Академический Документы
Профессиональный Документы
Культура Документы
Catalog
2003
Featuring:
7800 SERIES
Burner Control
Systems
BCS 7700
Boiler Control
Systems
ControLinks™
Fuel Air
Control System
Flame Safeguard
Controls
Flame Safeguard
Systems
Buying Rebuilts? Proceed with CAUTION
We would like to address a subject that is a concern to all of Although we no longer remanufacture Flame Safeguard
us—safety—specifically burner and boiler safety controls. controls, there are many Honeywell remanufactured controls
still operating safely and reliably. How do you differentiate
As an industry leader in the manufacture of Flame Safeguard genuine Honeywell remanufactured controls from indepen-
controls, Honeywell feels obligated to inform you of the dent rebuilt controls? How do you recognize an indepen-
difference between Honeywell controls and controls repaired dently rebuilt control? Typically, it has all of the approval body
by an independent rebuilder. designators removed. A rebuilder will often put his own label
on the device, but this label may be removed later; therefore,
There are a number of standards and codes for burners and a rebuilt control can be difficult to identify. The only way to be
boilers and the controls for burner and boiler equipment. sure you have a Honeywell remanufactured control is if it is
Among the most familiar are those established by Underwrit- stamped “REMFRD” or “REMFRD Listed” near the U.L. or
ers Laboratories Inc. (U.L.). The U.L. standards are often the Component Recognized symbol, and if the letter “R” follows
basis used for local, city, state, insurance, and other codes. the date code (e.g., 8850R) or the serial number (e.g.,
Chances are that when a burner or boiler was originally S/N8906Q018R).
purchased, it met the U.L. standard in effect at the time.
The products in this catalog are protected by U.S. and foreign patents. Illustrations and product descriptions published in this catalog are not
binding in detail. To determine the suitability of a product for a specific application, the customer should consult the product data sheets
provided with the product, or contact Honeywell directly. In keeping with its policy of continued improvement, Honeywell reserves the right to
change or modify design or specifications of products without notice or obligation.
Table of Contents
Flame Safeguard Products
This catalog features Honeywell Flame Safeguard Products.
Table of Contents......................................................................................................................................................... i
Subject Index...............................................................................................................................................................iii
Product Selection Matrix................................................... 2 - 17 Ignition Transformers—Solid State........................................ 74
7800 SERIES ................................................................. 18 - 32 Linkages ................................................................................ 75
BCS 7700 Product Selection Guides.............................. 33 - 35 Motors and Actuators ..................................................... 76 - 77
Boiler Control System..................................................... 36 - 39 Network Interface ........................................................... 78 - 80
ControLinks™ Fuel Air Control System.......................... 40 - 42 Flame Rectifier Gas Pilot Burners .................................. 81 - 82
Commercial Hydronic Controllers.......................................... 43 Modernization and Replacement.................................... 84 - 86
Flame Amplifiers............................................................. 44 - 47 Pressure Control and Limit ........................................... 87 - 101
Flame Detectors ............................................................. 48 - 54 Primary Control........................................................... 102 - 105
Fluid Actuators ............................................................... 56 - 58 Programmers....................................................................... 106
Diaphragm Gas Valve .................................................... 59 - 61 Programmer Controls ................................................. 107 - 109
Gas Valves, Firing Rate......................................................... 64 Remote Temperature Controllers ............................... 110 - 111
Industrial Gas Valves...................................................... 65 - 69 Testers and Demonstrators ........................................ 112 - 114
Solenoid Gas Valves ...................................................... 70 - 73
i
Model Number
MODEL FORM NO. PAGE MODEL FORM NO. PAGE MODEL FORM NO. PAGE
ii
Subject Index
Numerics D M
7800 SERIES ............................................ 29 Diaphragm Gas Valves ....................... 59–63 Manual Reset Safety Shut-off Gas Valve
Accessories .......................................... 31 High Temperature ................................ 60 Actuators .................................................58
Data ControlBus Module ...................... 30 Dynamic Self-Check Ultraviolet Flame Detector Manual Start Industrial Primary Control .....20
Expanded Annunciator ......................... 31 ................................................................. 53 Manual Start Industrial Primary Control with
Integrated Burner Control .................... 28 Purge .......................................................24
Keyboard Display Module .................... 30
E Miniature Rectifier Pilots ............................82
ModBus Module ................................... 31 Expanded Annunciator .............................. 31 Minipeeper Ultraviolet Flame Detector 51, 52
Multi-Drop Switch Module .................... 30 F Modernization .............................................84
Parts ..................................................... 32 Firing Rate Gas Valve Modernization and Replacement ........ 84–86
Plug In Purge Timer ............................. 29 Butterfly Air and Gas Valve .................. 64 Modulating Fluid Power Gas Valve Actuators
Relay Modules ............................... 18–27 Parts ..................................................... 64 .................................................................56
Remote Reset Module ......................... 31 Firing Rate Motors ............................... 76, 77 Modulating Reset Controller ............ 110, 111
Flame Amplifier Modules Modutrol™ IV Motors
A Firing Rate Motors ................................77
Accessories Primary Controls ................................ 102
7800 SERIES ....................................... 31 Flame Amplifiers ........................................ 46 N
Commercial Hydronic Controllers Flame Detectors Network Interface
Discharge Water Temperature Dynamic Self-Check Ultraviolet ........... 53 ControlBus™ Modules ................... 78, 79
Controller ............................. 43 Flame Rod Holder ................................ 48 Converter Module .................................78
Actuators Infrared ................................................. 49 Parts .....................................................80
Universal Parallel-Positioning .............. 41 Minipeeper Ultraviolet .................... 51, 52 Network Interface ControlBus™ Modules
Adapter Parts ..................................................... 55 .......................................................... 78, 79
Industrial Gas Valves ........................... 69 Solid State Purple Peeper Ultraviolet Network Interface Unit ................................79
Air Pressure Switch ................................... 92 ............................................ 50, 51
Ultraviolet ....................................... 50–53 O
B Flame Rectifier Gas Pilots ......................... 81 Off-Lo-Hi Fluid Power Gas Valve Actuator .56
BCS 77000 Product Selection Guide .. 33–35 Pilot Burners ........................................ 81 On-Off Fluid Power Gas Valve Actuator ....57
Boiler Control System Flame Rod Holder ..................................... 48 On-Off Primary Control ....................... 21, 24
Chassis Module ................................... 36 Flame Safeguard Amplifiers ...................... 47 On-Off Primary Control with Prepurge 22, 86
Firing Rate Interface ............................ 37 Flame Safeguard Systems Operating Controller
Keyboard Display ................................. 36 Product Selection Matrix .................. 1–17 Pressuretrol ..........................................97
Parts ..................................................... 39 Flame Signal Amplifiers ............................. 44 Order Number Guide ................................115
Pressure Sensor .................................. 38 Flame Switch ............................................. 18
Program Module .................................. 36 Fluid Actuators
P
Remote Display Module ....................... 37 Manual Reset Safety Shut-off .............. 58 Parts ...........................................................83
Sensors .......................................... 38–39 Modulating Gas Valve Actuators .......... 56 7800 SERIES ........................................32
Solid State Temperature Sensor .......... 39 Off-Lo-Hi Gas Valve Actuator .............. 56 Boiler Control System ...........................39
Burner Control System ............................ 106 On-Off Gas Valve Actuator .................. 57 Commercial Hydronic Controllers .........43
Butterfly Valves Parts ..................................................... 58 Firing Rate Gas Valves .........................64
Gas and Air .......................................... 64 Fuel Oil Pressure Switch ........................... 92 Flame Detectors ...................................55
Linkages ............................................... 75 Fluid Actuators ......................................58
G Network Interface ..................................80
C Gas Valves Pressure Control and Limit .................101
Combustion System Manager™ Software 79 Diaphragm ..................................... 61–63 Primary Controls .................................105
Commercial Hydronic Controllers Firing Rate ........................................... 72 Programmer Controls .........................109
Aquatrol™ Electronic Outdoor Reset Industrial ........................................ 65–69 Solenoid Gas Valves ............................73
Control ....................................... 43 Pilot ...................................................... 73 Pilot Burners ...............................................83
Discharge Water Temperature Controller Solenoid ......................................... 70–73 Miniature Rectifier Pilots .......................82
.................................................. 43 Parts ............................................... 73 Parts .....................................................83
Parts and Accessories ......................... 43 Pilot Gas Valves .........................................73
ControlBus™ Modules
H Pressure Control and Limit ................ 87–101
Network Interface ........................... 78, 79 High Temperature Diaphragm Gas Valves 60 Flow Limit Switch ..................................87
ControLinks™ I Fuel Oil Pressure Switch ......................92
Display Module .................................... 42 Ignition Transformer Gas or Air Pressure Switch ...................87
Fuel Air Control Wiring Subbase .......... 40 Solid State Ignition Transformer .......... 74 Gas or air Pressure Switch ...................92
Fuel Air Controller ................................ 40 Solid State Spark Generator ................ 74 Parts ...................................................101
Portable Combustion Analyzer ............ 42 Industrial Gas Valves ................................ 66 Pressure Control ...................................98
System Configuration Software ........... 41 Adapter ................................................ 69 Pressure Switch ....................................89
Universal Parallel-Positioning Actuator 41 Integrated Valve Train .......................... 68 Pressuretrol Limit Controller
ControLinks™ Fuel Air Control System 40–42 Integrated Valve Train Adapter ............ 69 ..............................93, 95, 97, 100
Controllers Infrared (Lead Sulfide) Flame Detector ..... 49 Proportional Pressuretrol Limit Controller
Commercial Hydronic ........................... 43 Integrated Burner Control .......................... 28 ....................................................96
Discharge Water Temperature ....... 43 Integrated Valve Train ............................... 68 Vacuumstat™ Controller .....................100
Electronic Outdoor Reset ............... 43 Integrated Valve Train Adapters ................ 69 Vaporized Controller .............................99
ControLinks™ ...................................... 40 IVT Vent Valves ......................................... 72 Pressure Sensor
Remote Temperature Controller Solid State Gas .....................................38
Outdoor Reset .............................. 111 L Solid State Oil .......................................39
Dual Bulb ................................. 110 Limit Controller Solid State Steam .................................38
Proportional Temperature ............. 111 Pressuretrol ............................ 93, 95, 100 Pressure Switch
Converter Module ...................................... 78 Proportional Pressuretrol ..................... 96 Gas or Air ..............................................87
Limit Switch ............................................... 87
Linkages .................................................... 75
iii
Subject Index
Pressuretrol Modulating Reset .......................110, 111 Training Booklets ................................ 123
Limit Controller ................ 93, 95, 96, 100 Outdoor Reset Controller ...........110, 111 Terminal Universal Wiring Subbases ......... 29
Operating Controller ............................. 97 Proportional Temperature Controller .. 111 Testers and Demonstrators
Primary Control .......................................... 18 7800 SERIES Demonstrators ............. 112
Manual Start Industrial .........................20
S Flame Simulators .......................112, 113
Manual Start Industrial with Purge ........ 24 Selection Chart Meters ................................................ 113
Meeting European Standards ............... 18 Industrial Gas Valves ........................... 65 Testers .......................................112, 114
On-Off .............................................21, 24 Selection Guide Training Material ...................................... 122
On-Off Primary with Pre and Post Purge 27 BCS 7700 .......................................33–35
On-Off with Prepurge .....................22, 86 Selection Matrix U
PLC Adaptable ..................................... 26 Flame Safeguard Systems ...............1–17 Ultraviolet Flame Detector ......................... 53
Primary Controls ...................................... 103 Sensors Minipeeper ............................................ 52
Flame Amplifier Modules .................... 102 Boiler Control System .....................38–39
Software
V
Parts ................................................... 105 Vacuumstat Controller ............................. 100
Protectorelay ...................................... 104 Combustion System Manager™ .......... 79
ControLinks™ System Configuration ... 41 Valves
Purge Timer ........................................ 103 Butterfly Gas Valves ............................. 64
Wiring Mount Base ............................. 105 Solenoid Gas Valves ................................. 70
IVT Vent Valves .................................... 72 Parts ................................................ 64
Programmer Controls Diaphragm Gas Valves ..................59–63
Automatic Programming Control ........ 108 Pilot Gas Valves ................................... 73
Solenoid Safety Shut-off ....................... 71 High Pressure ................................. 60
Parts ................................................... 109 High Temperature ........................... 60
Programming Module ......................... 107 Solenoid Safety Shut-off ............................ 71
Solid State Ignition Transformer ................ 74 Firing Rate Gas Valves ........................ 72
Subbase and Service Tool ................. 109 Industrial Gas Valves .....................65–69
Programmers .......................................23, 26 Solid State Purple Peeper Ultraviolet Flame
Detector .............................................50, 51 Normally Open Vent ............................. 72
Manual Start Industrial .........................25 Pilot Gas Valves ................................... 73
Programming Control ................................. 19 Solid State Spark Generator ...................... 74
Subbase and Service Tool ....................... 109 Solenoid Gas Valves ......................70–73
Meets European Standards .................. 19 Parts ................................................ 73
Protectorelay Subbase, Wiring
ControLinks Controller .......................... 40 Solenoid Safety Shut-off ....................... 71
Primary Controls ................................. 104 Vaporized Controller .................................. 99
Subbases ................................................... 29
R W
Relay Modules
T
Taining Wiring Mount Base .................................. 105
7800 SERIES .................................18–27
Remote Temperature Controller Service Handbooks ............................ 123
iv
Flame Safeguard Systems
Product Selection Matrix for CE Sequence
Primary/Programmer Relay Modules:
For 230 Vac nominal applications—
Fuel Burner Type Relay Module Type
Single Atmospheric EC7810
Single Atmospheric with fan EC7820
Combination or single On/Off Controlled Power Burner EC7830
Combination or single Full Modulation Power Burner EC7850
For 120 Vac nominal applications—
Fuel Burner Type Relay Module Type
Combination or single On/Off Controlled Power Burner RM7830
Combination or single Full Modulation Power Burner RM7850
Use the following pages to select the following required devices: Use the following pages to select the following optional devices:
Relay Module, 1 per burner Keyboard Display module, up to 1 mounted to relay module, remote as
Subbase, 1 per relay module desired
Purge Timer Card, 1 per relay module Communications, network and ControlBus™ modules to service
Flame Amplifier, 1 per relay module selected relays
Miscellaneous, as required to complete installation
Some products are available only through Authorized Flame Safeguard
Wholesalers and/or Distributors.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
1 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 2
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
3 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 4
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
5 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 6
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
7 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 8
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
9 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 10
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
11 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 12
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
13 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 14
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
15 70-8911
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 16
Product Selection Matrix
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
17 70-8911
7800 SERIES—Relay Modules
EC7810; EC7820 Primary Control Meeting European
Community Timings
European Directives: Complies with Gas Appliance Directive
(90/269/EEC). Low Voltage Directive (73/23/EEC). EMC Directive
(89/336/EEC).
Early Spark Termination: no
Flame Establishing Period - Main: 5 sec or 8 sec or intermittent
Flame Establishing Period - Pilot: 5 sec or 10 sec
Gastec/European Approvals: GASTEC: CE-63AP3070/1, Approved to
EN298.
Microprocessor-based integrated burner control for automatically Humidity Ratings: 85% RH continuous, non-condensing
fired gas, oil, or combination fuel single burner atmospheric with Interlocks: Lockout
fan applications. Provides automatic burner sequencing, flame Pilot Type: interrupted
supervision, system status indication, system or self-diagnostics, PostPurge: 5 sec
and troubleshooting. Preignition: Yes
• Access for external electrical voltage checks. PrePurge: Determined by ST7800 Purge Timer Card
• Application flexibility and communication interface capability. Second Stage Pilot Valve: Intermittent
• Four LEDs provide sequence information. Vibration: 0.5 G environment
• Five function Run/Test Switch. Weight: 1 lb 10 oz (0.7kg)
• Interchangeable plug-in amplifiers. Electrical Ratings, Power Supply: 220-240 Vac (+10/-15%); 50/60 Hz (±
• Local or remote annunciation of operation and fault information 10%)
(optional). Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C
• Non-volatile memory retains history files and lockout status after Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
loss of power. 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Compatible with existing Honeywell flame detectors. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
AirFlow Check: selectable Subbase.
Approvals, Factory Mutual: Approved: Report No. J.I.OY0A9.AF. Required Components: Q7800A,B Universal Wiring Subbases.
Approvals, Industrial Risk Insurers: IRI Acceptable. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
Amplifier.
ST7800 Plug-in Purge Timer Card.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 18
7800 SERIES—Relay Modules
EC7830; EC7850; RM7830; RM7850 Programming Control
meeting European Community Timings
Early Spark Termination: no
European Directives: Complies with Gas Appliance Directive (90/396/
EEC). Low Voltage Directive (73/23/EEC). EMC Directive (89/336/
EEC).
Flame Establishing Period - Main: 3 sec or 5 sec or intermittent
Flame Establishing Period - Pilot: 3 sec or 5 sec
Gastec/European Approvals: GASTEC: CE-63AP3070/1, Approved to
EN298.
Microprocessor-based integrated burner control for full modulation Humidity Ratings: 85% RH continuous, non-condensing
applications. Provides automatic burner sequencing, flame Interlocks: Lockout
supervision, system status indication, system or self-diagnostics, Pilot Type: interrupted
and troubleshooting. Preignition: Yes
• Access for external electrical voltage checks. PrePurge: Determined by ST7800 Purge Timer Card
• Application flexibility and communication interface capability. Second Stage Pilot Valve: Intermittent
• Five LEDs provide sequence information. Vibration: 0.5 G environment
• Five function Run/Test Switch. Weight: 1 lb 10 oz (0.7kg)
• Interchangeable plug-in amplifiers. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Local or remote annunciation of operation and fault information Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
(optional). 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Non-volatile memory retains history files and lockout status after 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
loss of power. Subbase.
• Compatible with existing Honeywell flame detectors. Required Components: Q7800A,B Universal Wiring Subbases.
AirFlow Check: selectable R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
Approvals, Factory Mutual: Approved: Report No. J.I.1V9AO.AF. Amplifier.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions. ST7800 Plug-in. Purge Timer Card.
Approvals, Industrial Risk Insurers: IRI Acceptable.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
19 70-8911
7800 SERIES—Relay Modules
EC7885A; RM7885 Manual Start Industrial Primary Control
• Flame signal check during standby.
• Shutter drive output.
• Compatible with existing Honeywell flame detectors.
• Terminal provided for external alarm to sound on flame failure.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Factory Mutual: Approved: Report No. J.I.OX4A5.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Microprocessor-based integrated burner control for industrial Approvals, Industrial Risk Insurers: IRI Acceptable.
semi-automatically fired gas, oil, coal, or combination fuel single Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
burner applications. Provides level of safety, functional capability Guide No. MCCZ.
and features beyond conventional controls. Flame Establishing Period - Pilot: 15 min.
• Functions include flame supervision, system status indication, Humidity Ratings: 85% RH continuous, non-condensing
system or self-diagnostics and troubleshooting. Pilot Type: intermittent
• Adaptable to continuous firing, high-low or modulating firing rate Vibration: 0.5 G environment
for semi-automatic burner sequencing. Weight: 1 lb 13 oz (0.8kg)
• Operates with the following: Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
—Torch-ignited main burner or torch-ignited pilot using S445A Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
Start-Stop Station, or conventional knee or foot operated 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
station. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
—Direct-ignition oil burner or electrically ignited pilot, using Subbase.
S445A Start-Stop Station. Required Components: Q7800A,B Universal Wiring Subbases.
• Five LEDs provide sequence information. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
• Non-volatile memory. Amplifier.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 20
7800 SERIES—Relay Modules
EC7890; RM7890 On-Off Primary Controls
• Nonvolatile memory retains history files and sequencing status
after power loss.
• Optional remote reset capability.
• Optional report generation.
• Selectable relight or lockout on loss of flame.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Microprocessor-based integrated primary burner control for Approvals, Industrial Risk Insurers: IRI Acceptable.
automatically fired gas, oil or combination fuel single burner Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
applications. Provides level of safety, functional capability and Guide No. MCCZ.
features beyond conventional controls. Humidity Ratings: 85% RH continuous, non-condensing
• Functions include automatic burner sequencing, flame Pilot Type: intermittent
supervision, system status indication, system or self-diagnostics Vibration: 0.5 G environment
and troubleshooting. Weight: 1 lb 13 oz (0.8kg)
• Subbase and amplifier are required for operation. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C
• Options include PC interface, keyboard display module, Data Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
ControlBus™ Module, remote display module, first-out expanded 6 3/32 in. deep with Q7800B Subbase;127 mm wide, 127 mm high,
annunciator, and Combustion System Manager™ software. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
• Five LEDs provide sequence information. Subbase.
• Interchangeable plug-in flame amplifiers. Required Components: Q7800A,B Universal Wiring Subbases.
• Optional local or remote annunciation of operation and fault R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
information. Amplifier.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
21 70-8911
7800 SERIES—Relay Modules
EC7895A,C; RM7895 On-Off Primary Control with Prepurge
• Optional report generation.
• Selectable relight or lockout on loss of flame.
• Airflow switch check.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Factory Mutual: EC7895—Approved
Microprocessor-based integrated primary burner control for RM7895—Approved: Report No. J.I.OX4A5.AF
automatically fired gas, oil, or combination fuel single burner Approvals, Industrial Risk Insurers: IRI Acceptable.
applications. Provides level of safety, functional capability and Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
features beyond conventional controls. Guide No. MCCZ.
• Functions include automatic burner sequencing, flame Humidity Ratings: 85% RH continuous, non-condensing
supervision, system status indication, system or self-diagnostics Interlocks: selectable
and troubleshooting. PrePurge: Determined by ST7800 Purge Timer Card
• Subbase, amplifier, and prepurge timer are required for Second Stage Pilot Valve: Yes
operation. Vibration: 0.5 G environment
• Options include PC interface, keyboard display module, Data Weight: 1 lb 15 oz (0.9kg)
ControlBus™ Module, remote display module, first-out expanded Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
annunciator, and Combustion System Manager™ software. Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
• Five LEDs provide sequence information. 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Interchangeable plug-in flame amplifiers. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
• Optional local or remote annunciation of operation and fault Subbase
information. Required Components: Q7800A,B Universal Wiring Subbases.
• Nonvolatile memory retains history files and sequencing status R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
after power loss. Amplifier.
• Optional remote reset capability. ST7800 Plug-in. Purge Timer Card.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 22
7800 SERIES—Relay Modules
RM7800 Programmers
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Factory Mutual: Approved: Report No. J.I.1V9AO.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers: IRI Acceptable.
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ.
Early Spark Termination: Yes, 5 sec
Microprocessor-based integrated burner control for automatically Flame Establishing Period - Pilot: 4 sec or 10 sec
fired gas, oil, coal or combination fuel single burner applications. Humidity Ratings: 85% RH continuous, non-condensing
Provides safety, functional capability and features beyond PostPurge: 15 sec
conventional controls. Preignition: Yes
• Functions include automatic burner sequencing, flame PrePurge: Determined by ST7800 Purge Timer Card
supervision, system status indication, system or self-diagnostics Vibration: 0.5 G environment
and trouble shooting. Weight: 1 lb 10 oz (0.7kg)
• Access for external electrical voltage checks. Electrical Ratings, Power Supply: 120 Vac (+10/-15%); 50/60 Hz (±
• Application flexibility and communication interface capability. 10%)
• Five LEDs provide sequence information. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Five function Run/Test Switch. Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
• Interchangeable plug-in flame amplifiers. 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Local or remote annunciation of operation and fault information 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
(optional). Subbase.
• Non-volatile memory retains history files and lockout status after Required Components: Q7800A,B Universal Wiring Subbases.
loss of power. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
• Compatible with existing Honeywell flame detectors. Amplifier.
• Includes Keyboard Display Module. ST7800 Plug-in. Purge Timer Card.
AirFlow Check: selectable
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
23 70-8911
7800 SERIES—Relay Modules
RM7824 On-Off Primary Control
• Plug-in flame amplifier.
• Nonvolatile memory retains history files and lockout status after
loss of power.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Factory Mutual: Approved: Report No. J.I.OX4A5.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers: IRI Acceptable.
24 Vdc microprocessor-based integrated burner control for Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
automatically fired gas, oil or combination fuel single burner Guide No. MCCZ.
applications. Provides level of safety, functional capability and Electrical Ratings, Power Supply: 24 Vdc, +7%/-8%. Load: 500 VA Max.
features beyond the capacity of conventional controls. Flame Establishing Period - Intermittent
• For use with R7824C Amplifier with C7024E,F Flame Detectors Flame Establishing Period - Pilot: 4 sec or 10 sec (RM7838C: 15 sec)
and R7848A,B with C7015A Flame Detectors. Humidity Ratings: 85% RH continuous, non-condensing
• Functions include automatic burner sequencing, flame Pilot Type: intermittent
supervision, system status indication, system or self-diagnostics Vibration: 0.5 G environment
and troubleshooting. Weight: 1 lb 13 oz (0.8kg)
• Five LEDs provide sequence information. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Selectable recycle or lockout on loss of flame airflow. Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
• Shutter drive output for use with dynamic self-check Flame 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
detectors. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
• Access for external electrical voltage checks. Subbase.
Required Components: Q7800A,B Universal Wiring Subbases.
R7824 or R7848 Flame Signal Amplifier.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 24
7800 SERIES—Relay Modules
RM7838B,C Manual Start Industrial Programmers
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Control Safety Devices: Acceptable: CSD-1.
Approvals, Factory Mutual: Approved: Report No. J.I.OX4A5.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers: IRI Acceptable.
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ.
Microprocessor-based integrated burner control with pilot hold Comments: Includes S7800 Display
function for industrial semi-automatically fired gas, oil, coal or Early Spark Termination: Yes, 5 sec
combination fuel single burner applications. Provides level of Flame Establishing Period - Main: 10 sec or Intermittent
safety, functional capability and features beyond conventional Flame Establishing Period - Pilot: 4 sec or 10 sec
controls. C alarms only on safety shutdown and requires ST7800C Humidity Ratings: 85% RH continuous, non-condensing
Purge Timers. Interlocks: Lockout
• Functions include automatic modulated high fire and low fire Pilot Type: selectable
proven purge, burner pilot start up with pilot valve hold, special Preignition: Yes
pilot valve hold from the Run condition, flame supervision, Vibration: 0.5 G environment
system status indication, system or self-diagnostics and Weight: 1 lb 10 oz (0.7kg)
troubleshooting. Electrical Ratings, Power Supply: 120 Vac (+10/-15%); 50/60 Hz (±
• Access for external electrical voltage checks. 10%)
• Application flexibility and communication interface capability. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Five LEDs provide sequence information. Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
• Five function Run/Test Switch. 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Interchangeable plug-in flame amplifiers. 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
• Local or remote annunciation of operation and fault information. Subbase.
• Non-volatile memory retains history files and lockout status after Required Components: Q7800A,B Universal Wiring Subbases.
loss of power. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
• Compatible with existing Honeywell flame detectors. Amplifier.
• Includes Keyboard Display Module. ST7800 Plug-in Purge Timer Card.
• Pilot Valve Hold function requires R7847C R7861A or R7886A
Plug-in Flame Signal Amplifiers.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
25 70-8911
7800 SERIES—Relay Modules
RM7840 Programmers
Approvals, Control Safety Devices: Acceptable: CSD-1.
Approvals, Factory Mutual: Approved: Report No. J.I.OX4A5.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers: IRI Acceptable.
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ.
Early Spark Termination: Yes, 5 sec
Flame Establishing Period - Pilot: 4 sec or 10 sec
Microprocessor-based integrated burner control for automatically Humidity Ratings: 85% RH continuous, non-condensing
fired gas, oil, coal or combination fuel single burner applications. Pilot Type: interrupted
Provides safety, functional capability and features beyond PostPurge: 15 sec
conventional controls. Preignition: Yes
• Functions include automatic burner sequencing, flame PrePurge: Determined by ST7800 Purge Timer Card
supervision, system status indication, system or self-diagnostics Vibration: 0.5 G environment
and troubleshooting. Weight: 1 lb 13 oz (0.8kg)
• Access for external electrical voltage checks. Electrical Ratings, Power Supply: 120 Vac (+10/-15%); 50/60 Hz (±
• Application flexibility and communication interface capability. 10%)
• Five LEDs provide sequence information. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Five function Run/Test Switch. Dimensions: 5 in. wide, 5 in. high, 5 1/4 in. deep with Q7800A Subbase,
• Interchangeable plug-in flame amplifiers. 6 3/32 in. deep with Q7800B Subbase; 127 mm wide, 127 mm high,
• Local or remote annunciation of RM7840 operation and fault 133 mm deep with Q7800A Subbase, 155 mm deep with Q7800B
information. Subbase.
• Non-volatile memory retains history files and lockout status after Required Components: Q7800A,B Universal Wiring Subbases.
loss of power. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
• Compatible with existing Honeywell flame detectors. Amplifier.
AirFlow Check: selectable ST7800 Plug-in Purge Timer Card.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
ORDER NUMBER Interlocks Flame Establishing Period - Main Second Stage Pilot Valve Comments
RM7840E1016 Lockout 10 sec or 15 sec Interrupted LHL-LF/HF Proven
RM7840G1014 Running 10 sec, 15 sec, 30 sec or Intermittent Selectable LHL-LF Proven
RM7840L1018 Lockout 10 sec or 15 sec Interrupted LHL-LF/HF Proven
RM7840L1026 10 sec, or 15 sec, or Intermittent Intermittent
RM7840M1017 Running 10 sec or Intermittent LHL-LF Proven
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 26
7800 SERIES—Relay Modules
RM7896 On-Off Primary Control with Pre and Post Purge
• Shutter drive output.
