Вы находитесь на странице: 1из 5

Outdoor Unit - Te

Area: A Block / Second Floor


System name: System 2 ( Left Side )
Capacity of Unit:Cooling / heating = 56 KW/ 63 KW
Power Input: Cooling / heating = 16.8 KW/ 16.5 KW
Date of Testing: 2012.03.15
Ambient Temperature:28°C
Mode of Operation: Cooling
Model number SPW-C1806DXH8

Additional Refrigerant gas charge ( R -410A ) 23.41Kg

Rated Voltage 380/400/415V, 3Phase /50Hz

Cooling Mode
Rated current ( A ) 28.2/26.8/25.8

Additional comments:
Outdoor Unit - Testing Report

Measured Voltage RY- 382 V


YB- 384 V
BR- 383 V

Measured current R = 19 A Y = 18 A B= 17
V
V
V

A
Radisson Hotel
Lazimpat, Kathmandu Nepal

Indoor Unit - Testing Report

Area: A Block / First Floor


System : System 2 ( Left Side)
Date of Testing: 2012.03.15
Ambient Temperature: 28°C
Mode of Operation: Cooling

Room 150 Room 152 Room 154 Room 156


Indoor unit identification
Model number: SPW-U225XH SPW-U225XH SPW-U225XH SPW-U225XH SPW-U225XH
Indoor Unit Capacity: 2 TR
Grill Temperature 16.9°C 17°C 16.2°C 16.5°C
Room Temperature 22°C 22.2°C 21.5°C 21.8°C

Room 158 Room 160 Room 162


Indoor unit identification
Model number SPW-U225XH SPW-U225XH SPW-U225XH
Grill Temperature 16.1°C 16.1°C 17.4°C
Room Temperature 21.1°C 21.2°C 22.5°C

Additional comments:

Prepared By: Checked By:


Radisson Hotel
Lazimpat, Kathmandu Nepal

Prepared By: Checked By: