Вы находитесь на странице: 1из 10

ARTICLE

760 Fire Alarm Systems

Introduction to Article 760—Fire Alarm Systems


Article 760 covers the installation of wiring and equipment for fire alarm systems, including all circuits controlled and powered by the fire
alarm system. These include fire detection and alarm notification, voice communications, guard’s tour, sprinkler waterflow, and sprinkler
supervisory systems. NFPA 72, National Fire Alarm Code provides other fire alarm system requirements.

Since many people have difficulty understanding this article from the text alone, pay close attention to the illustrations as you study this
material. The figures highlight important requirements and common Article 760 violations.

FPN No. 1: Fire alarm systems include fire detection and


Part I. General alarm notification, voice communications, guard’s tour,
sprinkler waterflow, and sprinkler supervisory systems.
760.1 Scope. Article 760 covers the installation of wiring Other circuits that might be controlled or powered by the
and equipment for fire alarm systems, including all circuits fire alarm system include elevator capture, elevator shut-
down, door release, smoke door and damper control, fire
controlled and powered by the fire alarm system. Figure 760–1
door and damper control, and fan shutdown.

NFPA 72, National Fire Alarm Code provides the require-


ments for the selection, installation, performance, use, test-
ing, and maintenance of fire alarm systems.

Author’s Comments:
• Building control circuits associated with the fire alarm system,
such as elevator capture and fan shutdown, must comply
with Article 725 [760.3(E)]. Article 760 applies if these com-
ponents are powered and directly controlled by the fire alarm
system.
• NFPA 101—Life Safety Code or the local building code speci-
fies when and where a fire alarm system is required.

760.2 Definitions.
Abandoned Cable. A cable that isn’t terminated to equipment
Figure 760–1 and not identified for future use with a tag.

Author’s Comment: Section 760.25 requires the accessible


Author’s Comment: Residential smoke alarm systems, includ- portion of abandoned cables to be removed.
ing interconnecting wiring, aren’t covered by Article 760,
because they aren’t powered by a fire alarm system as defined Fire Alarm Circuit. The portion of the wiring system and
in NFPA 72. connected equipment powered and controlled by the fire

226 Mike Holt’s Illustrated Guide to Understanding the National Electrical Code, Volume 2
Fire Alarm Systems 760.3

alarm system. Fire alarm circuits are classified as either non- Power-Limited Fire Alarm Circuit. A power-limited fire
power-limited or power-limited. alarm circuit must have the voltage and power limited by a
listed power supply that complies with 760.121 as follows:
Figure 760–3

Inherently Limited (ac) [Chapter 9, Table 12(A)]


Voltage Power
0 to 20V 5.00 x V
21V to 100V 100 VA

Not Inherently Limited [Chapter 9, Table 12(A)]


Overcurrent Voltage Power Protection
0 to 20V 5.00 x V 5A
21 to 100V 100 VA 100/V
101 to 150V 100 VA 1A

Figure 760–2 Author’s Comment: Inherently limited power supplies are


designed to burn out if overloaded.

760.3 Other Articles. Only those sections of Article 300


Nonpower-Limited Fire Alarm Circuit. A nonpower-limited
specifically referenced in this section apply to fire alarm cir-
fire alarm circuit can operate at up to 600V, and the power
cuits and equipment and complies with (A) through (G) as
output isn’t limited [760.41 and 760.43]. Figure 760–2
follows.
(A) Spread of Fire or Products of Combustion. Fire alarm cir-
cuits installed through fire-resistant-rated walls, partitions,

Figure 760–3
Figure 760–4

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 1.888.NEC.CODE (1.888.632.2633) 227


760.21 Fire Alarm Systems

floors, or ceilings must be firestopped to limit the possible (C) Hazardous (Classified) Locations. Fire alarm cir-
spread of fire or products of combustion in accordance with cuits installed in any hazardous location must be installed
the instructions supplied by the manufacturer for the specific in accordance with Articles 500 through 516, specifically
type of cable and construction material (drywall, brick, etc.), 501.150 and 502.150.
as required by 300.21. Figure 760−4
(D) Corrosive, Damp, or Wet Locations. Fire alarm circuits
(B) Ducts, Plenums, and Other Spaces Used for Environmental installed in corrosive, damp, or wet locations must be identi-
fied for use in the operating environment [110.11]; must be of
materials suitable for the environment in which they are to be
installed [300.6]; and must be of a type suitable for the appli-
cation [310.9].
(E) Building Control Circuits. Class 1, 2, and 3 circuits used
for building controls (elevator capture, fan shutdown, etc.),
associated with the fire alarm system, but not controlled and
powered by the fire alarm system, must be installed in accor-
dance with Article 725 [760.1].
(F) Optical Fiber Cables. Optical fiber cables utilized for fire
alarm circuits must be installed in accordance with Article
770.

