension Bolts
60 F 4-Suspension
F (I.D.Ø22.36) (I.D.Ø12.9) Min.100 M10 orBolts
W3/8 67
Side Min.100

256
Upper SideUpper M10 or W3/8 67
86 67 38 543 38 (Field-Supplied)
A A D C B Refrigerant Refrigerant
Gas
F BE
F IE H GD C
Gas
I H G (Field-Supplied) Min.100
60

551 Upper Side


60

50 50 50 50 Pipe Connection
Pipe Connection Min.100
Suspension Bracket Refrigerant Gas Upper Side
156

156

Electrical Box (8×Ø15.88 Flare Nuts)


100

100

This drawing is under license by Johnson Controls-Hitachi Air Conditioning


Flare Nuts)Technology(Hong ted
Kong)Limi 50 50 Refrigerant Liquid

60
(8×Ø15.88
100

100

1 2 3 4 4-(12×32) Slotted Hole CAD (High/Low Pressure) A B


50 50

60
156
199 352

100
Ground Terminal (M5) Pipe Connection Pipe Connection

100
1020

156
260

100
(in Electrical Box) Electrical Box
Electrical Box (I.D.Ø25.6) (I.D.Ø16.1)

100
Min.500 Min.500 86 67 38 783 38 Electrical Box
156

Min.400 Min.400 Electrical Box Min.400 Min.500


D D
60

Min.400 Min.500
100

Electrical Box
100

Bottom Side Min.100


Bottom Side Min.100 20

100
Power Supply Wiring 20 580 580 Ref
Control Wiring Connection Bottom Side

100
35 176 240 50 Ground Terminal (M5) Bottom Side Refrigerant
(12
42

Connection(Ø26) (2×Ø26) Service Service (For Suspension Bolt)


(For Suspension Bolt) Service Min.100
260

(in Electrical Box) A Min.100 (12×Ø15.88


A A Access
180 Door
Access Door View from View
A 198 198 A Service Access Door 20
from A Access Door View from A
(□450) (□450) (□450) 20

156
Refrigerant Gas Min.300 View from A

60
(□450)
(Low Pressure) 244
Min.300 110 Min.300 (
Min.300 110 50
Pipe Connection Control Wiring Connection
30

Power Supply Wiring


30

35 176 240 240

42
(I.D.Ø28.75) Connection(Ø26) (3×Ø26)
34

Outdoor Unit Connecting Side 180


Refrigerant Gas

30
(Low Pressure)

30
(For Suspension Bolt)

(For Suspension Bolt)

Pipe Connection 244


(I.D.Ø28.75) E
E
256

(For Suspension Bolt)


256

(For Suspension Bolt)


34
Outdoor Unit Connecting Side

256
256
551 551
81 SuspensionSuspension
Bracket Bracket
Refrigerant Refrigerant
Gas
551 82
4-(12×32) Slotted Hole
4-(12×32) Slotted Hole Gas 551 Suspension Bracket
(High/Low Pressure) Refrigerant Refrigerant
Liquid Liquid Suspension BracketSlotted Hole
199 199 352 352 (High/Low Pressure) 4-(12×32)
780 780 Pipe Connection
Pipe Connection Pipe Connection
Pipe Connection 199 352 4-(12×32) Slotted Hole
(I.D.Ø22.36) (I.D.Ø12.9) 199 352
CH-Box

4. DRAIN BOSS
The drain boss is for the drain pipe connection in order to use the bottom base of the outdoor unit as a drain pan.
Specifications
Model name Quantity
Type Multi-Port
Name Model Outdoor Unit HP class[kW]
Q'ty
Model Name JCH-AP16MSSX Drain Boss DBS-TP10A JTOR-BS1 series
8 - 18 (22.4 - 50.0kW) 1
20 - 36 (56.0 - 100.0kW) 2
38 - 40 (106.0 - 112.0kW) 3
Images 42 - 48 (118.0 - 136.0kW) 4
50 - 54 (140.0 - 150.0kW) 3

317S154185
DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
Dimensions (H*W*D) (mm) 260 × 1023 × 352

N/W (kg) 1 2 3
47 4 5 6 7 8

Power Supply
A
1~, 208/230V/60Hz, 220V/60Hz, 1~/N, 220V/60Hz, 220-240V/50Hz Refrigerant Liquid
Pipe Connections
images:DBS-TP10A
A
Dimensions
Service Access Door Service (JCH-AP16MSSX)
Access Door (16×Ø9.52 Flare Nuts)
(□450) Indoor Unit Connecting Side
Electrical Details Power Input (W) (□450) 44.8 Drain Boss + Rubber Cap Drain Cap + Rubber Cap Drain Boss×2 Drain Cap×2
67 900
6 7 8 4-Suspension Bolts To close the drain hall
Current (A) M10 or W3/8 0.8 60
(Field-Supplied)
uid Maximum Total Capacity Index (kW) 85

60
Upper Side Min.100
ons A

156
50 50
e Nuts)
100

Number of Port (for IDU) 16


100

D C B A E H G F I K J O N M L P Ø32 Ø32 Ø32 Ø32


B B
Maximum Connectable IDUs per Port Electrical Box 6Min.500 Refrigerant Gas Pipe Connection
100

Service Bottom Side (16×Ø15.88 Flare Nuts)


Maximum Piping Total piping length between CH-Box and each indoor Aunit Access Door
Min.300 40m

43

43

43

43
length per branch (□450) Min.400 Min.100 20 1060

30

30

30

30
(For Suspension Bolt)
View from A 198
Between CH-Boxes 15m
110 Ø20 Ø20
30

Maximum Height B
Between CH-Box and IDU 15m Ø25 Ø25 Ø25 Ø25
difference C C
(For Suspension Bolt)
256

Between IDUs connecting to same CH-Box 4m


551 Suspension Bracket
98 4-(12×32) Slotted Hole Refrigerant Gas
(High/Low Pressure) Refrigerant Liquid
199 352 Pipe Connection Pipe Connection
1260 (I.D.Ø28.75) (I.D.Ø19.3) install Drain
install
capDrain cap
86 67 (247) (247)
38 1023 38
Drain water treatment
317S154185
DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX 2 points 2 points
C Electrical Box
D D
Dimensions2 Ground Terminal(M5)
Drain water is discharged during heating and defrosting operation. (Rain water is also discharged.) Pay attention to the following.
260

1 3 4 5 6 (in Electrical Box) 7 8


(90) (90)

156

60
Refrigerant Liquid 35 176 240 240 240 Control Wiring Connection
1. Choose50
a location where well drainage is available,
Ø32
or provideØ32
a drain ditch.Ø32 Ø32
Refrigerant Gas Power Supply Wiring
A (4×Ø26)

42
Pipe Connections back back
Door Pressure) Service
(High/Low
Service Access Refrigerant Liquid (JCH-AP16MSSX)
(16×Ø9.52 Flare Nuts)
Connection(Ø26)
2.180Do not install the unit over a walkway, as condensation water may drip onto people.
(□450) Pipe Connection Access Door Pipe Connection Indoor Unit Connecting Side Refrigerant Gas
(I.D.Ø28.75) (□450) (I.D.Ø19.3)

42

42
(Low Pressure) 244
In the case of installing the unit in such a location, provide an additional drain pan.

43

43
38 67 900 Pipe Connection

43

43
30

30
4-Suspension Bolts (I.D.Ø32)
34

30

30
Outdoor Unit 3. Do notSide use the drain boss in a cold area. The drain water in the drain pipe may freeze, and the drain pipe may crack.

90

90
E
M10 or W3/8 60
E Connecting
(Field-Supplied) D

(48)

(48)
Drain piping
Drain
Ø20 piping bottom bas
bo
60

Upper Side Min.100 Ø20 install Drain


install
bollØ25
Drain
2 points
boll 2 points
156

156

50 50 field-supplied
field-supplied
Ø25 Ø25 ODU rearODU
Ø25 side rear side
60

Drain boss
Drain boss Drain capDrain cap
100

l Wiring Connection 50 D C B A E H G F I K J O N M L P
42

6) B
Electrical Box
180 Min.500 Refrigerant Gas Pipe Connection
Refrigerant Gas
How to use
100

Service Bottom Side (16×Ø15.88 Flare Nuts)


(Low Pressure)
Access Door 244 317S154185
Min.300 Pipe Connection
317S154185 DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX F
(□450) Min.400 Min.100 20 F 1060 DIMENSIONAL DRAWING OF MULTIPLE BRANCH TYPE COOLING/HEATING CHANGE-OVER BOX
(I.D.Ø32)
E
Bottom view Side view
Outdoor Unit Connecting Side (For Suspension Bolt) install Drain cap
View from A 198 1 2 3 4 5 6 install Drain 7cap 8 (247)
1 2 3 by Johnson Controls-Hitachi 4Air Conditioning Technology(Hong5 6 7 2 points 8 (247)
1 2
110
3
Service Space4 This drawing is under license ted
Kong)Limi
CAD 2 points
30

Refrigerant Liquid
A Refrigerant Liquid
Pipe Connections A
A Service Access Door Service (JCH-AP16MSSX) Pipe Connections A
Service Access Door Service
Access Door (JCH-AP16MSSX) (16×Ø9.52 Flare Nuts) (90)
(□450) Access Door C (16×Ø9.52 Flare Nuts) (90)
(For Suspension Bolt)

(□450) (□450) Indoor Unit Connecting Side


(□450) Indoor Unit Connecting Side
256

67 900
4-Suspension Bolts 67 900 back back front front
4-Suspension Bolts
M10 or W3/8 60
551 Suspension Bracket M10 or W3/8
(Field-Supplied) 60

42
F (Field-Supplied)

42
4-(12×32) Slotted Hole Refrigerant Gas
Refrigerant Liquid
60

(High/Low Pressure) Min.100


Upper Side Min.100
199 352
60
156

Upper Side

90
Pipe Connection 50 Pipe Connection
50
156

90
1260 (I.D.Ø28.75) 50 50
(I.D.Ø19.3)
100

100
100

86 67 Technology(Hongted
100

r license by Johnson Controls-Hitachi Air Conditioning Kong)Limi 38 1023 38

(48)
O N M L K J I H G F E D C B A P
CAD Drain piping bottom base

(48)
B P O N M L K J I H G F E D C B A
Drain piping B bottom base
Electrical Box B Electrical Box field-supplied install Drain boll 2 points
install Drain boll 2 points B
Electrical Box D Min.500 Refrigerant Gas Pipe Connection
field-supplied ODU rear side
100