• Airflow switch check.
• Delayed main valve.
AirFlow Check: Dynamic
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Factory Mutual: Approved: Report No. J.I.OX4A5.AF.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Microprocessor-based integrated full-function primary burner Approvals, Industrial Risk Insurers: IRI Acceptable.
control for automatically fired gas, oil, or combination fuel single Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
burner applications. Provides level of safety, functional capability Guide No. MCCZ.
and features beyond conventional controls. Comments: Includes Pre- and Post -Purge.
• Functions include automatic burner sequencing, flame Description: Primary Control, Full Function
supervision, system status indication, system or self-diagnostics Flame Establishing Period - Pilot: 4 sec or 10 sec
and troubleshooting. Humidity Ratings: 85% RH continuous, non-condensing
• Subbase, amplifier and purge card are required for operation. Interlocks: selectable
• Options include PC interface, keyboard display module, Data PrePurge: Determined by ST7800 Purge Timer Card
ControlBus™ Module, remote display module, first-out expanded Vibration: 0.5 G environment
annunciator, and Combustion System Manager™ software. Weight: 1 lb 15 oz (0.9kg)
• 15 second postpurge. Electrical Ratings, Power Supply: 120 Vac (+10/-15%); 50/60 Hz (±
• Five LEDs provide sequence information. 10%)
• Interchangeable plug-in flame amplifiers. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Local or remote annunciation of operation and fault information. Dimensions: 127 mm wide, 127 mm high, 133 mm deep with Q7800A
• Nonvolatile memory retains history files and sequencing status Subbase, 155 mm deep with Q7800B Subbase; 5 in. wide, 5 in. high,
after power loss. 5 1/4 in. deep with Q7800A Subbase, 6 3/32 in. deep with Q7800B
• Optional remote reset capability. Subbase.
• Optional report generation. Required Components: Q7800A,B Universal Wiring Subbases.
• Selectable recycle or lockout on loss of airflow or flame. R7847, R7848, R7849, R7851, R7861, or R7886 Flame Signal
Amplifier.
ST7800 Plug-in Purge Timer Card.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
27 70-8911
7800 SERIES—Relay Modules
CR7890 Integrated Burner Control
• Protective heat block built into mounting flange.
• Power LED blinks a fault code when device is in ALARM state.
• Optional Keyboard Display Module (KDM) provides additional
troubleshooting and diagnostic information.
Approvals, Underwriters Laboratories, Inc: Listed: File No. MP268,
Guide No. MCCZ
Approvals, Canadian Standards Association: Certified
Approvals, Control Safety Devices: Acceptable: CSD-1.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
Approvals, Industrial Risk Insurers: IRI Acceptable.
Approvals, Factory Mutual: Approved: Report No. J.I.1V9AO.AF.
The CR7890B Integrated Burner Control is a microprocessor-based Temperature Rating (Ambient):-40 F to 140 F; -40 C to 60 C
control for automatically fired gas, oil, or combination fuel single Electrical Ratings, Power Supply: 120 Vac (+10/-15%),
burner applications. It consists of a self contained relay module, 50/60 Hz (± 10%)
amplifier and a shutter type solid state Ultraviolet Detector for Interlocks: No
sensing the ultraviolet radiation generated by the combustion of Preignition: No
gas, oil, or other fuels. Options include the S7800 Keyboard PrePurge: No
Display Module (KDM), for use during burner setup or PostPurge: No
troubleshooting. AirFlow Check: No
Functions the CR7890B provides include automatic burner Second Stage Pilot Valve: No
sequencing, flame supervision, system status indication, system Vibration: 1.0 G environment
or self-diagnostics and troubleshooting. Dimensions: 5 1/4 in. wide, 5 1/8 in. high, 7 7/32 in. deep;
133 mm wide, 130 mm high, 183 mm deep.
• Oscillating shutter interrupts ultraviolet radiation reaching the UV
Accessories: 118367A Swivel Mount.
sensor to provide the UV sensor checking function. Amplifier
120934 Mounting Flange, aluminum, with 3/4 inch NPT internal
circuitry components are checked from the microprocessor in the
threads for attaching to sight pipe.
CR7890B Control.
124198 Mounting Flange, aluminum, with 1 inch NPT internal
• Device can be mounted horizontally, vertically or at any other
threads for attaching to sight pipe.
angle. The device has faceplate alignment and integral locating
123539 Antivibration Mount.
reference points to assure proper shutter mechanism operation.
204341 Mirror Assembly.
• Quartz viewing window is field replaceable.
32005580-001 Cable for connecting Keyboard Display Module
• Threaded conduit fitting and color-coded leadwires allow rapid
(KDM) to CR7890.
electrical installation.
32006648-001 NEMA 1 Cover with accessibility for connection or
• CR7890B1019 uses Brad Harrison® 3R9006A20A120 connector.
voltmeter test points.
• A swivel mount is available to facilitate flame sighting.
32007181-001 Wiring Assembly - 6 in.NEMA 6P (IP68) -4 to 221 F (-
• -40 F (-40 C) rated ultraviolet sensing tube.
20 to 105 C) to connect to Brad Harrison connector on C7890B.
• High pressure 50 psi (345 kPa) quartz viewing window,
S7800A1001 Keyboard Display Module (English). Other language
magnifying lens and antivibration mount are available as
models are available.
accessories.
• Housing meets NEMA 4 enclosure standards.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 28
7800 SERIES—Required Components
Q7800 22 Terminal Universal Wiring Subbases
• Provides terminals for field wiring.
• Twenty-two terminals.
Approvals, Canadian Standards Association: Certified, File No.
LR95329-3.
Approvals, Underwriters Laboratories, Inc.: Component Recognized,
File No. MP268; Guide No. MCCZ2.
Humidity Ratings: 85% RH continuous, non-condensing
Vibration: 0.5 G environment
Burner, panel or wall mount subbases for 7800 SERIES relay Weight: 7 oz (200g)
modules and S7830A Expanded Annunciator. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
• Makes electrical connections for 7800 SERIES relay modules or
S7830A Expanded Annunciator through bifurcated contacts.
ORDER NUMBER Dimensions Comments
Q7800A1005 4 31/32 in. wide, 4 31/32 in. high, 1 13/32 in. deep. Panel mount
126 mm wide, 126 mm high, 36 mm deep
Q7800B1003 Burner/wall mount 2 knockouts each end
Q7800B1011 4 31/32 in. wide, 4 31/32 in. high, 3 in. deep. Burner/wall mount 3 knockouts each end
126 mm wide, 126 mm high, 76 mm deep.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
29 70-8911
7800 SERIES—Optional Components
S7800 Keyboard Display Module
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ.
Description: Display Module
Electrical Ratings, Power Supply: 13 Vdc peak full wave rectified (+20/-
15%).
Humidity Ratings: 85% RH continuous, non-condensing
Vibration: 0.5 G environment
Weight: 4 oz (113 g)
Approvals, Canadian Standards Association: Certified, File No. Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
LR95329-3. Dimensions: 4 27/32 in. wide, 2 29/32 in. high, 29/32 in. deep;
Approvals, Factory Mutual: Approved: Report No. J.I.1V9AO.AF. 123 mm wide, 73 mm high, 23 mm deep.
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions. Accessories: 206311-Carrying Case for S7800 Display
Approvals, Industrial Risk Insurers: IRI Acceptable.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 30
7800 SERIES—Optional Components
S7810M ModBus Module
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ.
Comments: Includes 203541 5-wire Connector
Electrical Ratings, Power Supply: 13 Vdc peak full wave rectified (+20/-
15%).
Humidity Ratings: 85% RH continuous, non-condensing
Vibration: 0.5 G environment
Supports remote mounting of a Keyboard Display Module, personal Weight: 4 oz (113 g)
computer PLC interface for multi-dropped ModBus 7800 SERIES Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
subnetworks, and remote reset. Dimensions: 4 27/32 in. wide, 2 29/32 in. high, 29/32 in. deep;
• Multi-dropped ModBus communications bus interface. 123 mm wide, 73 mm high, 23 mm deep.
• Remote reset.
• Ability to remotely mount a Keyboard Display Module.
7800 SERIES—Accessory
ORDER NUMBER Description
206311 Carrying Case for S7800 Display
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
31 70-8911
7800 SERIES—Parts
7800 SERIES—Parts
ORDER NUMBER Description
203541 Connector for S7800 Display
203765 Remote Mounting Bracket for S7800 Display
203968A Plug-in. Power Supply (13Vdc) for remote mounting S7800 Display
204718A Nema 4 Cover Assembly for Mounting S7800 Display
204718B Nema 1 Cover Assembly for Mounting S7800 Display
204718C Nema 4 Cover Assembly with Reset Button for Mounting S7800 Display
205321B Mounting Bracket - Flush Mounting the S7800 Display
221729A Dust Cover for 7800 Relay Modules
221779 Terminal Slot Cover for Q7800
221818A Display Extension Cable - 60 inches for S7800 Display
221818C Display Extension Cable - 10 foot for S7800 Display
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 32
BCS 7700 Product Selection Guides
PRODUCT SELECTION MATRIX FOR
UL/CSA BCS 7700 SYSTEM
5
CHASSIS
MODULE
BC7700A1015
60 HZ MODEL
PLUS
PM7700A1042
PROGRAM
MODULE
50 HZ MODEL
PLUS
PM7700A1075
KEYBOARD
DISPLAY
MODULE (KDM)
ST7700A1015
PLUS
MODUTROL
MOTOR
M7484A1010
PLUS
PLUS PLUS
FUEL (S)
OPERATING
PRES./TEMP.
SENSORS
SENSORS
OR OR AND/OR OR OR
PLUS
FLAME OPTIONS
DETECTION
DYNAMIC SELF DYNAMIC AMPLI- DYNAMIC AMPLI- FIRING RATE REMOTE DIS- COMMUNI-
CHECK AMPLIFIER CHECK AMPLIFIER CHECK AMPLIFIER INTERFACE PLAY MODULE CATIONS 2
RECTIFICATION INFRARED ULTRAVIOLET Q7710A1012 (RDM) Q7700A1014
R7747C1014 R7748B1015 R7749B1014 ST7705A1006
5 TO MEET UL296 CODE REQUIREMENTS FOR OIL BURNERS, EXTERNAL ELECTROMECHANICAL OIL M 712E
PRESSURE LIMIT SWITCHES WOULD HAVE TO BE INSTALLED IN THE LOCKOUT INTERLOCK STRING.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
33 70-8911
BCS 7700 Product Selection Guides
PRODUCT SELECTION MATRIX FOR
KEMPER/NFPA-85 BCS 7700 SYSTEM
CHASSIS
MODULE
BC7700A1015
PLUS
60 HZ MODEL
PROGRAM ONLY
MODULE PM7700A1067
PLUS
KEYBOARD
DISPLAY
MODULE (KDM)
ST7700A1015
PLUS
MODUTROL
MOTOR
M7484A1010
PLUS
PLUS PLUS
FUEL (S)
OPERATING
PRES./TEMP.
SENSORS
SENSORS
OR OR AND/OR OR OR
PLUS
FLAME OPTIONS
DETECTION
DYNAMIC SELF DYNAMIC AMPLI- DYNAMIC AMPLI- FIRING RATE REMOTE DIS- COMMUNI-
CHECK AMPLIFIER CHECK AMPLIFIER CHECK AMPLIFIER INTERFACE PLAY MODULE CATIONS 2
RECTIFICATION INFRARED ULTRAVIOLET Q7710A1012 (RDM) Q7700A1014
R7747C1014 R7748B1015 R7749B1014 ST7705A1006
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 34
BCS 7700 Product Selection Guides
PRODUCT SELECTION MATRIX FOR
FM/IRI/IRM/CSD-1 BCS 7700 SYSTEM
CHASSIS
MODULE
BC7700A1015
PLUS
60 HZ MODEL
PROGRAM ONLY
MODULE PM7700A1059
PLUS
KEYBOARD
DISPLAY
MODULE (KDM)
ST7700A1015
PLUS
MODUTROL
MOTOR
M7484A1010
PLUS
PLUS PLUS
FUEL (S)
OPERATING
PRES./TEMP.
SENSORS
SENSORS
OR OR AND/OR OR OR
PLUS
FLAME OPTIONS
DETECTION
DYNAMIC SELF DYNAMIC AMPLI- DYNAMIC AMPLI- FIRING RATE REMOTE DIS- COMMUNI-
CHECK AMPLIFIER CHECK AMPLIFIER CHECK AMPLIFIER INTERFACE PLAY MODULE CATIONS 2
RECTIFICATION INFRARED ULTRAVIOLET Q7710A1012 (RDM) Q7700A1014
R7747C1014 R7748B1015 R7749B1014 ST7705A1006
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
35 70-8911
Boiler Control System—Chassis Module
BC7700 Chassis Module; PM7700 Program Module; and
ST7700 Keyboard Display
provides line voltage input, output signal connections, inputs for
solid state control and limit sensors. Program Modules are
available to meet the sequencing and limit input requirements for
UL/CSA, FM/IRI/ASME CSD-1, and Kemper/NFPA-85.
• The Keyboard Display Module is the primary user interface to the
BCS 7700 System. The module is used to configure the system,
adjust system operating parameters and monitor system status.
Approvals, Canadian Standards Association: Certified: LR80141
Approvals, Factory Mutual: Approved: J.I.2Q2A5.AF
Approvals, Federal Communications Commission: Part 15, Class B-
Microprocessor based integrated control system for gas, oil, or Emissions
combination fuel single burner with hot water or steam boiler Approvals, Industrial Risk Insurers: Acceptable
application. Approvals, Underwriters Laboratories, Inc.: Component Recognized:
• The basic unit of the BCS 7700 Boiler Management Control File No. MP268, Guide No. MCCZ2
System consists of a BC7700A1015 Chassis Module, a selected Electrical Connections: Terminal block (supplied)
PM7700A Program Module and the ST7700A1015 Keyboard Electrical Ratings (output signal): 120 Vac +10/-15% 50/60Hz, 2000VA
Display Module. An existing Honeywell flame detector and Max.
associated Flame Amplifier, Firing Rate Motor and solid state Humidity Ratings: 85% RH continuous, non-condensing
operating control and limit sensors must be added to the basic Vibration: 0.5 g continuous
unit. Optional equipment includes the Remote Display Module, Temperature Ratings (operating): 32 F to 130 F; 0 C to 54 C.
Firing Rate Interface, Communications Interface and personal Temperature Ratings (Shipping): -30 F to +150 F; -35 C to +66 C.
computer software. Dimensions:
• The Chassis Module provides a means of mounting the Program BC7700—8 13/22 in. high, 9 19/32 in. wide, 3 11/32 in. deep
Module and the flame signal amplifier, output electrical 213 mm high, 244 mm wide, 85 mm deep.
connections, line volt-age input connections and attachment to a PM7700—4 15/32 in. High, 7 27/32 in. wide, 2 13/32 in. deep
panel. 113.5 mm high, 196 mm wide, 61 mm deep
• The Program Module provides the programming for the functions ST7700—8 in. high, 9 1/2 in. wide, 1 17/32 in. deep
of automatic burner sequencing, flame supervision, system 203 mm high, 241 mm wide, 38.9 mm deep.
status indications and system diagnostics. in. addition, it
System Electrical
ORDER NUMBER Component Application Frequency Weight Ratings Power Dissipation Fusing
BC7700A1015 Chassis Module Main Chassis Module 50/60 Hz 3 lb 2 oz 120 Vac 10W Max. for BC7700, 10A field-
for 7700 System 1.42 kg (+10/-15%) PM7700 and Flame Amplifier replaceable.
Electrical
ORDER NUMBER System Component Application Frequency Weight Ratings Power Dissipation Fusing
PM7700A1042 Program Module, for UL/ Programming Module 60 Hz 1 lb 10 oz 120 Vac See BC7700 15A
CSA 60 Hz Applications providing operation 738 g (+10/-15%) Maximum,
sequence for 7700 Type FRN or
PM7700A1059 Program Module, for FM/
System equivalent.
IRI/IRM/CSD-1 60 Hz
Applications
PM7700A1067 Program Module, for
Kemper/NFPA 85 60 Hz
Applications
PM7700A1075 Program Module, for UL/ 50 Hz
CSA 50 Hz Applications
System Electrical
ORDER NUMBER Component Application Frequency Weight Ratings Power Dissipation Fusing
ST7700A1015 Keyboard Primary user 50/60 Hz 1 lb 9 oz 24 Vac 2W Max.
Display Module interface to the 7700 709 g (+20/-15%)
System for
programming system
or adjusting system
operating
parameters.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 36
Boiler Control System—Display Module
ST7705 Remote Display Module
Approvals, Federal Communications Commission: Part 15, Class B-
Emissions
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
File No. MP268, Guide No. MCCZ2
Electrical Connections: Terminal block (supplied)
Electrical Ratings: 24 Vac (+20/-15%)
Frequency: 50/60 Hz
Humidity Ratings: 85% RH continuous, non-condensing
Monitors system status from multiple locations. Power Dissipation: 2W Max.
System Component: Display Module
• User interface to BCS 7700; Up to 30 remote displays per BCS
Vibration: 0.5 g continuous
7700.
Temperature Ratings (operating): 32 F to 130 F; 0 C to 54 C.
• Replicates any information being displayed on the ST7700A
Weight: 1 lb 9 oz; 709 g
Keyboard Display Module.
Temperature Ratings (Shipping): -30 F to +150 F; -35 C to +66 C.
• Two row by 20 character liquid crystal display.
Dimensions: 8 in. high, 9 1/2 in. wide, 1 17/32 in. deep;
Application: Monitors 7700 System status
203 mm high, 241 mm wide, 38.9 mm deep.
Approvals, Canadian Standards Association: Certified: LR80141
Approvals, Factory Mutual: Approved: J.I.2Q2A5.AF
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
37 70-8911
Boiler Control System—Pressure Sensor
P7710 Solid State Steam Pressure Sensor
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
File No. MP268, Guide No. MCCZ
Electrical Connections: Leadwires
Electrical Ratings (output signal): 1.25 Vdc to 5.75 Vdc
Humidity Ratings: 85% RH continuous, non-condensing
Pipe Connections: Female 1/4 NPT thread
Power Dissipation: 250 mW max.
System Component: Pressure Sensor
Vibration: 0.5 g continuous
Temperature Ratings (operating): 32 F to 150 F; 0 C to 66 C
Temperature Ratings (Shipping): -30 F to +150 F; -35 C to +66 C
Application: Steam Pressure Sensor for use with 7700 System
Dimensions: 3 3/4 in. wide, 3 5/8 in. high, 4 7/8 in. deep;
Approvals, Canadian Standards Association: Certified: LR95329-3
95 mm wide, 92 mm high, 124 mm deep.
Approvals, Factory Mutual: Approved: J.I.2Q2A5.AF
Approvals, Industrial Risk Insurers: Acceptable
ORDER NUMBER Pressure Ratings (sustained) Pressure Ratings (operating)
P7710A1047 22.5 psi; 155.1 kPa 0.75 psi to 15 psi
P7710A1054 225 psi; 1546 kPa 7.5 psi to 150 psi
P7710A1062 450 psi; 3091 kPa 15 psi to 300 psi
P7710A1070 1125 psi; 7728 kPa 38 psi to 750 psi
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 38
Boiler Control System—Pressure Sensor
P7730 Solid State Oil Pressure Sensor
• Female 1/4 in. NPT thread pipe tapping.
• Tolerance ± 4%.
Application: Low and high Oil pressure sensor for 7700 System
Approvals, Canadian Standards Association: Certified: LR95329-3
Approvals, Factory Mutual: Approved: J.I.2Q2A5.AF
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
File No. MP268, Guide No. MCCZ
Electrical Connections: Leadwires
Provides a low voltage output that is proportional to the applied oil Electrical Ratings (output signal): 1.25 Vdc to 5.75 Vdc
(numbers 2, 4, 5 and 6) pressure. Humidity Ratings: 85% RH continuous, non-condensing
Pipe Connections: Female 1/4 NPT thread
• Solid state technology.
Power Dissipation: 250 mW max.
• Provides dual high oil pressure and low oil pressure limit
System Component: Pressure Sensor
functions.
Vibration: 0.5 g continuous
• Two pressure ranges available: 7.5 to 150 psi and 17.5 to 350 psia.
Temperature Ratings (operating): 32 F to 150 F; 0 C to 66 C
• Upper housing provides wiring enclosure with provisions for 1/2
Temperature Ratings (Shipping): -30 F to +150 F; -35 C to +66 C
in. conduit connector.
Dimensions: 3 3/4 in. wide, 3 5/8 in. high, 4 7/8 in. deep;
• NEMA 3 rated enclosure.
95 mm wide, 92 mm high, 124 mm deep.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
39 70-8911
ControLinks™ Fuel Air Control System
NOTE: THESE PRODUCTS ARE AVAILABLE ONLY THROUGH AUTHORIZED CONTROLINKS™ REPRESENTATIVES.
Provides terminals for field wiring for the R7999A ControLinks Fuel
Air Controller. Terminals on the R7999A,B Controller engage the
Q7999 contacts to make electrical connections.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 40
ControLinks™ Fuel Air Control System
ML7999A Universal Parallel-Positioning Actuator
Temperature Rating (Storage): -40 F to +150 F; -40 C to +65 C.
Humidity Range at 95 F (35 C): 5 to 95% RH, noncondensing.
Vibration: 0.0 to 0.5g continuous (V2 level).
Control Signal (at 5 mA current): Drive Clockwise: Minimum 4.25 Vdc
differential between DR1-DR2; Drive Counterclockwise: Maximum
-4.25 Vdc differential between DR1-DR2.
NOTE: Actuator does not respond until the 8-digit ID signal from the
R7999 is passed via DR1-DR2.
Actuator Stroke: 95° nominal ± 3°, mechanically limited.
Provides 100 lb-in. torque, pulse-width-modulating (PWM) control Output Hub Position Accuracy: ± 0.1°.
of combustion air dampers, butterfly gas valves, oil modulation Torque Ratings at Rated Voltages: Lift and Hold Minimum: 100 lb-in.
valves, and flue gas recirculation systems. The actuator includes a (11.3 Nm); Breakaway Minimum: 100 lb-in. (11.3 Nm); Stall Minimum:
precision feedback potentiometer and integral power supply 100 lb-in. (11.3 Nm); Stall Maximum: 150 lb-in. (17 Nm).
capable of direct line voltage connection. The ML7999A Actuator is Actuator Design Life (at 100 lb-in.): Full-Stroke Cycles: 100,000
part of the ControLinks™ Fuel Air Control System, and must be minimum; repositions: 2,000,000 minimum.
used with the R7999 Fuel Air Controller. Feedback Potentiometer: Total Resistance: 5000 ohms ± 10%.
Actuator Timing (90° Travel): Standard: 24 to 30 seconds; Derated
• Universal power supply input. Cold-Start Timing (from -40 F to -20 F (-40 C to -29 C), 150 seconds
• Password protected with an eight-digit hexadecimal identification maximum.
signal. Noise Rating: 55 dBA maximum at 1m during normal operation.
• 100 lb-in. (11.3 Nm) torque. Mounting: Mounts directly on 1/2 in. (13 mm) round or square shaft. With
• Includes integral position feedback potentiometer. proper accessories, mounts to 5/16 in. and 3/8 in. (8 mm,
• Separate wiring compartment between line voltage power wiring 10 mm) round or square shafts; 9/16 in., 5/8 in., and 3/4 in.
and low voltage control. (14 mm, 16 mm, and 19 mm) round shafts.
• Direct coupling shaft interface mounting. Position Indicator: Visible with cover on device.
• Couples directly to a 1/2 in. (13 mm) shaft with no additional parts Approvals: Underwriters Laboratories Inc. (UL): meets UL873; Canadian
required. Standards Association (CSA): Pending; European Community (CE):
• Couples directly to 5/16 in. (8 mm) and 3/8 in. (9 mm) shafts using Pending.
available self-centering shaft reduction accessories. Accessories: 201391 Shaft Adapter for 3/8 in. round or square shaft;
• Shaft coupler assembly available for shafts larger than 1/2 in. 32002935-001 ML7999 Weatherproof Kit; 32003167-001 Shaft
• Bracket Accessory Kit available for mounting to Honeywell V51 Adapter for 5/16 in. round or square shaft; 32003168-001 Shaft
Butterfly Gas Valves. Adapter for 3/4 in. diameter round shaft; 32003168-002 Shaft
• NEMA 2 Adapter for 5/8 in. diameter round shaft; 32003168-003 Shaft
• IP54 with weatherproof kit (see Accessories) Adapter for 9/16 in. diameter round shaft; 32003396-001 V51
Electrical Ratings: Power Input: 100 to 240 Vac (+10/-15%), 50/60 Hz; Mounting Bracket for 1-1/2 in. and 2 in. valves; 32003396-002 V51
Maximum Power Consumption: 15 VA. Mounting Bracket for 2-1/2 in., 3 in. and 4 in. valves.
Temperature Rating (Ambient): -40 F to +140 F; -40 C to +60 C.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
41 70-8911
ControLinks™—Optional Components
S7999 ControLinks™ Display Module
• Diagnostic information:
—Input/Output status.
—Demand/control input and position.
—Fuel selection.
—Fuel position.
• Motor settings:
—Light-off position of fuel, air and FGR.
The S7999 ControLinks Display module (DM) provides local or —purge position of fuel, air and FGR.
remote annunciation of system operation, fault information, —Programmed stop position of fuel, air and FGR.
diagnostic information, actuator settings and configuration • Configuration settings:
settings of the ControLinks system. —Low Fire Hold input (XmA).
—FGR Purge position.
• Communication interface capability to the ControLinks system.
—Manual potentiometer limit enabled/disabled.
• Dependable. long-term operation provided by microcomputer
—R7999 hardware/software revision.
technology.
—Display Module (DM) software revision.
• Local or remote system annunciation provided by a 2-row by 20-
Approvals, FCC Emissions: FCC Part 15, Class B, Emissions.
column display.
Approvals, Industrial Risk Insurers: IRI Acceptable.
• Operating Status:
Approvals, Underwriters Laboratories, Inc.: Component Recognized.
—Source of demand/control.
Description: Display Module
—Actuator positions.
Electrical Ratings, Power Supply: 13 Vdc peak full wave rectified
—Hold status.
(+20/-15%).
—Total cycles.
Humidity Ratings: 85% RH continuous, non-condensing
—Total hours of operation.
Vibration: 0.5 G environment
—Run time.
Weight: 4 oz (113 g)
• Fault history of six most recent faults.
Temperature Rating (Ambient): -40 F to 140 F; -40 C to 60 C.
—Fault code.
Dimensions: 4 27/32 in. wide, 2 29/32 in. high, 29/32 in. deep;
—Fault message.
123 mm wide, 73 mm high, 23 mm deep.
—Cycles at time of fault.
Accessories: 206311-Carrying Case for S7800 Display
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 42
Commercial Hydronic Controllers
W7100J Discharge Water Temperature Controller
• Use soft start to minimize boiler rapid cycling during system
startup.
• Provides minimum on and off stage timings.
• Uses reset signal from C7031G outdoor air thermistor sensor.
• Provides remote set point capability with use of S963B.
Description: Discharge Water Control
Electrical Ratings (power consumption): 12 VA
Electrical Ratings (power supply): 20 Vac to 30 Vac
Frequency: 60 Hz
A proportional plus derivative (P+D) discharge water temperature Temperature Ratings (reset ratio): 1:4 to 4:1
control for multistage electric boilers or multiple gas or oil-fired Electrical Ratings (output voltage): 24 Vac; 120 Vac; 240 Vac
packaged hot water boilers. Provides up to six (6) stages of ON/ Temperature Ratings (setback range): 2 F to 16 F; 1.1 C to 8.8 C
OFF heating and with W7101A satellite sequencer adds up to four Temperature Ratings (operating range): 80 F to 220 F; 27 C to 104 C
(4) additional ON/OFF heating stages. Dimensions: 8 5/8 in. high, 6 1/2 in. wide, 3 in. deep;
219 mm high, 165 mm wide, 76 mm deep.
• Maintain average discharge water temperature for multiple boiler
Accessories: S963B1037-Manual Potentiometer (480 ohm)
and staged electric boiler applications by staging on and off
S963B1078-Manual Potentiometer (500 ohm)
boilers.
S963B1128-Manual Potentiometer (135 ohm)
• Provide up to six stages of heating.
• Use C7170 for sensing of water temperature.
• Staged lead/lag function equalizes stage run time, may be
disabled for electric boilers.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
43 70-8911
Flame Amplifiers—Boiler Control System
R7747; R7748; R7749 Flame Amplifiers
• Flame signal test jacks for measuring flame signal at the
amplifier.
• Keyboard Display Module compatibility for display of flame signal
strength.
• Flame signal output range of 0-5 Vdc.
• Color-coded labels for identification of amplifier types.
Approvals, Canadian Standards Association: Certified: File No. LR80141
Solid state plug-in units that respond to flame sensor signals to
Approvals, Factory Mutual: Approved: Report No. J.I.1T4A9.AF
indicate the presence of flame. The R7747C amplifies the signals
Approvals, Industrial Risk Insurers: Acceptable
from ultraviolet radiation sensors. The R7747C is a rectification
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Dynamic Self-Check (electronics and ultraviolet sensor tube)
Guide No. MCCZ2
amplifier.
