International Journal on Applications in Mechanical and Production Engineering

Volume 1: Issue 2: February 2015, pp 1-5. www.aetsjournal.com


----------------------------------------------------------------------------------------------------------------------------- -------------------------

Analysis And Performance Enhancement Of


Intercooler In Two Stage Reciprocating Air
Compressor Using CFD
A.Sathyaraj

their production operations, which is produced by compressed


Abstract— Compressors are intended to compress a substance in air units ranging from 5 hp over 50,000hp. It is worth noting
a gaseous state. Almost all the multi stage compressor applications, that the running cost of a compressed air system is far higher
air will be cooled between thestages which are also known as than the cost of a compressor itself [2]. The ranges between 5
intercooling.Intercooling of a compressor is necessary for an efficient
process.With intercooling, the compression is more closely to an
to 30 horsepower are commonly seen in automotive
isothermal compression with resulting lower power requirement. applications and are typically for intermittent duty [3].The US
Intercooler is basically a heat exchanger, which is used to cool the department of energy (2003) reports that70% to 90% of
compressed air between the stages. In the present work,the circular compressed air is lost in the form of unstable heat friction,
cross section pins are inserted normal to the flow direction of air in misuse and noise. For this reason, compressors and
existingfinned tube heat exchanger(intercooler)of two stage compressed air systems are important areas to improve energy
reciprocating air compressoris to increase the convective surface
efficiency at industrial plants. For improving efficiency
contact area and create the turbulenceresulting in an increase the rate
of heat transfer.CFD analysis has been done on in this intercooler and compression is done in more than one stage and between each
comparing them using FLUENT software. The experimental data are stage intercoolers provide [4].
taken asthe reference for CFD analysis. From this analysis the rate of Vijay F.Pipalia[3] investigated that improving the efficiency
heat transfer increase and work requirement lowered when compared of two stage reciprocating air compressor by providing water
with the existing one. cooling source , radiator coolant and Ethylene glycol and
results are compared .. The experiments of a two double-
Keywords— Air compressor, Intercooler, Performance
enhancement,CFD analysis. cylinder reciprocating compressor system with air, water and
different intercoolants were performed. The equations
I. INTRODUCTION representing the volumetric and isothermal efficiency were
solved and the predicted results compared with the
A reciprocating compressor or piston compressor is a
positive displacement compressor that uses pistons driven
by a crankshaft to deliver gases at high pressure. The intake
experimental data and theoretical data of water, other cooling
sources and air cooling showing good agreement.
Pawan kumar gupta[4] described that the modeling of heat
gas enters the suction manifold, then flows into the
exchanger which is based on minimization of heat transfer
compression cylinder where it gets compressed by a piston
area using MATLAB. Shell diameter, baffle spacing, number
driven in a reciprocating motion via a crankshaft, and is then
of tube-side pass are varied. In this work, pressure drop for
discharged. Applications include oil refineries, gas pipelines,
both sides is trying to reduced with proper spacing of baffle
chemical plants, natural gas processing plants and
and baffle cut and also tube diameter and tube length.
refrigeration plants. In the study of heat transfer, a fin is a
Sikindar Baba.Md, Nagakishore.S ,Prof.M.Bhagvanth
surface that extends from an object to increase the rate of heat
Rao[2]they are investigated that the thermal analysis has been
transfer to or from the environment by increasing convection.
done on finned tube heat exchanger (Intercooler of two stage
The amount of conduction, convection or radiation of an
air compressor). Experimental analysis was done on the
object determines the amount of heat it transfers. Increasing
intercooler (Finned tube heat exchanger) model for the
the temperature difference between the object and the
particular pressure ratio. For the finned tube, inside and
environment, increasing the convection heat transfer
outside convection heat transfer coefficients are estimated
coefficient or increasing the surface area of the object
based on the experimental data. Theoretical analysis was done
increases the heat transfer. Sometimes it is not economical or
to estimate the heat transfer rate at different sections of the
it is not feasible to change the first two options. Adding a fin
bare tube as well as at the sections where the fins are present.
to an object, however, increases the surface area and can
Modified Bessel’s functions of the first and second kind were
sometimes be an economical solution to heat transfer
calculated for the annular fin of rectangular profile model and
problems[1].Industrial plants use compressed air throughout
temperature distribution over each fin was calculated. Finite
Element Analysis was done using ANSYS software.
A.Sathyaraj, PG Scholar, Department of Mechanical Engineering,
Government College of Technology (Coimbatore), India. ( Email : Temperature distribution at different sections and total heat
almksm@mal.com) flow is estimated for the finned tube with fins of rectangular

1
International Journal on Applications in Mechanical and Production Engineering
Volume 1: Issue 2: February 2015, pp 1-5. www.aetsjournal.com
----------------------------------------------------------------------------------------------------------------------------- -------------------------
profile and with fins of triangular profile. A comparison has All electrical controls and displays are fitted into a switch
been made among experimental data, theoretical data and cabinet as shown in the figure 1, the master switch, emergency
finite element analysis. stop switch, and digital displays for whole measuring
variables. It also displays the electrical output data, and the
II. EXPERIMENTAL ANALYSIS electric motor switch for compressor. Switch cabinet is
connected to a PC (computer) via USB cable for displaying
A. Experimental setup
and recording the measured data.
ThePhotographic view of the experimental setup is shown
in the Figure 1. The experiment was carried out in a two-stage Table 2. Calculated Data Of Compressor With Existing Inter Cooler
reciprocating air/gas compressor mounted in a Vshape with Connected To The Pipeline
two separated cylinders, as shown in the figure1.
Isoth
S Volu Rate
Delive erma Shaf Isothe
. Actual metri of
ry Swept l t rmal
Volu c Heat
Press Volume Wor Pow Efficie
N me Effici Reject
ure k er ncy
o ency ion
done

[kg/c
[m3/s] [m3 /s] [%] [kW] [kW] [%] [kW]
m2]

1 3 0.0063 4.55X10-3 76.7 0.594 1.99 30.10 0.2447

2 4 0.0064 4.53X10-3 77.78 0.602 1.98 30.40 0.2540

3 5 0.0065 4.55X10-3 79.14 0.652 1.97 33.09 0.2724

4 6 0.0067 4.55X10-3 82.8 0.68 2.01 33.83 0.2970


Fig.1 Photographic view of two stage reciprocating
compressor
B. Calculation
The compressor, manufactured by Coimbatore compressor
engineering corporation private limited.(Model type ELT 1) Swept volume =
600), is capable of producing about 12 Kg/cm2 maximum Where
output pressure and 4.5 Kg/cm2. The compressor was mounted D = Bore diameter
in tandem that the second stage was driven directly from the L = Stroke length
rear of the first stage. The air is firstly drawn into the intake N = Number of revolution
tank via a measuring nozzle that is used to determine the 2) Volumetric Efficiency =
intake volume. The intake tank acts as a calming zone and
housing for the measuring sensors of the intake state, i.e., 3) Isothermal Work done = P1 x Qactual x ln
pressure transducer and manometer. Between the first stage Where
and the second stage, there is a small pressure vessel for P1 = Inlet pressure
intermediate cooling. After the second stage, the compressed P3 = Delivery pressure
air is forced into a storage tank via a cooling tube. To achieve 4) Shaft power = Motor power x Motor efficiency
a steady operating state, the compressed air is blown off via a
5) Red =
bleeder valve with sound absorbing. Safety and pressure
regulator valves, which are compulsory components in any Where
compressor, are installed for safety and control. Red= Reynolds number
m = Mass flow rate
Table 1. Observation Data Of Compressor With Existing Intercooler µ = Absolute viscosity
Connected To The Pipeline 6) Nu = 0.023 x Redn x Prn
T1 T2 T3 T4 P1 P2 P3 P4 W N r(or)
[kg/ [kg/ [kg/ [kg/ Nu =
[K] [K] [K] [K] [kW] [rpm]
cm2] cm2] cm2] cm2]
Where
307 379 367.7 369.4 1.0 2.29 3.0 2.87 2.473 1116 Nu = Nusselt number
307 385 382.4 384.1 1.0 2.25 4.0 4.49 2.473 1041
Pr = Prandtl number
307 390 387.5 391.9 1.0 2.25 5.0 5.19 2.498 1058
307 408 395.7 398.9 1.0 2.29 6.0 6.23 2.498 1041
7) Q = h x A x
Where
h = Heat transfer coefficient
A = Fins Area

2
International Journal on Applications in Mechanical and Production Engineering
Volume 1: Issue 2: February 2015, pp 1-5. www.aetsjournal.com
----------------------------------------------------------------------------------------------------------------------------- -------------------------
= Temperature difference Theintercooler models have been modeled using
SOLIDWORKS 2013 software as shown in the fig 2 and fig 3.
III. SPECIFICATION OF INTERCOOLER They have been meshed using ICEM CFD software. The
The specification is measured directly from the existing meshed models have been exported into the FLUENT 14.5
intercooler component and Specification of new intercooler is version software and the solution is initialized and calculations
same as per the existing intercooler, but additionally circular have been obtained by applying boundary conditions.
pins are inserted in the intercooler, as shown below figure 2 &
3.