Service Bottom Side Min.500 Refrigerant Gas Pipe


(16×Ø15.88 FlareConnection
Nuts) ODU rear side Drain boss Drain cap
100

Ground Terminal(M5) Bottom Side (16×Ø15.88 Flare Nuts) Drain boss Drain cap
260

(in Electrical Box) A Service


Access Door
A Min.300 Access Door
156

Min.300 (□450) Min.400 Min.100 20 1060


(□450) Min.400 Min.100 20 1060
60

(For Suspension Bolt)


35 176 240 240 240 Control Wiring Connection 50 View from A (For Suspension Bolt) 198
Power Supply Wiring View from A
42

Connection(Ø26) (4×Ø26) 198


180 110
Refrigerant Gas
30

110
30

(Low Pressure) 244


Pipe Connection
(I.D.Ø32) C C
(For Suspension Bolt)
34

C C
(For Suspension Bolt)

E
Outdoor Unit Connecting Side
256
256

83 551 84
551 Suspension Bracket
Suspension Bracket
4-(12×32) Slotted Hole Refrigerant Gas
4-(12×32) Slotted Hole Refrigerant Gas Pressure)
(High/Low Refrigerant Liquid
199 352 (High/Low Pressure)
Pipe Connection Refrigerant Liquid
Pipe Connection
Options

Resistance to Salt Damage Specifications


Products for Order
About the installation location
Resistance to salt damage specifications Resistance to heavy salt damage specifications

A location that is not exposed A place that is susceptible to sea breezes


5. CABINET COVER to sea breezes, but that (But the device is not directly exposed to
ODU ODU

Installation
Location
appears to be suitable for water containing salt.)
such an atmosphere
ODU ODU
Air inlet grille Protection net
sea sea sea sea
HP class (kW) Air Inlet Grille HP class (kW) Protection Net
JTOR-BS1 series Rear Right Left JTOR-BS1 series Rear Right Left
8 - 12 (22.4 - 33.5) PSN-TP20BA PSN-TP20R PSN-TP20L 8 - 12 (22.4 - 33.5) PN-TP20BA PN-TP20R PN-TP20L
14 - 18 (40.0 - 50.0) PSN-TP20BB PSN-TP20R × 2 14 - 18 (40.0 - 50.0) PN-TP20BB PN-TP20R × 2
20 - 24 (56.0 - 67.0) PN-TP20BC PN-TP20R × 2 - A location where the outdoor unit is rinsed by the rain - A location where the outdoor unit receives little rain
20 - 24 (56.0 - 67.0) PSN-TP20BC PSN-TP20R × 2

installation location
- A location that is not exposed to sea breezes - A location that is directly exposed to sea breezes

Requirements for
- A location where the distance from the installation location of the - A location where the distance from the installation location of the outdoor unit to the
image:Air inlet grille image:Protection net outdoor unit to the sea is between approximately 300 meters and sea is up to approximately 300 meters
one kilometer - A location where the outdoor unit is mounted on the front of a building (beach side)
Left Side Left Side
- A location where the outdoor unit is in the shelter of a building - A location where corrugated iron roofs and the steel parts of balconies near the
installation location of the outdoor unit are often repainted

The standard of the installation distance from the beach


(conditions vary according to the installation environment)

1 A location that receives direct sea breezes


The standard of the installation distance

Right Side Rear Side Right Side Rear Side (1) A region that faces an inland sea 300 m 500 m 1000 m
(2) A region that faces the open sea
(3) Okinawa and remote islands
Resistance to salt damage Resistance to heavy salt damage

2 A location that does not receive direct sea breezes


The standard of the installation distance
(1) A region that faces an inland sea 300 m 500 m 1000 m
(2) A region that faces the open sea
(3) Okinawa and remote islands
Resistance to salt damage Resistance to heavy salt damage

Points to note for installation, maintenance and management


• Points to note for installation (regarding maintenance and management)
The units of JRA specifications for resistance to salt damage and resistance to heavy salt damage are made with strengthened materials and
paints, but they are not fully protected against corrosion.
It is therefore necessary to increase the anti-corrosion effects by carrying out the following installation plans and maintenance work.
(1) Please install the device in a location that avoids direct sea water splashes and sea breezes as much as possible.
-Please install the device on the leeward side of a building.
-If you have to install a device on the side of the beach, please avoid exposing it to direct sea breezes by erecting a wind-protective board.
-Please be careful about the direction of installation. (The degree of corrosion differs depending on whether a device is installed parallel to the coastline
or perpendicular to the coastline.)
(2) Please ensure that any sea salt particles that adhere to the exterior panels will be washed away by the rain.
(3) Because the pooling of water on the bottom base of the outdoor unit significantly boosts the corrosion effects, please be careful about the inclination so
that the ability for water to run through the bottom base of an outdoor unit will not be affected.
(4) For a device installed in a beach area, please rinse it with water on a regular basis to remove all salt adhering to the device.
(5) Please install the device in a location where water drains away well. In particular, please secure the drainage of the foundation parts.
(6) Please be sure to repair any scratches that are created during the installation and maintenance work.
(7) Please inspect the conditions of the device on a regular basis. (If necessary, please apply anti-rust treatments or replace parts.)

• Points to note for maintenance


-Please carry out sufficient maintenance work on the device.
-If you stop using the device for a long time, such as during the off-season, please take measures such as putting a cover on the device.

*If you install the device in a special atmosphere, you will need to undertake sufficient special consideration.
Units that are resistant to salt damage are based on the “Standard of Testing Resistance to Salt Damage of Air Conditioning Devices JRA9002” of the Japan Refrigeration and Air Conditioning
Industry Association (JRAIA).

85 86
Indoor Units

Indoor Units Index

Ceiling Cassette
90 4-way cassette type
95 4-way cassette compact type
97 2-way cassette type

Ducted
99 High external static pressure type
Medium external static pressure type
100 Low external static pressure type
101 Slim type
Compact type

Exposed & Concealed


103 Ceiling suspended type
105 Wall mounted type
106 Floor concealed type

Options
107 Motion sensor kit
108 Fresh air unit
AHU-kit

87 88
Ceiling Cassette

4-way cassette type

Dimensions

JTKF028H0PS0AS 20Kg 840mm 840mm

JTKF040~056H0PS0AS 21Kg 248mm

JTKF071H0PS0AS 22Kg

JP-AP160NA(1/E) 6.5Kg 950mm 950mm

JTKF080~160H0PS0AS 26Kg 840mm 840mm

298mm
Application

JP-AP160NA(1/E) 6.5Kg
950mm 950mm

Restaurant Retails Hospital


hall

Indoor Unit Type 4-Way Cassette Type


Model JTKF028H0PS0AS JTKF040H0PS0AS JTKF056H0PS0AS JTKF071H0PS0AS JTKF080H0PS0AS JTKF112H0PS0AS JTKF140H0PS0AS JTKF160H0PS0AS
Indoor Unit Power Supply AC 1Φ , 220-240V/50Hz, 220V/60Hz
Nominal Cooling Capacity kW(Btu/h) 2.8(9,600) 4.0(13,600) 5.6(19,100) 7.1(24,200) 8.0(27,300) 11.2(38,200) 14.0(47,800) 16.0(54,600)
Nominal Heating Capacity kW(Btu/h) 3.2(10,900) 4.8(16,400) 6.3(21,500) 8.5(29,000) 9.0(30,700) 12.5(42,600) 16.0(54,600) 18.0(61,400)
Sound Pressure Level(Overall A Scale) (Hi2/Hi/Me/Lo) dB 33/30/28/27 35/31/30/27 37/32/30/27 42/36/32/28 42/36/32/28 48/43/39/33 48/45/40/35 48/46/41/37
Height mm(in.) 248(9-3/4) 248(9-3/4) 248(9-3/4) 248(9-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4)
Outer
Width mm(in.) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16)
Dimensions
Depth mm(in.) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16)
Net Weight kg(lbs.) 20(44) 21(46) 21(46) 22(49) 26(57) 26(57) 26(57) 26(57)
Refrigerant R410A
15/13/11/9 21/17/14/11 22/17/14/11 27/23/18/14 27/23/18/14 37/31/24/20 37/33/26/21 37/35/28/22
Indoor Fan Air Flow Rate(Hi2/Hi/Me/Lo) m3/min.(l/s) (250/217/ (350/283/ (367/283/ (450/383/ (450/383/ (617/517/ (617/550/ (617/583/
183/150) 233/183) 233/183) 300/233) 300/233) 400/333) 433/350) 467/367)
Motor W 57 57 57 57 57 127 127 127
Connections Flare-Nut Connection (with Flare Nuts)
Liquid Line mm(in.) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8)
Refrigerant
Gas Line mm(in.) Φ 12.7(1/2) Φ 12.7(1/2) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8)
Piping
Condensate Drain VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25
Approximate Packing Measurement m3 0.21 0.21 0.21 0.21 0.25 0.25 0.25 0.25

JP-AP160NA1 JP-AP160NAE
Adaptable Panel Model
(without Motion Sensor) (with Motion Sensor)
Color Neutral White
Height mm(in.) 37(1-7/16) 37(1-7/16)
Outer
Width mm(in.) 950(37-3/8) 950(37-3/8)
Dimensions
Depth mm(in.) 950(37-3/8) 950(37-3/8)
Net Weight kg(lbs.) 6.5(14) 6.5(14)
Approximate Packing Measurement m3 0.10 0.10

NOTES:
1.The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature 2. The sound pressure level is based on following conditions.
are under the following conditions. 1.5 Meters Beneath the Unit.
Cooling Operation Conditions Heating Operation Conditions The data in the table above was measured in an anechoic chamber so that
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) reflected sound should be taken into consideration in the field.
o o
19.0 C WB (66.2 F WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB)
Piping Length:7.5 Meters Piping Lift:0 Meter

90
Ceiling Cassette

FEATURES AND BENEFITS OPTIONAL PARTS


Please consult your distributors or dealers in inquiry

Adaptability Design Flexibility

Duct adaptor: Branch duct flange


1) Wide Detection area of motion sensor 1) used in both narrow ceiling cavity, for fresh air absorption aperture [round duct direct-installation type]:
 adjust the airflow, air volume and even temperature  and with high ceiling Round ducts can be installed even without connecting chambers.
[(small):Φ 150mm, (large):Φ 200mm] (attached to aperture-shielding material)

drain
850 Branch duct flange
[chamber type]:
mm High humidity kit: You can remove it from the installation
Image use this kit for any situation where the sides in three directions (in the case
temperature at the ceiling appears to of one-way separation).
be over 30°C and the humidity at the In addition, two-way separation
ceiling seems to be above RH80%. can also be installed. [(Small):Φ 150
123˚ mm, (large):Φ 200 mm] (attached to
height aperture-shielding material)
3.2m

above floor level


Up to Fresh air absorption kit:
0.8m diameter
Fresh air aperture:two-chamber
8.8m
4.2m type (Φ 75×2) (Installation height:55
down mm raised)

