Calculating the drop cable size for submersible pump

Max cable length of single phase submersible pump is given as follows :

U x DU
L= r
I x 2 x 100 x ( cos f x q + sin f x XI )

Max cable length of three phase submersible pump is given as follows :

U x DU
L= r
I x 1.73 x 100 x ( cos f x q + sin f x XI )

Where : L : Max cable length [m]


U : Rated voltage {V}.
DU : Voltage drop {%}.
I : Rated current of motor {A}.
r : Specific resistance : 0.02 {Wmm2/m}
q : Cross section of submersible drop cable {mm2}.
XI : Inductive resistance : 0.078 x 10 -3 [W/m]
cosf : Power factor

Data : U= 380 Rated voltage {V}.


DU = 4 Voltage drop {%}.
I= 76 Rated current of motor {A}.
r= 0.02 Specific resistance : 0.02 {Wmm2/m}
q= 50 Cross section of submersible drop cable {mm2}.
XI = 7.8E-5 Inductive resistance : 0.078 x 10-3 [W/m]
cosf= 0.89 Power factor

Max cable length of single phase pump :


380 x 4
L= 0.02 = 255 m for 1 phase
76 x 2 x 100 x ( 0.89 x 50 + 0.46 x 7.8E-5 )

Max cable length of three phase pump :

380 x 4
L= 0.02 = 295 m for 3 phase
76 x 1.73 x 100 x ( 0.89 x 50 + 0.46 x 7.8E-5 )
###
###
Motor Kw Hp In [A] Eff. Dimention mm2
cos100%
1.5 2.5 4 6 10 16 25 35 50 70 95 120 150 185 240 300
MS 402 4" 0.37 0.5 3.3 0.68 0.72 ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###
MS 402 4" 0.55 0.75 4.8 0.68 0.7 ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###
MS 402 4" 0.75 1 5.65 0.71 0.73 ### ### ### ### ### ### ### ### ### ### ### ### ### ### ### ###
MS 4000R 4" 0.75 1 4.6 0.711 0.88 ### ### ### ### ### ### ### ### ### ### ###