Вы находитесь на странице: 1из 1

HDPE SPEEDBIRD PLANT - SAFETY RELEVANT LOOPS

3443-SK-LE-002

Plant: 320 KT/Y HDPE Client: Basell Polyolefins Location: Münchsmünster Sheet 1 of 1

Comments after SIL calculation considering Comments after internal Process, HSE and
No. P&ID Loop Dossier N. Initiator Logic Solver Final Element SIL Safety Notes Reference Doc. and SIF
Vendor reliability data. Instrumentation assessment

ITAS Ignition
SIL Assessment Flare done in
1 681A 3443-SK-FP-101 5PT68111 and Control 5XV68122 SIL 2 OK No comment 3443-SZ-RT-101 Att.15
August 2009
Panel

ITAS Ignition
SIL Assessment Flare done in
2 681A 3443-SK-FP-102 5PT68126 and Control 5XV68127 SIL 1 OK No comment 3443-SZ-RT-101 Att.15
August 2009
Panel