Detection Area AIR

Flexible duct: Blow unit:


Length:1m,2m,3m and 5m [(small): •G  rille part resin (no flocking)
Φ 150mm, (large):Φ 200mm] • Can be hung in the case of a single
one (middle hanging)
• E quipped with airflow adjustment
plates
2) Control air flow with individual four-way louvers 2) Standard drain pump with 850 mm lift
 more comfortable air conditioning can be achieved along each zone
requirement Aperture-shielding set:
Up to A set of aperture shields is applicable
Horizontal
850 Decorative panels:
to two sides of an aperture.

mm
• Neutral White, Beige, Gray, Black
Filter box:
•F  or oil guard filters use this filter box for installing antimicrobial high-performance filters and deodorizing
Horizontal Blow 25° • Equipped with Motion Sensor Kit filters. (Installation height:55 mm raised)
• For high humidity
louver opens up to 60°
Filter (for box):
down swing • Antimicrobial high-performance filters
Please use these filters in offices, hospitals and welfare facilities for the elderly.
• Deodorizing filters
3) Round ducts can be attached directly Please use these filters for locations where general living odors (ammonia odor,
Example: etc.) are bothersome, hospitals and welfare facilities for the elderly. The filters can
Reception be dried in the sunshine and can also be washed in water. (Lifespan of around three
swing
years)

Horizontal Blow
Filters (for panels):
• F or exchanging long-life filters Receiver Kit:
(anti-mold) For Remote Controller (JCRB10NEWS)
• Antimicrobial long-life filters
• Oil guard filters
no direct airflow blows the cold air
to those who remain to the visitors • High-performance filters (colorimetric
seated for long time from outside method 65%)
Space panel:
Please use these panels for handling the
space panel
4) The height of the space for installing the unit can be fine-tuned shallow ceiling cavity, and to prevent
smudging. If you wish to install a humidifier,
branch duct flanges and a fresh air absorption
kit in combination with space panels, you
may not be able to do so because of the
cradling structure of the ceiling. In addition,
Example: cabinet Wide panel (for renewal): a shallower ceiling cavity can handle double
Please choose the size of the wide layers of space panels.
Office
panel according to the measurements
of an existing ceiling opening and the 〈single〉 Ceiling 〈double〉
Horizontal Blow measurements of an already-installed
blowing down panel Easier indoor unit.
height Ceiling
• Standard
corner pocket Adjustment • Oil guard specifications
80mm
sensitive to heat sensitive to cold Type Small Large Ultra-large 40mm
Measurement of External form
1020*1020*12 1020*1340*12 1020*1490*12 Decorative Panel Decorative Panel
(mm) space panel space panel

91 92
Ceiling Cassette

4-way cassette type FEATURES AND BENEFITS


Adaptability Design Flexibility

1) Wide Detection area of motion sensor 1) used in both narrow ceiling cavity,
 adjust the airflow, air volume and even temperature  and with high ceiling
Dimensions
drain
850
mm
Image
JTKF028H0PSAQ 20Kg 840mm 840mm

JTKF040~056H0PSAQ 21Kg 248mm 123˚


height
JTKF071H0PSAQ 22Kg 3.2m
950mm 950mm
above floor level
0.8m diameter Up to
8.8m
4.2m
down
Detection Area
JTKF080~160H0PSAQ 26Kg 840mm 840mm

298mm
Application
2) Control air flow with individual four-way louvers 2) Standard drain pump with 850 mm lift
950mm 950mm
 more comfortable air conditioning can be achieved along each zone
Retails Hospital
requirement
Restaurant
hall Up to
Horizontal
850
Indoor Unit Type 4-Way Cassette Type mm
JTKF JTKF JTKF JTKF JTKF JTKF JTKF JTKF
Model
028H0PSAQ 040H0PSAQ 056H0PSAQ 071H0PSAQ 080H0PSAQ 112H0PSAQ 140H0PSAQ 160H0PSAQ
Indoor Unit Power Supply AC 1Φ , 220-240V/50Hz, 220V/60Hz
Nominal Cooling Capacity kW(Btu/h) 2.8(9,600) 4.0(13,600) 5.6(19,100) 7.1(24,200) 8.0(27,300) 11.2(38,200) 14.0(47,800) 16.0(54,600) Horizontal Blow 25°
Nominal Heating Capacity kW(Btu/h) 3.2(10,900) 4.8(16,400) 6.3(21,500) 8.5(29,000) 9.0(30,700) 12.5(42,600) 16.0(54,600) 18.0(61,400) louver opens up to 60°
Sound Pressure Level(Overall A Scale) (Hi2/Hi/Me/Lo) dB 33/30/28/27 35/31/30/27 37/32/30/27 42/36/32/28 42/36/32/28 48/43/39/33 48/45/40/35 48/46/41/37
Height mm(in.) 248(9-3/4) 248(9-3/4) 248(9-3/4) 248(9-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4)
Outer down swing
Width mm(in.) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16)
Dimensions
Depth mm(in.) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16) 840(33-1/16)
Net Weight kg(lbs.) 20(44) 21(46) 21(46) 22(49) 26(57) 26(57) 26(57) 26(57) 3) Round ducts can be attached directly
Refrigerant R410A Example:
15/13/11/9 21/17/14/11 22/17/14/11 27/23/18/14 27/23/18/14 37/31/24/20 37/33/26/21 37/35/28/22 Reception
Indoor Fan Air Flow Rate(Hi2/Hi/Me/Lo) m3/min.(l/s) (250/217/ (350/283/ (367/283/ (450/383/ (450/383/ (617/517/ (617/550/ (617/583/ swing
183/150) 233/183) 233/183) 300/233) 300/233) 400/333) 433/350) 467/367) Horizontal Blow
Motor W 57 57 57 57 57 127 127 127
Connections Flare-Nut Connection (with Flare Nuts)
Liquid Line mm(in.) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8)
Refrigerant
Gas Line mm(in.) Φ 12.7(1/2) Φ 12.7(1/2) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8)
Piping no direct airflow blows the cold air
Condensate Drain VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25 to those who remain to the visitors
Approximate Packing Measurement m 3
0.21 0.21 0.21 0.21 0.25 0.25 0.25 0.25 seated for long time from outside

NOTES:
1.The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature 2. The
 sound pressure level is based on following conditions.
4) The height of the space for installing the unit can be fine-tuned
are under the following conditions. 1.5 Meters Beneath the Unit.
Cooling Operation Conditions Heating Operation Conditions The data in the table above was measured in an anechoic chamber so that
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) reflected sound should be taken into consideration in the field.
o o
19.0 C WB (66.2 F WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) 3. Decoration
 panel is included.
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) Example: cabinet
Piping Length:7.5 Meters Piping Lift:0 Meter Office

Horizontal Blow
blowing down panel Easier
height
corner pocket Adjustment

sensitive to heat sensitive to cold

93 94
Ceiling Cassette

4-way cassette compact type FEATURES AND BENEFITS


Adaptability Design Flexibility

1) Top-class silent operation 1) Compact


 as quiet as gentle breeze 20mm
Dimensions
Adaptation to
600*600mm
IDU Capacity HP(Class) 0.6 0.8 1 1.5 2 2.5 ceilings 600mm
570mm 570mm
JTKM016~040H0PS0AS 16Kg Sound pressure level (dB(A)) 24.5 24.5 24.5 27.5 31 35
600mm
* air flow volume:low.
JTKM056~071H0PS0AS 17Kg
285mm 20dB 30dB 40dB
CLOCK MIDNIGHT LIBRARY
JP-AP56NAM 3Kg

620mm 620mm

between ceiling lights

2) Aesthetics 2) High Ceiling Available


 Standard drain-pump

Application 30mm
thickness drain
850
mm

Retails

Indoor Unit Type 4-Way Cassette (Compact) Type


Model JTKM016H0PS0AS JTKM022H0PS0AS JTKM028H0PS0AS JTKM040H0PS0AS JTKM056H0PS0AS JTKM071H0PS0AS Fully opened louvers
Indoor Unit Power Supply AC 1Φ , 230V 50Hz, 220-240V 50Hz, 220V 60Hz doesn’t exceed the Up to
Nominal Cooling Capacity kW(Btu/h) 1.6(5,500) 2.2(7,500) 2.8(9,600) 4.0(13,600) 5.6(19,100) 7.1(24,200) surface
simple design
3.5m
down
Nominal Heating Capacity kW(Btu/h) 1.9(6,500) 2.5(8,500) 3.2(10,900) 4.8(16,400) 6.3(21,500) 8.5(29,000)
Sound Pressure Level
dB 34-30-28-24.5 36-33-29-24.5 38-34-30-24.5 41-37-33-27.5 45-39-35-31 47-43-39-35
(Overall A Scale) (Hi2-Hi-Me-Lo)
Height mm(in.) 285(11-7/32) 285(11-7/32) 285(11-7/32) 285(11-7/32) 285(11-7/32) 285(11-7/32)
Outer
Width mm(in.) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16)
Dimensions
Depth mm(in.) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16) 570(22-7/16)
Net Weight kg(lbs.) 16(35.3) 16(35.3) 16(35.3) 16(35.3) 17(37.5) 17(37.5)
Refrigerant R410A
Air Flow Rate m3/min. 10-8.5-7.5-6 11-9.5-8-6 12-10-8.5-6 13-11-9.5-7 15-12-10-8 16-14-12-10
Indoor Fan
(Hi2-Hi-Me-Lo) (cfm) (353-300-265-212) (388-335-282-212) (424-353-300-212) (459-388-335-247) (530-424-353-282) (565-494-424-353) 3) Adopting new antibacterial agent of drain pan
 for the better air and easy maintenance
Motor W 57 57 57 57 57 57
Connections Flare-Nut Connection (with Flare Nuts)
Liquid Line mm(in.) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 9.52(3/8)
Refrigerant
Gas Line mm(in.) Φ 12.7(1/2) Φ 12.7(1/2) Φ 12.7(1/2) Φ 12.7(1/2) Φ 12.7(1/2) Φ 15.88(5/8)
Piping
Condensate Drain VP25 VP25 VP25 VP25 VP25 VP25

Adaptable Panel Model JP-AP56NAM (without Motion Sensor)


Color Neutral White
Height mm(in.) 30(1-3/16)
Outer
Width mm(in.) 620(24-13/32)
Dimensions
Depth mm(in.) 620(24-13/32)
Net Weight kg(lbs.) 3(6.6)

