Вы находитесь на странице: 1из 4

Keeping it cool: A look at causes of motor overheating

the curve. However,


there is the rule of di- 1,000,000

minishing returns: at

AVERAGE EXPECTED LIFE-HOURS


some point the cost
of designing and 100,000
CLASS F
operating a motor
to run cooler out-
weighs the benefits
of doing so. Here we 10,000
CLASS A CLASS H

will explore some of


the factors that con-
tribute to increased
CLASS B
temperature 1,000
By Jim Bryan
EASA Technical Support Specialist Overload
This is a very
Much has been written in EASA common culprit in 100
publications and elsewhere about the temperature prob-
60 80 100 120 140 160 180 200 220 240

consequences of excessive temperature lems. Sometimes the TOTAL WINDING TEMPERATURE - Degrees C
on a motor’s performance. We know overload condition 10° C HALF LIFE RULE
that excessive temperature and mois- is intermittent due to
ture are the largest contributors to load variations in the Figure 1. Total winding temperature in degrees C.
bearing and winding failures. Under- driven equipment.
standing the source of the increased Other times, the designer has chosen The insulation class determines
temperature will help us to correct the to operate above the rated load. This the maximum allowable operating
problem and improve the machine’s is actually permissible if the motor temperatures to yield “normal” service
life expectancy. has a service factor greater than 1.0. life as shown in Figure 2. If the life of
Figure 1 illustrates the theoretical The NEMA MG1-2011 definition of a motor is consistently too short in an
impact of increased temperature on Service Factor says that a motor is ther- application and little can be done to
the life of the motor insulation system. mally capable of overload to that point mitigate the temperature, a solution
This chart only addresses the impact of within the insulation class at normal may be to rewind with a higher tem-
thermal aging and not various other service conditions (rated voltage and perature class insulation system. Don’t
conditions that will affect the motor’s frequency).  Of course, any overload forget the bearings in this attempt.
life. In other words, it says that for will increase the operating temperature The lubricant is the limiting factor in
every 10º C increase in operating tem- of the motor. Also, most motor designs temperature related bearing problems,
perature, the expected life is reduced will be most efficient at around 75% so be sure your lubricant will work in
by one-half. Conversely, if we can re- of rated load, so the motor will run the environment.
duce the temperature of the motor by cooler and consume less power for Pulse width modulated (PWM)
10º C, we can expect the life to double. the same job. adjustable speed drives (ASD) pro-
Note that this is true at any point on duce negative sequence currents that
essentially add load to the motor. The
Class of Insulation System (see 1.65).................................................................................. A B F H motor must do work to overcome these
Time Rating (shall be continuous or any short-time rating given in 10.36) relatively low currents that are trying
Temperature Rise (based on a maximum ambient temperature of 40°C), Degrees C to make the motor run the opposite di-
a. Windings, by resistance method rection.The negative sequence currents
1. Motors with 1.0 service factor other than those given in items also greatly increase rotor temperature.
a.3 and a.4...................................................................................................................... 60 80 105 125
A properly designed inverter duty mo-
2. All motors with 1.15 or higher service factor.............................................................. 70 90 115 ...
3. Totally-enclosed nonventilated motors with 1.0 service factor................................. 65 85 110 130 tor will compensate for this.
4. Motors with encapsulated windings and with 1.0 service factor, all
enclosures ....................................................................................…………….............. 65 85 110 ...
Ventilation
b. The temperatures attained by cores, squirrel-cage windings, and miscellaneous The motor design includes a system
parts (such as brushholders, brushes, pole tips , etc.) shall not injure the insulation to carry the heat away that is produced
or the machine in any respect by the winding and bearings. This is of-

Continued on Page 2
Figure 2. Maximum temperature rise for motors. (Source: NEMA MG1-2011)

Electrical Apparatus Service Association, Inc. • Copyright © 2015 • www.easa.com • March 2015 1
Keeping it cool: A look at causes of motor overheating
Continued From Page 1

ten referred to as the “cooling circuit.”


Things such as the fan diameter, shaft
speed, air duct and air deflector pres- Air Ducts
ence and location, as well as altitude,
all affect this cooling circuit.
The amount of air provided by a fan
varies as the cube of the diameter and
is directly proportional to the speed.
Often in a totally enclosed fan cooled
motor, the fan is the greatest contribu-
tor to objectionable noise. The designer
must be sure the fan provides a suf-
ficient amount of cooling air without
creating too much noise.
Air ducts in larger open motors as
in Figure 3 distribute the cooling air
through the rotor and stator cores to Air Deflectors
improve cooling efficiency. Air deflec-
tors may be used in open or enclosed
motors to direct the air to locations that Figure 3. Cooling circuit in an open motor.
need it and to reduce turbulence. Tur- could be a factor. In a
bulent air is not an efficient method of certain case, some large
cooling. The location of the air deflector pump motors were in
as shown in Figure 4 is critical to the an open pit mine in the
efficiency of the cooling circuit. If the North American Sonoran
ducts are clogged or the air deflectors Desert. By painting the
are missing or incorrect, the motor gray motors white, the
Y