Fig 4 Meshing of modified intercooler

Mesh details
Total no of elements = 5636604
Total no of nodes = 972759
Surface mesh
No of shells = 5533480
Table 3 specification of intercoolers Volume mesh
Existing Modified No of cells = 553380
intercooler intercooler
Tube material Aluminium Aluminium Table 5 Temperature and pressure contours of existing
Inner diameter of intercooler
35mm 35mm Boundary conditions
bare tube
Outer diameter of Boundary condition 1 = (T 2= 379 K, P2= 2.29 kg/cm2),
bare tube
45mm 45mm Boundary condition 2 = (T2= 385 K, P2= 2.25 kg/cm2),
Length of the Temperature variation Pressure variation in
165mm 165mm Boundary
intercooler in intercooler from intercooler from
condition
No.of fins 21 21 inlet into outlet inlet into outlet
Thickness of each
3mm 3mm
fins Boundary
outer diameter of condition 1
85mm 85mm
fins
Height of the fins 20mm 20mm
Circular fin of Circular fin of
Boundary
Types of fin rectangular cross rectangular cross
section section condition 2
Diameter of the
- 3mm
pin
No. of pins - 11 Boundary
condition 3
IV. CFD ANALYSIS OF INTERCOOLER
Computational Fluid Dynamics (CFD) is the science of
predicting fluid flow, heat transfer, mass transfer, chemical Boundary
reactions and related phenomena by solving mathematical condition 4
equations that represent physical laws using a numerical
process. CFD is simply the use of computers and numerical
techniques to solve problems involving fluid flowand it is the Boundary condition 3 = (T2= 390 K, P2= 2.25 kg/cm2),
simulation of fluids engineering systems using modeling Boundary condition 4 = (T2= 400 K, P2= 2.29 kg/cm2).
(mathematical physical problem formulation) and numerical
methods (discretization methods, solvers, numerical
parameters and grid generations, etc.,).

3
International Journal on Applications in Mechanical and Production Engineering
Volume 1: Issue 2: February 2015, pp 1-5. www.aetsjournal.com
----------------------------------------------------------------------------------------------------------------------------- -------------------------
V. RESULTS AND DISCUSSION
The CFD analysis of existing intercooler without pipe line
is shown in thetable 4. Experimental data of compressor with
Table 6 Outlettemperatures and pressure of both
existing intercooler connected to the pipe line were taken as
intercoolers from CFD analysis at various input boundary
the reference for CFD analysis. Outlet pressure [P 2] and
condition.
temperature [T2]of the low pressure cylinder were taken as the
Outlet Outlet
input of the intercooler and also input boundary condition for Inlet Inlet
Temperat Temperat Outlet
Tempera pressure
CFD analysis. ture of of
ure of ure of pressure of
Boundary Existing Modified intercooler[
5.1 Temperature contours of existing intercooler intercool intercool
condition intercoole intercool P3]
In the existing intercooler, the exit pressure [P 3]equal to the er [T2] er[P2]
r [T3] er [T3]
inlet pressure [P2] that indicates (P2=P3) no pressure drop [K] [kg/cm2] [K] [K] [kg/cm2]
through length of intercooler because there is no any obstacle Boundary
to fluid flow inside of the tube. But in the modified intercooler condition 379 2.29 372 370 2.26
11 numbers of circular pins were inserted normal to the fluid 1
Boundary
flow direction so pressure drop may occur in the modified
condition 385 2.25 378 376 2.20
intercooler (P2≠P3). 2
The same boundary conditions are taken as the reference for Boundary
both the existing and the modified intercooler and it is found condition 390 2.25 380 373 2.22
3
experimentally in two stage reciprocating air compressor by Boundary
using existing intercooler between the stages. The temperature condition 408 2.29 397 393 2.23
and pressure contours of modified intercooler are shown in the 4
table 5.
4.2 Theoretical calculation
Boundary
Inlet of intercooler Outlet of intercooler Table 7Theoretical calculation of intercoolers
condition
Outlet Outlet
Boundary Outlet work
temperat pressur work
temperat required Rate of Rate of
condition ure of e of required
ure of for heat at heat at
H.P H.P for
1 H.P
cylinder cylinde compres
compres transfer transfer
cylinder sor in in in
in r in sor in
Boundary in exist
modifie modifie existing
modifie existing existing
intercoo d interco interco
condition ler
d d intercoo
intercoo oler oler
intercoo interco ler
2 ler oler
ler
[Qe] [Qm]
[W]
Boundary [T4]
[T4] [P4]
[W]
condition [kg/cm2
[K] [K] [kW] [kW] [kW] [kW]
3 ]