NOTES:
1.The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature 2. The
 sound pressure level is based on following conditions.
are under the following conditions. 1.5 Meters Beneath the Unit.
Cooling Operation Conditions Heating Operation Conditions The data in the table above was measured in an anechoic chamber so that
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) reflected sound should be taken into consideration in the field.
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
o o
Outdoor Air Inlet Temperature: 35 C DB (95 F DB) 6oC WB (43oF WB)
Piping Length:7.5 Meters Piping Lift:0 Meter
inhibit the generation of slime

95 96
Ceiling Cassette

2-way cassette type FEATURES AND BENEFITS


Adaptability Design Flexibility

1) Control air flow with individual louvers 1) High Ceiling Available


  suitable environment can be achieved for each person  Standard drain-pump
drain
850
Dimensions mm

JTKT022~028H0PS0AS 23Kg 860mm 630mm

JTKT040~056H0PS0AS 25Kg Up to
298mm
30mm Horizontal Blow
3.5m
JTKT071~080H0PS0AS 25Kg down
25°
710mm 1,100mm louver opens up to
JP-AP90DNA 7.5Kg 60°

2) The height of the space for installing the unit can be fine-tuned

630mm
JTKT112~160H0PS0AS 39Kg 1,420mm
Easier
height
Adjustment
JP-AP160DNA 10.5Kg
298mm
30mm
panel
Application
1,660mm
710mm

corner
pocket

Restaurant

Indoor Unit Type 2-Way Cassette Type


Model
Indoor Unit Power Supply
JTKT022H0PS0AS JTKT028H0PS0AS JTKT040H0PS0AS JTKT056H0PS0AS JTKT071H0PS0AS JTKT080H0PS0AS JTKT112H0PS0AS JTKT140H0PS0AS JTKT160H0PS0AS
AC 1Φ , 220-240V/50Hz, 220V/60Hz
OPTIONAL PARTS
Please consult your distributors or dealers in inquiry
Nominal Cooling
kW(Btu/h) 2.2(7,500) 2.8(9,600) 4.0(13,600) 5.6(19,100) 7.1(24,200) 8.0(27,300) 11.2(38,200) 14.0(47,800) 16.0(54,300)
Capacity
Nominal Heating
kW(Btu/h) 2.5(8,500) 3.2(10,900) 4.8(16,400) 6.3(21,500) 8.5(29,000) 9.0(30,700) 12.5(42,600) 16.0(54,600) 18.0(61,400)
Capacity
Sound Pressure Level Flexible duct: Branch duct flange:
dB 30-29-28-27 31-29-28-27 37-34-31-30 39-36-33-30 42-39-36-33 45-42-38-33 43-40-37-34 47-44-41-35 48-45-42-39
(Overall A Scale)(Hi2-Hi-Me-Lo) Length:1m, 2m, 3m and 5m [Φ 150 mm] in case you install the branch duct in to
Height mm(in.) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) 298(11-3/4) the cassette
Outer
Width mm(in.) 860(33-7/8) 860(33-7/8) 860(33-7/8) 860(33-7/8) 860(33-7/8) 860(33-7/8) 1,420(55-7/8) 1,420(55-7/8) 1,420(55-7/8)
Dimensions
Depth mm(in.) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) 630(24-13/16) AIR
Duct adaptor:
Blow unit:
Net Weight kg(lbs.) 23(50.7) 23(50.7) 25(55.1) 25(55.1) 25(55.1) 25(55.1) 39(86.0) 39(86.0) 39(86.0) •G
 rille part resin (no flocking) for fresh air absorption aperture
Refrigerant R410A (Nitrogen-Charged for Corrosion-Resistance) •C
 an be hung in the case of a single one
16.5-14.5- 18.5-16.5- 21-18.5-16- 30-26.5-23- 37-32.5-28.5- (middle hanging) Filter box:
10-9-7.5-6.5 11-9.5-8.5-7 15-13-11.5-10 35-31-27-21 •E
 quipped with airflow adjustment plates use this filter box for installing antimicrobial Decorative panels:
Air Flow Rate m3/min. 12.5-10.5 14.5-12.5 12.5 20 24
Indoor Fan (353-318- (388-335- (530-459- (1,236-1,095- high-performance filters and deodorizing filters. Neutral White, Beige, Gray, Black
(Hi2-Hi-Me-Lo) (cfm) (583-512- (653-583- (742-653- (1,059-936- (1,306-1,147-
265-230) 300-247) 406-353) 953-742) Aperture-shielding set: (Installation height:83 mm raised)
441-371) 512-441) 565-441) 812-706) 1,006-847)
Motor W 57 57 57 57 57 57 57 x 2 57 x 2 57 x 2 equipped with Branch duct flange
Connections Flare-Nut Connection (with Flare Nuts) Filters (for panels):
Liquid Line mm(in.) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 6.35(1/4) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) • For exchanging long-life filters (anti-
Refrigerant
Gas Line mm(in.) Φ 12.7(1/2) Φ 12.7(1/2) Φ 12.7(1/2) Φ 12.7(1/2) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Filter (for box): mold)
Piping • Antimicrobial long-life filters
Condensate Drain VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25 VP25 • Antimicrobial high-performance filters
• High-performance filters (colorimetric
Approximate Packing Measurement m3 0.24 0.24 0.24 0.24 0.24 0.24 0.36 0.36 0.36 Please use these filters in offices, hospitals and welfare facilities for the elderly. method 65%)
• Deodorizing filters
Adaptable Panel Model JP-AP90DNA (for 2.2~8.0kW) JP-AP160DNA (for 11.2~16.0kW) Please use these filters for locations where general living odors (ammonia odor, etc.) are
bothersome, hospitals and welfare facilities for the elderly. The filters can be dried in the Receiver Kit:
Color Neutral White For Remote Controller (JCRB10NEWS)
sunshine and can also be washed in water. (Lifespan of around three years)
Height mm(in.) 30(1-3/16) 30(1-3/16)
Outer
Width mm(in.) 1,100(43-5/16) 1,660(65-3/8)
Dimensions
Depth mm(in.) 710(27-15/16) 710(27-15/16)
Wide panel (for renewal): Space panel:
Net Weight kg(lbs.) 7.5(16.5) 10.5(23.2) Please choose the size of the wide panel Please use these panels for handling the shallow ceiling cavity, and to prevent smudging. If you wish to install a
3
Approximate Packing Measurement m 0.13 0.20 according to the measurements of an existing humidifier, branch duct flanges and a fresh air absorption kit in combination with space panels, you may not be able
ceiling opening and the measurements of an to do so because of the cradling structure of the ceiling. In addition, a shallower ceiling cavity can handle double
NOTES: already-installed indoor unit. layers of space panels.
1. The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature 2. The sound pressure level is based on following conditions. • Standard
〈single〉 Ceiling 〈double〉
are under the following conditions. 1.5 Meters Beneath the Unit. • Oil guard specifications
Cooling Operation Conditions Heating Operation Conditions The data in the table above was measured in an anechoic chamber so that Ceiling

reflected sound should be taken into consideration in the field. Type Small Large
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) 80mm
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) Measurement of External form 40mm
780*1580*12 780*1940*12
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) (mm)
space panel Decorative Panel space panel Decorative Panel
Piping Length:7.5 Meters Piping Lift:0 Meter

97 98
Ducted

High ESP (External Static Pressure) type Low ESP (External Static Pressure) type
Ducted High ESP type Ducted Low ESP type
JTDH224H0NF0AQ JTDH280H0NF0AQ JTDL022 JTDL028 JTDL036 JTDL043 JTDL050 JTDL056 JTDL063 JTDL071 JTDL084 JTDL090 JTDL112 JTDL142 JTDL160
Model JTDH084H0NB0AQ JTDH090H0NB0AQ JTDH112H0NB0AQ JTDH142H0NB0AQ JTDH160H0NB0AQ Model
JTDH224H0NB0AQ JTDH280H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ
220/1/60 220/1/60 Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60
Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60
380/3/60 380/3/60
Cooling kW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 8.4 9.0 11.2 14.2 16.0
Cooling kW 8.4 9.0 11.2 14.2 16.0 22.4 28.0 Capacity
Capacity Heating kW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 9.6 10.0 13.0 16.3 18.0
Heating kW 9.6 10.0 13.0 16.3 18.0 25.0 31.5
Air Flow Rate (H/M/L) m3/min 8/7/6 8/7/6 13/11/9 13/11/9 15/13/11 15/13/11 16/14/12 16/14/12 25/21/17 25/21/17 27/23/29 37/31/25 38/35/29
Air Flow Rate (H/M/L) m3/min 25/21/17 25/21/17 27/23/29 37/31/25 38/35/29 58 72
ESP Standard (min~max) Pa 30 30 30 30 30 30 30 30 60 60 60 60 60
ESP Standard (min~max) Pa 120(90-120) 120(90-120) 120(90-120) 120(90-120) 120(90-120) 180 180
270× 270× 270× 270× 270× 270× 270× 270× 350× 350× 350× 350× 350×
Dimension Unit (H×W×D) mm 350×(900+75)×800 350×(900+75)×800 350×(900+75)×800 350×(1300+75)×800 350×(1300+75)×800 470×1060×1120 470×1250×1120 Dimension Unit (H×W×D) mm
(650+75)×720 (650+75)×720 (650+75)×720 (650+75)×720 (900+75)×720 (900+75)×720 (900+75)×720 (900+75)×720 (900+75)×800 (900+75)×800 (900+75)×800 (1300+75)×800 (1300+75)×800
Weight Net Weight kg 46 46 46 58 58 96 104
Weight Net Weight kg 26 26 26 26 35 35 35 35 46 46 46 58 58
Refrigerant Type - R410A
Refrigerant Type - R410A
Noise (Anechoic) H/M/L dB(A) 42/39/35 42/39/35 43/40/36 44/41/37 45/41/37 50 52
Noise (Anechoic) H/M/L dB(A) 29.5/26/24.5 29.5/26/24.5 34/32/30 34/32/30 34/32/30 34/32/30 35/33/31 35/33/31 40/37/33 40/37/33 41.5/39/35 42/39/35 43/39/37
Connections - Flare-Nut Connection (with Flare Nuts) Brazing
Connections - Flare-Nut Connection (with Flare Nuts)
Liquid/Gas (Φ )mm 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/19.05 9.53/22.23
Piping Liquid/Gas (Φ )mm 6.35/12.70 6.35/12.70 6.35/12.70 6.35/12.70 6.35/15.88 6.35/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88 9.53/15.88
Drainage mm VP25 Piping
Drainage mm VP25
Packaging Volume m3 0.38 0.38 0.38 0.52 0.52 0.90 1.06
Packaging Volume m3 0.21 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.38 0.38 0.38 0.52 0.52
NOTES:
NOTES:
1.The nominal cooling capacity is the combined capacity of the standard 2. The sound pressure level is based on following conditions. 1.5
1.The nominal cooling capacity is the combined capacity of the standard 2. The sound pressure level is based on following conditions. 1.5
split system, and is based on the JIS standard B8616. Meters Beneath the Unit. With Discharge Duct (2.0m) and
split system, and is based on the JIS standard B8616. Meters Beneath the Unit. With Discharge Duct (2.0m) and
Cooling Operation Conditions Heating Operation Conditions Return Duct (1.0m). Voltage of the power source for the indoor
Cooling Operation Conditions Heating Operation Conditions Return Duct (1.0m). Voltage of the power source for the indoor
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) fan motor is 220V. In case of the power source of 240V, the
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) fan motor is 220V. In case of the power source of 240V, the
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) sound pressure level increases by about 1 dB. The above data
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) sound pressure level increases by about 1 dB. The above data
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) was measured in an anechoic chamber so that reflected sound
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) was measured in an anechoic chamber so that reflected sound
Piping Length: 7.5 Meters Piping Lift: 0 Meter should be taken into consideration in the field.
Piping Length: 7.5 Meters Piping Lift: 0 Meter should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure
3. The data for external pressure *3) indicates "Standard Pressure
Setting values when a filter is not used.
Setting values when a filter is not used.
4. (Concerning 224/280 unit)
H0NF0AQ = 380V/3Φ/60Hz
H0NB0AQ = 220V/1Φ/60Hz