Flame Failure Response Time: 2 to 4 sec
The R7748B amplifies the output from an infrared radiation sensor. Humidity Ratings: 85% RH continuous, non-condensing
The R7748B is an AMPLI-CHECK™ amplifier, in which the amplifier Use With Primary Safety Control: BCS7700
electronics are checked. Vibration: 0.5g continuous.
The R7749B amplifies the signals from ultraviolet radiation Temperature Rating (Shipping): -30 F to 150 F; -35 C to 66 C
sensors. The R7749B is an AMPLI-CHECK™ amplifier, in which the Temperature Rating (Operating Range): 32 F to 130 F; 0 C to 54 C
amplifier electronics are checked. Weight: 2.5 oz.; 71g
Dimensions: 4 1/32 in. wide, 2 in. high, 31/32 in. deep;
• Flame failure response time (FFRT) 0.5 second maximum 103 mm wide, 51 mm high, 25 mm deep.
(System: 2-4 seconds).
• Amplifiers plug into the BC 7700 Chassis Module by means of a
printed circuit board. The printed circuit board edge connector is
keyed to ensure proper orientation.
ORDER NUMBER Type Color Self Checking Use With Flame Sensor:
R7747C1014 Flame Amplifier, Rectification Green Dynamic Self-Check C7012E, F Flame Detector
R7748B1015 Flame Amplifier, Infrared Red AMPLI-CHECK C0715 Flame Detector
R7749B1014 Flame Amplifier, Ultraviolet Purple AMPLI-CHECK C7027, C7035 Flame Detector
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 44
Flame Amplifiers—7800 SERIES Required Component
,
Flame Failure
ORDER NUMBER Type Response Time Self Checking Use With Flame Sensor:
R7824C1002 Flame Amplifier, 3.0 sec Dynamic Self- C7024E, F Flame Detector
Ultraviolet Check
R7847A1025 Flame Amplifier, 0.8 sec or 1.0 sec None (standard) Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Rectification Q179
R7847A1033 2.0 sec or 3.0 sec Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C
Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847A1074 0.8 sec or 1.0 sec Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847A1082 2.0 sec or 3.0 sec Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C with leadwire
greater than 50 feet
Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847B1023 0.8 sec or 1.0 sec AMPLI-CHECK Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847B1031 2.0 sec or 3.0 sec Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C
Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847B1064 0.8 sec or 1.0 sec Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847B1072 2.0 sec or 3.0 sec Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C with leadwire
greater than 50 feet
Gas: Rectifying Flame Rods C7004, C7007, C7005, C7008, C7009,
Q179
R7847C1005 Dynamic Self- Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F
Check
R7848A1008 Flame Amplifier, None (standard) Gas, oil, coal: Infrared (lead sulfide) C7015
R7848B1006 Infrared AMPLI-CHECK
R7849A1015 Flame Amplifier, 0.8 sec or 1.0 sec None (standard) Gas, Oil: Minipeeper C7027A, C7035A, C7044
R7849A1023 Ultraviolet 2.0 sec or 3.0 sec
R7849B1013 0.8 sec or 1.0 sec AMPLI-CHECK
R7849B1021 2.0 sec or 3.0 sec
R7851B1000 Flame Amplifier, Gas, oil, C7927
R7851B1018 White (Optical) 0.8 sec or 1.0 sec
R7861A1026 Flame Amplifier, 0.8 sec or 1.0 sec Dynamic Self- Gas, oil, coal: Ultraviolet Flame Sensor C7061
R7861A1034 Ultraviolet 2.0 sec or 3.0 sec Check
R7886A1001 Gas, oil, coal: Adjustable Sensitivity Ultraviolet Flame Sensor C7076
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
45 70-8911
Flame Amplifiers—BC7000/R4140 Amplifiers
R7247; R7248; R7249; R7476 Flame Amplifiers
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ2
Approvals, Control Safety Devices: Acceptable (CSD-1)
Approvals, Canadian Standards Association: R7247—Certified: File No.
LR1620, Guide No. 140A-2
R7248; R7249; R7476—Certified: File No. LR1620, Guide No. 140A-
2 (gas), 300-I-0.2 (oil)
Approvals, Factory Mutual: Approved: Report No. 24181.01
Approvals, Industrial Risk Insurers: Acceptable
Humidity Ratings: 5% RH to 90% RH
Use With Primary Safety Control: R4140, BC7000, R4075C, D, E,
R4138C, D, FSP5075
Vibration: 0.5g continuous.
Weight: 227 g; 8 oz.
Dimensions: 5 13/16 in. high, 2 13/16 in. wide, 1 1/4 in. deep;
Solid state plug-in units respond to flame detector signal and 148 mm high, 71 mm wide, 32 mm deep.
indicate presence of flame. Color: R7247—Green;
R7248—Red
• Use with BC7000; R4140; R4075C,D,E; R4138C,D Flame R7249—Purple
Safeguard controls and appropriate flame detector and R7476—Blue
FSP5075A1, FSP5075A3 Flame Amplifier Modules.
Flame
Failure
Response Temperature Rating
ORDER NUMBER Type Time Self Checking (Operating Range) Use With Flame Sensor:
R7247A1005 Flame Amplifier, 2 to 4 sec None (standard) -40 F to +145 F Gas, oil, coal: Ultraviolet Flame Sensor C7012A, C
Rectification -40 C to +63 C Gas: Rectifying Flame Rods C7007, C7005,
R7247A1021 1 sec max C7008, C7009, Q179
R7247B1003 2 to 4 sec AMPLI-CHECK -40 F to +150 F
-40 C to +66 C
R7247C1001 Dynamic Gas, oil, coal: Ultraviolet Flame Sensor C7012E, F
Self-Check
R7248A1004 Flame Amplifier, None (standard) -40 F to +145 F Gas, oil, coal: Infrared (lead sulfide) C7015
Infrared -40 C to +63 C
R7248B1028 AMPLI-CHECK
R7249A1003 Flame Amplifier, None (standard) Gas, oil, coal: Ultraviolet (Minipeeper) C7027,
Ultraviolet C7035
R7476A1007 -40 F to +150 F Gas, oil, coal: Adjustable Sensitivity Ultraviolet
-40 C to +66 C Flame Sensor C7076
R7476A1015 2 sec max. Dynamic
Self-Check
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 46
Flame Amplifiers—Other Flame Amplifiers
R7257; R7258; R7259 Flame Safeguard Amplifiers
Approvals, Underwriters Laboratories, Inc.: Listed: File No. 268, Vol 15,
Solid state, plug-in units allow use of rectification, infrared and Sec. 1
ultraviolet flame detections. Use with Q518, Q519 and W688A Flame Failure Response Time: 3.0 sec
Flame Safeguard multiburner modules and appropriate flame Self Checking?: None (standard)
detector. Use With Primary Safety Control: Q518, Q519, W688A
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
47 70-8911
Flame Detectors—Flame Rod Holder
C7007 Flame Rod Holder
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 24181.03
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ
Comments: Holder only, order Kanthal flame rod separately.
Used to apply flame rod in gas-fired system controlled by Electrical Connections: Terminal screw
recitification type flame safeguard control. Mounting: 1/2 in. NPT
Type: Flame Rod
• Use with pressurized fire boxes. Hold flame rods firmly over the
Use With: Flame Amplifiers: R7247A, B, R7847A, B, R7257, R7289
pilot or burner with a chuck and setscrew arrangement.
Dimensions: 1 15/16 in. high, 2 3/16 in. diameter, 3 3/16 in. long;
• Provide electrical connection through a terminal screw.
49 mm high, 56 mm diameter, 81 mm long
• Allow ventilation to cool the unit or to minimize soot deposit
Required Parts: 102709A (12 in., 305 mm); 102709B (18 in., 457 mm);
through a 1/2 in. NPT tapping.
102709C (24 in., 610 mm); 102709D (36 in., 914 mm); 102709E (48
• Mount easily with sleeve or thread type mounting adapters, and a
in., 1219 mm)
straight or angle body.
Application: Gas fired pilot or gas fired system.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 48
Flame Detectors—Infrared Flame Sensor
C7015 Infrared (Lead Sulfide) Flame Detector
Application: Used for combination or dual-fuel applications
Approvals, Canadian Standards Association: Certified: Master Report
LR95329-1
Approvals, Factory Mutual: Approved: Report No. 24181.03
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ
Comments: Infrared (Lead Sulfide) Flame Detector
C7015A combination mount and 104662B and D Plug-in Lead Electrical Connections: Two no. 18 AWG wires
Sulfide Cell senses infrared radiation from gas, oil, coal or dual-fuel Mounting: 3/4 in. NPT.
flames. Type: Infrared (Lead Sulfide)
• Used for combination or dual-fuel applications. Temperature Ratings Ambient: 125 F max at sensor; 52 C max at sensor
• Detects pilot and main flame. Dimensions: 1 1/4 in. diameter, 2 3/4 in. long;
• Mounts quickly and easily on a standard 3/4 in. sighting pipe. 32 mm diameter, 70 mm long
• Works where flame rod or rectifying photocell mounts are difficult Use With: Flame Amplifiers: R7248, R7848, R7748, R7258
to apply. Accessories: 390427A-One 3/4 x 1/2 in. reducer bushing.
• Includes 110634A Bushing with magnifying lens and 105134-
00021 Orifice.
• Uses photoconductive lead sulfide cells 104662B and D.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
49 70-8911
Flame Detectors—Ultraviolet Flame Sensor
C7012 Solid State Purple Peeper™ Ultraviolet Flame Detector
Application: Gas, oil, or coal fired burners
Approvals, Canadian Standards Association: Certified: Master Report
LR95329-1
Approvals, Factory Mutual: Approved: Report No. 14740.01
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: C7012A,E,G—Listed: File
No. MP268, Guide No. MCCZ
C7012C,F—Listed: File No. E34649, Guide No. ZTSZ
Lead Length: 2.4 m; 8 ft
Solid state electronic flame detectors for use with Honeywell Flame
Electrical Ratings (power consumption): C7012A,C,G—2.5 W
Safeguard controls and amplifiers. Sense ultraviolet radiation
C7012E,F—7.0 W
produced by combustion of gas, oil, coal or other fuels.
Dimensions: C7012A,E,G—5 1/4 in. diameter (includes mounting
• Replace C7012 Vacuum tube models. flange), 7 7/32 in. long; 133 mm diameter (includes mounting flange),
• Mount horizontally, vertically or at any angle in between. 183 mm long
• Provide quick electrical hookup with threaded conduit fitting and C7012C,F—8 in. diameter, 12 in. long; 203 mm diameter, 305 mm
color coded leadwires. long
• Reduced nuisance shutdowns by wiring two in parallel. Dynamic Self-Checking models: C7012E,F
• For use with rectification flame signal amplifiers. Explosion proof models: Two piece, violet, cast aluminum enclosure
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 50
Flame Detectors—Ultraviolet Flame Sensor
C7024 Solid State Purple Peeper™ Ultraviolet Flame Detector
• Quick electrical installation with threaded conduit fitting and
color-coded leadwires.
• Reduce nuisance shutdowns by wiring two in parallel.
• Oscillating shutter interrupts UV radiation 12 times per minute
with R7824C.
• Works with 24 Vdc only.
Application: Gas, oil, or coal fired burners
Approvals, Canadian Standards Association: Certified
Electrical Connections: Six NEC CLASS 1 color-coded leaders
24 Vdc solid state electronic flame detectors for sensing the Electrical Ratings: 24 Vdc
ultraviolet radiation emitted by the combustion of most carbon Electrical Ratings (power consumption): 7.8 W maximum.
containing fuels, such as natural gas, LP gases, and oil. Type: Ultraviolet, Purple Peeper, Self-Checking
• Use with R7824C Dynamic Self-Check Flame Signal Amplifier. Use With: Flame Amplifier: R7824C
• Circuitry provides low power consumption and high reliability. Temperature Ratings Ambient: -20 F to +175 F; -20 C to +79 C
• Mount horizontally, vertically or at any angle in between. Lead Length: 2.4 m; 8 ft.
• Field-replaceable UV radiation sensing tube and quartz viewing
window.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
51 70-8911
Flame Detectors—Ultraviolet Flame Sensor
C7927 Minipeeper Ultraviolet Flame Detector
Approvals: Industrial Risk Insurers Acceptable: Pending.
Temperature Rating:
Ambient Operating:-40 F to +200 F (-40 C to +93 C).
Storage: -20 F to +120 F (-28 C to +49 C)
Maximum Pressure Rating: 5 psi (34.5 kPa).
Mounting: Collar with 12-14 NPSM internal threads for mounting on a
Ultraviolet Flame Detectors detect the ultraviolet radiation emitted 1/2 in. (13 mm) sight pipe.
by combustion flames. Wiring: Two four-foot (1.2 meter color-coded NEC class 1 leadwires.
• C7927A is used with only the R7851B Flame Amplifier and the Rear of detector has a clamp-type connector for 1/2 in. (13 mm)
appropriate Honeywell controls. flexible metal conduit.
• Has an integral Collar threaded (internal 1/2-14 NPSM) for mounting Dimensions: 3 3/4 in. tip to tip (including mounting nut), 3 1/4 in. long,
on a one-half inch sight pipe. 1 in. diameter; 95 mm tip to tip (including mounting nut), 82 mm long,
25 mm diameter.
Approvals: Underwriters Laboratories Inc.: Pending Leadwire Length: 4 ft.; 1.2 m
Approvals: Factory Mutual Approved: Pending
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 52
Flame Detectors—Flame Sensor, Ultraviolet
C7061 Dynamic Self-Check Ultraviolet Flame Detector
•Housing meets NEMA 4 enclosure standards.
•Protective heat block built into mounting flange.
•Swivel mount is available to facilitate flame sighting.
•-40 F (-40 C) rated ultraviolet sensing tube is available.
•High pressure 50 psi (345 kPa) quartz viewing window,
magnification lens and antivibration mount are available as
accessories.
Application: Gas, or oil fired burners
Dynamic self-checking flame detector used with R7861 Dynamic Approvals, Canadian Standards Association: Certified: Master Report
Self-check Amplifiers for sensing the ultraviolet radiation LR95329-1
generated by the combustion of gas, oil, or other fuels. Approvals, Factory Mutual: Approved: Report No. 14740.01
Approvals, Industrial Risk Insurers: Acceptable
• Oscillating shutter interrupts ultraviolet radiation reaching the UV Approvals, Underwriters Laboratories, Inc.: Component Listed
sensor 12 times per minute to provide the UV sensor tube Description: Dynamic self-checking flame detector
checking function. Amplifier circuitry components are checked Mounting: 3/4 in. NPT.
from the microprocessor in the 7800 SERIES Control. NEMA Rating: NEMA 4
• Can be mounted horizontally, vertically or at any angle in. Type: Ultraviolet, Purple Peeper, Self-Checking
between. The detector requires faceplate alignment and has Temperature Ratings Ambient: -40 F to 175 F; -40 C to 79 C
integral locating reference points to assure proper operation of Lead Length: 2.4 m; 8 ft
the shutter mechanism. Weight: 1.2 kg; 2.6 lb
• Field replaceable ultraviolet radiation sensing tube and quartz Dimensions: 5 1/4 in. diameter (includes mounting flange),
viewing window. 7 7/32 in. long;
• Threaded conduit fitting and color-coded leadwires allow rapid 133 mm diameter (includes mounting flange), 183 mm long.
electrical installation. Use With: Flame Amplifiers: R7861
• Two detectors can be wired in parallel to reduce nuisance
shutdowns in difficult flame sighting applications.
• Incorporates UV sensor tube checking feature; used with R7861
Dynamic Self-check Amplifiers.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
53 70-8911
Flame Detectors—Parts
Flame Detectors—Parts
ORDER NUMBER Description
102288 Magnifying Lens for C7003
102709A Kanthal Flame Rod - 12" for C7007A, C7011A
102709B Kanthal Flame Rod - 18" for C7007A, C7011A
102709C Kanthal Flame Rod - 24" for C7007A, C7011A
102709D Kanthal Flame Rod - 36" for C7007A, C7011A
102709E Kanthal Flame Rod - 48" for C7007A, C7011A
104662B Lead Sulphide Cell, Medium Sensitivity for C7015
104662D Lead Sulphide Cell, High Sensitivity for C7015
105061 3/4 in. Heat Block for C7015
105171 Gasket used in. C7015 or C7027
105172A Pressure Seal-off Adapter (3/4 NPT) for C7015
105172C Pressure Seal-off Adapter (3/4 NPT) w/UV Quartz window for C7012, C7024, C7027, C7035, C7061, C7076
105465 Insulator for C7007A
105478A Kanthal Flame Rod - 6" for C7008
105478B Kanthal Flame Rod - 12" for C7008
105478C Kanthal Flame Rod - 18" for C7008
105478D Kanthal Flame Rod - 24" for C7008
105644A Kanthal Flame Rod 4" includes Electrical Terminal and Washer for C7009A
105644B Kanthal Flame Rod 8" includes Electrical Terminal and Washer for C7009A
105644C Kanthal Flame Rod 12" includes Electrical Terminal and Washer for C7009A
110634A Magnifying Lens Assembly for C7015A
113228 UV Sensing Tube for C7012; C7024
113236 Vacuum Tube for C7012
113672A Seal Off Assembly for C7012, C7024, C7061
114372 Bulk Pack -20 PSI window for C7012E, F; C7024; C7061
114465 Window Gasket for C7012A, E;C7024A;C7061A
114638 Rubber Washer for C7012A, E;C7024A;C7061A
115594A Flange Assembly for C7012C, F,C7024F, C7061F
117181 Cork Gasket for C7012A, E;C7024A;C7061A
118367A Swivel Mount for C7012, C7015, C7024, C7027, C7035, C7061, C7076
118369 Reducing Bushing (1" NPT External to 3/4 in. Internal) for C7012, C7015, C7024, C7061
120739 Flange Gasket for C7012, C7024, C7061
122037 100 PSI Quartz Window for C7012C, F; C7061F
122748 50 PSI Quartz Window for C7012, C7061
123539 Anti-Vibration Mount for C7012, C7024 or C7061
124204 Quartz Magnifying Lens for C7012, C7024 or C7061
129464M UV Power Tube (0 to 250F) for C7035
129464N UV Power Tube (-40 to 250F) for C7035, C7061
129685 Flange Gasket for C7027
129808 Flange Gasket for C7035
129809 Mounting Nut for C7035
130716A Auto Transformer for Vertical Mounting of C7012E, F, C7061A, F
133711 Adapter, 1/2 in. internal to 1/2 in. external for C7015
136733 Heat Block for C7027
190105 Water Cooling Jacket for C7012A, F;C7024;C7061
190971B 120 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F
190971D 100 Vac Coil and Shutter Assembly for C7012E, F, C7061A, F
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 54
Flame Detectors—Parts
ORDER NUMBER Description
190971E 120 Vac Coil and Shutter Assembly for C7076A, D
191002B 120 Vac Plug in. Electronics less UV Sensing Tube for C7076A
191050 Quartz Viewing Window for C7076
191053 UV Sensing Tube for C7076
191054 Housing Gasket for C7076
191284 Aluminum Shield for C7035
191286 UV Sensing Tube (-40F) for C7012, C7024
191702 Electronics less UV sensing tube for C7012F (120 Vac)
204341A UV Mirror Assembly for C7012, C7024, C7027, C7035, C7061, C7076
32004080-001 120 Vac Electronics less UV Sensing Tube for C7012F
32004080-002 24Vdc Plug in. Electronics less UV Sensing Tube for C7024F
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
55 70-8911
Fluid Actuators—Modulating Actuator
V9055 Modulating Fluid Power Gas Valve Actuators
Description: Modulating-OFF actuator for use with V5055B valve bodies.
Low pressure.
Installed Switches - Auxiliary: No
Maximum Operating Pressure: 5 psi
Proof of Closure (Factory Mutual) Switch Contact Ratings (12: 9.8 AFL,
58.8 ALR, 1/2 hp
Proof of Closure (Factory Mutual) Switch Contact Ratings (24: 4.9 AFL,
29.4 ALR, 1/2 hp
Control gas supply for commercial and industrial burners. Valve Timing (Closing): < 1 sec
opens to low fire position when power is applied, then modulates Timing (Opening): 26 sec
to meet firing rate controller demand. Temperature Ratings: -40 F to +125 F; -40 C to +52 C
Electrical Ratings: 120 Vac; 60 Hz
• Include integral shaft to drive combustion air damper in unison
Accessories:203422C-4-20 ma Adapter for V9055
with valve
Q5055A1001-Adapter Assembly- adapts ITT general V710 gas valve
• One-second maximum closing time.
to accept Honeywell gas valve actuators, replacing ITT General AH2,
• Always displays the valve position; when open, a red indicator
AH4 or AH8 gas valve actuators.
appears and, when closed, a yellow indicator appears.
• Mount in. any position directly to valve bonnet with three
setscrews.
• Use with Q5055A Adapter Assembly to replace ITT General
Actuators on ITT General V710 gas valves.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 56
Fluid Actuators—On/Off Actuator
V4055A,B,D,E On-Off Fluid Power Gas Valve Actuator
Proof of Closure (Factory Mutual) Switch Contact Ratings (120V: 9.8
AFL, 58.8 ALR, 1/2 hp
Proof of Closure (Factory Mutual) Switch Contact Ratings (240V: 4.9
AFL, 29.4 ALR, 1/2 hp
Timing (Closing): < 1 sec
Auxiliary Switch Contact Ratings: 4.9 AFL, 29.4 ALR, 1/2 hp; 9.8 AFL,
58.8 ALR, 1/2 hp
Temperature Ratings: -40 F to +150 F; -40 C to +66 C
Use with V5055 Valve to control gas supply to commercial and Accessories:7616BR-Damper Arm (damper arm and clip).
industrial burners. Q5055A1001-Adapter Assembly- adapts ITT general V710 gas valve
• Use where smooth lightoff is important. to accept Honeywell gas valve actuators, replacing ITT General AH2,
• One-second maximum closing time. AH4 or AH8 gas valve actuators.
• Always displays the valve position, when open a red indicator
appears and closed a yellow indicator appears.
• Mount in any position directly to valve bonnet with three
setscrews.
• Provide final safety shutoff service when used with V5055 valve.
Maximum Installed
Operating Electrical Timing Switches - Installed Switches -
ORDER NUMBER Pressure Ratings Damper Shaft (Opening)a Auxiliary Proof of Closure Comments
V4055A1007 5 psi 120 Vac; 60 Hz No 26 sec No No
V4055A1031 13 sec
V4055A1064 Yes 26 sec
V4055A1080 240 Vac; 60 Hz
V4055A1098 120 Vac; 60 Hz 13 sec
V4055A1114 240 Vac; 60 Hz
V4055A1296 120 Vac; 60 Hz No Yes - adjusted to
90 degree stroke
V4055A1304 Yes with return 26 sec No
spring installed.
V4055A1312 No NEMA 4 Enclosure
V4055B1021 15 or 25 psi Yes
V4055B1039 13 sec
V4055D1001 5 psi 26 sec Yes
V4055D1019 13 sec
V4055D1027 No Yes NEMA 4 Enclosure
V4055D1035
V4055D1043 No
V4055E1016 15 or 25 psi Yes
V4055E1024 26 sec Yes NEMA 4 Enclosure
V4055E1040 13 sec No
a can also be used at 50 Hz, however, opening time will increase by 20%
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
57 70-8911
Fluid Actuators—Manual Reset Actuator
V4055F,G Manual Reset Safety Shut-off Gas Valve Actuators
Damper Shaft: No
Installed Switches - Auxiliary: No
Maximum Operating Pressure: 5 psi
Proof of Closure (Factory Mutual) Switch Contact Ratings (120V: 9.8
AFL, 58.8 ALR, 1/2 hp
Proof of Closure (Factory Mutual) Switch Contact Ratings (240V: 4.9
AFL, 29.4 ALR, 1/2 hp
Timing (Closing): < 1 sec
Timing (Opening): 13 sec
Provide manual reset, safety shut-off functions as required on FM, Temperature Ratings: -40 F to +150 F; -40 C to +66 C
IHEA-IRI and NFPA 86A,B,C industrial furnaces, ovens and kilns. Electrical Ratings: 120 Vac; 60 Hz
• Close in. one second maximum.
• Continuously displays the valve position with a red indicator
when closed.
• Mount directly to valve bonnet with three setscrews.
Fluid Actuators—Parts
ORDER NUMBER Description
118778 Damper Arm Spring Return (L.H.) for V4055, V4062 or V9055
118779 Damper Arm Spring Return (R.H.) for V4055, V4062 or V9055
118846 Brass Tubing When adding Spring Return, for V4055, V4062 or V9055
130618 replacement Clip for Damper Shaft on V4055, V4062 or V9055
133533A Short Stem Adaptor for V4055, V4062, V9055 to V5034 Valves
133534A Long Stem Adaptor for V4055, V4062, V9055 to V5034 Valves
133568 Auxiliary Switch bag assembly for V4055, V4062 or V9055
133569 Replacement Valve Closed Position Indicator Switch for V4055, V4062 or V9055
135796 Adjustment Wrench for V4062
203422C 4-20 ma Adapter for V9055
7616BR Crank Arm assembly with clip for Damper Arm of V4055/V4062 or V9055
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 58
Diaphragm Gas Valve
V48A; V88A Diaphragm Gas Valves
Approvals, Underwriters Laboratories, Inc.: File No. MH1639, Guide No.
YIOZ
Bleed Tapping: 1/8-27 NPT
Body Material: Aluminum
Description: Solenoid operated diaphragm valve
Electrical Terminations: 6 in. Leadwires
Frequency: 60 Hz
Ground terminal: Yes
Mounting: Upright (horizontal)
Solenoid-operated diaphragm valves provide slow opening and
Type of gas: LP, natural, or manufactured
fast closing for controlling fuel gases.
Valve Opening Time: 5 sec max
• Close firmly with diaphragm that is both weight and spring Valve Closing Time: 2 sec max
loaded. Valve pattern: Straight-through
• Close on power failure; recommended for final shutoff service. Temperature Ratings: 32 F to 125 F; 0 C to 52 C
• Set opening time with various sized bleed orifices or adjustable Power Supply: V48A—120 Vac
bleed valve. V88A—24 Vac
• Use with LP, natural or manufactured gases. Power Consumption: 15 VA max; 9 W
• Made with cast aluminum in straight-through valve pattern. Current (max amps at rated Vac/Hz): V48A—0.12 amps
• Optional valve position indicator available for 1-1/4 in. and larger V88A—0.62 amps
valves. Replacement Parts: V48A—116931 Coil
Approvals, Canadian Gas Association IAS: Certified V88A—116930 Coil
ORDER NUMBER Pipe size Capacity Pressure Rating Pilot Tapping Size
V48A2151 3/4 in. 668 cfh; 18.9 m 3/hr 1/2 psi; 3.4 kPa 1/8-27 NPT 5 7/16 in. high, 4 5/8 in. wide, 3 13/16 in. deep.
138 mm high, 118 mm wide, 97 mm deep
V48A2169 1 in. 1021 cfh; 28.9 m3/hr 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V48A2177 1 1/4 in. 2100 cfh; 59.5 m3/hr 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V48A2185 1 1/2 in. 2400 cfh; 67.9 m3/hr
V48A2227 1 1/4 in. 2100 cfh; 59.5 m3/hr 1 psi; 6.9 kPa
V48A2243 2 in. 4178 cfh; 118.3 m3/hr 1/4-18 NPT 9 3/16 in. high, 9 1/2 in. wide, 9 5/16 in. deep.
233 mm high, 241 mm wide, 237 mm deep
V48A2250 2 1/2 in. 5100 cfh; 144.4 m3/hr
V48A2268 3 in. 5562 cfh; 157.5 m3/hr
V48A2276 1 1/2 in. 2400 cfh; 67.9 m3/hr 1/8-27 NPT 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V48A2334 1 in. 1021 cfh; 28.9 m3/hr 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V48A2342 1 1/4 in. 2100 cfh; 59.5 m3/hr 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V88A1618 1 in. 1021 cfh; 28.9 m3/hr 1/2 psi; 3.4 kPa 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V88A1626 1 1/4 in. 2100 cfh; 59.5 m3/hr 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V88A1634 1 1/2 in. 3
2400 cfh; 67.9 m /hr
V88A1659 3/4 in. 668 cfh; 18.9 m3/hr 5 7/16 in. high, 4 5/8 in. wide, 3 13/16 in. deep.
138 mm high, 118 mm wide, 97 mm deep
V88A1667 3/4 in. 1 psi; 6.9 kPa
V88A1675 1 in. 1021 cfh; 28.9 m3/hr 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V88A1683 1 1/4 in. 2100 cfh; 59.5 m3/hr 1 psi; 6.9 kPa 1/8-27 NPT 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V88A1691 1 1/2 in. 2400 cfh; 67.9 m3 /hr
V88A1709 2 in. 4178 cfh; 118.3 m3/hr 1/4-18 NPT 9 3/16 in. high, 9 1/2 in. wide, 9 5/16 in. deep.
233 mm high, 241 mm wide, 236 mm deep
V88A1717 2 1/2 in. 5100 cfh; 144.4 m3/hr
V88A1725 3 in. 5562 cfh; 157.5 m3/hr
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
59 70-8911
Diaphragm Gas Valve, High Pressure
V48F Diaphragm Gas Valves
Bleed Tapping: 1/8-27 NPT
Body Material: Aluminum
Current (max amps at rated Vac/Hz): 0.12 amps
Description: Solenoid operated diaphragm valve, 5 psi pressure
Electrical Terminations: 6 in. Leadwires
Frequency: 60 Hz
Ground terminal: Yes
Mounting: Upright (horizontal)
Pilot Tapping: 1/4-18 NPT
Solenoid-operated diaphragm valves provide slow opening and
Pipe size: 2 in.
fast closing for controlling fuel gases.
Power Supply: 120 Vac
• Close firmly with diaphragm that is both weight and spring Type of gas: LP, natural, or manufactured
loaded. Valve Opening Time: 5 sec max
• Close on power failure; recommended for final shutoff service. Valve Closing Time: 2 sec max
• Set opening time with various sized bleed orifices or adjustable Valve pattern: Straight-through
bleed valve. Temperature Ratings: 32 F to 125 F; 0 C to 52 C
• Use with LP, natural or manufactured gases. Pressure Rating: 5 psi; 34.5 kPa
• Made with cast aluminum in straight-through valve pattern. Size: 9 3/16 in. high, 9 5/16 in. wide, 9 1/2 in. deep;
Approvals, Canadian Gas Association IAS: Certified 233 mm high, 237 mm wide, 241 mm deep.
Approvals, Underwriters Laboratories, Inc.: File No. MH1639, Guide No. Power Consumption: 15 VA max; 9 W
YIOZ Capacity: 4178 cfh; 118.3 m3/hr
ORDER NUMBER Pipe size Capacity Pressure Rating Pilot Tapping Size
V48J1005 3/4 in. 668 cfh; 18.9 m3/hr 1/2 psi; 3.4 kPa 1/8-27 NPT 5 7/16 in. high, 4 5/8 in. wide, 3 13/16 in. deep.
138 mm high, 118 mm wide, 97 mm deep
V48J1013 1 in. 1021 cfh; 28.9 m3/hr 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V48J1021 1 1/4 in. 2100 cfh; 59.5 m3/hr 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V48J1039 1 1/2 in. 2400 cfh; 67.9 m3/hr
V48J1047 2 in. 4178 cfh; 118.3 m3/hr 1/4-18 NPT 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
V88J1006 1 in. 1021 cfh; 28.9 m3/hr 1 psi; 6.9 kPa 1/8-27 NPT 6 1/16 in. high, 5 in. wide, 4 5/16 in. deep.
154 mm high, 127 mm wide, 109 mm deep
V88J1022 1 1/4 in. 2100 cfh; 59.5 m3/hr 6 13/16 in. high, 5 7/8 in. wide, 5 5/16 in. deep.
173 mm high, 149 mm wide, 135 mm deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 60
Diaphragm Gas Valve
V4943; V4944; V8943; V8944 Diaphragm Gas Valves
Approvals, International Approval Services (AGA, CGA):
Report no. C2030020
Approvals, Underwriters Laboratories, Inc.: File No. MH1639, Guide No.
YIOZ (60 Hz only)
Body Material: Aluminum
Mounting: Upright (horizontal)
Pilot Tapping: 1/8-27 NPT
Valve pattern: Straight-through, non-offset
Temperature Ratings: -40 F to 150 F; -40 C to 66 C
V4943/V8943A On-Off Diaphragm Gas Valves. Pressure Rating: 1/2 psi; 3.4 kPa
Power Supply: V4943; V4944 —120 Vac
V4943/V8943B,C,N Single Stage Pressure Regulating Diaphragm
V8943; V8944—24 Vac
Gas Valves.
Power Consumption: V4943—6.6 VA
V4944/V8944B,C,L,N Two-stage Pressure Regulating Diaphragm V4944—9 VA
Gas Valves. V8943—6 VA
• Designed as replacement for V4843/V8843; V4844/V8844 Gas V8944—12.4 VA
Valves. Current (max amps at rated Vac/Hz): V4943—0.055 amps
• Suitable for use on atmospheric boilers, commercial water V4944—0.077 amps
heaters, and rooftop heaters. V8943—0.33 amps
• V4943/V8943A models are solenoid-operated diaphragm valves V8944—0.5 amps
for on-off flow control of fuel gases. Frequency: 60 Hz
• V4943/V8943B,C,N and V4944/V8944B,C,L,N models are solenoid- Except V4944N1029; V4944N1037; V4944N1045; V4944N1052;
operated diaphragm valves that combine the functions of safety V4944N1060—50Hz/60 Hz
shutoff and pressure regulation in a single unit. Valve Size: For 1 in. and 1 1/4 in. pipe—6 9/16 in. high, 6 in. wide, 6 in.
• V4943/V8943B,N and V4944/V8944B,N are for use with natural deep; 167 mm high, 152 mm wide, 152 mm deep
gas. For 1 1/2 in. and 2 in. pipe—7 3/8 in. high, 6 in. wide, 6 in. deep; 187
• V4943/V8943C and V4944/V8944C,L are for use with LP gas. mm high, 152 mm wide, 152 mm deep.
• Valve body of die-cast aluminum with a straight-through pattern. Electrical Terminations: 1/4 in. (6 mm) spade terminals (quick connects).
• V4943 are used with line voltage, two-wire thermostats or 30 in. (762 mm) leadwires and cover for electrical conduit connection
controllers; V8943 are used with 24 Vac thermostats or provided
controllers. Except V4944N1052 and V4944N1060—1/4 in. (6 mm) spade
• V4944 are used with line voltage, dual-stage thermostats or terminals (quick connects). 76 in. (1930 mm) leadwires and cover for
controllers; V8944 are used with 24 Vac dual-stage thermostats or electrical conduit connection provided.
controllers. Valve Opening Time: Slow opening—3 sec to 25 sec
• Valve closes on power failure; recommended for final shutoff Rapid opening—6 sec max
service. Valve Closing Time: 2 sec max at 7 in. w.c.
Regulator Regulator
Regulator Setpoints; Regulator Setpoints;
Setpoints; Factory Setpoints; Factory
Valve Pipe Type of Bleed Adj. Range, Setting, Adj. Range, Setting,
ORDER NUMBER Description Type size Capacity gas Tapping Low Fire Low Fire High Fire High Fire
V4943A1011 Solenoid on-off, 1 in. 1000 cfh Natural Internal — — — —
V4943A1029 operated rapid 1 1/4 in. 1600 cfh and LP Bleed
diaphragm valve opening
V4943A1037 for internal bleed 1 1/2 in. 2300 cfh
V4943A1045 2 in. 3000 cfh
V4943B1019 Solenoid single- 1 in. 300 cfh to Natural Internal — — 3 in. w.c. to 3.5 in. w.c.
operated stage, 1000 cfh Bleed 4.5 in. w.c.
diaphragm valve, slow Standard
V4943B1027 1 1/4 in. 480 cfh to
single stage opening 5/16-24
1600 cfh
pressure UNF
V4943B1035 regulating 1 1/2 in. 780 cfh to optional
2300 cfh
V4943B1043 2 in. 870 cfh to
3000 cfh
V4943N1012 1 in. 300 cfh to
1000 cfh
V4943N1020 1 1/4 in. 480 cfh to
1600 cfh
V4943N1038 1 1/2 in. 780 cfh to
2300 cfh
V4943N1046 2 in. 870 cfh to
3000 cfh
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
61 70-8911
Diaphragm Gas Valve
Regulator Regulator
Regulator Setpoints; Regulator Setpoints;
Setpoints; Factory Setpoints; Factory
Valve Pipe Type of Bleed Adj. Range, Setting, Adj. Range, Setting,
ORDER NUMBER Description Type size Capacity gas Tapping Low Fire Low Fire High Fire High Fire
V4944B1018 Solenoid two- 1 in. 300 cfh to Natural Two 0.8 in. w.c. to 0.8 in. w.c. 3 in. w.c. to 3.5 in. w.c.
operated stage, 1000 cfh 5/16-24 2 in. w.c. 4.5 in. w.c.
diaphragm valve, slow UNF
V4944B1026 1 1/4 in. 480 cfh to
two stage opening
1600 cfh
pressure
V4944B1034 regulating 1 1/2 in. 780 cfh to
2300 cfh
V4944B1042 2 in. 870 cfh to
3000 cfh
V4944B1059 1 in. 300 cfh to 0.7 in. w.c. 3.0 in. w.c.
1000 cfh
V4944L1016 Solenoid two- 1 in. 300 cfh to LP 1.4 in. w.c. to 1.4 in. w.c. 8.8 in. w.c. 10.0 in. w.c.
operated stage, 1000 cfh 4.2 in. w.c. to 11.5 in.
V4944L1024 diaphragm valve, rapid 1 1/4 in. 480 cfh to w.c.
two stage opening 1600 cfh
pressure
V4944N1011 regulating 1 in. 300 cfh to Natural 0.8 in. w.c. to 0.8 in. w.c. 3 in. w.c. to 3.5 in. w.c.
1000 cfh 2 in. w.c. 4.5 in. w.c.
V4944N1029 1 1/4 in. 480 cfh to
1600 cfh
V4944N1037 1 1/2 in. 780 cfh to
2300 cfh
V4944N1045 2 in. 870 cfh to
3000 cfh
V4944N1052 1 in. 300 cfh to Two 1.65 in. w.c.
1000 cfh 5/16-24
V4944N1060 1 1/4 in. 480 cfh to UNF 1.0 in. w.c. 3.0 in. w.c.
1600 cfh
V8943A1012 Solenoid on-off, 1 in. 1000 cfh Natural Internal — —
operated rapid and LP Bleed
V8943A1020 1 1/4 in. 1600 cfh
diaphragm valve opening
V8943A1038 for internal bleed 1 1/2 in. 2300 cfh
V8943A1046 2 in. 3000 cfh
V8943B1010 Solenoid single- 1 in. 300 cfh to Natural 5/16-24 3 in. w.c. to 3.5 in. w.c.
operated stage, 1000 cfh UNF 4.5 in. w.c.
V8943B1028 diaphragm valve, slow 1 1/4 in. 480 cfh to
single stage opening 1600 cfh
pressure
V8943B1036 regulating 1 1/2 in. 780 cfh to
2300 cfh
V8943B1044 2 in. 870 cfh to
3000 cfh
V8943C1018 1 in. 300 cfh to LP 8.8 in. w.c. 10.0 in. w.c.
1000 cfh to 11.5 in.
w.c.
V8943C1026 1 1/4 in. 480 cfh to
1600 cfh
V8943N1013 single- 1 in. 300 cfh to Natural 3 in. w.c. to 3.5 in. w.c.
stage, 1000 cfh 4.5 in. w.c.
rapid
V8943N1021 1 1/4 in. 480 cfh to
opening
1600 cfh
V8943N1039 1 1/2 in. 780 cfh to
2300 cfh
V8943N1047 2 in. 870 cfh to
3000 cfh
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 62
Diaphragm Gas Valve
Regulator Regulator
Regulator Setpoints; Regulator Setpoints;
Setpoints; Factory Setpoints; Factory
Valve Pipe Type of Bleed Adj. Range, Setting, Adj. Range, Setting,
ORDER NUMBER Description Type size Capacity gas Tapping Low Fire Low Fire High Fire High Fire
V8944B1019 Solenoid two- 1 in. 300 cfh to Natural Two 5/ 0.8 in. w.c. to 0.8 in. w.c. 3 in. w.c. to 3.5 in. w.c.
operated stage, 1000 cfh 16-24 2 in. w.c. 4.5 in. w.c.
diaphragm valve, slow UNF
V8944B1027 1 1/4 in. 480 cfh to
two stage opening
1600 cfh
pressure
V8944B1035 regulating 1 1/2 in. 780 cfh to
2300 cfh
V8944B1043 2 in. 870 cfh to
3000 cfh
V8944C1017 1 in. 300 cfh to LP 1.4 in. w.c. to 1.4 in. w.c. 8.8 in. w.c. 10.0 in. w.c.
1000 cfh 4.2 in. w.c. to 11.5 in.
w.c.
V8944C1025 1 1/4 in. 480 cfh to
1600 cfh
V8944C1033 1 1/2 in. 780 cfh to
2300 cfh
V8944L1017 Solenoid two- 1 in. 300 cfh to
operated stage, 1000 cfh
diaphragm valve, rapid
V8944L1025 1 1/4 in. 480 cfh to
two stage opening
1600 cfh
pressure
V8944N1012 regulating 1 in. 300 cfh to Natural 0.8 in. w.c. to 0.8 in. w.c. 3 in. w.c. to 3.5 in. w.c.
1000 cfh 2 in. w.c. 4.5 in. w.c.
V8944N1020 1 1/4 in. 480 cfh to
1600 cfh
V8944N1038 1 1/2 in. 780 cfh to
2300 cfh
V8944N1046 2 in. 870 cfh to
3000 cfh
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
63 70-8911
Gas Valves, Firing Rate—Butterfly Gas Valve
V51 Butterfly Gas/Air Valve
• Adjustable stroke over low fire-high fire range.
• Straight-through valve pattern.
• Rugged cast aluminum body provides durability and
maintenance-free operation.
Body Material: Aluminum
Provides modulating control of natural, manufactured, LP gases or Description: Modulating gas control
air. Mounting: Motor shaft horizontal
• Use in commercial and industrial installations where large Type of gas: Air, natural, manufactured, and LP
amounts of gas must be closely controlled. NOT for use as safety Underwriters Laboratories Inc Approvals: File no. MH5968 vol. 1 sec. 1,
shutoff valve. guide no. MHKZ
• Adaptable to most modulating jobs. Valve pattern: Straight-through
• Modutrol motor, such as the M9484 or M9494, may be mounted Temperature Ratings: 32 F to 140 F; 0 C to 60 C
directly on valve or close to it. Pressure Rating: 5 psi; 34.5 kPa
• Valve mechanism has strain release.
ORDER NUMBER Pipe size Capacity Dimensions
V51E1000 1 1/2 in.; 38 mm 4200 cfh; 118.9 m3/hr 2 11/16 in. high, 3 1/16 in. wide, 5 13/16 in. deep;
68 mm high, 77 mm wide, 148 mm deep
V51E1018 2 in.; 51 mm 9210 cfh; 260.7 m3/hr 3 3/16 in. high, 3 9/16 in. wide, 6 1/16 in. deep;
80 mm high, 90 mm wide, 154 mm deep
V51E1034 2 1/2 in.; 64 mm 8390 cfh; 199.8 m3/hr 3 7/8 in. high, 4 3/4 in. wide, 7 1/8 in. deep;
98 mm high, 120 mm wide, 181 mm deep
V51E1059 3 in.; 76 mm 14640 cfh; 414.5 m3/hr 4 1/16 in. high, 4 3/4 in. wide, 7 3/8 in. deep;
102 mm high, 120 mm wide, 188 mm deep
V51E1075 4 in.; 101 mm 33000 cfh; 934.2 m3/hr 5 3/8 in. high, 5 1/4 in. wide, 8 9/16 in. deep;
135 mm high, 134 mm wide, 217 mm deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 64
Gas Valves
Selection Chart: V5055 and V5097 Industrial Gas Valves with
V4055, V4062 or V9055 Fluid Power Actuators
The chart below describes every model of V5055 or V5097 Valve in the • NEMA 4 enclosure.
left column, and every model of Fluid Power Actuator across the top. • Fast or slow open time (13 or 26 seconds).
While it's possible to combine any valve with any actuator, we've marked • Auxiliary switch.
the recommended valve/actuator combinations which cover most appli- • Valve seal overtravel interlock switch.
cations with a !. The Q5055A Adapter Assembly is available for adapting ITT General
Each valve described in the left column is available: V710 gas valve to accept Honeywell gas valve actuators (V4055, V4062
• in these sizes: 3/4 to 3 in. (NPT or parallel BSP). V5055A,B,C are also and V9055) as replacements for ITT General AH2, AH4, AH8 gas valve
available in 4 in. size (flange connection only). actuators. Refer to Index for specific page number of Q5055A.
• With upstream and/or downstream tap. For complete specifications and ordering information on V5055 and
Options available on some Fluid Power Actuators include: V5097 Valves and V4055, V4062 and V9055 Fluid Power Actuators,
• Damper arm shaft, with or without spring return. refer to Index for specific page numbers.
Actuator
V4055F
Manual
V4055D V4055E Reset V4062D V9055D
On-Off On-Off Safety Modulating Modulating
V4055A V4055B Lo Press. Hi Press. Shutoff Lo Press. Lo Press.
On-Off On-Off Valve Seal Valve Seal Valve Seal V4055G V4062A Valve Seal V9055A Valve Seal
Lo Hi Overtravel Overtravel Overtravel Manual Hi-Lo-Off Overtravel Modulating Overtravel
Valve Press. Press. Interlock Interlock Interlock Reset Lo Press. Interlock Lo Press. Interlock
V5055A, V5097A On-Off Lo ! !b !
Pressure
V5055B, V5097B Lo Pressure ! !b ! ! !
Characterized Guidea
V5055C, V5097C Lo ! !b ! ! !
Pressure Double Sealc
V5055D, V5097D On-Off Hi !b !
Pressure
V5055E, V5097E Hi Pressure !b ! !b !b
Double Seal c
a
Provides a predictable relationship between stem travel and gas flow.
b
See next page for higher opening and close-off ratings for these combinations.
c
Use with actuators having valve seal overtravel interlock
VALVE ACTUATOR APPROVALS: FACTORY MUTUAL APPROVED (Report No. 20698, 20835, 21172
The following combinations of V5055 and V5097 Valves, and V4055, and 24061) and AMERICAN GAS ASSOCIATION CERTIFIED
V4062 and V9055 Fluid Power Actuators are approved by these (Report No. 21-1C):
agencies. V4055A/V5055A and V5097A.
UNDERWRITERS LABORATORIES INC. LISTED: MH1639 V4055D/V5055C and V5097C.
V4055A/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055A/V5055B and V5097B.
V4055B/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055B/V5055D and V5097D.
V4055D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055E/V5055E and V5097E.
V4055E/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). V4055F/V5055Ca and V5097C.
V4055F/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V4055G/V5055A,Ba and V5097A,B.
V4055G/V5055A-E (3/4-4 in.a) or V5097A-E (3/4-3 in.). V9055A/V5055B,C and V5097B,C.
V4062A,D/V5055A-E (3/4-4 in.) or V5097A-E (3/4-3 in.). INDUSTRIAL RISK INSURERS ACCEPTABLE.
V9055A,D/V5055A,B,C,E (3/4-4 in.) or V5097A-E (3/4-3 in.). a Manual reset safety shut-off valves.
CANADIAN GAS ASSOCIATION CERTIFIED: Report No.1209-SSV-
5965-60 Hz models only.
VALVE-ACTUATOR PRESSURE RATINGS:
Actuator
a
V4055A,D V4055B,Ea V4062, V9055a
Diff.b Close-Offc Diff.b Close-Offc Diff.b Close-Offc
Valve psi kPa psi kPa psi kPa psi kPa psi kPa psi kPa
V5055A,C and V5097A,C (3/4 to 3 in.) 5 34.5 15 103.4 15 103.4 15 103.4 5 34.5 15 103.4
V5055A,C (4 in.) 3 20.7 15 103.4 5 34.5 15 103.4 3 20.7 15 103.4
V5055B and V5097B (3/4 to 3 in.) 5 34.5 15 103.4 15 103.4 15 103.4 5 34.5 15 103.4
V5055B (4 in.) 3 20.7 15 103.4 5 34.5 15 103.4 3 20.7 15 103.4
V5055D,E and V5097D,E (3/4, 1, 1-1/4, 1-1/2 in.) 5 34.5 75 517.1 25 172.4 75 517.1 5 34.5 75 517.1
V5055D,E and V5097D,E (2, 2-1/2, 3 in.) 5 34.5 45 310.3 15 103.4 45 310.3 5 34.5 45 310.3
a Use a V4055D, V4055E, V4062D or V9055D (with valve-closed indication switch) with a V5055C,E or V5097C,E (with double seal) for a Valve Seal
Overtravel Interlock.
b Maximum operating pressure differential.
c Maximum close-off pressure without seal leakage. This is the maximum allowable pressure drop to which a valve may be subjected while fully
closed, and is independent of the
Some products arevalve bodyonly
available rating.
through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
65 70-8911
Industrial Gas Valves
V5055 Industrial Gas Valves
Approvals, American Gas Association IAS: V5055A—Design Certified,
Report No. 21 -1 C (used with V4055A)
V5055B,C—Design Certified, Report No. 21 -1 C (used with V4055A,
V4062, V9055)
V5055D—Design Certified, Report No. 21 -1 C (used with V4055B)
V5055D—Design Certified, Report No. 21 -1 C (used with V4055E)
Approvals, Canadian Gas Association IAS: Certified, Report No. 1029-
SSV-4098, 60 Hz actuators only
Approvals, Factory Mutual: Approved, Report No. 20698, 20835, 21172,
Safety shutoff valves used with V4055, V4062 and V9055 fluid and 24061
power actuators to control gas flow to commercial and industrial Approvals, Industrial Risk Insurers: Acceptable (used with
burners. V4055A,B,D,E, V4062, V9055)
• Use with natural or LP gases. Includes: Includes 1/4 in. -18 NPT upstream tap and plug, 1/4 in. -18
• Mount directly in gas supply line. NPT downstream tap and plug
• Include 1/4 in. NPT upstream and downstream taps and plug; 4 in. Operating Temperature Ratings: -40 F to 150 F; -40 C to 66
models have only flanged connections. Temperature Ratings when used with V9055: -40 F to 125 F;
Approvals, Underwriters Laboratories, Inc.: V5055A—File No. MH1639, -40 C to 52 C
Guide No. YIOZ (used with V4055A,B,D,E, V4062, V9055)
V5055B,C,D,E—File No. MH1639, Guide No. YIOZ
Maximum Operating Maximum Operating
Differential Pressure Differential Pressure
ORDER NUMBER Pipe size Capacity (V4055A,D; V4062) (V4055B or E) Description
V5055A1004 1 in. NPT 3
960 cf/hr; 27.2 m /hr 5 psi (34.5 kPa) 15 psi (103.4 kPa) On-off safety shut-off
V5055A1012 1 1/4 in. NPT 1406 cf/hr; 39.8 m3/hr
V5055A1020 1 1/2 in. NPT 1717 cf/hr; 48.6 m3/hr
V5055A1038 2 in. NPT 3620 cf/hr; 102.5 m3/hr
V5055A1046 2 1/2 in. NPT 4250 cf/hr; 120 m3/hr
V5055A1053 3 in. NPT 5230 cf/hr; 148 m3/hr
V5055A1228 4 in. Flanged 10200 cf/hr; 288.8 m3/hr 3 psi (20.7 kPa) 5 psi (34.5 kPa)
V5055A1343 3/4 in. NPT 665 cf/hr; 18.8 m3/hr 5 psi (34.5 kPa) 15 psi (103.4 kPa)
V5055B1002 1 in. NPT 960 cf/hr; 27.2 m3/hr On-off safety shut-off with
characterized guide for slow
V5055B1010 1 1/4 in. NPT 1406 cf/hr; 39.8 m /hr
3
opening, HI-LO-OFF, or
V5055B1028 1 1/2 in. NPT 1717 cf/hr; 48.6 m3/hr modulating service
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 66
Industrial Gas Valves
Maximum Operating Maximum Operating
Differential Pressure Differential Pressure
ORDER NUMBER Pipe size Capacity (V4055A,D; V4062) (V4055B or E) Description
V5055C1109 4 in. Flanged 9180 cf/hr;259.9 m3/hr 3 psi (20.7 kPa) 5 psi (34.5 kPa) On-off safety shut-off with Valve
Seal Overtravel
V5055C1182 3/4 in. NPT 665 cf/hr 5 psi (34.5 kPa) 15 psi (103.4 kPa)
V5055D1008 1 in. NPT 960 cf/hr;27.2 m3/hr 25 psi (172.4 kPa) On-off safety shut-off for high
pressure applications
V5055D1016 1 1/4 in. NPT 1406 cf/hr;39.8 m3 /hr
V5055D1024 1 1/2 in. NPT 1717 cf/hr;48.6 m3/hr
V5055D1032 2 in. NPT 3620 cf/hr;102.5 m3/hr 15 psi (103.4 kPa)
V5055D1040 2 1/2 in. NPT 4250 cf/hr;120 m3/hr
V5055D1057 3 in. NPT 5230 cf/hr
V5055D1065 3/4 in. NPT 665 cf/hr 25 psi (172.4 kPa)
V5055E1005 2 in. NPT 3620 cf/hr;102.5 m 3/hr 15 psi (103.4 kPa) On-off safety shut-off for high
pressure applications, with Valve
V5055E1013 2 1/2 in. NPT 4250 cf/hr;120 m3/hr Seal Overtravel
V5055E1021 3 in. NPT 5230 cf/hr;148 m3/hr
V5055E1039 1 in. NPT 960 cf/hr;27.2 m3/hr 25 psi (172.4 kPa)
V5055E1047 1 1/4 in. NPT 1406 cf/hr;39.8 m3/hr
V5055E1054 1 1/2 in. NPT 1717 cf/hr;48.6 m3/hr
V5055E1062 3/4 in. NPT 665 cf/hr
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
67 70-8911
Industrial Gas Valves—Integrated Valve Train
V5097 Industrial Gas Valves
• Provides three 1/4 in. upstream and two 1/4 in. downstream tap
and plug. CE version provides an additional downstream tap and
plug.
• Yellow SHUT indicator attached to the valve stem provides an
indication of the valve closed position.
Approvals, Canadian Gas Association IAS: Certified, Report No. 1029-
SSV-4098, 60 Hz actuators only
Approvals, Factory Mutual: Approved, Report No. 20698, 20835, 21172,
and 24061
Safety shutoff valves used with V4055, V4062 and V9055 fluid Approvals, Industrial Risk Insurers: Acceptable (used with
power actuators to control gas flow to commercial and industrial V4055A,B,D,E, V4062, V9055)
burners. Approvals, Underwriters Laboratories, Inc.: File No. MH1639, Guide No.
• Use with natural or LP gases. YIOZ
• Mount directly in gas supply line. Comments: Select Proper Pipe Adapter
• Two Valve body types. Small body type for 3/4 in., 1 in., 1-1/4 in., Includes: Three 1/4 in. -18 NPT upstream and
1-1/2 in., 2 in. pipes. Large body types for 2 in., 2-1/2 in. and 3 in. two 1/4 in. -18 NPT downstream taps
pipes. Maximum Operating Differential Pressure (V4055A,D; V4062):
• Seven pipe adapter sizes from 3/4 in. to 3 in. have NPT or BSP 5 psi (340 mbar)
threaded connections. Operating Temperature Ratings: -40 F to +150 F; -40 C to +66 C
Temperature Ratings when used with V9055: -40 F to +125 F;
-40 C to +52 C
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 68
Industrial Gas Valves—Integrated Valve Train Adapter
Integrated Valve Train Adapter
Integrated Valve
ORDER NUMBER Train Body Size Pipe size Description
32000109-001 Small body 3/4 in. NPT Integrated Valve Train Pipe Adapter, Small body, 3/4 in. NPT
32000109-002 1 in. NPT Integrated Valve Train Pipe Adapter, Small body, 1 in. NPT
32000109-003 1 1/4 in. NPT Integrated Valve Train Pipe Adapter, Small body, 1 1/4 in. NPT
32000109-004 1 1/2 in. NPT Integrated Valve Train Pipe Adapter, Small body, 1 1/2 in. NPT
32000109-005 2 in. NPT Integrated Valve Train Pipe Adapter, Small body, 2 in. NPT
32000109-006 3/4 in. BSP Integrated Valve Train Pipe Adapter, Small body, 3/4 in. BSP
32000109-007 1 in. bsp Integrated Valve Train Pipe Adapter, Small body, 1 in. BSP
32000109-008 1 1/4 in. bsp Integrated Valve Train Pipe Adapter, Small body, 1 1/4 in. BSP
32000109-009 1 1/2 in. bsp Integrated Valve Train Pipe Adapter, Small body, 1 1/2 in. BSP
32000109-010 2 in. bsp Integrated Valve Train Pipe Adapter, Small body, 2 in. BSP
32001605-001 Large body 2 in. NPT Integrated Valve Train Pipe Adapter, Large body, 2 in. NPT
32001605-002 2 1/2 in. NPT Integrated Valve Train Pipe Adapter, Large body, 2 1/2 in. NPT
32001605-003 3 in. NPT Integrated Valve Train Pipe Adapter, Large body, 3 in. NPT
32001605-004 2 in. bsp Integrated Valve Train Pipe Adapter, Large body, 2 in. BSP
32001605-005 2 1/2 in. bsp Integrated Valve Train Pipe Adapter, Large body, 2 1/2 in. BSP
32001605-006 3 in. bsp Integrated Valve Train Pipe Adapter, Large body, 3 in. BSP
32004771-001 Small body 1/4 in. NPT Multi-tap Adapter Assembly, Includes three 1/4 in. NPT taps and plugs
32005096-001 — Screen Assembly for Small Body Multi-tap Adapter
32005096-002 Large body — Screen Assembly for Large Body Multi-tap Adapter
M16596
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
69 70-8911
Solenoid Gas Valves
V4295; V8295 Solenoid Gas Valves
• Low rush-in current.
• Upstream and downstream taps allows tapping and testing
pressure points.
