Академический Документы
Профессиональный Документы
Культура Документы
• Power Factor is the ratio between the kW component and the kVA
component of power, drawn by an electrical load
• Where kW is the actual load power & kVA is the apparent load power
c) The vector sum of the active power and reactive power make up the total
(or apparent) power used -- kVA
Causes of Low Power Factor
1. Most of the motors used in industries are of induction type, which have
low lagging pf
2. Lamps, discharge lamps operate at low lagging pf
3. Transformer system work at low lagging pf
4. Load on the system is varying which results in decreasing or low pf
Disadvantages of Low Power
Factor
1. Lower the pf, higher is the load current required
2. Lower the pf, kVA rating of the equipment has to be more which means
the equipment has to be larger and expensive
3. To transmit or distribute a fixed amount of power at constant voltage,
the conductor will have to carry more current at LPF which means the
conductor size has to be large
4. Large current at LPF, makes I2R losses to increase which results in poor
efficiency
5. The lagging PF reduces the handling capacity of all elements of the
system due to the reactive component of the current
6. Large current at LPF causes greater voltage drops in alternators,
transformers, transmission lines and distributors – poor voltage
regulation
Power Factor Improvement – Some important points
• The total current is less than the original circuit current
• The active component remains the same before and after pf correction
i.e., I cosφ1 = I’ cosφ2
• The reactive component is reduced i.e., I’ sinφ2 = I sinφ1 – Ic
• Active power remains unchanged due to pf improvement since
I cosφ1 = I’ cosφ2 => VI cosφ1 = VI’ cosφ2
• KVAR (after pf correction) = lagging KVAR (before pf correction) – leading
KVAR (after pf correction)
• The capacitance of the capacitor required to improve pf from cosφ1 to
cosφ2 is given by: C = IC / [ ω*V]
• The leading KVAR supplied by pf correction device is given by:
kW[tanφ1 - tanφ2]
Advantages of Power Factor Correction
• Reduction in Electricity Bill due to reduced maximum demand
• Maintenance:
- Current unbalance
- Harmonics in the system
- Check on the design - revisit
Power Factor Correction
• SPF correction should never be applied at the output of a solid state Soft
starter
Bulk Correction
Selection of Capacitors
• A chemical industry had installed a 1500 kVA transformer. The initial
demand of the plant was 1160 kVA with power factor of 0.70. The % loading
of transformer was about 78%. To improve the power factor and to avoid
the penalty, the unit had added about 410 kVAr in motor load end. This
improved the power factor to 0.89, and reduced the required kVA to 913,
which is the vector sum of kW and kVAr.
Considerations of supply harmonics in selection of Capacitors
• Detuned filters are reactors which make the circuit very inductive for
resonant frequency and very capacitive on fundamental frequency
Performance Assessment of Power Factor
Capacitors
• Voltage effects: Ideally capacitor voltage rating is to match the supply
voltage