Medium ESP (External Static Pressure) type FEATURES AND BENEFITS OPTIONAL PARTS
Design Flexibility Optional Drain Pump
Ducted Medium ESP type
Drain-up mechanism can be supplied as optional part.
JTDM022 JTDM028 JTDM036 JTDM043 JTDM050 JTDM056 JTDM063 JTDM071 JTDM224 JTDM280
Model
H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NB0AQ H0NF0AQ H0NF0AQ 1) Air Inlet
Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 380/3/60 380/3/60
Cooling kW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1 22.4 28.0
Capacity
Heating kW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5 25.0 31.5
Air Flow Rate (H/M/L) m3/min 8/7/6 8/7/6 13/11/9 13/11/9 15/13/11 15/13/11 16/14/12 16/14/12 58 72
ESP Standard (min~max) Pa 50(50-80) 50(50-80) 50(50-80) 50(50-80) 50(50-80) 50(50-80) 50(50-80) 50(50-80) 180 180 Air Inlet
270×(650+75) 270×(650+75) 270×(650+75) 270×(650+75) 270×(900+75) 270×(900+75) 270×(900+75) 270×(900+75) 470×1060 470×1250
Dimension Unit (H×W×D) mm Muximum
×720 ×720 ×720 ×720 ×720 ×720 ×720 ×720 ×1120 ×1120
Weight
Refrigerant Type
Net Weight kg
-
26 26 26 26 35
R410A
35 35 35 96 104 900
mm
Noise (Anechoic) H/M/L dB(A) 35/33/31 35/33/31 35/33/31 35/33/31 35/33/31 35/33/31 36/34/32 36/34/32 56 (58) (*4) 70 (72) (*4)
Connections - Flare-Nut Connection (with Flare Nuts) Brazing Air Inlet
Liquid/Gas (Φ )mm 6.35/12.70 6.35/12.70 6.35/12.70 6.35/12.70 6.35/15.88 6.35/15.88 9.53/15.88 9.53/15.88 9.53/19.05 9.53/22.23
Piping Drain Pump IDU capacity
Drainage mm VP25
Nomenclature kW (Cooling) HP Class
Packaging Volume m3 0.21 0.21 0.21 0.21 0.27 0.27 0.27 0.27 0.90 1.06
JDUPI-132CQ 2.2 - 7.1 0.8 - 2.5
NOTES: JDUPI-162Q 8.4 - 16.0 3.0 - 6.0
1.The nominal cooling capacity is the combined capacity of the standard 2. The sound pressure level is based on following conditions. 1.5 JDUPI-15H2Q 22.4 - 28.0 8.0 - 10.0
split system, and is based on the JIS standard B8616. Meters Beneath the Unit. With Discharge Duct (2.0m) and
Cooling Operation Conditions Heating Operation Conditions Return Duct (1.0m). Voltage of the power source for the indoor
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) fan motor is 220V. In case of the power source of 240V, the
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) sound pressure level increases by about 1 dB. The above data
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) was measured in an anechoic chamber so that reflected sound
Piping Length: 7.5 Meters Piping Lift: 0 Meter should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure
Setting values when a filter is not used.
(*4) Indoor Fan Air flow rate data in brackets () is the one then
Optional Filter
the power supply is 50Hz Filter Nomenclature Ducted Category kW (Cooling) HP Class
Medium ESP
JKW-PP1Q 2.2 - 4.3 0.8 - 1.5
Low ESP
Medium ESP
JKW-PP2Q 5.0 - 7.1 1.8 - 2.5
Low ESP
High ESP
JKW-PP3Q 8.4 - 11.2 3.0 - 4.0
Low ESP
High ESP
JKW-PP4Q 14.2 - 16.0 5.0 - 6.0
Low ESP

99 100
Ducted

Slim type
Model
Ducted Slim type
JTDS022H0PB0AQ JTDS028H0PB0AQ JTDS036H0PB0AQ JTDS043H0PB0AQ
FEATURES AND BENEFITS OF SLIM / COMPACT MODEL
Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60
Cooling kW 2.2 2.8 3.6 4.3
Design Flexibility
Capacity
Heating kW 2.8 3.3 4.2 4.9
Air Flow Rate (H/M/L) m3/min 8/7/6 8/7/6 10/8/7 10/8/7 1) Slim & compact design 2) Standard drain pump with 900 mm lift
ESP Standard (min~max) Pa 10(10-30) 10(10-30) 10(10-30) 10(10-30) 700mm
Dimension Unit (H×W×D) mm 192×700×602 192×700×602 192×700×602 192×700×602 602mm 700 mm
Weight Net Weight kg 21 21 21 21
Refrigerant Type - R410A drain
192 mm
Noise (Anechoic)
Connections
H/M/L dB(A)
-
28/25/22 28/25/22 32/30/28
Flare-Nut Connection (with Flare Nuts)
32/30/28
900
mm
Liquid/Gas (Φ )mm 6.35/12.70 6.35/12.70 6.35/12.70 6.35/12.70
Piping
Drainage mm VP25 2.2-4.3kW
Packaging Volume m3 0.15 0.15 0.15 0.15
In dropped Ceiling
Slim
NOTES:
1.The nominal cooling capacity is the combined capacity of the standard 2. The sound pressure level is based on following conditions. 1.5
split system, and is based on the JIS standard B8616. Meters Beneath the Unit. With Discharge Duct (2.0m) and 900mm Adaptability
Return Duct (1.0m). Voltage of the power source for the indoor 900mm 447mm
Cooling Operation Conditions Heating Operation Conditions
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) fan motor is 220V. In case of the power source of 240V, the
sound pressure level increases by about 1 dB. The above data Quiet Operation
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) was measured in an anechoic chamber so that reflected sound
should be taken into consideration in the field.
192 mm
slim 2.2 3.6
Piping Length: 7.5 Meters Piping Lift: 0 Meter Cooling capacity (kW)
3. The data for external pressure *3) indicates "Standard Pressure
compact 2.2 3.6 5.0 6.3
Setting values when a filter is not used.
2.2-4.3kW Sound Pressure Level (dB(A)) 21 26 28 30
* air flow volume:low.
Compact Over the closet
20dB 30dB
1,200mm CLOCK MIDNIGHT

1,170mm
447mm

192 mm

5.0-7.1kW

In dropped Ceiling over the window


Optional Filter
Filter Nomenclature Ducted Category kW (Cooling) HP Class

Compact type JKW-PP5Q


JKW-PP6Q
Compact
Compact
2.2 - 4.3
5.0 - 7.1
0.8 - 1.5
1.8 - 2.5

Ducted Compact type


Model JTDN022H0PB0AQ JTDN028H0PB0AQ JTDN036H0PB0AQ JTDN043H0PB0AQ JTDN050H0PB0AQ JTDN056H0PB0AQ JTDN063H0PB0AQ JTDN071H0PB0AQ
Power Supply V/Ph/Hz 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60 220/1/60
Cooling kW 2.2 2.8 3.6 4.3 5.0 5.6 6.3 7.1
Capacity
Heating kW 2.8 3.3 4.2 4.9 5.6 6.5 7.5 8.5
Air Flow Rate (H/M/L) m3/min 8/7/6 8/7/6 10/8/7 10/8/7 14.5/12.5/10.5 14.5/12.5/10.5 16/14/12 16/14/12
ESP Standard (min~max) Pa 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30) 10(10-30)
Dimension Unit (H×W×D) mm 192×900×447 192×900×447 192×900×447 192×900×447 192×1170×447 192×1170×447 192×1170×447 192×1170×447
Weight Net Weight kg 20 20 21 21 26 26 26 26
Refrigerant Type - R410A
Noise (Anechoic) H/M/L dB(A) 27/24/21 27/24/21 31/29/26 31/29/26 34/30/28 34/30/28 35/33/30 35/33/30
Connections - Flare-Nut Connection (with Flare Nuts)
Liquid/Gas (Φ )mm 6.35/12.70 6.35/12.70 6.35/12.70 6.35/12.70 6.35/15.88 6.35/15.88 9.53/15.88 9.53/15.88
Piping
Drainage mm VP25
Packaging Volume m3 0.15 0.15 0.15 0.15 0.18 0.18 0.18 0.18

NOTES:
1.The nominal cooling capacity is the combined capacity of the standard 2. The sound pressure level is based on following conditions. 1.5
split system, and is based on the JIS standard B8616. Meters Beneath the Unit. With Discharge Duct (2.0m) and
Cooling Operation Conditions Heating Operation Conditions Return Duct (1.0m). Voltage of the power source for the indoor
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) fan motor is 220V. In case of the power source of 240V, the
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB) sound pressure level increases by about 1 dB. The above data
Outdoor Air Inlet Temperature: 35oC DB (95oF DB) 6oC WB (43oF WB) was measured in an anechoic chamber so that reflected sound
Piping Length: 7.5 Meters Piping Lift: 0 Meter should be taken into consideration in the field.
3. The data for external pressure *3) indicates "Standard Pressure
Setting values when a filter is not used.