Approvals, American Gas Association IAS: Certificate No.C2030014
Approvals, Canadian Gas Association IAS: Certificate No.C2030014
Approvals, Control Safety Devices: Acceptable
Approvals, Factory Mutual: Approved: 3/8, 1/2, 3/4 in. only
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Component Recognized;
File No. YLOZ
V4295A/V8295A are normally closed and V4295S/V8295S are
Body Material: Aluminum
normally open (vent) solenoid gas valve. Suitable for use on
Electrical Terminations: screw terminal connections
furnaces, ovens, atmospheric burners, commercial water heaters,
Power Supply: V4295—120 Vac; V8295—24 Vac
roof-top make-up air units, power burners, and commercial/
Frequency: 50/60 Hz
industrial boilers.
Inlet and Outlet Pressure Tapping: 1/4 in. NPT
• V4295A,S are used with 120 Vac controllers. Mounting: Vertical to 90 degrees from vertical
• V8295A,S are used with 24 Vac controllers. Type of gas: Air, natural, manufactured, mixed, and LP
• Positive close off of gas flow when de-energized. Valve Closing Time: less than 1 sec
• High valve spring force allows up to 0.7 psi back pressure at Valve Opening Time: less than 1 sec
valve seat. Valve pattern: Straight-through, non-offset
• No inlet pressure influence at valve seat. Inlet pressure changes Temperature Ratings: -40 F to 140 F; -40 C to 60 C
do not affect ability to close valve. Description: V4295A; V8295A—Normally closed
• Low operating noise. V4295S; V8295S—Normally open
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 70
Solenoid Gas Valves—IVT Vent Valve
Pressure Current (max A Replacement
ORDER NUMBER Pipe size Capacity Rating at rated Vac/Hz) Dimensions Parts
V4295S1005 3/4 in. 350 cfh 2 psi; 0.160 A 5 1/2 in. high, 3 7/16 in. wide, 2 3/4 in. deep. BBA51307 Coil
19 mm 13.8 kPa 140 mm high, 87 mm wide, 70 mm deep Assembly
V4295S1013 1 in. 420 cfh 5 1/2 in. high, 3 15/16 in. wide, 3 in. deep.
25 mm 140 mm high, 100 mm wide, 76 mm deep
V4295S1021 1 1/4 in. 1100 cfh 0.340 A 8 3/4 in. high, 5 15/16 in. wide, 4 3/8 in. deep. BBA51308 Coil
32 mm 222 mm high, 151 mm wide, 111 mm deep Assembly
V8295A1008 3/8 in. 230 cfh 0.8 A 4 7/16 in. high, 2 7/8 in. wide, 2 3/16 deep. BBA52402 Coil
9 mm 113 mm high, 73 mm wide, 56 mm deep Assembly
V8295A1016 1/2 in. 250 cfh
13 mm
V8295A1024 3/4 in. 645 cfh 5 1/4 in. high, 3 7/16 in. wide, 2 3/4 in. deep.
19 mm 133 mm high, 87 mm wide, 70 mm deep
V8295A1032 1 in. 790 cfh 5 1/4 in. high, 3 15/16 in. wide, 3 in. deep.
25 mm 133 mm high, 100 mm wide, 76 mm deep
V8295A1040 1 1/4 in. 1450 cfh 8 in. high, 5 15/16 in. wide, 4 3/8 in. deep. BBA52403 Coil
32 mm 203 mm high, 151 mm wide, 111 mm deep Assembly
V8295A1057 1 1/2 in. 2190 cfh 8 3/8 in. high, 5 15/16 in. wide, 4 3/8 in. deep. BBA52401 Coil
38 mm 213 mm high, 151 mm wide, 111 mm deep Assembly
V8295A1065 2 in. 3465 cfh 8 3/8 in. high, 6 11/16 in. wide, 5 3/8 in. deep. BBA52404 Coil
51 mm 213 mm high, 170 mm wide, 137 mm deep Assembly
V8295S1006 3/4 in. 350 cfh 5 1/2 in. high, 3 7/16 in. wide, 2 3/4 in. deep. BBA52407 Coil
19 mm 140 mm high, 87 mm wide, 70 mm deep Assembly
V8295S1014 1 in. 420 cfh 5 1/2 in. high, 3 15/16 in. wide, 3 in. deep. BBA52407 Coil
25 mm 140 mm high, 100 mm wide, 76 mm deep Assembly
V8295S1022 1 1/4 in. 1100 cfh 8 3/4 in. high, 5 15/16 in. wide, 4 3/8 in. deep. BBA524078
32 mm 222 mm high, 151 mm wide, 111 mm deep Coil Assembly
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
71 70-8911
Solenoid Gas Valves—IVT Vent Valve
V4297S Normally Open Vent Valve
Description: Integrated Valve Train, Normally Open (Vent)
Electrical Terminations: screw terminal connections
Flanges: Required
Inlet and Outlet Pressure Tapping: 1/4 in. NPT
Mounting: Directly bolted to Integrated Valve Train Components
Pressure Rating: 5 psi
Valve Closing Time: less than 1 sec
Valve Opening Time: less than 1 sec
Valve pattern: Straight-through, non-offset
Power: 110 Vac; 120 Vac
Approvals, International Approval Services (IAS): Design Certified
Temperature Ratings: -40 F to 145 F; -40 C to 63 C
Approvals, Industrial Risk Insurers: Acceptable
Frequency: 50 Hz; 60 Hz
Approvals, Underwriters Laboratories, Inc.: Listed
Body Material: Aluminum
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 72
Solenoid Gas Valves—Pilot Gas Valve
V4046C; V8046C Pilot Gas Valves
Approvals, Underwriters Laboratories, Inc.: Listed: File no. MH1639,
vol. 3, sec. 3, guide no. YIOZ
Approvals, American Gas Association IAS: Certified: Certified Nos.
(F-212.3 and 1.3).001
Approvals, Canadian Gas Association IAS: Certified: Report no.
1029-AV-6265, 120 and 24 Vac, 60 Hz.
Approvals, Canadian Standards Association: Canadian Standards
Association Certified: File no. LR95329-1
Approvals, Factory Mutual: Approved: Report No. 17450
Provide on-off control of natural, LP and manufactured gases to Approvals, Industrial Risk Insurers: Acceptable
pilot burners in industrial and commercial applications. Body Material: Aluminum
• Magnetically operated, normally closed. Description: Normally closed
• Provide instantaneous action when energized. Electrical Ratings (power consumption): 8 W
• On power failure, valve closes in one second maximum. Mounting: Directly in pipe or on support bracket
• Use in any position, directly in pipe line or on support bracket. Type of gas: Air, natural, manufactured, and LP
• Replace the solenoid coil without removing the valve body from Valve Closing Time: 1 sec max
the piping connections. Valve Opening Time: 1 sec max
• Straight-through valve pattern. Valve pattern: Straight-through
• Available in line voltage or low voltage models. Temperature Ratings: -40 F to 125 F; -40 C to 52 C
Pressure Rating: 10 psi; 68.9 kPa
ORDER NUMBER Pipe size Capacity Power Frequency Electrical Terminations Dimensions
V4046C1005 1/8 in. 20 cfh; 110 Vac 50 Hz Two 36-in. leadwires and 2 3/4 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
3 mm 0.57 m3/hr 120 Vac 60 Hz 1/2 in. conduit bushing 70 mm high, 67 mm wide, 41 mm deep
V4046C1021 1/4 in. 3 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
6 mm 76 mm high, 67 mm wide, 41 mm deep
V4046C1047 55 cfh; 3 1/4 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
1.56 m3/hr 83 mm high, 67 mm wide, 41 mm deep
V4046C1054 3/8 in. 67 cfh;
9 mm 1.90 m3/hr
V4046C1088 208 Vac 60 Hz
V4046C1120 120 Vac Two 10 ft. leadwires and
1/2 in. conduit bushing
V8046C1006 1/8 in. 20 cfh; 24 Vac Two 36-in. leadwires and 2 3/4 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
3 mm 0.57 m3/hr 1/2 in. conduit bushing 70 mm high, 67 mm wide, 41 mm deep
V8046C1014 1/4 in. 3 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
6 mm 76 mm high, 67 mm wide, 41 mm deep
V8046C1022 55 cfh; 3 1/4 in. high, 2 5/8 in. wide, 1 5/8 in. deep.
1.56 m3/hr 83 mm high, 67 mm wide, 41 mm deep
V8046C1030 3/8 in. 67 cfh
9 mm 1.90 m3/hr
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
73 70-8911
Ignition Transformers—Solid State
Q624 Solid State Ignition Transformer
• Mount in same space used by conventional ignition transformer.
• Light weight, 3 lbs. (1.4 kg) versus 8-1/2 lbs. (3.9 kg) for standard
transformers.
Accessories: 32004766-001 24" Ignition Wire w/ends; 32004766-002
120" Ignition Wire w/ends; 32004766-003 Ignition Wire by the foot
Approvals, Canadian Standards Association: File #1620 Guide 140-A-2
Approvals, Underwriters Laboratories Inc.: Component Recognized; File
no. MH7453, Guide No. JHYR2.
Industrial Risk Insurers Approvals: Acceptable
Use to ignite pilots on commercial or industrial gas burners. Humidity Ratings: 95% RH
Weight: 3 lbs (1.4 Kg)
• Ignite gas pilots with spark gaps up to 1/4 in. (6.5 mm).
Electrical Ratings, Power Supply: 120 Vac; 60 Hz
• Reliable lightoff with 15,000 peak voltage.
Temperature Rating (Ambient): -40 to +125 F; -40 to + 52 C
• Prevent detection of the ignition spark when properly applied in a
Dimensions: 6-3/4 in. high x 4-1/4 in. wide x 3 in. deep;
flame detection system with the C7027, C7035 or C7044
171.5 mm high x 108 mm wide x 76 mm deep.
Minipeeper Ultraviolet Flame Detector.
• For use only in interrupted ignition applications.
ORDER NUMBER Description
Q624A1014 Solid State Ignition Transformer
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 74
Linkages—Valve Linkage
Q100 Linkage
Connects V51E valve to M9484 and M9494 Modutrol IV Motors with
adapter plate.
• Fits all sizes of V51E Valves
• Mounts easily.
Comments: Use with V51E Gas Valve
Includes: Adapter bracket
Linkage Type: Butterfly Gas Valve
ORDER NUMBER Valve Size Compatibility Linkage Rod Used with Actuator:
Q100B1006 all sizes 10 3/4 in. Modutrol Motor
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
75 70-8911
Motors and Actuators, FSG—BCS 7700 System Motor
M7484 BCS 7700 Firing Rate Motor
Approvals, Industrial Risk Insurers: Acceptable
Crankshaft: double-ended, 3/8 in. (9.5 mm) square
Description: Proportional control motor for BCS 7700 System
applications
Frequency: 50/60 Hz
Input Signal: BCS 7700
Power Consumption: 18 W
Power Supply: 24 Vac
Timing (90 degree stroke): 30 seconds
Dead Weight Load On Auxiliary Shaft: 200 lb (300 lb combined power
Low voltage, reversing, proportional modutrol motor used to drive
and auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary
a fuel valve and combustion air damper as command by the BCS
shafts)
7700.
Dead Weight Load On Power Shaft: 200 lb (300 lb combined power and
• Requires 24 Vac power supply. auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary
• Electronic vibration-resistant drive circuit. shafts)
• Die cast aluminum case. Temperature Ratings (ambient): 32 F to 150 F; 0 C to 66 C
• Feedback potentiometer circuit provides position indication input Dimensions: 6.45 in. high, 5.50 in. wide, 7.30 in. deep;
to the BCS 7700 System, as well as Low and High fire position 164 mm high, 140 mm wide, 185 mm deep.
proving. Accessories: 220738A-Adapter Bracket. Adjusts shaft height to match
• Double-ended, 3/8 in. square crankshaft. M741B
Approvals, Canadian Standards Association: Certified: File LR95329-1 220741A-Screw Terminal Adapter- Converts quick-connect terminals
Guide 400-E to screw terminals.
Approvals, Underwriters Laboratories, Inc.: Component Recognized; 4074ERU-Weatherproofing kit. Weatherproofs motor.
File no. MP268, Guide no. MCCZ 7617ADW-Adjustable Modutrol IV Motor Crank Arm.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 76
Motors and Actuators, FSG—Firing Rate Motor
M9484D,E,F; M9494D Modutrol™ IV Motors
Description: Proportional control motor for 135 ohm firing rate
applications
Frequency: 50/60 Hz
Input Signal: 135 ohm
Power Consumption: 18 W
Power Supply: 24 Vac
Switch Ratings, 120 Vac: 7.2 AFL, 43.2 ALR, 40 VA pilot duty opposite
contact
Switch Ratings, 240 Vac: 3.6 AFL, 21.6 ALR, 40 VA pilot duty opposite
Reversing, proportional motors used to drive burner firing rate contact
valves, dampers or auxiliary equipment. Replace M941A,C,D Dead Weight Load On Auxiliary Shaft: 200 lb (300 lb combined power
motors. and auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary
shafts)
• Designed for flame safeguard applications in commercial/
Dead Weight Load On Power Shaft: 200 lb (300 lb combined power and
industrial oil or gas burner system.
auxiliary shafts); 90.8 kg (136 kg combined power and auxiliary
• Vibration resistant electronic drive circuit.
shafts)
• Regulated by three-wire proportional controller.
Temperature Ratings (ambient): -40 F to 150 F; -40 C to 66 C
• Stroke is field-adjustable to 90 or 160 degrees.
Dimensions: 164 mm high, 140 mm wide, 185 mm deep; 6.45 in. high,
Approvals, Canadian Standards Association: Certified: File LR1620,
5.50 in. wide, 7.30 in. deep.
Guide 400-E
Accessories: 220741A-Screw Terminal Adapter- Converts quick-connect
Approvals, Underwriters Laboratories, Inc.: Listed: File No. E4436,
terminals to screw terminals.
Guide No. XAPX
221455A-Infinitely adjustable Motor Crank Arm
Approvals, Industrial Risk Insurers: Acceptable
7617DM-Coupling- Must be used with ES650117 explosion-proof
Crankshaft: double-ended, 3/8 in. (9.5 mm) square
housing.
Timing Timing
Torque, Torque, (90 degree (160 degree Auxiliary Auxiliary Switch
ORDER NUMBER running breakaway stroke) stroke) switches Setting Comments
M9484D1010 150 lb-in. 300 lb-in. 30 seconds 60 seconds — — —
17.0 N m 34.0 N m
M9484E1009 75 lb-in. 150 lb-in. 15 seconds 30 seconds 1 11 degrees Includes tapped shaft
8.5 N m 17.0 N m
M9484E1017 150 lb-in. 300 lb-in. 30 seconds 60 seconds 1 degree —
17.0 N m 34.0 N m
M9484E1033 4 degrees Shipped in 90 degree
position, includes motor
crank arm
M9484F1007 2 5 degrees and 54 Shipped in 90 degree
degrees position
M9484F1023 75 lb-in. 150 lb-in. 15 seconds 30 seconds — Includes tapped shaft
8.5 N m 17.0 N m
M9484F1031 150 lb-in. 300 lb-in. 30 seconds 60 seconds 5 degrees and 54 Shipped in 90 degree
17.0 N m 34.0 N m degrees position, includes tapped
shaft
M9484F1049 35 degrees and Shipped in 160 degree
120 degrees position
M9494D1000 150 lb-in. — 54 degrees and 5 —
17.0 N m degrees
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
77 70-8911
Network Interface—Data Acquisition
QM4520 Isolated RS-232 to RS-485 Converter Module
• Power consumption: 1.2W.
• Mounts on DIN rail, panel or in a `piggyback' stack.
Accessories: 208527 ADAM-UTI
Communications: RS-485 two wire host; Baud Rates:1200, 2400, 4800,
9600, and 19200 bps.
Description: RS-232 to RS-485 Converter
Electrical Ratings (power supply): Unregulated +10 Vdc to +30 Vdc;
protected against power reversal
Humidity Ratings: 5% RH to 95% RH, non-condensing
Isolated RS-232 to RS-485 Converter Module. Temperature Ratings (ambient): 32 F to 158 F; 0 C to +70 C
Weight: 6 oz; 174 g
• Accepts RS-232 signal as input (4-wire: TX, RX, RTS, and GND).
Dimensions: 2 11/32 in. wide, 4 3/32 in. high, 1 3/16 in. deep;
(Null modem may be required.)
60 mm wide, 112 mm high, 30 mm deep.
• Outputs RS-485 signal (2-wire).
• Isolation voltage is 500 Vdc.
ORDER NUMBER Description
QM4520A1004 RS-232 to RS-485 Converter
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 78
Network Interface—Data ControlBus™ Module
QS7800B Network Interface ControlBus™ Modules
Approvals, Federal Communications Commission: FCC, Part 15; Class
B-Emissions, Part 68: registered. FCC registration No. HS92SJ-
10735-D-T-E.,
Approvals, Canadian Department of Communications: CS-03,
Certification No. 573-3459A
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
File No. MP268, Guide No. MCCZ
Communications: RS485 ControlBus™
Allows remote monitoring and diagnostics of multi-dropped 7800
Description: Network Interface ControlBus™ Module
SERIES Relay Modules.
Electrical Ratings (power supply): Current Draw: 75 mA
• Up to six ControlBus™ Modules per Network Interface Unit. Enclosure: NEMA 1
• Up to 32 multi-dropped 7800 SERIES subnetworks per module Humidity Ratings: operating: 85% rh continuous
without a RS-485 repeater; up to 61 subnetworks with a repeater. Use With: Multi-Dropping 7800 SERIES Relay Modules
• Provides local and remote annunciation of 7800 SERIES Relay Temperature Ratings (ambient): 32 F to 130 F; 0 C to +54 C
Module faults. Weight: 8 oz; 227 g
• Personal computer user interface. Temperature Ratings (Shipping): -30 F to 150 F; -34 C to 66 C
• Modular construction. Dimensions:4 21/32 in. wide, 3 29/32 in. high, 1 in. deep;
• Microsoft Windows™ based Combustion System Manager™ user 118 mm wide, 99 mm high, 25 mm deep.
interface. Includes: 200603 ControlBus™ Three-Prong Electrical Connector
Approvals, Canadian Standards Association: Certified: LR80141 (Included)
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
79 70-8911
Network Interface—Parts
Network Interface—Parts
ORDER NUMBER Description
200603 ControlBus™ Module 3-Wire Electrical Connector
202433 Slot Inserts, Controlbus™ Slots
203541 ControlBus™ Module 3-Wire Electrical Connector
209162 Power Supply for Din Rail Mounting - 110V
209163 Power Supply for Din Rail Mounting - 220V
209164 Power Supply for Din Rail Mounting - 120/240V
221237 Cover Assembly, Base Unit
221240 Cover Assembly, Electrical Enclosure
206610A Accessory Disk for QS7850
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 80
Flame Rectifier Gas Pilot Burners
C7005 Flame Rectifier Pilots
• Models available for use with natural or LP gas.
• Provide maximum flame current with flame-retention type pilot
head and bomb type fins.
• Mount in vertical, horizontal or inclined position.
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report No. 24181.04
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Combination rectification flame rod and pilot burner for use with Guide No. MCCZ
suitable relay on industrial or commercial gas or gas pilot-ignited Gas Fitting: 1/2 in. NPT male thread
oil burners. Includes: Ignition electrode
Dimensions: 3 in. diameter, 3 1/2 in. deep;
76 mm diameter, 343 mm deep,
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
81 70-8911
Miniature Rectification Pilot Burners
Q179C,D Miniature Rectifier Pilots
• Primary-aerated type burner is equipped with stainless steel
target to stabilize flame and provide correct flame rod area to
ground area ratio for maximum flame current.
• Use Rajah electrical connectors.
Application: Q179C—For Intermittent or Interrupted Ignition
Q179D—For Continuous (Standing) pilot
Aeration: Primary
Approvals, American Gas Association IAS: Certified: Report No. G-
140.104
Approvals, Canadian Standards Association: Certified: Master File
Gas pilot burner assemblies prove pilot flame on industrial or LR95329-1
commercial gas burners or gas pilot-ignited oil burners. Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
• Replace Q179A and B.
File No. MH9928, Guide No. MCUR2
• Side or end mounting bracket.
Gas Fitting: 1/4 in. compression coupling; 6.4 mm compression coupling
• Include natural gas orifice. Order 388146KD Orifice Assembly for
Type of gas: Natural
LP gas.
Except for Q179D1925—LP
• Include compression coupling for 1/4 in. (6.4 mm) O.D. tubing.
Mounting
ORDER NUMBER Orifice Target Mount Bracket Dimensions Includes
Q179C1009 0.026" dia. (0.66 Dual Wing- Rear rear 3 1/8 in. high, 2 7/16 in. wide, 1 in. deep. Flame electrode and
mm dia.) 79 mm high, 62 mm wide, 25 mm deep ignition electrode
Q179C1025 0.024" dia. (0.60 Single Wing- Rear rear
mm dia.)
Q179C1033 0.026" dia. (0.66 Dual Wing- Left Side left side 3 1/8 in. high, 3 1/32 in. wide, 1 in. deep.
mm dia.) 79 mm high, 77 mm wide, 25 mm deep
Q179C1041 Dual Wing- Right Side right side
Q179C1058 0.024" dia. (0.60 Single Wing- Left Side left side
mm dia.)
Q179C1066 Single Wing- Right Side right side 3 1/8 in. high, 2 7/16 in. wide, 1 in. deep.
79 mm high, 62 mm wide, 25 mm deep
Q179D1008 0.026" dia. (0.66 Dual Wing- Rear rear Flame electrode and
mm dia.) thermocouple
adapter
Q179D1016 0.026" dia. (0.66 Dual Wing- Left Side left side 3 1/8 in. high, 3 1/32 in. wide, 1 in. deep.
mm dia.) 79 mm high, 77 mm wide, 25 mm deep
Q179D1024 Dual Wing- Right Side right side
Q179D1057 0.024" dia. (0.60 Single Wing- Left Side left side
mm dia.)
Q179D1925 0.016" dia. (0.40 Dual Wing- Rear rear 3 1/8 in. high, 2 7/16 in. wide, 1 in. deep.
mm dia.) 79 mm high, 62 mm wide, 25 mm deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 82
Pilot Burners—Parts
ORDER NUMBER Description
104312 Rajah Connector for Flame Electrode, Q179A, B
105066A 45 degree RH ELL Tip Assembly, Q179A, B
105067A 45 degree LH ELL Tip Assembly, Q179A, B
131065 Adapts Q340 Thermal Couple to Q179B w/102462
133444A 45 degree LH ELL Flame Rod & Insulator, Q179A, B
133445A Ignition Electrode & Insulator Assembly, Q179A, B
133446A 45 degree Y Port Flame Rod & Insulator, Q179A, B
133447A Top ELL Flame Rod & Insulator, Q179A, B
133448A I Port Flame Rod & Insulator, Q179A, B
133449A RH 90 degree Flame Rod & Insulator, Q179A, B
133450A 45 degree I Port Flame Rod & Insulator, Q179A, B
133451A T Port or LH 90 degree Flame Rod & Insulator, Q179A, B
133452A 45 degree RH ELL or T Port Flame Rod & Insulator, Q179A, B
133453 Insulator for Q179A, B
388146AF Natural Gas spud orifice, 0.024" dia., Q179C, D
388146KD LP Gas spud orifice, 0.016" dia., Q179C, D
395390-13 LP Gas Orifice 0.013" dia. for Q179A, B
395390-25 Natural Gas Orifice 0.025" dia. for Q179A, B
395390-28 Natural Gas Orifice 0.028" dia. for Q179A, B
7617CV Insulator Assembly for C7005A, B, includes electrode insulator and mounting hardware
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
83 70-8911
Modernization and Replacement
For All Modernization and Replacement Applications,
Follow the Instructions Below.
CAUTION
Installer must be a trained, experienced, flame safeguard control service technician.
Disconnect power supply before beginning installation to prevent electrical shock and equipment damage. More than one disconnect may
be involved.
All wiring must comply with applicable local electrical codes, ordinances, and regulations.
Voltage and frequency of the power supply and flame detector(s) connected to this control must agree with those marked on the device.
Loads connected to the control terminals must not exceed those listed in specification sheet for this product.
All external timers must be listed or component recognized by authorities having jurisdiction, for the specific purpose for which they are
used.
Perform all required checkout tests after installation is complete.
INSTALLING AN R4795
2
1 Make simple 3
Disconnect wiring change Install
power sup- in subbase. R4795.
ply and
remove
RA890.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 84
Modernization and Replacement
4 5
Plug in Plug in
ST71A R7289/R7290
purge timer. amplifier
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 86
Pressure Control and Limit—Flow Limit Switch
L4049 Flow Limit Switch
• L4049A NEMA 1 enclosure model.
• L4049B NEMA 4 enclosure model.
• Flow paddles (1 in. to 8 in. pipe diameters).
• One SPDT line voltage switch.
• Two SPDT line voltage switches.
Application: Control of liquid flow lines (non-hazardous fluids)
Approvals, Canadian Standards Association: Listed: File No. LR 84611-3
and LR84611-7
Approvals, European Community: EN 60 947-5-1
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MH26193,
The L4049A,B Flow Limit Switches are used in liquid flow lines Guide Nos. NKPZ and MFHZ
carrying water or any fluid not harmful to brass, stainless steel or Description: Flow Limit Switch
silicone and not classified as a hazardous fluid. Typical Includes: NEMA 4 Enclosure
applications include secondary limits for low mass boilers and Maximum flow rate: 410 gpm
chillers; actuator for signal lights, process controls monitoring Minimum flow rate: 3.5 gpm
fluid flow, and to start pumps or compressors in sequence in Mounting: 1 in. NPT internal thread
cooling water systems and control of chemical feed systems. Piping Connections, Main or High Pressure: 1 in. NPT external
• Use with water or any fluid not harmful to brass, stainless steel or Switch Contact Ratings: 120V: 3.8 AFL, 22.8 ALR, 125 VA pilot duty,
silicone and not classified as a hazardous fluid. 1/8 horsepower;
• Flow-activated secondary safety-limit switch. 240V: 2.9 AFL, 17.4 ALR, 125 VA pilot duty, 1/4 horsepower
• Can be wired to stop a process or turn on an alarm. Temperature Ratings: 32 F to 176 F; 0 C to 80 C
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
87 70-8911
Pressure Control and Limit—Pressure Switch
Maximum
Sustained
Switching Switch Operating Pressure Differential
ORDER NUMBER Action Operating Range Operation Switch Contact Ratings Pressure Differential Type
C437D1005 SPST, 1 in. w.c. to 26 in. w.c. Manual 1.2 AFL, 12.0 ALR, 2.0 A resistive 5.0 psi 1 3/4 in. w.c. Subtractive
break on 0.5 kPa to 7.0 kPa Reset, 2.4 AFL, 24.0 ALR, 5.0 A resistive 34.5 kPa 0.44 kPa
rise lockout on 5.1 AFL, 30.6 ALR, 5.0 A resistive
C437D1013 1/2 psi to 5 psi 15.0 psi 1/2 psi
rise 8.0 AFL, 48.0 ALR, 10.0 A
3.0 kPa to 35.0 kPa 103.4 kPa 3.45 kPa
resistive
C437D1021 1 psi to 10 psi 30.0 psi 1 psi
5.0 kPa to 70.0 kPa 206.8 kPa 6.89 kPa
C437E1004 SPST, 1 in. w.c. to 26 in. w.c. Manual 5.0 psi 0.31 kPa Additive
break on 0.5 kPa to 7.0 kPa Reset, 34.5 kPa 1 1/4 in. w.c.
C437E1012 fall 1/2 psi to 5 psi lockout on 15.0 psi 1/4 psi
3.0 kPa to 35.0 kPa fall 103.4 kPa 1.72 kPa
C437E1020 1 psi to 10 psi 30.0 psi 1/2 psi
5.0 kPa to 70.0 kPa 206.8 kPa 3.45 kPa
C437E1038 1/2 in. w.c. to 5 1/2 in. 20.7 kPa 0.25 in. w.c.
w.c. 3.0 psi 0.06 kPa
0.1 kPa to 1.4 kPa
C437F1003 SPST 1 in. w.c. to 26 in. w.c. Auto 1.0 AFL, 10.0 ALR, 4.0 A resistive 5.0 psi 1 1/4 in. w.c.
(two), 0.5 kPa to 7.0 kPa recycle 2.0 AFL, 20.0 ALR, 8.0 A resistive 34.5 kPa 0.31 kPa
break one 5.1 AFL, 30.6 ALR, 5.0 A resistive
C437F1011 1/2 psi to 5 psi 15.0 psi 1/4 psi
and make 8.0 AFL, 48.0 ALR, 10.0 A
3.0 kPa to 35.0 kPa 103.4 kPa 1.72 kPa
one resistive
C437F1029 1 psi to 10 psi 30.0 psi 1/2 psi
5.0 kPa to 70.0 kPa 206.8 kPa 3.45 kPa
C437F1037 1/2 in. w.c. to 5 1/2 in. 20.7 kPa 0.25 in. w.c.
w.c. 3.0 psi 0.06 kPa
0.1 kPa to 1.4 kPa
C437F1045a 1 in. w.c. to 26 in. w.c. 5.0 psi 1 1/4 in. w.c.
0.5 kPa to 7.0 kPa 34.5 kPa 0.31 kPa
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 88
Pressure Control and Limit—Pressure Switch
C6097 Pressure Switch
• 1/4 in. NPT or flange mount models for direct mounting to
Honeywell Integrated Valve Train.