End ring
could run hotter. operating temperature
Fan
w
The ambient temperature directly was reduced 10-15º C Airflo
impacts the motor operating tempera- (18-27º F). Building a
ture. A motor doing a given amount of structure to shade the Rotor shaft Air deflector
work will produce a level of tempera- motors produced the
ture increase known as temperature same result.
rise. The operating temperature will be Airflo
w
Voltage
End ring

this rise plus the ambient temperature. Fan X


The nameplate will have the maximum A motor is designed
ambient temperature allowable for a such that the optimum
motor for NEMA motors. IEC motors performance is obtained
are limited to 40° C (104° F) ambient when the voltage applied
per IEC 60034-1 5.3. The design tem- is that which is indicated
perature rise at rated load plus this on the nameplate referred
maximum ambient should not exceed to as the rated voltage.
the temperature class rating. NEMA MG1 requires the Figure 4. Correct air deflector placement.
As altitude increases, the air gets motor be capable of start-
thinner and its ability to carry heat ing and operating at the rated voltage their 230/460V designs are "Suitable
away from the motor is reduced. If a ±10%; IEC requires ±5%. Both stan- for Use on 208V.” This plays on the
motor is to be operated at an altitude dards include a tolerance on frequency NEMA requirement that motors be
greater than 1000 m (3300 ft) the design that affects the voltage tolerance. For able to successfully operate at ±10%
should be adjusted to accommodate our purposes, we will consider the of rated voltage; 230 - 10% = 207V. If
the less efficient cooling that results. frequency variation to be zero. NEMA the 208V voltage supply varies, there
If the motor is outdoors, the ambi- goes on to say that the motor’s perfor- is no margin for the motor and its per-
ent temperature will be affected but mance may be affected. For instance,
some other factors such as sunshine some manufacturers will indicate that Continued on Page 3

Electrical Apparatus Service Association, Inc. • Copyright © 2015 • www.easa.com • March 2015 2
Keeping it cool: A look at causes of motor overheating
Continued From Page 2

formance may suffer. If the nameplate current in the motor results in more heat calculate the amount of this unbal-
or some other communication from the produced by winding resistive losses ance as shown in the formula below:
manufacturer does not indicate "Suit- and higher operating temperature. The
able for Use,” it is not a good idea. The slip of induction motors is inversely
motor will produce less torque, higher proportional to the applied voltage; the
full load amps, and will run hotter. higher the voltage the less the slip and This is used to calculate both the
Under-voltage results in higher the faster the motor turns. As shown average voltage and current. NEMA
amperage being required to produce before, the fan will move more air at MG1 states that the percent current
the needed power or work. Ohm’s higher speeds and this will increase unbalance may be 6-10 times the
Law states P=IE where P is power, I is the power required to turn the fan. This percent voltage unbalance. Because
current and E is voltage. If E goes down could have as large or larger impact on of this, it is important that the voltage
and P is constant, then I must go up. the motor current offsetting a portion of measurement be accurate within 0.5%
Since the heat produced varies as the the decrease in motor current. for all three phases. Further, with any
square of the current, this additional The converse is also true: if E goes voltage unbalance greater than 1%, the
up, I will decrease when rated load should be reduced due to
15 coils P is constant. This is the additional heating.
one reason motors are
designed with a rated Electrical steel
10 coils voltage of 460 volts (core iron)
when the nominal volt- A number of factors are involved
age applied is 480 volts. to determine the ability of steel to
The higher voltage helps transmit flux. The type or grade of
Figure 5. Uneven coils. the motor to run cooler steel, the thickness and the quantity
as shown here. Care are all factors.
must be taken, however, Modern steels have been developed
in applying this princi- with the capability to handle higher
Normal AC sinusoidal waveform
pal. The magnetic flux flux levels. This is one reason higher
produced in the core rated horsepowers can be developed
iron also increases. For in smaller frame sizes. These properties
A a given electrical steel, are defined in the various grades avail-
there is a maximum able. You might expect that the grades
amount of flux per cross capable of higher flux will be more
5th harmonic sectional area. This point expensive, and that always figures into
is known as saturation. If the design equation.
B the voltage is increased The cores for alternating current
beyond this saturation motors are laminated using thin
7th harmonic point, additional flux sheets of steel stacked to produce a
is possible only with a core. The length and diameter of this
C disproportionately large core determine its quantity or volume.
increase in current. The The thickness of each lamination is
Combined waveforms additional current gen- important to control the eddy currents
erates heat. This will be in that piece and ultimately the entire
discussed further in the core. Eddy currents are circulating
next section. loop currents induced within the steel
Unbalanced voltage by the changing magnetic field. The
D
in a three-phase motor thinner the lamination, the smaller
supply will also result the circulating loops and lower the
in high temperatures, current. These eddy currents do not
particularly in the phase contribute to the work done by the
1 2 that has the highest volt- motor and are losses that just produce
age applied. NEMA MG1 heat. The interlaminar insulation is
Figure 6. Harmonic distortion.
defines the method to
Continued on Page 4