101 102
Exposed & Concealed

Ceiling Suspended type FEATURES AND BENEFITS


Adaptability Design Flexibility

1) Auto louver 1) High Ceiling Available


Auto louver

IDU Capacity HP(Class) 1.5-3.0 4.0-6.0

Height (m) 3.5 4.3


Dimensions
* air flow volume: high2
960mm
690mm
off down horizontal
JTCS040H0NS0AS 26Kg
ceiling
235mm
JTCS056H0NS0AS 27Kg drain
600
mm
1,270mm
690mm
Floor 8m
JTCS071~080H0NS0AS 35Kg
235mm

2) Quiet operation Up to
 new design in fan inlet and fan resulted in the low sound pressure 3.5m
1,580mm 690mm down

JTCS112~160H0NS0AS 41Kg 235mm Cooling capacity (kW) 4.0 8.0 11.2 14.0

Sound Pressure Level (dB(A)) 28 29 32 35


* air flow volume: low.

20dB 30dB
Application CLOCK MIDNIGHT

Kitchen
Space

Indoor Unit Type


Model
Ceiling Suspended Type
JTCS040H0NS0AS JTCS056H0NS0AS JTCS071H0NS0AS JTCS080H0NS0AS JTCS112H0NS0AS JTCS140H0NS0AS JTCS160H0NS0AS
OPTIONAL PARTS
Please consult your distributors or dealers in inquiry
Indoor Unit Power Supply AC 1Φ , 220-240V/50Hz, 220V/60Hz Duct adaptor:
Nominal Cooling Capacity kW(Btu/h) 4.0(13,600) 5.6(19,100) 7.1(24,200) 8.0(27,300) 11.2(38,200) 14.0(47,800) 16.0(54,600) for fresh air absorption aperture
Filter (for box): [Φ 100 mm]
Nominal Heating Capacity kW(Btu/h) 4.8(16,400) 6.3(21,500) 8.5(29,000) 9.0(30,700) 12.5(42,600) 16.0(54,600) 18.0(61,400) • Antimicrobial high-performance filters
Sound Pressure Level (Overall A Scale) Please use these filters in offices,
dB 37/35/31/28 38/35/31/28 38/35/31/28 40/37/33/29 44/42/37/32 48/45/41/35 49/47/42/36
(Hi2/Hi/Me/Lo) hospitals and welfare facilities for the
Cabinet Color Neutral White elderly.
Height mm(in.) 235(9-1/4) 235(9-1/4) 235(9-1/4) 235(9-1/4) 235(9-1/4) 235(9-1/4) 235(9-1/4) • Deodorizing filters
Outer Please use these filters for locations
Width mm(in.) 960(37-4/5) 960(37-4/5) 1270(50) 1270(50) 1580(62-1/5) 1580(62-1/5) 1580(62-1/5)
Dimensions where general living odors (ammonia Rear side decoration panel:
Depth mm(in.) 690(27-1/5) 690(27-1/5) 690(27-1/5) 690(27-1/5) 690(27-1/5) 690(27-1/5) 690(27-1/5) odor, etc.) are bothersome, hospitals to conceal the sheet metal in the
Net Weight kg(lbs.) 26(57) 27(60) 35(78) 35(78) 41(91) 41(91) 41(91) and welfare facilities for the elderly. The rear side of unit
Refrigerant R410A filters can be dried in the sunshine and
can also be washed in water. (Lifespan
Air Flow Rate 15/13/11/9 15/13/11/9 19/16.5/14/11.5 21/18.5/15.5/12.5 30/26.5/22/17 35/31/25.5/20(1236/ 37/32.5/27/21(1306/
Indoor Fan m3/min.(l/s) of around three years)
(Hi2/Hi/Me/Lo) (530/459/388/318) (530/459/388/318) (671/582/494/406) (741/653/547/441) (1059/935/777/600) 1094/900/706) 1147/953/741)
Motor W 50 50 80 80 160 160 160
Connections Flare-Nut Connection (with Flare Nuts)
Liquid Line mm(in.) Φ 6.35(1/4) Φ 6.35(1/4) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Φ 9.52(3/8) Optioned: Drain pump:
Refrigerant Up to 600mm
Gas Line mm(in.) Φ 12.7(1/2) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Φ 15.88(5/8) Receiver Kit:
Piping For Remote Controller (JCRB10NEWS) • (4.0kW)JDUPC-63K1
Condensate Drain VP20 VP20 VP20 VP20 VP20 VP20 VP20 • (5.6kW)JDUPC-71K1
Approximate Packing Measurement m3 0.23 0.23 0.31 0.31 0.38 0.38 0.38 • (7.1-16.0kW)JDUPC-160K1

NOTES:
1.The cooling and heating capacities above show the maximum capacities when the outdoor and indoor temperature 2. The
 sound pressure level is based on following conditions. Filters (for panels):
are under the following conditions. 1.5 Meters Beneath the Unit. • For exchanging long-life filters (anti-mold)
Cooling Operation Conditions Heating Operation Conditions The data in the table above was measured in an anechoic chamber so that • Oil guard filters
Indoor Air Inlet Temperature: 27oC DB (80oF DB) Indoor Air Inlet Temperature: 20oC DB (68oF DB) reflected sound should be taken into consideration in the field.
19.0oC WB (66.2oF WB) Outdoor Air Inlet Temperature: 7oC DB (45oF DB)
o o
Outdoor Air Inlet Temperature: 35 C DB (95 F DB) 6oC WB (43oF WB)
Piping Length:7.5 Meters Piping Lift:0 Meter

103 104
Exposed & Concealed

Wall mounted type Floor concealed type


Indoor Unit Wall Type Floor concealed type

JTFC028H0NB0AQ JTFC043H0NB0AQ JTFC056H0NB0AQ JTFC071H0NB0AQ


JTHW022H0NB0AQ JTHW028H0NB0AQ JTHW036H0NB0AQ JTHW040H0NB0AQ JTHW050H0NB0AQ JTHW056H0NB0AQ JTHW063H0NB0AQ

2.3 2.9 3.8 4.1 5.2 5.8 6.5

2,000 2,500 3,300 3,550 4,500 5,000 5,600

7,800 9,900 13,000 14,100 17,700 19,800 22,200

2.2 2.8 3.6 4.0 5.0 5.6 6.3

1,900 2,400 3,100 3,450 4,300 4,800 5,400

7,500 9,600 12,300 13,600 17,000 19,100 21,500

2.5 3.3 4.0 4.5 5.6 6.3 7.5

2,150 2,800 3,450 3,900 4,800 5,400 6,500

8,500 11,100 13,600 15,300 19,100 21,500 25,600

38/36/32 38/36/32 40/36/34 41/38/35 41/38/35 41/38/35 44/41/38

280 280 280 280 290 290 290

11 11 11 11 12 12 12

780 780 780 780 1,050 1,050 1,050

31 31 31 31 41 41 41

220 220 220 220 220 220 220

9 9 9 9 9 9 9
18 22 26 27
10 10 10 10 13.5 13.5 13.5
(40) (49) (57) (60)
22 22 22 22 30 30 30

8.5/7.5/6.5 8.5/7.5/6.5 9.2/7.5/6.5 10/8.5/7.5 12/10.3/8.7 12/10.3/8.7 13.7/12/10.3

30 30 30 40 50 50 60

Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35 Φ6.35

(1/4) (1/4) (1/4) (1/4) (1/4) (1/4) (1/4)

Φ12.7 Φ12.7 Φ12.7 Φ12.7 Φ15.88 Φ15.88 Φ15.88

(1/2) (1/2) (1/2) (1/2) (5/8) (5/8) (5/8)

VP16 VP16 VP16 VP16 VP16 VP16 VP16

0.12 0.12 0.12 0.12 0.15 0.15 0.15

Floor type: 1.5 meters from floor level.


Floor concealed type: 1.5 meters from the unit and 1.5 meters from the floor level.
1 meter beneath the unit and 1 meter from the inlet grille.

105 106
Options

FRESH AIR UNIT


Indoor Unit Type Fresh Air Unit
Model JVAF1080H0NB0AQ JVAF1680H0NB0AQ JVAF2180H0NB0AQ
Power supply AC 1Φ , 220V/60Hz
Capacity kW 14.0 22.4 28.0
Cooling Power kW 0.35 0.55 0.58
Introduction of Motion Sensor Kit Nominal Current A 1.61 2.53 2.65
Capacity kW 13.7 21.9 24.5
Heating Power kW 0.35 0.55 0.58
image
Nominal Current A 1.61 2.53 2.65
Senses the amount of human activity, Motion Sensor Sound pressure level (overall a scale) dB(A) 42 44 47

undertakes automatic saving and Dimensions H×W×D mm 370 × 1320 × 800 486 × 1270 × 1069 486 × 1270 × 1069
Net Weight kg 63 110 110
achieves intelligent energy saving Refrigerant R410A
Air Flow Rate m3/min 18 28 35
External Pressure Pa 200 220 220
Liquid mm Φ 9.53 Φ 9.53 Φ 9.53
Piping Gas mm Φ 15.88 Φ 19.05 Φ 22.2
Condensate Drain VP25, outer diameter: Φ 32mm
Temperature range of fresh air drawn Cooling: 20oC~43oC, Heating: -7oC~15oC
Connectable Outdoor Unit YORK Commercial VRF Heat Pump Type (JTOH-BS1 series)
NOTES:
1. Cooling capacity and heating capacity test in the following conditions:
Cooling conditions: 33°CDB, 28°CWB, pipeline length 7.5m, pipe height difference 0.0m
Heating conditions: 0°CDB, -2.9°CWB, pipeline length 7.5m, pipe height difference 0.0m ( heating is the data without defrosting)
2. Noise test conditions are as follows:
At a distance of 1.5m from the unit surface
The above parameters are measured in the anechoic chamber without reflected echo, therefore the impact of the reflected echo must be counted at the scene.
3. An air filter with dust removal efficiency of 50% or more needs to be installed at the air inlet.
4. When the field duct resistance is small and the fan speed is too high, the unit will appear the phenomena of abnormal shutdown, fault, water spray etc., and the duct pipe should be insulated to prevent
generating dew.
5. Air processor can only be used for processing fresh air, indoor air conditioning load processing need to use other air conditioners.
6. Fresh air processing unit should be connected with YORK Heat Pump type VRF (JTOH-BS1 series).
motion sensor kit When fresh air processing unit and other indoor units air all connected to the same (JTOH-BS1 series) outdoor unit, Its equivalent cooling capacity is calculated by the following criteria:
detecting area Type_5HP: 21.0kW; 8HP: 33.3kW; 10HP: 42.0kW
7. Refer to capacity restrains shown on Table below for indoor unit capacity connectable to outdoor unit.
System All Fresh Air Unit System (Only All Fresh Air Unit) Mixed System (All Fresh Air Unit and Other Indoor Unit)
i) 80 to 100%
Range of Combination Capacity 80 to 100% and
ii) Total Capacity of All Fresh Air: 30%
8. When outdoor temperature is below 20°C in cooling operation, the system will be automatically converted to ventilation operation. When outdoor temperature is higher than 15°C in heating operation, it will
be automatically converted to ventilation operation. When lower than -7°C, the fresh air processing unit will stop running.
Saving Energy