• Optional switch position indicator lamp available.
• IP54 enclosure standard.
• Ranges: 0.4 to 5 in.wc, 3 to 21 in.wc, 12 to 60 in.wc or 1.5 to 7 psi.
• Surge orifice.
Alternate Ratings: Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main
Valve: 400 VA with 2-1/2 times inrush
Application: Safety devices used in positive-pressure or differential-
pressure systems to sense gas or air pressure changes
The C6097 Pressure Switches are safety devices used in positive- Approvals, Canadian Standards Association: Certified 158158-1084772
pressure or differential-pressure systems to sense gas or air Approvals, Factory Mutual: Approved; J.I. 2D4A1.AF
pressure systems. Approvals, Industrial Risk Insurers: Acceptable
Approvals, CSD-1 AFB: Acceptable
• For use with natural gas, liquid propane (LP) gas, or air. Approvals, Underwriters Laboratories, Inc.: Listed MP2168
• Diaphragm-actuated safety-limit switch. Differential Type: C6097A—Additive
• Switch can be wired to turn on alarm. C6097B—Subtractive
• C6097A models break control circuit at setpoint on pressure fall. Piping Connections, Electrical: 27/32 in. (22 mm) hole
• C6097B models break control circuit at setpoint on pressure rise. Piping Connections, Vent or Low pressure: 1/8 in. NPT internal thread
• Lockout with manual reset and recycle options. Switch Contact Ratings: 3.0 AFL, 18.0 ALR, 5.0 A resistive
• Lockout models have external manual reset button. Switching Action: C6097A—Break N.O. to C. on pressure fall
• Removable transparent cover protects scaleplate and adjusting C6097B—Break N.C. to C. on pressure rise.
knob. Temperature Ratings:-40 F to 140 F; -40 C to 60 C
• Pipe tappings allow selection of positive pressure (air only) or
venting connections (NPT mount only).
Switch
ORDER NUMBER Mounting Operating Range Operation Pressure Differential Dimensions
C6097A1004 1/4 in. NPT 0.4 in. w.c. to 5 in. Auto recycle nominal: 0.16 in. w.c.; 3 3/16 in. high, 2 23/32 in. wide,
internal thread w.c. maximum: 0.24 in. w.c. 2 23/32 in. deep.
0.10 kPa to 1.25 kPa nominal: 0.04 kPa; maximum: 81 mm high, 69 mm wide, 69 mm
0.06 kPa deep
C6097A1012 3 in. w.c. to 21 in. w.c. Manual Reset max. 2.4 in. w.c. @ min. 3 17/32 in. high, 2 23/32 in. wide,
0.7 kPa to 5.2 kPa setpoint; 2 23/32 in. deep.
max. 4.2 in. w.c. @ max. 90 mm high, 69 mm wide, 69 mm
setpoint: deep
max. 0.60 kPa @ min. setpoint;
C6097A1020 Flange Mount max. 1.05 kPa @ max. setpoint: 2 19/32 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
66 mm high, 69 mm wide, 69 mm
deep
C6097A1038 1/4 in. NPT 12 in. w.c. to 60 in. max. 10 in. w.c. @ min. setpoint; 3 17/32 in. high, 2 23/32 in. wide,
internal thread w.c. max. 12 in. w.c. @ max. 2 23/32 in. deep.
3.0 kPa to 15 kPa setpoint: 90 mm high, 69 mm wide, 69 mm
max. 2.5 kPa @ min. setpoint; deep
max. 3.0 kPa @ max. setpoint:
C6097A1046 Flange Mount 2 19/32 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
66 mm high, 69 mm wide, 69 mm
deep
C6097A1053 1/4 in. NPT 3 in. w.c. to 21 in. w.c. Auto recycle nominal: 0.06 kPa; maximum: 3 3/16 in. high, 2 23/32 in. wide,
internal thread 0.7 kPa to 5.2 kPa 0.12 kPa 2 23/32 in. deep.
nominal: 0.24 in. w.c.; 81 mm high, 69 mm wide, 69 mm
maximum: 0.48 in. w.c. deep
C6097A1061 Flange Mount 2 1/4 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
57 mm high, 69 mm wide, 69 mm
deep
C6097A1079 1/4 in. NPT 12 in. w.c. to 60 in. nominal: 1.1 in. w.c.; maximum: 3 3/16 in. high, 2 23/32 in. wide,
internal thread w.c. 2.4 in. w.c. 2 23/32 in. deep.
3.0 kPa to 15 kPa nominal: 0.27 kPa; maximum: 81 mm high, 69 mm wide, 69 mm
0.60 kPa deep
C6097A1087 Flange Mount 2 1/4 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
57 mm high, 69 mm wide, 69 mm
deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
89 70-8911
Pressure Control and Limit—Pressure Switch
Switch
ORDER NUMBER Mounting Operating Range Operation Pressure Differential Dimensions
C6097A1095 1/4 in. NPT 0.4 in. w.c. to 5 in. Manual Reset max. 0.6 in. w.c. @ min. 3 17/32 in. high, 2 23/32 in. wide,
internal thread w.c. setpoint; 2 23/32 in. deep.
0.10 kPa to 1.25 kPa max. 0.25 in. w.c. @ max. 90 mm high, 69 mm wide, 69 mm
setpoint deep
max. 0.15 kPa @ min. setpoint;
max. 0.25 kPa @ max. setpoint
C6097A1103 Flange Mount 1.5 psi to 7 psi max. 1.1 in. w.c. @ min. 2 19/32 in. high, 2 23/32 in. wide,
10.3 kPa to 48 kPa setpoint; 2 23/32 in. deep.
max. 1.4 in. w.c. @ max. 66 mm high, 69 mm wide, 69 mm
setpoint deep
max. 7.6 kPa @ min. setpoint;
C6097A1111 1/4 in. NPT 3 17/32 in. high, 2 23/32 in. wide,
max. 9.6 kPa @ max. setpoint
internal thread 2 23/32 in. deep.
90 mm high, 69 mm wide, 69 mm
deep
C6097A1129 Flange Mount Auto recycle nominal: 0.1 psi; 2 1/4 in. high, 2 23/32 in. wide,
maximum: 0.3 psi 2 23/32 in. deep.
nominal: 0.69 kPa; maximum: 57 mm high, 69 mm wide, 69 mm
2.07 kPa deep
C6097A1137 1/4 in. NPT 3 3/16 in. high, 2 23/32 in. wide,
internal thread 2 23/32 in. deep.
81 mm high, 69 mm wide, 69 mm
deep
C6097A1210 Flange Mount 0.4 in. w.c. to 5 in. nominal: 0.16 in. w.c.; 2 1/4 in. high, 2 23/32 in. wide,
w.c. maximum: 0.24 in. w.c. 2 23/32 in. deep.
0.10 kPa to 1.25 kPa nominal: 0.04 kPa; maximum: 57 mm high, 69 mm wide, 69 mm
0.06 kPa deep
C6097A1228 Manual Reset 2 19/32 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
66 mm high, 69 mm wide, 69 mm
deep
C6097B1002 1/4 in. NPT 12 in. w.c. to 60 in. max. 2.5 kPa @ min. setpoint; 3 17/32 in. high, 2 23/32 in. wide,
internal thread w.c. max. 3.0 kPa @ max. setpoint: 2 23/32 in. deep.
3.0 kPa to 15 kPa max. 10 in. w.c. @ min. setpoint; 90 mm high, 69 mm wide, 69 mm
max. 12 in. w.c. @ max. deep
setpoint:
C6097B1010 Flange Mount 2 19/32 in. high, 2 23/32 in. wide,
2 23/32 in. deep.
66 mm high, 69 mm wide, 69 mm
deep
C6097B1028 1/4 in. NPT 3 in. w.c. to 21 in. w.c. Manual Reset max. 2.4 in. w.c. @ min. 3 17/32 in. high, 2 23/32 in. wide, 2
internal thread 0.7 kPa to 5.2 kPa setpoint; 23/32 in. deep.
max. 4.2 in. w.c. @ max. 90 mm high, 69 mm wide, 69 mm
setpoint: deep
max. 0.60 kPa @ min. setpoint;
C6097B1036 Flange Mount max. 1.05 kPa @ max. setpoint: 2 19/32 in. high, 2 23/32 in. wide, 2
23/32 in. deep.
C6097B1044 Flange Mount 1.5 psi to 7 psi max. 1.1 in. w.c. @ min. 66 mm high, 69 mm wide, 69 mm
10.3 kPa to 48 kPa setpoint; deep
max. 1.4 in. w.c. @ max.
C6097B1051 1/4 in. NPT setpoint 3 3/16 in. high, 2 23/32 in. wide, 2
internal thread max. 7.6 kPa @ min. setpoint; 23/32 in. deep.
81 mm high, 69 mm wide, 69 mm
max. 9.6 kPa @ max. setpoint deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 90
Pressure Control and Limit—Pressure Switch
Switch
ORDER NUMBER Mounting Operating Range Operation Pressure Differential Dimensions
C6097B1069 Flange Mount 3 in. w.c. to 21 in. w.c. Auto recycle nominal: 0.24 in. w.c.; 2 1/4 in. high, 2 23/32 in. wide, 2
0.7 kPa to 5.2 kPa maximum: 0.48 in. w.c. 23/32 in. deep.
nominal: 0.06 kPa; maximum: 57 mm high, 69 mm wide, 69 mm
0.12 kPa deep
C6097B1077 Flange Mount 12 in. w.c. to 60 in. nominal: 1.1 in. w.c.; maximum:
w.c. 2.4 in. w.c.
C6097B1085 1/4 in. NPT 3.0 kPa to 15 kPa 3 3/16 in. high, 2 23/32 in. wide, 2
nominal: 0.27 kPa; maximum: 23/32 in. deep.
internal thread
0.60 kPa 81 mm high, 69 mm wide, 69 mm
deep
C6097B1093 Flange Mount 1.5 psi to 7 psi nominal: 0.1 psi; 2 1/4 in. high, 2 23/32 in. wide, 2
10.3 kPa to 48 kPa maximum: 0.3 psi 23/32 in. deep.
nominal: 0.69 kPa; maximum: 57 mm high, 69 mm wide, 69 mm
2.07 kPa deep
C6097B1101 1/4 in. NPT 3 3/16 in. high, 2 23/32 in. wide, 2
internal thread 23/32 in. deep.
81 mm high, 69 mm wide, 69 mm
C6097B1119 1/4 in. NPT 3 in. w.c. to 21 in. w.c. nominal: 0.24 in. w.c.; deep
internal thread 0.7 kPa to 5.2 kPa maximum: 0.48 in. w.c.
nominal: 0.06 kPa; maximum:
0.12 kPa
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
91 70-8911
Pressure Control and Limit—Pressure Switch
C645A,B Gas/Air Pressure Switches; C645C,D Air Pressure
Switches; C645E Distillate Fuel Oil Pressure Switch
Approvals, CSA: Certified: File No. LR1620, Guide No. 140-A-2
Approvals, Factory Mutual: Approved: Report Nos. 19268, 13233-S3
Approvals, Industrial Risk Insurers: Acceptable
Approvals, UL, Inc.: Listed: File No. MP2168, Guide No. MFHX
Mounting: 1/4 in. NPT internal thread
Piping Connections, Main or High Pressure: 1/4 in. NPT internal thread
Piping Connections, Vent or Low pressure: 1/8 in. NPT internal thread
Pressure Sensing Element: BUNA N Diaphragm
Switching Action;
C645A—SPDT break on pressure fall
C645B—SPDT make on pressure rise
C645C,D—SPDT break on pressure fall
Switch Contact Ratings:
C645A,B—3.7 AFL, 22.2 ALR, 7.4 AFL, 44.4 ALR
C645C—5.1 AFL, 30.6 ALR; 8.0 AFL, 48.0 ALR
C645D—3.7 AFL, 22.2 ALR; 7.4 AFL, 44.4 ALR
Positive or differential limit controls. Maximum Sustained Operating Pressure:
• SPDT diaphragm operated snap-acting Micro-Switch ™ C645A,B—5.0 psi; 34.5 kPa
mechanism. C645C—1.5 psi; 10.3 kPa
• C645E models for use with only distillate fuel; not with natural or C645D—5.0 psi; 34.5 kPa
LP gases. Temperature Ratings: -20 F to 125 F; -29 C to 52 C
Alternate Ratings: Ignition Transformer: 540 VA, Pilot Valve: 50 VA. Main Accessories: 112657A-C645 Mounting Bracket Assembly
Valve: 250 VA with 10 times inrush, 400 VA with 2-1/2 times inrush 137637B-Cover with Window - C645A.
Application: Safety devices used in. positive-pressure or differential- 137637C-Cover with Window - C645B.
pressure systems to sense gas or air pressure changes 15865AC-Mounting Bracket Assembly - C645A, B, D.
Pressure Differential
Switch
ORDER NUMBER Operating Range Operation Nominal Maximum Dimensions Includes
C645A1006 3 in. w.c. to 21 in. w.c. Auto recycle 1.0 in. w.c.; 3.0 in. w.c; 4 3/4 in. diameter, —
0.7 kPa to 5.2 kPa 0.2 kPa 0.7 kPa 3 1/2 in. deep.
C645A1022 121 mm diameter, Switch position indicator and
89 mm deep cover window
C645A1030 Manual
C645A1055 5 in. w.c. to 35 in. w.c. Reset 4.0 in. w.c;
1.2 kPa to 8.7 kPa 1.0 kPa
C645A1063 Auto recycle Does not include cover or window
C645A1097 3 in. w.c. to 21 in. w.c. 3.0 in. w.c.; —
0.7 kPa to 5.2 kPa 0.7 kPa
C645A1105 Manual Switch position indicator and
Reset cover window
C645A2004 Auto recycle Switch position indicator, cover
window, and meet ANSI mis-
wiring requirements
C645B1013 Manual Switch position indicator and
C645B1039 5 in. w.c. to 35 in. w.c. Reset 1.0 in. w.c.; 4.0 in. w.c.; cover window
1.2 kPa to 8.7 kPa 0.2 kPa 1.0 kPa
C645B1047a 3 in. w.c. to 21 in. w.c. 3.0 in. w.c.
0.7 kPa to 5.2 kPa 0.7 kPa
C645B2003 Position indicator, cover window,
and meet ANSI mis-wiring
requirements
C645C1004 0.6 in. w.c. to 5.3 in. w.c. Auto recycle 0.2 in. w.c.; 0.8 in. w.c.; 7 7/8 in. diameter., Cover Window
0.15 kPa to 1.3 kPa 0.05 kPa 0.2 kPa 3 1/2 in. deep.
C645C1020 200 mm diameter, Switch position indicator. Does
898 mm deep not include window
C645C1038 Manual
Reset
C645D1029 3 in. w.c. to 21 in. w.c. Auto recycle 1.0 in. w.c.; 3.0 in. w.c.; 4 3/4 in. diameter, Does not include window.
0.7 kPa to 5.2 kPa 0.2 kPa 0.7 kPa 3 1/2 in. deep.
121 mm diameter,
C645D1052 2.0 in. w.c. to 20.0 in. w.c. 89 mm deep
0.5 kPa to 5.0 kPa
C645E1002b 3 in. w.c. to 21 in. w.c.
0.7 kPa to 5.2 kPa
a
With scaleplate setpoint stop set at 5 1/4 in. (133.4 mm) w.c. Meets A.G.A. high gas pressure switch requirements for burners with inputs greater
than 2.5 million Btuh.
b
Used with distillate fuel oil, cannot be used for natural or LP gases.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 92
Pressure Control and Limit—Pressuretrol® Controllers
L404A,B,C,D,F; L604 Pressuretrol® Controllers
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 400E-O
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP466,
Guide No. MBPR
Differential Type: Subtractive
Mounting: 1/4 in. NPT internal thread or surface mount through back of
case
Piping Connections, Main or High Pressure: 1/4 in. NPT internal thread
Provide operating control, automatic or manual reset limit Switch Operation: L404A,B,C,F; L604A,N—Auto recycle
protection for pressure systems up to 300 psi (2068 kPa). L404C,D; L604L—Manual Reset
• Use with steam, air, noncombustible gases, or other fluids Switch Contact Ratings: L404A,B,C,D; L604A,L—120 Vdc: 2.4 AFL,
noncorrosive to pressure sensing element. 24.0 ALR, 5.0 A resistive; 240 Vdc: 1.2 AFL, 12.0 ALR, 2.0 A
• Provide dust-proof, trouble-free mercury switching; L404F has resistive;120 Vac: 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac: 5.1
snap-acting switching. AFL, 30.6 ALR, 5.0 A resistive
• Trip-free mechanism on manual reset models so the limit function L404F—120 Vac: 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac: 5.1 AFL,
of the controller cannot be defeated by jamming the reset lever. 30.6 ALR, 5.0 A resistive
• Adjustments are made by screws on top of case. L604N—120 Vac: 8.0 AFL, 48.0 ALR, 10.0 A resistive; 240 Vac: 5.1
• Mount using 1/4 in. NPT female threads or surface mount through AFL, 30.6 ALR, 8.0 AFL, 48.0 ALR
base of case. Temperature Ratings: -35 F to 150 F; -37 C to 66 C
Application: Provide control of steam, air, non-combustible gases or non- Accessories: 33312B-Pressure Control/Limits, Knurled Adjustment
corrosive fluids knob-with set screw.
4074BWJ-Pressure Control/Limits, Limit Stop Assembly
14026 - Siphon Loop
Maximum
Sustained Pressure
Switching Operating Pressure Sensing
ORDER NUMBER Action Operating Range Pressure Differential Dimensions Element
L404A1354 SPST break 2 psi - 15 psi 25 psi 2 psi - 6 psi 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep. Stainless
on pressure 14 kPa - 103 kPa 172 kPa 14 kPa - 41 kPa 123 mm high, 114 mm wide, 83 mm deep steel
L404A1370 rise 5 psi - 50 psi 85 psi 4 psi - 12 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep. diaphragm
35 kPa - 345 kPa 586 kPa 28 kPa - 83 kPa 126 mm high; 114 mm wide; 70 mm deep
L404A1396 10 psi - 150 psi 225 psi 8 psi - 16 psi
69 kPa - 1034 kPa 1551 kPa 55 kPa - 110 kPa
L404A1404a 20 psi - 300 psi 350 psi 15 psi - 40 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
138 kPa - 2068 kPa 2413 kPa 103 kPa - 276 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
L404A1636 2 psi - 15 psi 25 psi 1 psi - 6 psi 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep. Stainless
14 kPa - 103 kPa 172 kPa 7 kPa - 41 kPa 123 mm high, 114 mm wide, 83 mm deep steel
L404B1296a SPST make
diaphragm
on pressure
L404B1304 rise 2 psi - 6 psi
14 kPa - 41 kPa
L404B1320 5 psi - 50 psi 85 psi 4 psi - 12 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep.
35 kPa - 345 kPa 586 kPa 28 kPa - 83 kPa 126 mm high; 114 mm wide; 70 mm deep
L404B1346 10 psi - 150 psi 225 psi 8 psi - 16 psi
69 kPa - 1034 kPa 1551 kPa 55 kPa - 110 kPa
L404B1353 20 psi - 300 psi 350 psi 15 psi - 40 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
138 kPa - 2068 kPa 2413 kPa 103 kPa - 276 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
L404B1361 2 psi - 15 psi 25 psi 1 psi - 6 psi 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep. Stainless
14 kPa - 103 kPa 172 kPa 7 kPa - 41 kPa 123 mm high, 114 mm wide, 83 mm deep steel
L404B1577
diaphragm
L404C1113a SPST break 5 psi - 50 psi 85 psi Manual Reset 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep.
on pressure 35 kPa - 345 kPa 586 kPa 126 mm high; 114 mm wide; 70 mm deep
rise 20 psi - 300 psi 350 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
L404C1139a
138 kPa - 2068 kPa 2413 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
a Includes Siphon Loop
b
Includes BSPT ground screw and European Enclosure
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
93 70-8911
Pressure Control and Limit—Pressuretrol® Controllers
Maximum
Sustained Pressure
Switching Operating Pressure Sensing
ORDER NUMBER Action Operating Range Pressure Differential Dimensions Element
L404C1147 SPST break 2 psi - 15 psi 25 psi Manual Reset 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep. Stainless
on pressure 14 kPa - 103 kPa 172 kPa 123 mm high, 114 mm wide, 83 mm deep steel
L404C1154 rise 5 psi - 50 psi 85 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep. diaphragm
35 kPa - 345 kPa 586 kPa 126 mm high; 114 mm wide; 70 mm deep
L404C1162 10 psi - 150 psi 225 psi
69 kPa - 1034 kPa 1551 kPa
L404D1088a SPST make 2 psi - 15 psi 50 psi
on pressure 14 kPa - 103 kPa 345 kPa
rise 10 psi - 150 psi 225 psi
L404D1096a
69 kPa - 1034 kPa 1551 kPa
L404F1060a SPDT snap 2 psi - 15 psi 25 psi 2 psi - 6 psi
action, 14 kPa - 103 kPa 172 kPa 14 kPa - 41 kPa
make R-W, 5 psi - 50 psi 85 psi 6 psi - 14 psi
L404F1078a break R-B 35 kPa - 345 kPa 586 kPa 41 kPa - 97 kPa
on pressure
L404F1094a rise 20 psi - 300 psi 350 psi 20 psi - 50 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
138 kPa - 2068 kPa 2413 kPa 138 kPa - 345 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
L404F1102 10 psi - 150 psi 225 psi 10 psi - 22 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Stainless
69 kPa - 1034 kPa 1551 kPa 60 kPa - 152 kPa 126 mm high; 114 mm wide; 70 mm deep steel
L404F1227b diaphragm
L404F1235b 20 psi - 300 psi 350 psi 20 psi - 50 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
138 kPa - 2068 kPa 2413 kPa 138 kPa - 345 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
L404F1243b 5 psi - 50 psi 85 psi 6 psi - 14 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Stainless
35 kPa - 345 kPa 586 kPa 41 kPa - 97 kPa 126 mm high; 114 mm wide; 70 mm deep steel
60 psi - 180 psi 225 psi 6 psi diaphragm
L404F1300b
1151 kPa 41 kPa
L604A1169a Isolated 2 psi - 15 psi 25 psi 2 psi - 6 psi 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep.
SPST (two) 14 kPa - 103 kPa 172 kPa 14 kPa - 41 kPa 123 mm high, 114 mm wide, 83 mm deep
make R1-W 5 psi - 50 psi 85 psi 4 psi - 12 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep.
L604A1177a Break R2-B 35 kPa - 345 kPa 586 kPa 28 kPa - 83 kPa 126 mm high; 114 mm wide; 70 mm deep
on pressure
L604A1185a rise 10 psi - 150 psi 225 psi 8 psi - 16 psi
69 kPa - 1034 kPa 1551 kPa 55 kPa - 110 kPa
L604A1193a 20 psi - 300 psi 350 psi 15 psi - 40 psi 5 3/4 in. high, 4 1/2 in. wide, 2 3/4 in. deep. Phos-
138 kPa - 2068 kPa 2413 kPa 103 kPa - 276 kPa 146 mm high, 114 mm wide, 70 mm deep bronze
bellows
L604A1219 2 psi - 15 psi 25 psi 1 psi - 6 psi 4 27/32 in. high, 4 1/2 in. wide, 3 1/4 in. deep. Stainless
14 kPa - 103 kPa 172 kPa 7 kPa - 41 kPa 123 mm high, 114 mm wide, 83 mm deep steel
SPDT make Manual Reset diaphragm
L604L1035a
R-W, break
R-B on
pressure
rise
L604N1009a SPDT (two) 10 psi - 150 psi 225 psi 7 psi 4 31/32 in. high, 4 1/2 in. wide, 2 3/4 in. deep.
break R-B 69 kPa - 1034 kPa 1551 kPa 48.2 kPa 126 mm high; 114 mm wide; 70 mm deep
simultaneou
sly
a
Includes Siphon Loop
b Includes BSPT ground screw and European Enclosure
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 94
Pressure Control and Limit—Pressuretrol® Controllers
L404T,V,W,Y Pressuretrol® Limit Controllers
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 400E-O
Approvals, Factory Mutual: Approved: Report No. 26036
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP2168,
Guide No. MFHX
Differential Type: Subtractive
Includes: Siphon Loop
Mounting: 1/4 in. NPT internal thread or surface mount through back of
Oil pressure sensing devices for use on oil burner systems using case
any type of fuel oil, including heavy pretreated oils. Piping Connections, Main or High Pressure: 1/4 in. NPT internal thread
Pressure Sensing Element: Stainless steel diaphragm
• Provide dustproof, trouble-free mercury switching.
Switch Contact Ratings: 1.2 AFL, 12.0 ALR, 2.0 A resistive; 2.4 AFL,
• Clear plastic cover allows observation of the pressure settings
24.0 ALR, 5.0 A resistive; 5.1 AFL, 30.6 ALR, 5.0 A resistive; 8.0
and switch action.
AFL, 48.0 ALR, 10.0 A resistive
• Siphon loop provides thermal buffer to diaphragm.
Temperature Ratings: -35 F to 150 F; -37 C to 66 C
• Trip-free mechanism on manual reset models so the limit function
Accessories: 33312B-Pressure Control/Limits, Knurled Adjustment
of the controller cannot be defeated by jamming the reset lever.
knob-with set screw.
• Adjustments are made by screws on top of case (under a
4074BWJ-Pressure Control/Limits, Limit Stop Assembly
protective cover).
• Mount using 1/4 in. NPT female threads or surface mount through
base of case.
Maximum
Sustained
Switching Switch Operating Pressure
ORDER NUMBER Application Action Operating Range Operation Pressure Differential Dimensions
L404T1022 High oil SPST break 10 psi to 50 psi Auto recycle 85 psi 4 psi to 8 psi 4 31/32 in. high,
pressure limit on pressure 69 kPa to 345 kPa 586 kPa 28 kPa to 55 kPa 4 1/2 in. wide,
switch rise 2 3/4 in. deep.
L404T1030 25 psi to 150 psi 225 psi 8 psi to 16 psi 126 mm high;
172 kPa to 1034 kPa 1551 kPa 50 kPa to 110 kPa 114 mm wide;
L404V1046 Operating SPST make 8 psi to 16 psi 70 mm deep
control and on pressure 50 kPa to 110 kPa
L404V1053 low oil rise 10 psi to 50 psi 85 psi 4 psi to 8 psi
pressure limit 69 kPa to 345 kPa 586 kPa 28 kPa to 55 kPa
L404W1037 High oil SPST break 25 psi to 150 psi Manual Reset 225 psi 8 psi 5 1/2 in. high;
pressure limit on pressure 172 kPa to 1034 kPa 1551 kPa 55 kPa 4 1/2 in. wide;
switch rise 2 3/4 in. deep.
140 mm high;
L404Y1043 Operating SPST make 114 mm wide;
control and on pressure 70 mm deep
low oil fall
pressure limit
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
95 70-8911
Pressure Control and Limit—Pressuretrol® Controllers
L91 Proportional Pressuretrol® Controllers
chemically harmful to phos-bronze bellows (10-300 psi models) or
brass bellows (all other pressure range models).
• 14026 Siphon Loop included with the models for 10 to 300 psi (69
to 2068 kPa)
Application: Modulating pressure control for regulation of liquid, air, or
other non-corrosive gases.
Description: Pressuretrol™ Controllers
Includes: Siphon Loop
Modulating pressure operating control for regulation of liquid or air Mounting: optional surface mount through back of case
and other non-corrosive gases. Piping Connections, Electrical: Internal screw terminals. Knockout for
1/2 in. conduit.
• Use with steam, air, noncombustible gases, or other fluids non- Switch Operation: Modulating
corrosive to the brass or phos-bronze (300 psi models) bellows. Temperature Ratings: 32 F to 150 F; 0 C to 66 C
Do NOT use with combustible mediums or any medium Modulating Output: Single potentiometer, 140 ohms
L91D—Dual potentiometer, 140 ohms
Piping Maximum
Pressure Connections, Sustained
Sensing Main or High Operating Pressure
ORDER NUMBER Element Operating Range Pressure Pressure Differential Dimensions
L91A1037 Brass bellows 0 psi to 15 psi 1/4 in. NPT 25 psi 7 oz. 6 7/8 in. high, 4 1/2 in. wide,
0 kPa to 103 kPa external 172 kPa 3.4 kPa 2 7/8 in. deep.
thread 175 mm high, 114 mm wide,
73 mm deep
L91A1052 5 psi to 150 psi 1/4 in. NPT 225 psi 5 psi 5 3/4 in. high, 4 1/2 in. wide,
34 kPa to 1034 kPa internal thread 1551 kPa 34 kPa 2 3/4 in. deep.
146 mm high, 114 mm wide,
70 mm deep
L91A1078 Phos-bronze 10 psi to 300 psi 325 psi 12 psi 6 1/16 in. high, 4 1/2 in. wide,
bellows 69 kPa to 2068 kPa 2241 kPa 83 kPa 2 3/4 in. deep.
L91A1136 154 mm high, 114 mm wide,
70 mm deep
L91B1019 Brass bellows 0 oz/in2 to 16 oz/in2 1/4 in. NPT 6 psi 2 oz/in2 to 38 oz/in2 7 1/32 in. high, 4 7/8 in. wide,
0 kPa to 6.9 kPa external 41 kPa 0.9 kPa to 16.4 kPa 4 7/8 in. deep.
thread 179 mm high, 124 mm wide,
124 mm deep
L91B1035 0 psi to 15 psi 25 psi 1 psi to 12 psi 6 7/8 in. high, 4 1/2 in. wide,
0 kPa to 103 kPa 172 kPa 10 kPa to 83 kPa 2 7/8 in. deep.