760.21 Access to Electrical Equipment Behind


Panels Designed to Allow Access. Access to equip-
ment must not be prohibited by an accumulation of cables
that prevent the removal of suspended-ceiling panels. Cables
must be located so that the suspended-ceiling panels can be
moved to provide access to electrical equipment.

Figure 760–5

Air-Handling Purposes.
Where necessary for direct action upon, or sensing of the
contained air, fire alarm cables are permitted to be installed
in ducts or plenums if they are installed in a metal raceway
as required by 300.22(B). Figure 760–5
Exception: Plenum-rated fire alarm cables are permitted
above a suspended ceiling or below a raised floor used for
environmental air [760.30(B)(1) and (2), 760.154(A), and
760.179(A)].
Nonplenum-rated fire alarm cables are permitted to be
installed above a suspended ceiling or below a raised floor
used for environmental air, if the cable is installed in a metal
raceway [300.22(C)(1)]. Figure 760–6

228 Mike Holt’s Illustrated Guide to Understanding the National Electrical Code, Volume 2
Fire Alarm Systems 760.25

760.24 Mechanical Execution of Work. Equipment Author’s Comment: Raceways and cables are permitted to be
and cabling must be installed in a neat and workmanlike supported by independent support wires attached to the sus-
manner. pended ceiling [300.11(A) and 760.46]. Figure 760–7

Cables run through or parallel to framing members or fur-

Figure 760–7

Exposed cables must be supported by the structural com-


ponents of the building so that the cable will not be dam- Figure 760–9
aged by normal building use. Cables must be secured by
straps, staples, hangers, cable ties, or similar fittings designed
and installed in a manner that will not damage the cable. ring strips must be protected where they are likely to be pen-
Figure 760–6 etrated by nails or screws, by installing the wiring method so

Figure 760–10
Figure 760–8

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 1.888.NEC.CODE (1.888.632.2633) 229


760.30 Fire Alarm Systems

it isn’t less than 11⁄4 in. from the nearest edge of the framing circuit conductors extend beyond a building, they must be
member or furring strips, or by protecting them with a 1⁄16 in. installed in accordance with Article 800, or they must be
thick steel plate or equivalent [300.4(D)]. Figure 760–8 installed in accordance with Part I of Article 300.

760.25 Abandoned Cable. To limit the spread of fire or 760.35 Fire Alarm Circuit Requirements.
products of combustion within a building, the accessible
(A) Nonpower-Limited Fire Alarm Circuits. Nonpower-
portion of cable that isn’t terminated at equipment and not
limited fire alarm (NPLFA) circuits must comply with Parts
identified for future use with a tag must be removed [760.2].
I and II of this article.
Figure 760–9
Cables identified for future use must be with a tag that can

Figure 760–11
Figure 760–12

withstand the environment involved. Figure 760–10


(B) Power-Limited Fire Alarm Circuits. Power-limited fire
alarm (PLFA) circuits must comply with Parts I and III of
Author’s Comment: Cables installed in concealed raceways
this article.
aren’t considered “accessible,” therefore they’re not required to
be removed.

760.30 Fire Alarm Circuit Identification. Fire alarm Part III. Power-Limited Fire
circuits must be identified at all terminal and junction loca-
Alarm (PLFA) Circuits
tions. The identification must be in such a manner that
will help to prevent unintentional signals on the fire alarm 760.121 Power Sources for Power-Limited Fire
system circuits during testing and servicing of other systems. Alarm Circuits.
Figure 760–11
(B) Branch Circuit. Power-limited fire alarm equipment must
Author’s Comment: The marking of raceways and cables isn’t be supplied by an individual branch circuit that is not GFCI
required by this section [760.124]. or AFCI protected. Figure 760–12

760.124 Equipment Marking. Fire alarm equipment


760.32 Fire Alarm Circuit Cables Extending Beyond supplying power-limited fire alarm cable circuits must be
a Building. Where twisted-pair power-limited fire alarm

230 Mike Holt’s Illustrated Guide to Understanding the National Electrical Code, Volume 2
Fire Alarm Systems 760.139

durably marked to indicate each circuit that is a power-lim- must be protected by a 1⁄16 in. thick steel plate or the equiva-
ited fire alarm circuit. lent [760.8].

Author’s Comment: Fire alarm circuits must be marked at all Cable splices or terminations must be made in listed fittings,
terminal and junction locations [760.30]. boxes, enclosures, fire alarm devices, or utilization equip-
ment. Figure 760–13
760.130 Wiring Methods on Load Side of Power-
Limited Fire Alarm Power Source. 760.136 Separation from Power Conductors.
(B) PLFA Wiring Methods and Materials. Power-limited fire (A) General. Power-limited fire alarm conductors must not
alarm conductors and cables described in 760.179 must be be placed in any enclosure, raceway, or cable with conductors
installed as detailed in (1), (2), or (3). of electric light, power, or Class 1 circuits.
(1) Exposed or Fished in Concealed Spaces. Power-limited (B) Separated by Barriers. Where separated by a barrier,
fire alarm circuits installed exposed must be adequately sup- power-limited fire alarm circuits are permitted with electric
ported and protected against physical damage, or be installed power conductors.

