Вы находитесь на странице: 1из 9

F6TesT

Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670

Location Path Cebu\Banilad\Colon2013

Test and Test Definition Information

Test Plan Name PMS


Test Name ZTIME
Test Type Z-Time

Test Definition Name Cebu-Colon Z Time Test


Tested Date

Tested By Evaluation New

Test Definition Description

Relay Under Test General Parameters

Relay Name REL670


Serial Number
Manufacturer ABB Model REL670
Nominal Ratings: fn 60.000 Hz Max Test Current 2000.000% In
Vn 120.00 V (Ph-Ph) Max Test Voltage 1000.00% Vn
In 5.000 A A-B-C
Phase Names And Rotation
VTR 1 : 1 CTR 1 : 1
Station Name

Protected Object Parameters

Protected Object Name

Protected Object Parameters

Relay Functions

Function Name CEB-COL Function Type Impedance


Display values in Secondary Inherent Op Time 0 ms
General Tolerances

Absolute Minimum 0.010 Ohm Absolute Minimum Time 20.0 ms

Zone Elements
Zone Name Char Type Fault Characteristic t nom Residual Compensation Z tol t tol
Type Angle [ms]
-% +% -% +%

ZM01 General Ph-Ph 79.82 25 10.00 10.00 10.00 10.00


ZM01 General Ph-N 79.82 25 KN 0.00 0.00 10.00 10.00 10.00 10.00
ZM02 General Ph-Ph 79.81 525 10.00 10.00 10.00 10.00
ZM02 General Ph-N 79.81 525 KN 0.00 0.00 10.00 10.00 10.00 10.00
ZM03 General Ph-Ph 79.81 1025 10.00 10.00 10.00 10.00
ZM03 General Ph-N 79.81 1025 KN 0.00 0.00 10.00 10.00 10.00 10.00

Doble Page 1 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Relay Triggers
Signal Name F6 Sense Relay OutPut
Input Condition Name Terminal
No
Inp 1 LN1

Doble Page 2 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670

Test Configuration
Prefault Voltage 115.00 V
Prefault Current 0.000 A Angle 0 Deg
Test Method Constant Current
Desired Test Current 4 A
Max Acceptable Voltage 90 % of rating
dc transient, fault inception angle
Minimum Offset
Time constant L/R 0.00 ms CT direction Towards Line
Values are in Secondary

Test Timing Trigger Selection

Prefault Duration 0.7000 s Fault Type Trigger


Max. Fault Duration 1.5000 s AN LN1 0->1
Max Fault Duration For Faster Zones x Tmax BN LN1 0->1
CN LN1 0->1
CBTripTime 0.0000 s
AB LN1 0->1
Time between shots 0.1000 s
BC LN1 0->1
CA LN1 0->1
ABC

Doble Page 3 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type AN

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.355 70.39 37.80 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.419 88.01 81.00 ZM02 0.5250 0.4725 0.6273 0.00 0.000
6.704 88.98 87.10 ZM03 1.0250 0.9225 1.3138 0.00 0.000
2.735 7.02 70.50 ZM01 0.0250 0.0050 0.0450 0.00 0.000
5.280 40.90 82.90 ZM02 0.5250 0.4725 0.6587 0.00 0.000
8.958 51.67 91.30 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type AN

Doble Page 4 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type BN

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.355 70.39 37.80 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.419 88.01 81.00 ZM02 0.5250 0.4725 0.6273 0.00 0.000
6.704 88.98 87.10 ZM03 1.0250 0.9225 1.3138 0.00 0.000
2.735 7.02 70.50 ZM01 0.0250 0.0050 0.0450 0.00 0.000
5.280 40.90 82.90 ZM02 0.5250 0.4725 0.6587 0.00 0.000
8.958 51.67 91.30 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type BN

Doble Page 5 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type CN

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.355 70.39 37.80 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.419 88.01 81.00 ZM02 0.5250 0.4725 0.6273 0.00 0.000
6.704 88.98 87.10 ZM03 1.0250 0.9225 1.3138 0.00 0.000
2.735 7.02 70.50 ZM01 0.0250 0.0050 0.0450 0.00 0.000
5.280 40.90 82.90 ZM02 0.5250 0.4725 0.6587 0.00 0.000
8.958 51.67 91.30 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type CN

Doble Page 6 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type AB

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.852 99.79 92.70 ZM01 0.0250 0.0050 0.5775 0.00 0.000
1.219 21.36 77.70 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.206 56.68 80.00 ZM02 0.5250 0.4725 0.6153 0.00 0.000
2.757 100.80 80.90 ZM02 0.5250 0.4725 0.6259 0.00 0.000
6.630 101.40 93.70 ZM03 1.0250 0.9225 NoOp 0.00 0.000
6.616 71.47 90.50 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type AB

Doble Page 7 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type BC

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.852 99.79 92.70 ZM01 0.0250 0.0050 0.5775 0.00 0.000
1.219 21.36 77.70 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.206 56.68 80.00 ZM02 0.5250 0.4725 0.6153 0.00 0.000
2.757 100.80 80.90 ZM02 0.5250 0.4725 0.6259 0.00 0.000
6.630 101.40 93.70 ZM03 1.0250 0.9225 NoOp 0.00 0.000
6.616 71.47 90.50 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type BC

Doble Page 8 of 9
Impedance Relay Timing Test Report 28-Aug-13

Banilad \ Colon2013 \ REL670


Fault Type CA

Z Angle %Zone Zone t exp t act Eval t min t max Err V I


Test Test
[Ω] [°] [s] [s] [s] [s] [%]
[V] [A]
0.852 99.79 92.70 ZM01 0.0250 0.0050 0.5775 0.00 0.000
1.219 21.36 77.70 ZM01 0.0250 0.0050 0.0450 0.00 0.000
3.206 56.68 80.00 ZM02 0.5250 0.4725 0.6153 0.00 0.000
2.757 100.80 80.90 ZM02 0.5250 0.4725 0.6259 0.00 0.000
6.630 101.40 93.70 ZM03 1.0250 0.9225 NoOp 0.00 0.000
6.616 71.47 90.50 ZM03 1.0250 0.9225 NoOp 0.00 0.000
Fault Type CA

Doble Page 9 of 9