Perceives the amount of human activity and undertakes


automatic saving
AHU-KIT
Type AHU CONNECTION KIT
Model JDXF-2.0A JDXF-4.0A JDXF-6.0A JDXF-10.0A JDXF-20.0A
Capacity(HP) 2HP 4HP 6HP 8HP 10HP 12HP 14HP 16HP 18HP 20HP
Power Source - AC 1Φ , 220V/60Hz
Height(H) mm 341
Width(W) mm 291
Control Box Depth(D) mm 127
Net Weight kg 5.2
Casing Material Steel Plate with White Grey Coating (anti-corrosion)
Height(H) mm 200
Width(W) mm 165
Expansion Valve
Depth(D) mm 62
Box
Net Weight kg 1.7
Material Steel Plate+White Grey Coating
Capacity Control Mode Outlet Air Temperature Control/Inlet air(room air) Temperature Control/Duty Signal control
Compatibility Multi Combination - 2-6HP
Single Combination - 8-20HP
Standard operation for a room Moderate operation for a room More moderate operation if It is also possible to stop the Pipe Size mm Φ 6.35 Φ 9.53 Φ 9.53 Φ 9.53 Φ 12.7
with a lot of human movement. with little human movement. people are absent for a certain operation of the unit by applying Distance of the Valve Box and AHU m 5
Height Difference of the Valve Box and AHU m 2
period of time. a particular setting if people Installation for Exp. Valve - Vertical/Horizontal
remain absent for more than 30 Installation Indoor/Outdoor
Refrigerant Flow Control Electrical Expansion Valve
minutes.
Model Name Installation Outlet Air Thermistor 2.5m
Inlet Air Thermistor 2.5m
Liquid Pipe Thermistor 2.5m
Motion Sensor Kit Indoor Unit
Gas Pipe Thermistor 2.5m
Exp. Valve wire 2.5m
JP-AP160NAE 4-way cassette (RCI-FSN3)
Cooling Temperature Range DB °C 17~35
Heating Temperature Range DB °C 10~27
JPS-MSK2 4-way cassette (RCI-FSKDNQ)
* Cooling capacity data based on the following indoor and outdoor temperature conditions:
* AHU Kit not available to connect to central control system.

Operation conditions Cooling DB: dry bulb; WB: wet bulb


Pipe length: 7.5m; pipe height: 0m
DB 27.0°C
Indoor air inlet temperature
WB 19.0°C
DB 35.0°C
Outdoor air inlet temperature
WB -

107 108
Controllers Index

Controllers INDIVIDUAL CONTROL SYSTEMS


111 JCWB10NEWS
ADVANCED WIRED REMOTE CONTROLLER

Office

113 JCRB10NEWS
ADVANCED WIRELESS REMOTE CONTROLLER

Residence

113 JCRA10NEWQ
WIRELESS REMOTE CONTROLLER

Residence

114 Receiver kit


FOR WIRELESS REMOTE CONTROLLER

115 JCWA10NEWQ
WIRED REMOTE CONTROLLER

Office

116 JCSA10NEWS
SIMPLIFIED WIRED REMOTE CONTROLLER

Hotel Room

CENTRALIZED CONTROL SYSTEMS Groups

117 JCMA101EWS 32
CENTRAL STATION mini
FOR SMALL SCALE BUILDING

Office

119 JCTA121EWS 64
CENTRAL STATION EZ
FOR MEDIUM-SCALE BUILDING

Hospital

121
CENTRALIZED ON / OFF CONTROLLER 16
JCOA111EWS

Restaurant

122 OTHERS
3P Connector Cable
Remote Sensor
Remote Control Cable

110
INDIVIDUAL CONTROL SYSTEMS

JCWB10NEWS
Office Supermarket Cultural Clinic
Heritage

ADVANCED WIRED REMOTE CONTROLLER


Room Name Indicator
Swing Louver Indicator Filter Sign Indicator FLTR

Fan Speed Indicator Operation Lock Indicator


Ventilation Indicator
Specifications Schedule Timer Indicator Weekly Schedule
Outer Dimensions (H*W*D) Seven‑day timer with multiple set‑points (up to 5 actions per day): For example :
Restaurant
(mm) 120.0 * 120.0 * 17.9 Operation Mode No need to worry about controlling the air conditioner each time, Closing Time Fewer People
Indicator
(inch) 4.72 * 4.72 * 0.70 each day.
28
Net Weight Operation Guide Setting 1 3
200 g Indicator Temperature 27 Preparation Preparation
Indicator
1/2 lbs
26
Busiest Hours 5

Temperature setting (°C)


25 Night Time

24
Run Indicator Menu
Switch In Case of Restaurant 4
in Cooling Mode
23 Dinner Time
2
RUN / STOP Switch
Lunch Time
0
8:00 11:00 14:00 17:00 21:00 23:00
(Time)

Directional Key Enter Key Return Help Switch


Example of System Configuration Switch Auto-Recovery of Temperature Temperature Range Setting
1 IDU Connection Up to 16 IDU Connection Reducing excessive energy consumption thanks to automatic Prevent wasteful power consumption due to excessive use of
temperature reset. cooling/heating mode.
[Cooling Mode] [Cooling Mode]

Temperature Temperature
Set-Point 19°C/66°F 30°C/86°F
2 RCS
Normal
controll is ........ 28°C/82°F
available
Back to 25°C/77°F 30°C/86°F
Lower to
28°C/82°F ON
19°C/66°F
Up to 16 IDU Automatically
Lower Limit
H-LINK 19°C/66°F 25°C/77°F
Can not go lower Available set range
Main RCS Sub RCS Transition wiring is necessary Remote Control Cable
Time

After a certain time passes, the changed temperature returns


Run/Stop Screen Adjustment Operation Lock / Set to the set point. The time can be selected from four options
(15‑30‑60‑90 mins).
Operation Mode Language Lower Limit for Cooling Operation New
Screen
Auto Mode Setting Temperature Unit - °C /°F Management Upper Limit for Heating Operation
Temperature Setting Adjusting Brightness of Run Indicator Built-in Timer (On / Off)
Temperature Setting Rate _ 1°C / 1°F Sensor Condition Check Adjusting Date / Time Setting New
Built-in Timer Guidance
Fan Speed _ 3/4 Taps Sensor Data Check Weekly Schedule At a predetermined time, the indoor unit can be turned off thanks “Indication” “Operation” “Problem” “Contact” If there is a problem,
Louver Direction Model Display Settable Timer Operation Times (Per Day)
Check Menu Schedule to the built‑in timer. the Guidance System will help you to find out the causes and provide
Setting Individual Louver Setting Indoor / Outdoor PCB Check Holiday Setting New
The time can be chosen from those below. measures or help desk contact.
Remote Control Main-Sub Setting Self Checking Schedule On / Off
In Use of Ventilation Alarm History Display [Minutes] 30-40-45-50-55-90 min (e.g. useful for classrooms)
Total-Heat-
Exchanger Total Heal Exchanger Setting Test Run
Automatic Restart with Function Selection (Optional Function Setting)
Eco-operation 30min 45min 55min
Function Thermistor Selection
Automatic Reset Temperature 40min 50min 90min
Selection (Cooling /Heating) Input / Output Setting
Temperature Indication Indoor Unit Address Change
Test Run
Filter Sign Indoor Unit Address Checking Operation
[Hours] 1h-2h......24h
Filter Sign Reset Indoor Unit Address Initialization
Service Louver Open / Close Input-Output Setting Initialization
1h 2h 24h
Room Name Setting Compressor Pre-Heat Control Cancellation
Alarm Sign Contact Information Registration

111 112
INDIVIDUAL CONTROL SYSTEMS

JCRB10NEWS
ADVANCED WIRELESS REMOTE CONTROLLER
Transmitter Residence Hotel Room Hospital
Room
Classroom
Receiver kit
FOR WIRELESS REMOTE CONTROLLER
See "Page 114: Receiver kit" Transmitting Indication
LCD (Liquid Crystal Display)

Mode Selection Switch Fan Speed Switch Category Cassette Ducted Others
Specifications On Switch 4-way Cassette 2-way Ducted Ceiling Floor Wall
Reset Switch Description 4-way Cassette Ducted HEP Ducted MEP Ducted LEP Ducted Slim
Compact Cassette Compact Suspended Concealed Mounted
Outer Dimensions (H*W*D) Off Switch
Indoor
(mm) 140.0 * 55.0 * 16.8 Unit
Louver Angle Switch Model
(inch) 5.51 * 2.17 * 0.66
Timer Switches Temp. Switch
Net Weight Filter Sign Reset Switch
JTKFH0PS0AS JTKFH0PSAQ JTKMH0PS0AS JTKTH0PS0AS JTDHH0NB0AQ JTDMH0NB0AQ JTDLH0NB0AQ JTDNH0PB0AQ JTDSH0PB0AQ JTCSH0NS0AS JTFCH0NB0AQ JTHWH0NB0AQ

75 g JR4A10NEWS JRMA10NEWS JR2A10NEWS


Standard(JRDA10NEWQ)
JRCA10NEWS
Standard(JRDA10NEWQ)
(Optioned:JRDA12NEWS) ※ (Optioned:JRDA12NEWS) ※
1/6 lbs
Receiver
Model
kit

Example of System Configuration


1 IDU connection
JCRB10NEWS

Run / Stop Filter Sign Reset


Operation Mode Service Identifying indoor units side-by-side
Wireless
Auto Mode Setting Temperature Unit - °C / °F Remote
Setting Temperature Setting Schedule Built-in Timer (On / Off) Controller JCRA10NEWQ
H-LINK
Temperature Setting Rate _ 1°C / 1°F − − − − −
Remote Control Cable
Fan Speed _ 3 / 4 Taps
Louver Direction
Centralized Controller (JCMA101EWS/JCTA121EWS) cannot be operated when you use standard receiver kit (JRDA10NEWQ) equipped with Wireless Remote Controller (JCRA10NEWQ).