Author’s Comment: Separation is required to prevent a fire or

Figure 760–13

Figure 760–14

in a raceway.

Author’s Comment: Exposed cables must be supported by the shock hazard that can occur from a short between the fire alarm
structural components of the building so the cable won’t be circuit and the higher-voltage circuits.
damaged by normal building use. Cables must be secured by
straps, staples, hangers, or similar fittings designed and installed (D) Associated Systems Within Enclosures. Power-limited
in a manner that won’t damage the cable. Cables run through fire alarm conductors are permitted to be mixed with elec-
or parallel to framing members or furring strips must be pro- tric light, power, and Class 1 circuit conductors in enclosures
tected where they’re likely to be penetrated by nails or screws, where these other conductors are introduced solely for con-
by installing the wiring method so it isn’t less than 11⁄4 in. from nection to the same equipment, and:
the nearest edge of the framing member or furring strips, or it (1) A minimum of 1⁄4 in. separation is maintained from the
power-limited fire alarm cable conductors.

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 1.888.NEC.CODE (1.888.632.2633) 231


760.143 Fire Alarm Systems

Figure 760–15
Figure 760–16
(G) Other Applications. Power-limited fire alarm circuit con-
ductors must be separated by not less than 2 in. from insu-
lated conductors of electric light, power, or Class 1 circuits
unless:
(1) All of the electric light, power, and Class 1 circuit con-
ductors, or all of the power-limited fire alarm circuit
conductors, are in a raceway or in metal-sheathed, metal-
clad, nonmetallic-sheathed, or underground feeder
cables. Figure 760–14

760.139 Power-Limited Fire Alarm Circuits, Class 2,


Class 3, and Communications Circuits.
(A) Two or More Circuits. Power-limited fire alarm circuits,
communications circuits, or Class 3 circuits are permitted
to be in the same cable, enclosure, cable tray, or raceway.
Figure 760–15
(B) PLFA and Class 2 Circuits. Class 2 circuits are permitted
to be within the same cable, enclosure, cable tray, or raceway
as conductors of power-limited fire alarm circuits provided
the Class 2 circuit conductor insulation isn’t less than that Figure 760–17
required for the power-limited fire alarm circuit.

Author’s Comment: Listed Class 2 cables have a voltage rating cable, cable tray, or raceway with power-limited fire alarm
of 150V [725.179(G)], whereas listed power-limited fire alarm conductors or cables.
cables have a voltage rating of 300V [760.179(C)].
Author’s Comment: The concern is that a fault from audio
(D) Audio System Circuits and Power-Limited Fire Alarm amplifier circuits to fire alarm circuits has the potential to create
Circuits. Audio system circuits [640.9(C)] using Class 2 or a hazard by disrupting the operation of fire alarm systems.
Class 3 wiring methods must not be installed in the same However, this new restriction doesn’t apply to the voice annun-
ciation audio circuits supplied and controlled from a fire alarm

232 Mike Holt’s Illustrated Guide to Understanding the National Electrical Code, Volume 2
Fire Alarm Systems 760.179

panel and commonly required in high-rise buildings and simi- Author’s Comment: Power-limited fire alarm cables identified
lar applications. as suitable for plenum or riser use are not required in one- or
two-family dwellings.
760.143 Support. Power-limited fire alarm cables are not
permitted to be strapped, taped, or attached to the exterior
of any raceway as a means of support. Figure 760–16

760.154 Applications of Power-Limited Fire Alarm


Cables (PLFA).
(A) Ducts, Plenums, and Other Space Used for Environ­mental
Air. Where necessary for direct action upon, or sensing of
the contained air, power-limited fire alarm cables are permit-
ted to be installed in ducts or plenums if installed in a metal
raceway [300.22(B)]. Power-limited fire alarm cables identi-
fied as suitable for plenum use can be installed above a sus-
pended ceiling or below a raised floor used for environmental
air. Figure 760–17