Electrical Apparatus Service Association, Inc. • Copyright © 2015 • www.easa.com • March 2015 3
Keeping it cool: A look at causes of motor overheating
Continued From Page 3

also important to control the eddy If coil groups in parallel do not should not exceed 5% at the point of
current. If this insulation is damaged, contain the same number of turns as common coupling (the facility service
the eddy currents can cross to adjacent in Figure 5, circulating currents will entrance).
laminations and become larger. This produce high temperatures in the circuit These harmonics are produced by
will increase the magnetizing (no load) with fewer turns or coils. In the case of non-resistive loads being supplied by
current. The core loss test will reveal odd grouping, where the number of slots the same power feeder as the motor.
this increase and indicate that remedial per phase is not equally divisible by the Motors themselves are a source of har-
action is needed to repair or replace number of poles, the uneven number monics since they are mostly inductive
the bad steel. of coils must be distributed equally loads. Ballasts, rectifiers, and power
through all phases. A good check is to factor correction capacitors are a few
Current density count the total number of coils in each examples of other sources.
Another derivative of Ohm’s Law phase to confirm they are the same.
says P=I²R where R is resistance. In Two-speed, two-winding motors Conclusion
the case of a motor winding, the P can also produce circulating currents. The higher the operating tempera-
here is the power that is wasted (also If one or both windings are connected ture of a motor, the lower its expected
called loss). As wire size is decreased, delta or multiple parallel wye circuits, life will be. Anything that can be done
the resistance per foot is increased. a closed circuit will be present when to lower the temperature, whether it be
For a given current, the resistance of that winding is not energized. A special improving the ventilation or optimiz-
the smaller wire will produce higher connection with four leads can open ing the design, will provide better life
P or losses. As before, these losses are this circuit on motors connected with and reliability. For additional infor-
manifested as heat. For this reason, it is one delta circuit. For this to be effec- mation on this important topic, the
always better to increase the total cross tive, the motor starter must have four following Currents articles (available
section of the wire per turn in an AC contacts rather than three. Energizing in the “Resource Library” of easa.com)
motor until it comfortably fills the slot. the other winding will induce a voltage will be helpful.
Another reason is that the resin used in in the unenergized winding and the
the process is a better conductor of heat closed circuit may allow current flow. “How to Avoid Circulating Currents in
than air. If the slot is less than about This unintended current flow will pro- Multi-Speed, Two-Winding Motors”;
45% full, the resin will not be able to duce additional heat in the motor. For Cyndi Nyberg; June 2000
bond all of the wires in the slot and will this reason, it is always advisable to use “Fan Law Knowledge Can Help Per-
leave voids. This will result in higher a one-wye connection since it does not formance”; Chuck Yung; October 2002
operating temperatures. have this closed circuit. Where not pos-
When designing a motor there are sible, “The Pole-Group Connections “Consider Load Requirements, Appli-
many trade-offs. One of these is the for Three Phase Windings” table in cations”; Cyndi Nyberg; March 2003
number of turns versus the pitch of Section 2 of the EASA Technical Manual “Taming Those Misbehaving Motors”;
the winding. Generally, as the pitch will help identify the connections with Tom Bishop; December 2009
is increased (up to and including full the highest probability of success.
pitch minus one slot) the number of “When It Comes to Motors, How Hot
turns may be reduced. With fewer Harmonics Is Hot?”; Jim Bryan; June 2011
turns in each coil, larger cross section of The odd harmonics of the funda-
wire per turn is possible. The trade-off mental AC (except multiples of 3) will “Cool Facts about Cooling Electric
in this instance is the length of the end produce negative torques when the Motors”; Chuck Yung; July 2011
turns, especially in two-pole motors. rotor speed is above the synchronous
So to optimize the design, we need to speed for that harmonic. These nega- l l l l l
use the longest pitch practical while tive torques are in opposition to the
keeping in mind the windability and fundamental torque and add load Editor’s Note: A PDF of this article is
total length of turn. thus increasing the heat. The results available in the “Resource Library” of
of the 5th and 7th harmonics to the www.easa.com.
Circulating currents fundamental are shown in Figure 6.
Circulating currents are produced These can be measured using a power
in the winding when certain conditions quality analyzer to find the total har-
are present. These do not contribute to monic distortion (THD) expressed as a
the work being done by the motor and percentage. IEEE 519 states this THD
are losses that produce additional heat.

Electrical Apparatus Service Association, Inc. • Copyright © 2015 • www.easa.com • March 2015 4

Вам также может понравиться