JCRA10NEWQ
WIRELESS REMOTE CONTROLLER
Transmitter
Residence Hotel Room Hospital
Room
Classroom

Transmitting Indication
See "Page 114: Receiver kit"

LCD (Liquid Crystal Display)

Specifications Run/Stop Switch Fan Speed Switch

Outer Dimensions (H*W*D) Reset Switch Louver Angle Switch

(mm) 125.0 * 56.0 * 16.4 Temp. Switch

Timer Switches

Run / Stop Identifying indoor units side-by-side


Service
Operation Mode Temperature Unit _ 1°C
Auto Mode Setting Schedule Built-in Timer (On / Off)
Setting Temperature Setting
Temperature Setting Rate _ 1°C
Fan Speed _ 3 Taps
Louver Direction

Centralized Controller cannot be operated when you use this wireless remote controller (JCRA10NEWQ).

113 114
INDIVIDUAL CONTROL SYSTEMS

JCWA10NEWQ
WIRED REMOTE CONTROLLER
Office Supermarket Cultural
Heritage
Clinic
JCSA10NEWS
SIMPLIFIED WIRED REMOTE CONTROLLER
Hotel Room Hospital
Room
Classroom

Swing Louver Indicator ON / OFF Timer (Timer Operation) Indicator


Defrost Indicator TEMP.(Set Temperature) Indicator
CENTRAL (Central Control) Indicator
Specifications Alarm Code Indicator
"NO FUNCTION" Indicator
Specifications
Fan Speed Indicator Operation Lock Indicator
Outer Dimensions (H*W*D) Ventilation Indicator Automatic ControI lndicator Outer Dimensions (H*W*D) Run Indicator (Red) TEMP (Temperature Setting)
(mm) 120.0 * 120.0 * 17.0 (mm) 120.0 * 70.0 * 17.0 ON / OFF Switch
Switch

(inch) 4.72 * 4.72 * 0.67 (inch) 4.72 * 2.76 * 0.67


Net Weight Operation Mode Indicator Net Weight Swing Louver
Automatic Cooling / Heating Operation Mode Switch
150 g 90 g (Swing Louver Operation)
Operation Indicator "FILTER" Indicator : FAN Switch
1/3 lbs "ABNML" (ALARM) Indicator 1/5 lbs : COOL
Run Indicator (Red Lamp)
: HEAT
: DRY
RUN / STOP Switch TEMP (Temperature Setting) : AUTO
Switch
Fan Speed Switch
Open the cover by pulling MODE FAN SPEED ON/OFF TIMER RESET By repeatedly pressing the button,
in the direction of the arrow By repeatedly pressing the button, the fan speed setting will change sequentially.
RESET (Filter Reset) Switch
the setting will change sequentially.
VENT LOUVER CHECK
TIME Check Switch
Mode (Operation Mode Selection) Switch Run / Stop Temperature Setting Rate _ 1°C
Fan Speed Selection Switch
Operation Mode Setting Fan Speed_ 3 Taps
Setting
Auto Mode Setting Louver Direction
Temperature
Elevating Grille Operation Switch
ON / OFF TIMER Switch
VENTI (Ventilator Operation) Switch
TIME (Time Setting) Switch
SWING LOUVER (Swing Louver Operation) Switch

Example of System Configuration


1 IDU Connection Up to 16 IDU Connections

2 RCS control is ........


available

Up to 16 IDU

H-LINK
Remote Control Cable
Primary Secondary Transition wiring is necessary.
RCS RCS

Run / Stop Sensor Condition Check Operation Lock-Set


Check Menu
Operation Mode Sensor Data Check Manage- Lower Limit for Cooling Operation
Auto Mode Setting Test Run ment Upper Limit for Heating Operation
Temperature Setting Function Selection (Optional Function Setting) Built-in Timer (On/Off)
Setting Temperature Setting Rate _ 1°C Thermistor Selection Schedule Weekly Schedule (+ PSC-A1T)
Fan Speed _ 3 Taps Input - Output Setting
Louver Direction Test Run Indoor Unit Address Change
Remote Control Primary-Secondary Setting Indoor Unit Address Checking Operation
Automatic Reset Temperature (Cooling / Heating) Indoor Unit Address Initialization
Filter Sign Input-Output Setting Initialization
Filter Sign Reset Compressor Pre-Heat Control Cancellation
Service Elevating Grille
Louver Open / Close
Alarm Sign

115 116
CENTRALIZED CONTROL SYSTEMS

JCMA101EWS
(5-inch) Touch Panel Operation Schedule
Easy to check the operation status using either of two monitoring Up to 10 actions/day per RCS
screens (all groups or four pattern blocks [2/4/8/16]) group can be set as available as auto For example :
School
switch‑off timer
CENTRAL STATION mini In case of classroom
mini
FOR SMALL SCALE BUILDING in cooling mode
9:00 ~ 10:00 27 °C Class: on
10:00 ~ 11:00 27 °C Class: on
11:00 ~ 12:00 - °C No class: off
22 52.7 12:00 ~ 13:00 25 °C LUNCH TIME
Specifications Display 5.0-inch Wide Color LCD (Full dot)
13:00 ~ 14:00 - °C No class: off
Display Control Touch Panel 14:00 ~ 15:00 27 °C Class: on
Outer Dimensions (H*W*D) 15:00 ~ 16:00 - °C No class: off
(mm) 120.0 * 140.0 * 74.7 16:00 ~ 17:00 27 °C Class: on
RCS Group 32 17:00 ~ - °C No class: off
(inch) 4.72 * 5.51 * 2.94
Group 32
Net Weight Total Connection Capacity Block 4 patterns (2/4/8/16)
0.5 kg Indoor Unit 160
1.1 lbs Outdoor Unit 64 [Monitor (Block)]
Built-in part Building Scale Small

52.70 mm / 2.07 inch


Lateral View (mm)

RCS Group Function Control Accumulated Operation-Time Visualization


‑each operational item blocking‑prevent incorrect operation Support energy-saving management

ON/OFF, "operation mode," "fan speed," "swing louver direction," "setting


temperature," and "prohibition of remote control operation for individual items (run/
stop, operation mode, fan speed, wind direction, setting temperature)"

Example of System Configuration


RAC Adapter

CS mini Energy Saving


Outdoor unit power consumption control by schedule or external signals. Setting temperature range.

RAC

Total 32 H-LINK
RCS Groups Remote Control Cable

Recommended Facilities

[Capacity Control of ODU] [Temperature Limitation for Each Remote Controller]

Office Shops Cultural Small Hospital School


Heritage Building

117 118
CENTRALIZED CONTROL SYSTEMS

(8.5-inch) Touch Panel Operation

JCTA121EWS
A total of 64 remote controller groups (4 blocks)(64 outdoor units/160 indoor units) can be controlled
Easy to check the operation status using either of two monitoring screens (all groups or blocks)
The panel for the block is bigger than for the CS MINI; you can check Mode, Fan Speed, Louver, Temperature, Inlet and Ambient Temperature.

CENTRAL STATION EZ
FOR MEDIUM SCALE BUILDING

80
Specifications Display 8.5-inch Wide Color LCD (Full dot) 25 55

Outer Dimensions (H*W*D) Display


Touch Panel
Control
(mm) 170.0 * 250.0 * 80.0
(inch) 6.69 * 9.84 * 3.15
RCS Group 64
Net Weight Group 64
Total
1.5 kg Connection Block 4 [Monitor 1 (all groups)] [Monitor 2 (block)]
Capacity
3.3 lbs Indoor Unit 160
Outdoor Unit 64
Built-in part
55.00 mm / 2.17 inch Building Scale Small Medium
Lateral View (mm)
Accumulated Operation-Time Visualization
Supports Energy-Saving Management

Alarm Information
Red color indication: immediate display of malfunction location and cause.

Example of System Configuration


RAC Adapter

CS EZ

RAC Schedule
Up to 10 actions/day per RCS groups can be set as available as auto switch‑off timer.

Total 64 H-LINK
RCS Groups Remote Control Cable

Recommended Facilities
HOTEL

Hospital Office Small Nursing Educational Hotel [Weekly Schedule] [Holiday Setting]
Building Home Facility

119 120
CENTRALIZED CONTROL SYSTEMS OTHERS

CENTRALIZED ON / OFF CONTROLLER

JCOA111EWS 3P Connector Cable


JPCC-1A
FOR CONNECTION TO REMOTE ON/OFF DEVICE /
RECEIPT OF OUTPUT SIGNAL
Example of System Configuration

«JPCC-1A» 3
2
*One set contains five 3P connector cables. Thermostat
1
*J PCC-1A can connect to external signal input-
output terminal both in Outdoor Unit and Indoor 3 CN3
Unit. 2
1
Temperature
Increase
Operation «example»
Remote ON / OFF device
Cooling Operation:
Compressor is ON by closing terminals 2 and 3 of CN3 Indoor Unit PCB
Compressor is OFF by opening terminals 2 and 3 of CN3

Heating Operation:
Compressor is ON by closing terminals 1 and 2 of CN3 H-LINK
Compressor is OFF by opening terminals 1 and 2 of CN3 Remote Control Cable

Only performs operation / stop control per remote control group. Outer Dimensions (mm)
By connecting to the H-LINK, up to 16 remote control groups and 160 indoor units can be controlled.
H W D
Up to 8 controllers can be connected to the H-LINK.

Remote Sensor
An external input terminal is provided as standard. External signals enable the following functions: 120.0 120.0 68.5
central operation / stop, emergency stop, central operation output, central alarm output. Outer Dimensions (inch)
Can be used in combination with the central station.
H W D
* Be sure to use it with a remote control switch. Indoor units cannot be used without a remote
control switch. 4.72 4.72 2.70 JTHM-R2A
* There are restrictions on remote group registration. Please contact our sales staff for more information. TO SENSE THE Example of System Configuration
Weight
grams pounds INDOOR TEMPERATURE
300 g 0.7 lbs

H 50.0
Outer
Dimensions W 50.0
(mm) H-LINK
D 15.0 Remote Sensor Cord
H 1.97
Outer
Dimensions W 1.97 *W hen the room temperature sensing thermistor (Remote Sensor) is
(inch) attached to the auxiliary connector, the unit is controlled at average air
D 0.59
temperature at the indoor inlet and Remote Sensor point.
M 8.00
Length «JTHM» *Not compatible with Wall mounted type indoor unit.
ft 26.25

Remote Control Cable


PRC-5K, 10K, 15K
FOR WIRING TO CONNECT ANY TWO POINTS AMONG
INDOOR UNIT, WIRED REMOTE CONTROLLER AND
CENTRALIZED CONTROLLER

H-LINK
«PRC-5K, 10K, 15K»
PRC-5K PRC-10K PRC-15K Remote Control Cable

M 5.00 10.00 15.00


Length 50mm 100mm *Neither JCWA10NEWQ or JCWB10NEWS
ft 16.40 32.81 49.21
Shielded Twist-Pair Cable include a remote control cable.
Use this cable if you don’t have one
available in your field.

121 122