Author’s Comments:
• Power-limited fire alarm cables not identified as suitable for Figure 760–18
plenum use can be installed above a suspended ceiling or
below a raised floor used for environmental air, but only if the
power-limited fire alarm cables not identified as suitable for
plenum use are installed in a metal raceway [300.22(C)(1)]. (C) Other Wiring Within Buildings.
• Fire alarm cables installed beneath a raised floor in an infor- (1) General. Type FPL cable is permitted.
mation technology equipment room (computer room) aren’t
(2) In Raceways. Cables are permitted to be installed in
required to be plenum-rated [300.22(D) and 645.5(D)(6)(c)].
raceways.
(B) Riser. (3) Nonconcealed Spaces. Chapter 3 cables meeting the
requirements of 760.179(A) and 760.179(B) can be installed
(1) Power-limited fire alarm cables installed in vertical runs
in noncon­cealed spaces where the exposed length of cable
penetrating more than one floor must be riser-rated
doesn’t exceed 10 ft.
Types FPLR or FPLP [760.179(E)]. Listed riser raceways
and listed plenum signaling raceways are permitted to be (D) Cable Substitutions. Power-limited fire alarm circuit
installed in vertical riser runs, but only if the cables con- cables are permitted to be substituted in accordance with
tained in these raceways are riser- or plenum-rated Types Table 760.154.
CL2R, CL3R, CL2P, or CL3P.
(2) Power-limited fire alarm cables installed in vertical runs
penetrating more than one floor aren’t required to be
riser-rated if installed within a metal raceway.
Part IV. Listing Requirements
760.179 Listing and Marking Requirements of
Author’s Comment: Metal raceways containing circuit con- Power-Limited Fire Alarm Cables (PLFA). Power-lim-
ductors from a power-supply system that operates below 50V ited fire alarm cable installed within buildings must be listed
generally aren’t required to be connected to an equipment in accordance with (A) through (H) and must be marked in
grounding conductor [250.86 and 250.112(I)]. accordance with (I).

(3) FPL cable is permitted for all applications in one- and Power-limited fire alarm cable used in a wet location must be
two-family dwellings. listed for use in wet locations or have a moisture-impervious
metal sheath. Figure 760–18

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 1.888.NEC.CODE (1.888.632.2633) 233


760.179 Fire Alarm Systems

(A) Conductor Materials. Conductors must be solid or


stranded copper.
(B) Conductor Size. The size of conductors in a multicon-
ductor cable must not be smaller than 26 AWG. Single con-
ductors must not be smaller than 18 AWG.
(C) Cable Voltage Rating. Power-limited fire alarm cable
must have a voltage rating of 300V and this rating must not
be marked on the cable [760.179(I)].
(D) Type FPLP. Power-limited fire alarm plenum cables
(FPLP) are listed for use in ducts, plenums, and other envi-
ronmental air spaces [760.154(A)]. Figure 760–19

Author’s Comment: Cables identified as suitable for plenum


use can be installed in environmental air spaces, but they are
Figure 760–19 not permitted to be installed in ducts or plenums! See 760.3(B)
in this textbook for details.

(E) Type FPLR. Power-limited fire alarm riser cables (FPLR)


are listed for use in a vertical run in a shaft, or from floor to
floor [760.154(B)].
(F) Type FPL. Power-limited fire alarm cables (FPL) are
listed for general-purpose use [760.154(C)].
(H) Coaxial Cables. Coaxial cables are listed as FPLP,
FPLR, or FPL.
(I) Cable Marking. The 300V rating of power-limited fire
alarm cable must not be marked on the cable [760.176(C)].

FPN: Voltage markings on cables may suggest that the


cables are suitable for Class 1, or electrical power applica-
tions, which they’re not.

234 Mike Holt’s Illustrated Guide to Understanding the National Electrical Code, Volume 2
Practice Questions Article 760

760
ARTICLE

Practice Questions
Article 760—Fire Alarm 5. Cable splices or terminations in power-limited fire alarm
systems shall be made in listed _____ or utilization
Systems—Practice Questions
equipment.
1. Fire alarm cables that are not terminated at equipment
(a) fittings
and not identified for future use with a tag are consid-
(b) boxes or enclosures
ered abandoned.
(c) fire alarm devices
(a) True (d) all of these
(b) False
6. Audio system circuits using Class 2 or Class 3 wiring
2. Fire alarm cables identified for future use shall be methods shall not be installed in the same cable or
marked with a tag of sufficient durability to withstand raceway with _____.
_____.
(a) other audio system circuits
(a) moisture (b) power-limited fire alarm conductors or cables
(b) humidity (c) a or b
(c) the environment involved (d) none of these
(d) none of these
7. Power-limited fire alarm cables installed within buildings
3. The power source for a nonpower-limited fire alarm shall be _____ as being resistant to the spread of fire.
circuit shall not be supplied through a(n) _____.
(a) marked FR
(a) ground-fault circuit interrupter (b) listed
(b) arc-fault circuit interrupter (c) identified
(c) inverse time circuit breaker (d) color-coded
(d) a or b
4. The number of nonpower-limited fire alarm conductors
in a raceway shall not be required to comply with the fill
requirements contained in 300.17.
(a) True
(b) False

Mike Holt Enterprises, Inc. • www.MikeHolt.com • 1.888.NEC.CODE (1.888.632.2633) 235

Вам также может понравиться