175 mm high, 114 mm wide,
73 mm deep
L91B1043 2 psi to 50 psi 1/4 in. NPT 85 psi 4 psi to 32 psi 5 3/4 in. high, 4 1/2 in. wide,
14 kPa to 345 kPa internal thread 586 kPa 34 kPa to 221 kPa 2 3/4 in. deep.
146 mm high, 114 mm wide,
L91B1050 5 psi to 150 psi 225 psi 5 psi to 23 psi 70 mm deep
34 kPa to 1034 kPa 1551 kPa 35 kPa to 160 kPa
L91B1068 Phos-bronze 10 psi to 300 psi 325 psi 28 psi to 110 psi 6 1/16 in. high, 4 1/2 in. wide,
bellows 69 kPa to 2068 kPa 2241 kPa 193 kPa to 758 kPa 2 3/4 in. deep.
154 mm high, 114 mm wide,
L91B1241 10 psi to 300 psi 12 psi to 48 psi 70 mm deep
69 kPa to 2068 kPa 85 kPa to 330 kPa
L91D1015 Brass bellows 0 psi to 15 psi 1/4 in. NPT 25 psi 1 psi to 12 psi 6 7/8 in. high, 4 1/2 in. wide,
0 kPa to 103 kPa external 172 kPa 10 kPa to 83 kPa 2 7/8 in. deep.
thread 175 mm high, 114 mm wide,
73 mm deep
L91D1031 5 psi to 150 psi 1/4 in. NPT 225 psi 11 psi to 52 psi 5 3/4 in. high, 4 1/2 in. wide,
34 kPa to 1034 kPa internal thread 1551 kPa 76 kPa to 359 kPa 2 3/4 in. deep.
146 mm high, 114 mm wide,
70 mm deep
L91D1049 Phos-bronze 10 psi to 300 psi 325 psi 28 psi to 110 psi 6 1/16 in. high, 4 1/2 in. wide,
bellows 69 kPa to 2068 kPa 2241 kPa 193 kPa to 758 kPa 2 3/4 in. deep.
154 mm high, 114 mm wide,
70 mm deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 96
Pressure Control and Limit—Pressuretrol® Controllers
P455 Pressuretrol® Operating Controller
Application: On-off and proportional control of steam boilers fired by
modulating burners
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 360-E-1.16
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. E4436,
Guide No. XAPX
Description: Pressuretrol™ Controllers
Differential Type: Subtractive
Includes: Siphon Loop
Provides both on-off and modulating control of steam boilers.
Modulating Output: 135 ohms
• Modulating portion of the controller operates the burner over 85% Mounting: 1/4 in. NPT internal thread
of the on-off differential. Piping Connections, Electrical: Screw terminals in side-mounted wiring
• On-off portion of the controller shuts the burner off when compartment with 1/2 in. conduit knockouts
pressure rises to main scale set point. Switch Operation: Auto recycle
• Common bellows assembly actuates SPST snap switch (on-off Switching Action: SPST break on pressure rise
operation) and wiper of the 135 ohm potentiometer (modulating Temperature (max. ambient): 125 F; 52 C
operation) Switch Contact Ratings: 5.1 AFL, 30.6 ALR; 8.0 AFL, 48.0 ALR
• Cover encloses differential and unison-sequence adjustments. Accessories: 33312B-Pressure Control/Limits, Knurled Adjustment
• Provides wiring and two conduit connections in. wiring knob-with set screw. Fits head of main adjusting screw to permit
compartments. adjusting without screwdriver.
• Includes steam trap.
Maximum Piping
Sustained Connections,
Operating Pressure Main or High
ORDER NUMBER Operating Range Pressure Differential Pressure Dimensions
P455A1006 0 psi to 15 psi 20 psi; 138 kPa 1.0 psi to 5.5 psi 1/4 in. NPT 7 in. high, 5 1/16 wide, 2 23/32 in. deep.
0 kPa to 103 kPa 7 kPa to 38 kPa external thread 178 mm high, 129 mm wide, 69 deep
P455A1022 5 psi to 150 psi 225 psi; 1550 kPa 7 psi to 20 psi 1/4 in. NPT 7 in. high, 5 1/16 wide, 2 15/32 in. deep.
34 kPa to 1034 kPa 47 kPa to 138 kPa internal thread 178 mm high, 129 mm wide, 63 deep
P455A1030 10 psi to 300 psi 325 psi; 2240 kPa 16 psi to 45 psi 7 19/32 in. high, 5 1/16 wide, 2 15/32 in. deep.
69 kPa to 2068 kPa 110 kPa to 310 kPa 193 mm high, 129 mm wide, 63 deep
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
97 70-8911
Pressure Control and Limit—Pressuretrol® Controllers
P7810 Pressure Control
Approvals, Canadian Standards Association: Certified: File No. LR
95329-6
Approvals, Factory Mutual: Approved: Report No. J.I.2D3A6AF
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP268,
Guide No. MCCZ
Case Material: Plastic
Description: Pressuretrol® Controllers
Frequency: 50/60 Hz
Humidity Ratings: 5% RH to 95% RH, non-condensing
Includes: 4074EVP Door /Wrench
Line voltage pressure controller that provides automatic operating Modulating Output: 4 mA to 20 mA
control, automatic limit protection, manual reset limit protection, or Piping Connections, Electrical: Screw terminals
modulating firing rate control for pressure systems up to 300 psi. Pressure Sensing Element: Stainless steel, solid state sensor
• May be used with steam, air, non-combustible gases or fluids that Switch Contact Ratings: 9.8 AFL, 58.8 ALR, 10.0 A resistive
will not corrode the pressure sensing element. Switching Action: Break on pressure rise
• Models available in 15, 150, 300 psi maximum set points. Voltage: 120 Vac
• LED indicators show limit function lockout. Temperature Ratings: -40 F to 185 F; -40 C to 85 C
• Reset function easily accessible under cover. Dimensions: 5 1/4 in. high, 4 21/32 in. wide, 3 5/8 in. deep;
• Clear cover allows set point and differentials to be read (but not 133 mm high, 119 mm wide, 92 mm deep.
adjusted) without opening the cover. Accessories: 209731A-P7810C, D Siphon Loop
4074EDC-Resistor Kits
4074EWD-P7810 Mounting Bracket and Mounting Screws (6)
Maximum Piping
Sustained Connections,
Operating Pressure Main or High
ORDER NUMBER Application Power Consumption Operating Range Pressure Differential Pressure
P7810C1000 On-off, Modulate and 3.6 W, 4.7 VA @ 50Hz; 0 psi to 15 psi 22.5 psi 2 psi to 10 psi 1/2 in. (13 mm)
Limit Control 3.3 W, 4.0 VA @ 60 Hz 0 kPa to 103 kPa 155 kPa 14 kPa to 69 kPa NPT Internal
P7810C1018 0 psi to 150 psi 225 psi 5 psi to 20 psi Threads
0 kPa to 1034 kPa 1551 kPa 35 kPa to 135 kPa
P7810C1026 0 psi to 300 psi 450 psi 15 psi to 50 psi
0 kPa to 2068 kPa 3103 kPa 103 kPa to 340 kPa
P7810D1008 On-off and Limit 0 psi to 15 psi 22.5 psi 2 psi to 10 psi
Control 0 kPa to 103 kPa 155 kPa 14 kPa to 69 kPa
P7810D1016 0 psi to 150 psi 225 psi 5 psi to 20 psi
0 kPa to 1034 kPa 1551 kPa 35 kPa to 135 kPa
P7810D1024 0 psi to 300 psi 450 psi 15 psi to 50 psi
0 kPa to 2068 kPa 3103 kPa 103 kPa to 340 kPa
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 98
Pressure Control and Limit—Vaporstat® Controllers
L408; L608 Vaporized Controllers
Application: Provide operating control and automatic limit protection for
pressure systems with pressures up to 4 psi (8 kPa)
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 400E-O
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP466,
Guide No. MBPR
Description: Vaporstat™ Controllers
Differential Type: Subtractive
Includes: Siphon Loop
Provide operating control and automatic high limit protection for
Mounting: 1/4 in. NPT internal thread or surface mount through back of
vapor heating systems with pressures up to 4 psi (8 kPa)
case
• Stainless steel diaphragm for use with liquids, air, Piping Connections, Main or High Pressure: 1/4 in. NPT internal thread
noncombustible gases, ammonia, oxygen, distilled water and Pressure Sensing Element: Stainless steel diaphragm
similar media. Switch Operation: Auto recycle
• Provide dustproof, trouble-free mercury switching. Pressure Differential: 4 oz/in2 to 16 oz/in2;1.7 kPa to 6.9 kPa
• Clear plastic cover allows observation of the pressure settings, Temperature Ratings: -35 F to 150 F; -37 C to 66 C
leveling indicator and switch action. Dimensions: 5 1/8 in. high, 4 1/2 in. wide, 4 1/2 in. deep;
• Include 14026 Siphon Loop. 130 mm high, 114 mm wide, 114 mm deep.
• Integral plumb bob for accurate leveling at installation. Accessories: 33312B-Pressure Control/Limits, Knurled Adjustment
• Mount using hexagonal fitting with 1/4 in. NPT internal threads for knob-with set screw.
direct mounting to the 14026 Steam Trap (siphon loop), which is 4074BWJ-Pressure Control/Limits, Limit Stop Assembly
included.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
99 70-8911
Pressure Control and Limit—Vacuumstat® Controllers
L411 Vacuumstat® Controllers
Approvals, Canadian Standards Association: Certified: File No. LR1620,
Guide No. 400E-O
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Listed: File No. MP466,
Guide No. MBPR
Description: Vacuumstat® Controllers
Differential Type: Subtractive
Includes: Siphon Loop
Mounting: 1/4 in. NPT internal thread or surface mount through back of
case
Provide operating or limit control for Vacuum and pressure
Piping Connections, Main or High Pressure: 1/4 in. NPT internal thread
systems.
Pressure Sensing Element: Stainless steel diaphragm
• Use stainless steel diaphragm with steam, air or noncombustible Switch Operation: Auto recycle
fluids not corrosive to stainless steel. Pressure Differential: 2 psi to 30 psi; 13.8 kPa to 206.8 kPa
• Provide dustproof, trouble-free mercury switching. Maximum Sustained Operating Pressure: 85 psi; 586 kPa
• Clear plastic cover allows observation of the pressure settings, Switch Contact Ratings:115 Vdc: 2.4 AFL, 24.0 ALR, 5.0 A resistive; 230
leveling indicator and switch action. Vdc:1.2 AFL, 12.0 ALR, 2.0 A resistive; 120 Vac: 8.0 AFL, 48.0 ALR,
• Include 14026 Siphon Loop. 10.0 A resistive; 240 Vac: 5.1 AFL, 30.6 ALR, 5.0 A resistive
• Integral plumb bob for accurate leveling at installation. Temperature Ratings: -35 F to 150 F; -37 C to 66 C
• Mount using 1/4 NPT female fitting on diaphragm assembly or Dimensions: 5 1/16 in. high, 4 1/2 in. wide, 2 3/4 in. deep;
surface mount through back of case. 129 mm high, 114 mm wide, 70 mm deep.
Application: Provide operating or limit control for Vacuum and pressure Accessories: 33312B-Pressure Control/Limits, Knurled Adjustment
systems. knob-with set screw.
4074BWJ-Pressure Control/Limits, Limit Stop Assembly
Maximum Sustained
ORDER NUMBER Switching Action Operating Range Operating Pressure
L4079A1035 SPST (two) break simultaneously on pressure rise 2 psi to 15 psi; 14 kPa to 103 kPa 25 psi; 172 kPa
L4079A1050 10 psi to 150 psi; 69 kPa to 1034 kPa 225 psi; 1551 kPa
L4079B1033 SPST break on pressure rise 2 psi to 15 psi; 14 kPa to 103 kPa 25 psi; 172 kPa
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 100
Pressure Control and Limit—Parts
Pressure Control and Limit—Parts
ORDER NUMBER Description
106729 C437, C637 Glass Lens, 6" diameter
106747 C437, C637 Lens Retainer manufactured before 1973
112657A C645 Mounting Bracket Assembly. (Includes screws)
122160 Orifice- 0.018 in. for V48, V88 or C437
124674 Orifice- 0.011 in. for V48, V88 or C437
127120A P455 Potentiometer
129178 L404, L604, Plain Thermoplastic Cover, no labels or mounting screw
129178E L404, L604 Cover, Thermoplastic, includes screw and fiber washer
137632 C437, C637 Paper Lens Gasket
137637B Cover with Window - C645A.
137637C Cover with Window - C645B.
139870 C437, C637 Lens Gasket for Rainproof Models
14026 Steam Trap “Siphon Loop” for L404, L604 and L91s
15865AC Mounting Bracket Assembly - C645A, B, D.
23176CB L91 Potentiometer - 135 ohm
23176CF L91 Potentiometer - 135 ohm
23226D L91 Blade Assembly
32003039-001 C6097 Lamp Kit, Position Indication
32003040-001 C6097 Cover, Recycle Model
32003041-001 C6097 Cover, Manual Reset Model
33312B Pressure Control/Limits, Knurled Adjustment knob-with set screw. Fits head of main adjusting screw to permit adjusting
without screwdriver.
4074BVK C7044 Mounting Clamp, includes Machine Screw and Nut
4074BWJ Pressure Control/Limits, Limit Stop Assembly - to limit set point. Includes 129564 Range Stop, 107194 Range Stop Screw and
23466 Wrench.
4074BWK C437, C637 Surface Mounting Bracket and Self-Tapping Screw
4074EVP P7810 Locking Door Wrench
4074EWC P7810 Door Assembly with captive screws and Wrench
4074EWD P7810 Mounting Bracket and Mounting Screws (6)
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
101 70-8911
Primary Control—Flame Amplifier Module
FSP5075A1; FSP5075A3 Flame Amplifier Modules
• Removable cover allows easy access to amplifier, relays and
terminal strip.
• Provide hermetically sealed relays for use in hostile
environments.
Approvals, Factory Mutual: Approved: Report No. 26098
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories, Inc.: Component Recognized:
Use electronic flame detection to provide continuous flame File No. MP268, Guide No. MCCZ
supervision from lightoff to shutdown. Electrical Ratings (power supply): 120 Vac
• Solid state, color-coded, flame signal amplifier plugs into Flame Failure Response Time: Reference flame signal amplifier
FSP5075A1 or FSP5075A3. (Order plug-in amplifiers separately.) Frequency: 60 Hz
• Offer safe start check for a flame when starting burner. Power Consumption: 5.0 W running (max); 2.4 W standby.
• Include safety shutdown feature for loss of flame during run Temperature Ratings: -40 F to +140 F; -40 C to +60 C
period or failure in flame detection system when a self-checking Dimensions: 4 7/8 in. high, 8 1/2 in. wide, 4 in. deep;
system is used. 124 mm high, 216 mm wide, 102 mm deep.
Electrical Ratings
ORDER NUMBER Connections Description (power supply)
R4795A1016 Alarm contacts: male quick connect terminals. 120V 50/60 HZ less Amplifier and Prepurge Timer 120 Vac
R4795A1040 Alarm contacts: male quick connect terminals 220V 50/60 HZ less Amplifier and Prepurge Timer 220 Vac
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 102
Primary Control—Primary Control
R7795 Primary Controls
• Require manual reset after safety switch lockout.
• Field-selectable recycle or lockout on flame failure.
Alarm Relay Switching: 120 Vac Output for Alarm
Application: Provides Flameout Protection plus Automatic control of
Commercial and Industrial Gas and Oil Burners
Approvals, Canadian Standards Association: CSA Certified: Report No.
LR1620-681
Approvals, Factory Mutual: Factory Mutual Approved: J.I.OK389.AF
Approvals, Industrial Risk Insurers: Acceptable
Provide solid state, electronic flame safeguard protection for Approvals, Underwriters Laboratories, Inc.: Component Recognized:
commercial and industrial single or dual fuel burners. File No. MP268, Guide No. MCCZ
Connections: Terminals in Q795 Wiring Subbase
• Include flame signal amplifiers that are color-coded: purple for
Electrical Ratings (power supply): 120 Vac
ultraviolet and green for rectification.
Flame Failure Response Time: 3 sec nominal
• Require a plug-in prepurge timer of 1.5, 7, 10, 30, 60, or 90
Frequency: 50/60 Hz
seconds.
Purging Time: Determined by Plug -in Purge Timer
• Mount on a Q795A1004 (wall mount) or Q795A1012 (cabinet
Safety Switch Timing: Electronic - 10 seconds, Mechanical - 15 seconds
mount) Wiring Subbase with two captive screws.
Temperature Ratings: -40 F to +135 F; -40 C to +57 C
• Include line voltage airflow switch to prove airflow from the start
Dimensions: 5 in. high, 5 in. wide, 5 1/4 in. deep;
of prepurge through the run period.
127 mm high, 127 mm wide, 133.5 mm deep.
• Prevent start-up with lockout if flame or a flame simulating failure
Required Components: ST795 Prepurge Timer and Q795 Wiring
exists.
Subbase
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
103 70-8911
Primary Control—Primary Control
RA890F Protectorelay™ Primary Control
• Includes SPDT alarm contacts.
• Optional alarm circuit indicates safety shutdown.
• Solid state circuitry.
• Mounts and removes easily through use of captive mounting
screws.
• Mounting base is made of strong thermoplastic.
Alarm Relay Switching: SPDT
Application: Either a line or low voltage controller can be used
Primary control provides solid state, electronic flame safeguard Approvals,: AGA Certified for -20 F (-29 C) Certified. No. 20-AL
protection for industrial and commercial single or dual fuel Approvals: CSA Certified: 120V models only; File No. LR1620
burners. Approvals: Factory Mutual Approved: Report Nos. 17678,19417,19784
Approvals: UL Listed: 120V models only; File No. MP268, Guide No.
• Uses rectification principle of electronic flame detection. MCCZ
• Replaces RA890E in low cost applications; Mounts on same Frequency: 50/60 Hz
Q270A1024 Subbase. Temperature Ratings: 50 Hz models -20 F to +105 F, -29 C to +41 C;
• Relights once after flame failure in attempt to re-establish pilot 60 Hz models -20 F to +115 F, -29 C to +46 C
before lockout. Safe-start check prevents start-up if flame- Dimensions: 5 in. high, 5 in. wide, 4 3/4 in. deep (including subbase);
simulating failure occurs in flame detector circuit. 127 mm high, 127 mm wide, 121 mm deep (including subbase)
• Includes built-in protection against ignition crossover in flame
rod systems.
ORDER NUMBER Frequency Electrical Ratings (power supply) Flame Failure Response Time
RA890G1229 50/60 Hz 120 Vac 0.8 sec.
RA890G1245 220 Vac
RA890G1260 120 Vac 3.0 sec.
RA890G1286 240 Vac
RA890G1302 50 Hz 220 Vac
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 104
Primary Control—Subbase, Primary Control
Q270 Wiring Mount Base
ORDER NUMBER Description
Q270A1024 Wiring Mounting Base for RA890, R4795
Primary Control—Parts
ORDER NUMBER Description
106807 Neon Bulb for Q518, Q519
118702E Remote Reset Cover for RA890F, G and R4795, 120V/50-60 Hz
122765 Neon Bulb for remote First out for W688, Q518, Q519
125133A Connecting Cable 6' for remote “first out” indicating light, Q518, Q519
125435 Lamp socket for Remote First Out for W688, Q518, Q519
198365B Remote Reset Cover for Series 2 R7795A-D, (120V/60)
198365C Remote Reset Cover for Series 2 R7795E-H, (120V/60)
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
105 70-8911
Programmers
BC7000 ‘Blue Chip’ Microcomputer Burner Control System
is employed to reduce fuel consumption by optimizing the prepurge
and terminating wasteful blower operation when the system
encounters an inoperative field interlock. This condition can cause
conventional sequencers to permanently stall in an unproductive
purge.
• Universal System Chassis—Minimizes Inventory Investment
Now, through the flexibility of microcomputer technology, a single
control chassis can be universally applied to perform any standard
burner program. Solid state program modules plug in to implement the
Intelligent microcomputer-based integrated control system for required burner sequence of operation, timings and desired features.
automatically fired commercial and industrial single burner The universal BC7000 System chassis allows you to cover the full
applications. Requires a PM720G,L or M Program Module. range of applications, supports standardization and minimizes
inventory investment.
Provides higher levels of protection than conventional flame safeguard
APPROVALS:
programmers to reduce service, maintenance, downtime and energy
Canadian Standards Association Certified: LR1620-520.
costs. Referred to as the Blue Chip because of its computer “chip” tech-
Factory Mutual Approved: Report No. J.I.1F6A1.AF (when used with
nology and its distinctive blue color, the BC7000 System provides a
PM720L Program Module).
return on investment (ROI/Payback): a real Blue Chip investment!
Industrial Risk Insurers Acceptable.
Directly replaces R4150 and R4140 in most applications; mounts
directly on the same Q520A Subbase. Sequences burner motor, firing TEMPERATURE RATINGS:
rate motor (PM720G and L models only), ignition, pilot valve and main Ambient: Wall mounted—32 F to 130 F (0 C to 55 C)
fuel valve(s). Safety shutdown on flame failure (lockout). Ten second Horizontal mounting—32 F to 125 F (0 C to 53 C).
pilot flame establishing period. Flame failure response time: 2-4 sec- Shipping: -30 F to +150 F (-34 C to +66 C).
onds. Lockout switch timing: less than 1 second. ELECTRICAL RATINGS:
FEATURES: Power Supply: 120 Vac (+10, -15%), 50/60 Hz (BC7000).
• Dynamic Self-Check Logic—Provides Major Safety Improvement ACCESSORIES:
A major breakthrough in safety through advanced microcomputer 123514A Flame Simulator for use with R7247A rectification
technology has allowed the extension of the original Honeywell amplifiers.
Dynamic Self Check/Max Safety concept (formerly restricted to the 123514B Flame Simulator for use with R7249A ultraviolet amplifiers.
flame detection circuit) to the basic program logic system. Called 199037B Terminal strip, which adapts 13 and 15 terminal Q520As
Dynamic Self Check Logic, it is a comprehensive family of unique (used with R4150A,B,C) to accept the BC7000 with little or no
safety provisions that continuously monitors the total system wiring changes.
performance to provide the highest degree of safety available. FSP5004 R4150/ R4140/ BC7000 Tester—provides a quick
• Annunciation and Self-Diagnostics—Cut Service Costs “Plug-Instantly” operational check of BC7000 Microcomputer Burner Control
Burner system startup, control, troubleshooting and repair have never System.
been easier, thanks to the BC7000 Microcomputer Burner Control Q520A1089 Subbase (3-sided)—for mounting inside a suitable
System. Integral First-Out Annunciation and Self-Diagnostic functions enclosure, 20 terminals.
reduce service costs and minimize the inconvenience and cost Q520A1121 Subbase (4-sided)—serves as suitable wiring enclosure,
associated with downtime. These important new features are called 20 terminals.
“Plug-Instant” because they are a standard provision of the BC7000 Q520E1002 Service Tool—allows all programmer terminals to be
System—no additional hardware need be purchased, installed or monitored with the programmer operating.
maintained. W136A1045 Test Meter (includes 196146 Meter Connector Plug)—
• Energy Saving Innovations—Reduce Fuel Consumption has SPL position with damping for testing self checking flame
Unnecessary purge-related heat losses are minimized by innovative detection systems.
BC7000 System program logic provisions. Microcomputer intelligence
Available only through Honeywell Authorized Flame Safeguard Distributors.
ORDER NUMBER Use With
BC7000L1000 PM720G, L or M Program Module, R7247, R7248, R7249, R7476 amplifier and matching rectification, infrared, or ultraviolet
flame detector. Mounts on Q520A Mounting Subbase.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 106
Programmer Controls—Program Module
PM720 Programming Module
AirFlow Check: selectable
Approvals, Factory Mutual: Reference BC7000
Comment: Energy Saving Sequence
Early Spark Termination: Yes, 5 sec
Pilot Type: interrupted
PostPurge: 15 sec
Preignition: Yes
Required Components: Works with BC7000
Plug-in Programming Module designed to provide burner program
sequence, timing and features for BC7000 Universal System.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
107 70-8911
Programmer Controls—Programmer
R4140 Automatic Programming Control
Approvals, Canadian Standards Association: Certified File No. LR1620,
Guide Nos.-A-Z
Approvals, Industrial Risk Insurers: Acceptable
Approvals, Underwriters Laboratories Inc.: Component Recognized: File
No. MP269, Guide No. MCCZ2, MCCZ
Approvals, Factory Mutual: R4140G—Approved: Report No. 24180
R4140L—Approved: Report No. 24181
R4140M—Approved: Report No. 24150
Comment: Less Cover
Early Spark Termination: Yes, 5 sec
Provide flameout protection and automatic sequencing for
Flame Establishing Period - Pilot: 10 sec
commercial and industrial single or dual fuel burners.
Frequency: 50/60 Hz
• Directly replace R4150 for most applications; mount on same Humidity Ratings: 85% RH continuous, non-condensing
Q520A Subbase as R4150. Vibration: 0.5G environment
• Provide safety shutdown on flame failure (lockout). Voltage: 120 Vac +10/-15%
• Safe-start check. Weight: 4 lb. 12 oz (2.15 kg)
• Include sequence burner motor, ignition, pilot valve and main fuel Dimensions: 6 5/32 in. high, 7 3/16 in. wide, 5 5/8 in. deep;
valves. 156 mm high, 183 mm wide, 143 mm deep.
AirFlow Check: selectable Accessories: 202051B-Remote Reset Cover (120V/60)
Temperature Flame
Rating Establishing Required
ORDER NUMBER Description (Ambient) Interlocks Preignition PrePurge Pilot Type Period - Main PostPurge Components
R4140G1064 Mechanical -40 F to 150 F Start, No 60 sec intermittent 10 sec 15 sec Q520A Subbase,
Programmer, -40 C to 66 C Running R7247, R7248,
R4140G1171 70 sec interrupted 10 sec 25 sec
Modulating, and Low 30 sec or R7249 Flame
LHL, Proven Fire 60 sec Signal Amplifier
Low Fire
PrePurge
R4140L1089 Mechanical -40 F to 130 F Pre- Yes 60 sec 10 sec 15 sec Q520A1147
Programmer, -40 C to 54 C ignition, 4 sec Subbase, R7247,
Modulating, Lockout, R7248, or R7249
LHL, Proven Low Fire Flame Signal
High and Low and High Amplifier
R4140L1147 Fire PrePurge Fire 10 sec Q520A Subbase,
15 sec R7247, R7248,
30 sec or R7249 Flame
R4140M1038 Mechanical -40 F to 150 F Start and 42 sec. intermittent 10 sec Signal Amplifier
Programmer, -40 C to 66 C Running
R4140M1053 90 sec. 25 sec
On-Off with
Proven Low Fire
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 108
Programmer Controls—Programmer Subbase
Q520 Subbase and Service Tool
Used to test most R4140 Flame Safeguard programming controls
and BC7000 Microcomputer Burner Control Systems. Can also be
used to test some R4150 programming controls. Allows any of the
programmer terminals to be monitored while programmer is
operating.
• Mounts on wiring subbase; programmer mounts on Q520E.
• Includes external terminal box that is connected to Q520E by 3 ft
(0.9 m) cable and has pin jacks corresponding to terminals on
programmer.
• Monitors programmer operation with test meter connected to the
terminal box.
Dimensions: 6 5/32 in. high, 7 1/16 in. wide, 1 3/4 in. deep;
156 mm high, 179 mm wide, 45 mm deep.
Programmer Controls—Parts
ORDER NUMBER Description
124731D Terminal Strip, center, for Q520 Subbase
129410 Motor, Synchronized, for R4140 Automatic Programming Control
197446 Fault Code Label, for BC7000
199037B Terminal Board Assembly, for Q520 Subbase
202050C Cover with Reset Button, for R4140 Automatic Programming Control
202051B Remote Reset Cover (120V/60), for R4140 Automatic Programming Control
4074BZU Bag Assembly including. Adaptor, Cover Insert, 2 Plugs and #8-32 Screw
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
109 70-8911
Remote Temperature Controllers—Modulating Reset
T678B; T991B Outdoor Reset Dual Bulb Temperature
Controller
T991B–5 5/8 in. high, 2 in. wide, 2 1/4 in. deep;
143 mm high, 51 mm wide, 57 mm deep.
Number of sensors: 2
Output: 2 SPDT switch contacts
Sensor Element: Copper bulb
Type: Remote bulb
Frequency: 50 Hz; 60 Hz
Maximum Operating Temperature: 125 F; 52 C
Throttling Range: 1.7 C to 16.7 C; 3 F to 10 F
Automatic outdoor reset controllers for air or liquid.
