Вы находитесь на странице: 1из 3

DETAILS FOR DESIGNING A CLADDING WITH WEATHERBOARDS ABOVE BRICK VENEER

DESIGN
RIGHT Weatherboards
above brick veneer
House designs with brick veneer cladding at the bottom and weatherboards above
BY ANN GALLOWAY,
FNZIA, ANN GALLOWAY
present a design challenge. Here we have some details that allow ventilation
ARCHITECT LTD, NAPIER and drainage from the upper cladding while preventing additional moisture
entering from the brick cavity and maintaining ventilation of the veneer cavity.

FOR ALL ITS SOLID appearance, masonry veneer is E2/AS1 applies Figures 1a and 1b highlight some issues with
not a waterproof cladding. Masonry veneers are E2/AS1 applies to veneers of clay brick, details in E2/AS1 Figure 73E(m).
absorbent, and water can migrate through to concrete brick or concrete block attached to
the cavity – hence masonry veneers are known timber framing, with a drained and ventilated Let moisture drain or evaporate
as wet cavity systems. cavity between the framing and the veneer. Any moisture that penetrates the veneer must be
The width of the cavity must be between 40 able to drain away or evaporate from the cavity,
and 75 mm. so the cavity must be:

wall underlay to
outside of cavity
closer (or closer taped
cavity closure fibre-cement to wall underlay)
or H3 plywood

5 mm gap
wall underlay 50 mm
returns behind minimum
closure cover potential Note: Proprietary
moisture path cavity closer
(depends on provides support
potential joints of top course type of upper for bottom
moisture path raked out to provide cavity closer) weatherboard
cavity ventilation
6 mm
minimum gap

Unacceptable detail – Figure 73E(m) from E2/AS1 Unacceptable detail – Figure 73E(m) with upper
with upper cladding on a cavity and ventilation via cladding on a cavity and continuous ventilation above
Figure 1a Figure 1b
top course of bricks allows transfer of air between the top of the bricks. The top of the veneer cavity is
cavities. unvented (blocked by the weatherboard cavity closure).

38 — June/July 2017 — Build 160


50 mm flashing upstand
(75 mm in EH wind zone)

35 mm flashing
(60 mm in EH
wind zone)

50 mm cover

5 mm minimum gap
potential
potential moisture
moisture path path
brick cavity ventilated in
second-to-top course

Brick cavity vented through second-to-top course of


Figure 1c bricks allows moisture to exit the cavity well clear of Figure 2 Bevel-back weatherboard, flashed cavity.
the upper level cladding.

○ drained and ventilated at the head of openings Important to get cavity ventilation right BRANZ recommends providing ventilation by
to allow moisture out Veneer cavity ventilation is usually provided by raking out joints in the second-to-top course,
○ drained and ventilated at the bottom to allow raking out perpend joints to a minimum of 75 mm rather than the top course of brickwork (see
air in and moisture out at 800 mm maximum centres, or 1,000 mm²/m Figure 1c). This allows moisture to evaporate clear
○ ventilated at the top of walls and beneath wall length. of the cavity above and facilitates installation of
openings wider than 2.4 m to allow air in to Ventilation can also be achieved by forming a the upper course of bricks.
the cavity 5 mm minimum continuous gap between the top
○ sealed off from the roof, subfloor space and any course and the soffit. The upper cladding must Adapting E2/AS1 details not the answer
cladding cavity above the veneer to prevent have 6 mm minimum clearance to the bricks and The details in E2/AS1 cover a variety of situations
moisture from migrating into these areas. extend 50 mm below the top of the veneer. but do not provide a solution where there is

Build 160 — June/July 2017 — 39


lap lower wall underlay
behind flashing upstand;
upper underlay to outside

50 mm flashing upstand 5 mm gap


(75 mm in EH wind zone) to lowest
weatherboard
35 mm flashing
(60 mm in EH
wind zone) 15 mm drip edge

cladding cover 50 mm
50 mm cover minimum (75 mm in EH
5 mm minimum gap wind zone) 35 mm minimum
cover (60 mm in
EH wind zone)
potential
moisture path
potential
moisture brick cavity ventilated in
path second-to-top course

Rusticated weatherboard, flashed cavity


Figure 3 Figure 4 Upper floor framing in line with lower floor.
(flat sheet similar).

an upper floor with a lightweight cladding fixed upper cavity without compromising the venti- the upper cladding to provide ventilation for the
over a 20 mm cavity. Simply adapting Figure lation of the veneer cavity. To further protect upper cavity.
73E(m) from ES/A21 by adding a cavity behind the upper cavity from ingress of moisture, a The soffit or closure to the brick cavity shown
the upper cladding may create a path for flashing can be installed at the base of the in these details provides a consistent finish where
moisture to migrate into the upper cavity (see upper cladding (see Figures 2–4). there may be a porch or other recess in the lower
Figures 1a and 1b). The flashing upstand should be 50 mm wall.
minimum (75 mm in EH wind zone) and cover
Detailing options the veneer by 35 mm minimum (60 mm in EH
There are several detailing options to isolate wind zone). A 5 mm minimum gap must be
the two cavities, allowing drainage from the maintained between the flashing and the back of

40 — June/July 2017 — Build 160

Вам также может понравиться