Boundary 457 455 5.633 1.152 1.141 0.204 0.262


condition
464 462 5.523 1.148 1.143 0.204 0.2728
4
467 458 5.535 1.151 1.147 0.219 0.375
Table 6 Temperature and pressure contours of Modified
intercooler 488 483 5.623 1.195 1.182 0.237 0.438

5.3 Outlet temperature [T3]


5.2 Temperature and pressure contours of modified
The output temperature of the modified intercooler
intercooler
is lower than that of existing intercooler it is shown in the
From the temperature contours modified intercooler shows graph 1.
that when comparing exit temperature of modified intercooler
is lower than that of existing intercooler by applying same
boundary condition. In the modified intercooler the circular
cross section pins are inserted to increase the surface contact
area and create turbulence for increases the rate of heat
transfer (Q). Why need of turbulence means the middle flow
air need to contact with tube surface.
4.1 Result from CFD analysis

4
International Journal on Applications in Mechanical and Production Engineering
Volume 1: Issue 2: February 2015, pp 1-5. www.aetsjournal.com
----------------------------------------------------------------------------------------------------------------------------- -------------------------
improvement in the rate of heat transfer. The rate of heat
transfer has been increased in modified intercooler to 10-22%
of the existing intercooler. The outlet temperature of the
intercooler has been reduced to 1.5%-2.5% of the inlet
temperature in the modified intercooler. Modified intercooler
has 1% - 1.5% efficient than existing

REFERENCES
[1] Nagakishore.S, prof.M.Bhagvanth rao,“thermal analysis on a finned tube
heat exchanger of a two stage air compressor, IJRASET, vol.2, issue.V,
2014
[2] Mr. pawan kumar gupta, “A study based on design of air compressor
intercooler performance” – 2009
[3] Mr. Vijay f. Pipalia, “Experimental investigation of overall efficiency of
Graph1comparison of output temperature intercooler with two stage reciprocating air compressor by way of intercooling”,
respect to the input temperature of intercooler IJARSET,2010, vol.03, issue.03, pp.09-14.
[4] Pawn Kumar gupta, “Minimization of heat transfer area of an air
compressor intercooler using MATLAB”, (IJRAME) vol.1 issue.8 2013.
5.4 Work requirement of compressor [W] pp 20-45.
Graph.2 shows that the work requirement of [5] Vinod Kumar, smasher, “Technique and processes for performance
compressor by using modified intercooler is reduced when improvement of gas and steam turbine power plant”, (IJETAE), vol.4,
with comparing existing intercooler. issue 1, 2014.
[6] Caniere H.willockx A, Dick E, and De Paepe M, “Efficiency
calculations of air-cooled gas turbine with intercooling” HEFAT2007
paper number: CH3
[7] Mohd Muqeem, Dr. Monoj Kumar, “Design of intercooler of a
turbocharger unit to enhance the volumetric efficiency of diesel engine”,
IJMET, vol.4, issue.3, 2013, pp. 01-10.
[8] Jeng-Min Huang, “Numerical investigation of the intercooler of a two-
stage refrigerant compressor”-2011
[9] Y.L Lin, T.I.P. shih, “Film cooling of a cylindrical leading edge with
injection through rows of compound-angle holes”, ASME journal of
Heat Transfer,2001,pp.645-654.
[10] S.G. Schwarz, R.J. Goldstein,“Two-dimensional behavior of filmcooling
jet on concave surface, ASME journal of turbomachinery,1989, pp.124-
130.
Graph 2Comparison of work requirement of compressor
with respect to the inlet temperature of intercooler\
5.5. Rate Of Heat Transfer [Q]

Graph 3 comparison of heat transfer rate with the inlet


temperature of intercooler
The rate of heat transfer increased by using
modified intercooler it shown in graph 3.

VI. CONCLUSION
Thus the analysis and comparison of the proposed
intercooler and existing intercooler of two stage reciprocating
air compressor using CFD software, it has been known that the
outlet temperature of the modified intercooler has been
decreased by inserting the circular cross section pins normal to
the flow direction of air. This modification is resulting in
reduction of work required for the compressor and