Contact Ratings: 5.1 AFL, 30.6 ALR; 8.0 AFL, 48.0 ALR
• Raises heating medium control point automatically as outdoor Voltage:T678B—120 Vac, 240 Vac
temperature falls. T991B—24 Vac to 30 Vac
• One remote element senses heating medium, the other senses Output Type: T678B–Relay
outdoor air temperature. T991B–Analog
• T991 has 135 ohm potentiometer for proportional heating control. Differential Temperature: Interstage: 3 F to 10 F adjustable;
Analog Output: One 135 Ohm Potentiometer Switch: 6 F fixed
Approvals, Canadian Standards Association: CSA Listed Interstage: 1.7 C to 5.5 C adjustable; Switch: 3.3 C fixed
Approvals, Underwriters Laboratories Inc.: UL Listed: E4436, Vol. 4, Accessories: 107324A-Capillary Holder Assembly, copper
Sec. 11, Guide XAPX 112620BA-Well Assembly, copper
Color: Gray 112620BB-Well Assembly, copper
Dimensions: T678B–5 5/8 in. high, 2 in. wide, 2 5/8 in. deep;
143 mm high, 51 mm wide, 67 mm deep.
Setpoint
Temperature Reset
ORDER NUMBER Application Range Capillary Length Bulb Size Ratio Comments
T678B1006 Automatic reset based 70 F to 140 F Indoor: 10 ft., 1/2 in. diameter, 1.0 to 1.0 Indoor bulb temperature plus
on outdoor temperature 21 C to 60 C Outdoor: 30 ft. 4 in. long outdoor bulb temperature must
Indoor: 3 m 13 mm diameter, not exceed 265 F (129 C)
Outdoor: 9.1 m 102 mm long
T678B1014 1.0 to 1.5 Indoor bulb temperature plus
1.5 times outdoor bulb
temperature must not exceed
312 F (156 C)
T678B1022 1.5 to 1.0 Indoor bulb temperature plus
0.67 times outdoor bulb
temperature must not exceed
312 F (156 C)
T678B1030 Indoor: 18 ft., 1.0 to 1.0 Indoor bulb temperature plus
Outdoor: 20 ft. outdoor bulb temperature must
Indoor: 5.5 m, not exceed 265 F (129 C)
Outdoor: 6.1 m
T991B1003 Provide modulating Indoor: 10 ft.,
control of water or air Outdoor: 30 ft.
T991B1011 Indoor: 3 m, 1.0 to 1.5 Indoor bulb temperature plus
temperature in ducts or 1.5 times outdoor bulb
tanks, setpoint Outdoor: 9.1 m
temperature must not exceed
automatically reset as 312 F (156 C).
outdoor temperature
T991B1029 changes 1.5 to 1.0 Indoor bulb temperature plus
2/3 times outdoor bulb
temperature must not exceed
242 F (117 C).
T991B1037 Indoor: 1.8 m, 1/8 in. diameter, 1.0 to 1.0 Indoor bulb temperature plus
Outdoor: 6.1 m 12 ft. long outdoor bulb temperature must
Indoor: 6 ft., 3 mm diameter, 3 not exceed 265 F (129 C).
Outdoor: 20 ft. m long
T991B1060 10 C to 49 C Indoor: 20 ft., 3.5 to 1.0 Indoor bulb temperature plus
50 F to 120 F Outdoor: 30 ft. 0.29 times outdoor bulb
Indoor: 6.1 m, temperature must not exceed
Outdoor: 9.1 m 206 F (97 C).
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 110
Remote Temperature Controllers—Modulating Reset
T991E,F Proportional Temperature Controller
Color: Gray
Output: 1 SPST
Output Type: analog and relay
Reset Ratio: 1.0 to 1.0
Sensor Element: Copper bulb
Type: Remote bulb
Voltage: 24 Vac to 30 Vac
Bulb Size: 1/2 in. diameter, 4 3/16 in. long;
13 mm diameter, 107 mm long
Provide both on-off and modulating control of water or air Frequency: 50 Hz; 60 Hz
temperatures in ducts, tanks and similar applications. Throttling Range: 11 F; 6 C
Differential Temperature: 4 F additive; 2.2 C additive
• Micro Switch™— end switch cycles burner on and off at low fire; Dimensions: 5 7/8 in. high, 4 1/8 in. wide, 2 3/16 in. deep;
T991 then modulates burner as required. 149 mm high, 105 mm wide, 56 mm deep.
• Designed for use with V9055; can be used with any series 90 Accessories: 107324A-Capillary Holder Assembly,
motor. 112620AA-Well Assembly, copper
• Ambient compensated. 112620BA-Well Assembly, copper
• Set point adjustment on front of case. 112620BB-Well Assembly, copper
• Switch makes 1 F (0.6 C) above end of throttling range. Comments: Indoor bulb temperature plus outdoor bulb temperature must
• Mount using three holes in the back of the case. not exceed 265 F (129 C).
Analog Output: One 135 Ohm Potentiometer
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
111 70-8911
Testers and Demonstrators—7800 SERIES
7800 SERIES Demonstrator
Comments: Complete Flame Safeguard Training Package
Frequency: 50/60 Hz
Voltage: 120 Vac
Temperature Rating:0 F to 120 F; -18 C to 49 C
A7800 Tester
• Function switches and selectors simulate interlocks and control
functions that allow 7800 SERIES devices to operate through
sequences.
• Indicator lamps represent outputs as activated.
Comments: Configures A7800 and DSP2672
Frequency: 50/60 Hz
Required Components: Configuration Plugs: 203579A; 203579B;
203579C; 203579D; 203579E; 203579F; 203579G
Voltage: 120 Vac
Provides quick operational check of the 7800 SERIES System Temperature Rating:0 F to 120 F; -18 C to 49 C
components.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 112
Testers and Demonstrators—Flame Simulator
123514 Flame Simulator, Flame Amplifier
W136 Meter
• Measure ac voltage of 0 to 300 Vac and dc voltages of 0 to 150
Vdc.
• Has 0 to 25 dc microamp scale for accurate checking of flame
signal strength.
• Protective circuit prevents meter burnout on 25 uA or SPL
settings.
• Provides black leather carrying case that holds meter and has
compartment for storing test leads and accessories.
• Includes two push-on alligator clips that fit over probes and
Combination ac/dc voltmeter and dc microammeter used to test all 196146 Cable Connector to plug into flame current jack and
flame safeguard controls and associated burner equipment. The connect meter in series with flame current lead.
W136A can be used to verify flame detector output is sufficient to Comments: Scale ranges: 0 to 300 Vac; 0 to 150 Vdc; 0 to 25 microamps
operate the flame relay. Includes: Two color coded, 30 in. (762 mm) long pin jack probe terminals
Products used with: flame safeguard controls
Dimensions: 8 1/2 in. high, 6 in. wide, 2 1/3 in. deep;
216 mm high, 152 mm wide, 59 mm deep.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
113 70-8911
Testers and Demonstrators
FSP1535 Tester
• Includes indicator lights that visually represent functions of
ignition, pilot and main valve as unit simulates system operation.
• Eliminates need to operate entire system.
• Tests units with rated voltage from 100 to 240, 50/60 Hz by
connecting line cord to the rated voltage.
Application: Tester
Frequency: 50/60 Hz
Products used with: RA890, R4795
Voltage: 120 Vac
Provides quick operational check of Honeywell RA890 or R4795
primary controls.
FSP5004 Tester
• Use to test some Gordon-Piatt programmers.
• Cannot be used to test some R4140 and R4150 models due to
design or wiring differences. If you have controls that CANNOT
be tested, check these out using the instructions provided in their
respective instruction manuals.
Application: Tester
Frequency: 50/60 Hz
Products used with: BC7000; R4140; R7795
Voltage: 120 Vac
Comments: DO NOT USE WITH: BC7000L1018, BC7000L1034,
Provides quick operational check of most Honeywell BC7000,
BC7000L1063; R4140D1004, R4140E1001, R4140M1079, or non-
R4140 and R4150 programmers and R7795 primary controls (order
120 Vac R4140 models
198355A adapter separately).
• Includes indicator lights that visually represent control functions
of programmer as unit simulates system operation.
• Works with 120 Vac, 50/60 Hz controls.
Some products are available only through Honeywell Authorized Flame Safeguard Distributors and/or Wholesalers.
70-8911 114
General Information
Order Specification Number System
TYPE LETTER TYPE NUMBER SUFFIX LETTER OS NUMBER
V 4055 A 1007
The type letter is the single letter, or two letter group, which begins the L, LA or LS — Limit controllers.
model number. This letter usually indicates the general type of device M — Motors.
involved, however, some product model numbers may not follow these P — Pressure controllers.
designations exactly. If you have questions about a particular product PM — Program modules.
designation, please contact your Honeywell sales representative. A list Q — Accessories.
of type letters used is shown below (some may fit in more than one cate- QS — Communication interface modules.
gory): R, RA or RW — Relays.
A — Testers. RM — Primary controls.
AT — Transformers. S — Switches and ignition modules.
BC — Microcomputer burner control system. ST — Electronic fan timers.
C or CS — Combustion controls; sensors. SV — Integrated controls.
D or DM — Dampers. T, TA or TS — Thermostats and remote bulb temperature
DSP — Demonstrators. controllers.
EL — Lighting controls. TG — Thermostat guards.
ER — Energy recovery ventilators. V, VR, VS or VW— Valves.
F — Electronic air cleaners. W — Load control panels, accessories.
H — Humidity controls, including combination Y — Package sets.
temperature and humidity controllers. ZM — Software packages.
115 70-8911
General Information
Approval Bodies
Most of the devices described in this catalog have been approved or or an Accessory Certificate and is permitted to display the trademarked
listed by one or more of the approval bodies listed below. Laboratories' Certification Seal or trademarked Laboratories' Certifica-
tion Symbol on the appliance or accessory.
Underwriters Laboratories Inc.
Underwriters Laboratories Inc., is a nonprofit organization that exam- International Approval Services—Canada
ines and tests devices, systems and materials. Its membership repre- IAS represents all segments of the Canadian gas industry, has been
sents a broad cross section of industry, education, and government. accredited by the Standards Council of Canada and the Standards Advi-
Field inspectors for Underwriters Laboratories Inc., do not normally sory Committee to prepare National Standards in the area of equipment
inspect equipment installed on job sites, but restrict their activities for use with natural gas and propane. IAS has laboratories in Toronto,
entirely to periodic inspections of products coming off manufacturers' Canada.
assembly lines. Each standard is intended to be used within the scope of the standard
The three general categories of acceptance of a product by Underwrit- by the manufacturing sector, those applying the equipment or those
ers Laboratories Inc., are: responsible for its application. It is the responsibility of the user to deter-
1. General listing. mine in each case that the standard is suitable for the application.
2. Component recognized. IAS operates a certification program for gas appliances, equipment,
3. Classification. and accessories.
General listed devices are structurally and functionally complete and
Factory Mutual
suitable for field installation.
Factory Mutual is an association of mutual insurance companies dedi-
Component recognized devices are incomplete in some way that
cated to loss prevention. Through its research arm, the Factory Mutual
makes them unsuitable for general field installation. They are intended to
Research Corporation, it investigates means of preventing and minimiz-
be factory installed as part of some other piece of equipment.
ing fire and other losses. Factory Mutual Laboratories test and approve
Classified devices or products have been evaluated as to specific haz-
two broad categories of devices and materials:
ards only.
1. Those used for the control or prevention of property damage.
Canadian Standards Association 2. Those that in themselves would present serious hazards if not prop-
The Canadian Standards Association is a nonprofit, nongovernmental erly designed.
organization which provides a national standardizing body for Canada.
The Canadian Standards Association Testing Laboratories, inaugu- Factory Mutual Acceptance refers to a specific installation or arrange-
rated in May 1940, is a division of the Canadian Standards Association, ment of equipment. Installations using approved devices, if found satis-
and is recognized as a testing and investigating agency by Inspection factory following review of plans and inspection of completed work, are
Authorities and by Fire Marshalls and Fire Commissioners throughout “accepted”.
Canada. A continuing follow-up program is carried out through periodic plant
The Canadian Standards Association Laboratories test and examine inspections and reports of performance in actual use.
electrical products submitted for approval in compliance with pertinent Industrial Risk Insurers
Canadian Standards Association codes and standards. Industrial Risk Insurers (formerly FIA) is composed of member stock
The Canadian Standards Association now includes International insurance companies, concerned with all phases of fire protection and
Approval Services (IAS). other perils insured against by its members.
International Approval Services—U.S. Generally, Industrial Risk Insurers accepts Underwriters Laboratories
IAS is the testing organization of the American gas industry with labo- Inc., listing as evidence of device acceptability, but approves or disap-
ratories in Cleveland, Ohio and Irvine, Calif. The IAS sponsors the Amer- proves each job on its own merits including:
ican National Standards Institute Z21 and Z83 Committees on standards 1. Oven, dryer, furnace or boiler construction.
for gas-fired equipment. 2. Flame safeguard control systems.
Any manufacturer of gas appliances or gas appliance accessories may 3. Fire protection equipment, sprinkler and alarm systems, etc.
submit their products to the Laboratories and secure certification of their Inspectors are located in field offices in major cities.
designs upon compliance with the appropriate national standards. Upon The home office is in Hartford, Conn., where a laboratory is main-
such compliance, the manufacturer is granted an Appliance Certificate tained.
70-8911 116
Reference Information
Date Code
A date code is stamped on each device to identify the date of manufac- ment covered hereby, including use or occupation taxes, shall be added
ture. to the price and paid by the Purchaser; or in lieu thereof, the Purchaser
In October 1975, Honeywell adopted the industry standard date code shall furnish the Company with a tax-exemption certificate acceptable to
system of a 4-digit code. The first 2 digits indicate the year; the second 2 the taxing authorities.
digits indicate the week of the year. EXAMPLE: 7812—the last week of
March 1978.
For devices manufactured before October 1975, the following date
code was used. If the letter “R” is added as a third letter, it indicates a
International Controls
repair date. Some Honeywell controls are available with Celsius scales and/or at
A January G July H 1962 Z 1970 110/220V, 50 Hz. For information on the availability of these devices,
B February H August G 1963 Y 1971 contact:
C March I September F 1964 X 1972 Burner and Boiler Controls and Systems
D April J October E 1965 W 1973 Honeywell Inc., MN10-2497
E May K November D 1966 V 1974 1985 Douglas Drive North
F June L December C 1967 U 1975 Golden Valley, MN 55422-3992
B 1968 T 1976
A 1969 Commercial Environmental and Direct Digital Controls Lighting Con-
trols and Systems
Customer Assistance Center
Terms of Payment and Prices Honeywell Inc.
P.O. Box 524, MN27-2164
Contact your local Honeywell TRADELINE Wholesaler or Authorized Minneapolis, MN 55440-0524
Distributor for your discount and terms of payment.
All other controls and systems:
International Marketing MN10-2523
Taxes Honeywell Inc.
1985 Douglas Drive North
The amount of any and all present or future taxes or other government Golden Valley, MN 55422-3992
charges upon the production, shipment, installation or sale of the equip-
Horsepower Ratings
Ratings of Honeywell controls listed herein are in amperes, and corre- All motors do not necessarily come within the maximum ampere rat-
spond generally to the values for various horsepowers as shown in this ings shown in the table, and control devices must be used which have a
chart. Full load ratings are taken from the National Electrical Code, 1978 rating equal to, or greater than, the actual motor running and starting
edition; locked motor ratings are 6 times full load rating (ac) or 10 times currents.
full load rating (dc).
120V 240V
Approximate Horsepower Full Load Locked Rotor Full Load Locked Rotor
1/6 ac 4.4 26.4 2.2 13.2
dc — — — —
1/4 ac 5.8 34.8 2.9 17.4
dc 3.1 31.0 1.6 16.0
1/3 ac 7.2 43.2 3.6 21.6
dc 4.1 41.0 2.0 20.0
1/2 ac 9.8 58.8 4.9 29.4
dc 5.4 54.0 2.7 27.0
3/4 ac 13.8 82.8 6.9 41.4
dc 7.6 76.0 3.8 38.0
1 ac 16.0 96.0 8.0 48.0
dc 9.5 95.0 4.7 47.0
1-1/2 ac 20.0 120.0 10.0 60.0
dc 13.2 132.0 6.6 66.0
2 ac 24.0 144.0 12.0 72.0
dc 17.0 170.0 8.5 85.0
3 ac 34.0 204.0 17.0 102.0
dc 25.0 250.0 12.2 122.0
117 70-8911
Reference Information
NEMA Standard Classification Code for Flame Safeguard
Enclosures
NEMA 1—General purpose. for indoor protection, where conditions are NEMA 6—Submersible. For submerged operation under specified
not unusually severe. pressures and time.
NEMA 2—Driptight. Designed to exclude falling moisture or dirt. Particu- NEMA 7—Hazardous Locations, National Electrical Code Class 1
larly applicable to cooling rooms, laundries, etc., where condensation is (circuit breaks in air).
prevalent. For indoor use. NEMA 8—Hazardous Locations, National Electrical Code Class 1
NEMA 3—Weather Resistant (weatherproof). For outdoor use; designed (circuit breaks immersed in oil).
to withstand all normal exposure to natural elements. Controls mounted NEMA 9—Hazardous Locations, National Electrical Code Class 2.
on pullout racks for easy access. With rain hood and weather seals. NEMA 10—Explosion-proof. Meets U.S. Bureau of Mines requirements
NEMA 4—Watertight. Withstands water pressure from 1 in. hose nozzle, for explosive atmospheres.
65 gallons per minute, from distance of not less than 10 ft for five
NEMA 11—Acid or Fume Resistant. Provides for immersion of enclosed
minutes. Suitable for maritime applications, breweries, etc.
equipment in oil.
NEMA 5—Dust-tight. Equipped with dust-tight gaskets. Suitable for mills
NEMA 12—IIndustrial Use. Excludes oils, dust, moisture, to satisfy
and other high-dust atmospheres.
individual requirements.
IP Standard Classification
• The IP classification system is used to indicate the degree of • A classification consists of the letters IP followed by two digits which
protection provided by the housings of electrical products operating on indicate conformity with test conditions as defined in the table below.
low and middle voltages (up to 1000 V ~ and 1500 V =).
70-8911 118
Reference Information
First Digit Second Digit
Protection against Solid Objects Protection against Water
IP Tests IP Tests
119 70-8911
Reference Information
Capacities
Most gas capacities listed in this catalog are stated for natural gas, .
based on 1,000 Btu per cu ft, 0.64 sp. gr. nat. gas, at a pressure drop of
Total Heating Value for Gas X
1.0 in. w.c. (37.3 MJ/m3, 0.64 sp. gr. at a pressure drop of 0.25 kPa). Conversion
To calculate the Btu/h capacity for other gases, multiply the listed Btu/h Btu/cu ft MJ/m3 At sp. gr. Factor (multiply)
capacity by the conversion factor
500 to 800 18.7 to 29.8 0.60 0.516a
800 to 950 29.8 to 35.4 0.70 0.765a
2500 93.3 1.53 (LP gas) 1.62
a
Nominal conversion factor for range of total heat value.
For gases not listed in table, use one of the following formulas:
( Listed—Btu/h Capacity
(0.64 sp. gr.) )( 0.64
sp. gr. gas X )( Btu/cu ft (MJ/m3 gas X)
1000 Btu/cu ft (37.3 MJ/m3 ) =
Btu/h Capacity
gas X
or
( Btu/h Capacity
(gas A) ) ( sp. gr. gas A
sp. gr. gas B ) ( Btu/cu ft (MJ/m3) gas B
Btu/cu ft (MJ/m3) gas A ) =
Btu/h Capacity
gas B
M18317
70-8911 120
Reference Information
Flame Safeguard Conversion Factors
Simplified method of determining combustion air required to com- Normally useful for determining standard cubic feet of fuel consumed
pletely burn a given amount of fuel. when metering pressure is other than standard; e.g., gas passing
Btu/hr input through a volumetric gas meter at 5 psig. (The heating value of fuel
Cf/h Air = gases is based on Btu/cf at standard gas conditions.)
100
M18318
121 70-8911
Training/Reference Materials
Training Materials
As the major flame safeguard manufacturer, Honeywell strives to build high quality products. We are well aware, however, that the consumer's comfort
and safety depend on proper application, installation, service and use of our control devices.
Since these vitally important functions depend on the skills of service technicians, we have made a long-term commitment to the technical training of our
customers.
As part of our extensive involvement in training, we publish the materials listed on these pages. By making these materials available to instructors in
schools and industry, we hope to share our experience in training with others who have similar educational objectives.
Available Training Materials Include–
• Service Handbooks
• Training Booklets
• Video Programs
• Demonstrators and Trainers, and much more!
7800 SERIES
This series of videotapes includes the following: VH-147 $45.00
(3-tape
• 7800 SERIES: The Complete Line of Safety package)
This product overview video highlights the features, benefits and accessories of the 7800
SERIES Burner Control. The video acquaints the viewer with a wide range of applications,
including traditional boiler room, industrial and rooftop applications. The 7800 SERIES
replaces more than 400 Honeywell and non-Honeywell controls, including programmers,
primaries, and semi-automatic controls. Accessories highlighted include the Expanded
Annunciator, which monitors additional safety limits and control points to minimize
troubleshooting and downtime by identifying the source of the problem. 9:45, 1995
• 7800 SERIES: Easy, Basic Installation
This video demonstrates how easy it is to install 7800 SERIES controls to upgrade
equipment with state-of-the-art controls. In addition to covering basic installation procedures
and tips, the video also reviews safety precautions and materials and tools needed for the
job. 13:10, 1995
• 7800 SERIES: BCS Communications Packages
Featuring the cost-saving benefits of using communications with Honeywell burner and
boiler controls, this video highlights the QS7850 General Purpose Interface, which enables
end-users to communicate through their current Honeywell and non-Honeywell industrial
and building automation systems. Also demonstrated are features of Honeywell
Combustion System Manager Software, a user-friendly Microsoft® Windows software
package that supports networking for single-and multi-facility monitoring. 16:15, 1995
122
Service Handbooks/Training Booklets
Service Handbooks/Training Booklets
Flame safeguard technicians throughout the industry use Honeywell Service Handbooks every day on the job. Our handbooks are valuable resources
for teaching and for convenient reference. Information typically found in them:
• Current products–their application and operation
• Wiring diagrams
• Installation and Checkout Procedures
• Service and troubleshooting–current and older models
Service Handbooks
RA890, R4795 and R7795 Service Handbook
Wiring and checkout, normal operation summary, flame current check, flame simulator, final 70-8610 $5.00
checkout, service notes and test equipment. 59 pages
123
Promotional Literature
Promotional Literature
Promotional literature is available through your Authorized Honeywell Distributor
Rebuilders
Rebuilders Brochure—Important information on the potential risks of using independently 63-9141
rebuilt controls
Valves
V4295 Sell Sheet 63-8465
V4297 Sell Sheet 63-9130
V5097 Sell Sheet 63-8565
124
FSG Textbook
FSG Textbook, “Flame Safeguard Controls: A Honeywell Textbook” 2nd edition
The most comprehensive and popular Flame Safeguard textbook available in our industry. It’s where the beginners begin and where the “Old Pros”
return year after year and problem after problem.
Student Notebook – Review questions to use with the FSG Textbook, 50 pages 71-97555 $5.00
125
Reference Manuals
These reference manuals are collations of Honeywell publications used to apply, install and service various categories of control products. Combined
they represent virtually all of the technical information Honeywell publishes on its residential and light commercial electric and electronic controls.
126
Lab Trainers
A lab trainer requires the student to actually perform point-to-point wiring to achieve a properly functioned control system.
.
DSP2672 Demonstrator
Demonstrator for use with 7800 SERIES Burner Controls. Includes RM7800L, R7849A, DSP2672 $2300.00
ST7800A, S7830A and (2) Q7800A plus control panel. Emulates a typical burner through the
means of switches, relays, flame signal simulator and lamp loads.
Provides semi-automatic means to demonstrate the functionality of the Honeywell 7800
SERIES Burner Controls.
ACCESSORIES:
Q7700 Communications Interface Base Unit.
QS7800 Communications Interface ControlBus™ Module.
ZM7850 Combustion System Manager™ Software.
127
Ordering Information
Shipping
All U.S. orders for training materials are shipped freight collect, UPS ground. Please pay with a credit card and the charges will be
added to your total.
Expedited Orders
When requested, we will expedite an order and ship by air, but you must pay by credit card and you will be billed for the shipping costs.
International Orders
International orders MUST be placed through your local Honeywell subsidiary. They can advise you on ordering and shipping proce-
dures. We cannot accept or ship international orders.
Returns
Returned items are accepted within four months of purchase. There are no cash refunds, and a $30 restocking fee per item will be
deducted from your credit. You are responsible for return shipping costs. The address for returns is printed on the bill of lading. Please
call or fax in advance of your return and provide a list of the items that you are returning and a reason as to why you are returning them.
Form of Payment
Check or Money Order (Mailed orders only)
Enclose a check or money order with your order. Make check payable to Honeywell International Inc.
Credit Card
Charge your Training Materials Order to your VISA, MasterCard or American Express card. Include card number, card-
holder’s name and expiration date on the Training Materials Order Form when you mail or fax in your order, or enter your
credit card information on-line.
Inquiries
If it is necessary to contact us regarding your order, please specify the date the order was sent. Contact us at:
128
Training Materials Order Form
Ship to:
!Company Check made payable to Honeywell International Inc. (Please add $5.95 for shipping and handling)
!Money order made payable to Honeywell International Inc. (Please add $5.95 for shipping and handling)
!Company Check made payable to Honeywell International Inc. (Please add $5.95 for shipping and handling)
!Money order made payable to Honeywell International Inc. (Please add $5.95 for shipping and handling)
INSTRUCTIONS—INSTALLING OR (iii) are protected from shipping damage; return.) Honeywell reserves the right to
SERVICING CONTRACTOR OR (iv) have certification by the installer or disallow this credit option in cases of
servicing dealer that the product was warranty abuse.
DEALER removed, due to failure, within the 2. REPAIR OR REPLACEMENT
When replacing a Honeywell product under applicable warranty period; PROCEDURE. Honeywell will, at its
warranty, including those products furnished (v) are received transportation pre-paid option, either repair or replace the
on original heating and/or cooling equipment, at: product free of charge and return it or
you should rely on your local Honeywell Honeywell Return Goods its replacement lowest cost
Wholesaler or Distributor for prompt and Dock 4 MN10-3860 transportation prepaid. The
efficient product replacement service. 1885 Douglas Drive replacement will be, at Honeywell’s
Golden Valley, MN 55422 option, either a functionally equivalent
A Honeywell Returned Goods Identification (vi) and are found by Honeywell’s new or replacement exchange product
Tag (form 87-0030) must be completed and inspection to be defective in or an equivalent TRADELINE product.
signed by the servicing dealer/contractor prior workmanship or materials under Premium transportation will be used at
to submitting the product to the Honeywell normal use and service customer’s request and expense.
Wholesaler or Distributor. (Tags may be will be handled in accordance with one of the
obtained from the Wholesaler or Distributor in two following procedures, as specified by the
advance.) No warranty claim for product Final disposition of any warranty claim will be
customer making the return: determined solely by Honeywell. If inspection
replacement or credit will be honored by the
Wholesaler/Distributor without a completed 1. CREDIT PROCEDURE. Honeywell will by Honeywell does not disclose any defect
warranty tag attached. issue credit, at Honeywell’s lowest covered by the warranty, the product will be
wholesaler net price in effect at the returned, scrapped, repaired, or replaced as
INSTRUCTIONS—WHOLESALER OR time of the return (as set forth on instructed by the customer and Honeywell’s
DISTRIBUTOR Honeywell’s then current price sheet) regular service charges will apply. Products
or at the actual invoice amount if a returned to the customer may be sent
The following will apply to the return of any shipping charges collect.
product to Honeywell under this warranty: copy of that invoice is attached to the
packing list. (TRADELINE If you have any questions relative to product
Any products which are: Replacement Exchange Products will returns to Honeywell, contact your Customer
(i) identified with Honeywell’s Returned be at Honeywell’s lowest replacement Care Representative:
Goods Identification Tag (form exchange net price in effect at the time Honeywell
87-0030), or similar tag; of such return, as shown on MN10-1465
(ii) are listed individually with Returned Honeywell’s then current price sheet, 1985 Douglas Drive
Goods ID Tag numbers and date and the Wholesaler’s Salvage Value Golden Valley, MN 55422
codes listed on Honeywell’s Returned balance will be adjusted to reflect the
Goods Order (form 71-96024) or a
similar form;
SPECIAL MESSAGE TO INDUSTRIAL that is furnished with Honeywell Your supplier can rely on its local Honeywell
USERS AND BUILDING OWNERS controls or components (refer to your Wholesaler/Distributor or Honeywell for
owner’s manual furnished with the prompt replacement.
Thank you for using Honeywell products. equipment).
3. A control has failed on your existing If you have any questions, need additional
As a user, when you purchase a Honeywell information or would like to comment on
product from this catalog you should expect commercial and/or process heating Honeywell’s products or services, please
performance from the product and, if it fails, and/or cooling equipment and is
replaced by a Honeywell TRADELINE write or phone:
replacement of the product by the installing Honeywell
dealer. product. Customer Care MN10-1461
With few exceptions, you utilize the services
Typically, you will have purchased a of a competent plumbing, heating and/or 1885 Douglas Drive North
Honeywell product under the following Golden Valley, MN 55422-4386
cooling dealer/contractor for new or (612) 951-1000
circumstances: replacement work performed.
1. To modernize or refurbish your existing or check your telephone directory (white
commercial and/or process control Although our warranty does not extend to pages) for one of many Honeywell field sales
system. you, Honeywell does extend a warranty to offices.
2. You have purchased new commercial your supplier.
and/or process heating, cooling, air
cleaning or humidification equipment