CIRWATT-C Series
(Version 1.xx)
Installation Manual
(M98166001-03-04A)
Index of tables
1.- INTRODUCTION.
CIRWATT is a multi-purpose three-phase, four quadrant, digital meter. Its great
versatility is its main feature, allowing it to adapt to the needs of each user.
It has been especially designed for installations where the electro-mechanical meters
do not meet current requirements. It is specifically for those installations that require a
meter with a tariff system or where electricity billing is done by using load profiles.
CIRWATT 4__ - _ __ _ - _ _ _ - __
44wire
hilos 44 Modo
Connection mode
de conexión
Class
Clase0.5S
0.5SActive
Activa/ /Class
Clase1.0
1.0Reactive
Reactiva 05 Precisión
05 Accuracy
Class
Clase1.0
1.0Active
Activa/ /Class
Clase2.0
2.0Reactive
Reactiva 10
10
3x57/100V
3x57/100V......3x230/400V (Multirrange)
3x230/400V (Multirrango) UU Tensión
Measureddevoltage
medida
/1A (Transformer. Maximum 2A
/1A (Transformador. Máximo 2A effective)
eficaces) T1 Current measurement
T1 Medida de corriente
/5A
/5A(Transformer. Maximum
(Transformador. Máximo 10A
10Aeffective)
eficaces) T5
T5
10
10AA(Direct. Maximum
(Directo. Máximo 100A
100Aeffective)
eficaces) D1
D1
Automatic (50/60
Automático Hz)
(50/60Hz) CC Frecuencia
Frequency
Without communications
Sin comunicaciones 00 Comunicaciones
Communications
RS-232
RS-232 11
RS-485
RS-485 22
Sin entradas/salidas
Without inputs/outputs 00 Expansion
Expansión
44inputs
entradas
+3+ 3 salidas
outputs (optomos)
(optomos) 44
44inputs
entradas
+3+ 3 salidas
outputs (relé)
(relay) 55
44inputs
entradas
+3+ 3 salidas
outputs (optoacoplador
(Optocoupled 24V) 24V) 99
ModeloMedium
Model: Mediana Industria
sized industry CC Modelo
Model:
Revisión
Revision 00
00
DISPLAY
• Terminal cover seals. These are attached
BUTTON once the equipment has been installed These
seals prevent the modification of the meter
SETTING BUTTON, BILL connection.
CLOSURE AND METER
START
• Button seal. Bill closure and equipment
RESET operations are protected by these
seals.
LABEL SEAL
• Label Seal. This prevents the equipment
features label from being changed.
(Transformation ratios, integration period, type
or market and area of installation).
TERMINAL CASING
SEALS
CIRWATT INSTALLATION MANUAL Page no. 4
4.- DISPLAY.
The different menus and/or screens may be displayed by using the key on the
CIRWATT. Pressing the key, for less than 2 seconds (short press), moves through
the different active menus on the screen. Pressing the same key ( ) for two seconds
(long press), automatically accesses the different secondary options and menus.
09-09-2003 12:23:10
Q1 1+2+3+ T534 NBC
Quadrante
Quadrant Alarmas
Alarms
Línieas de fase
Active phase Sentido
Energy Tarifas
Active activas
tariffs
activas
lines energía
direction
Data is displayed via a one line LCD display especially designed for the CIRWATT.
The units and resolution of the energy values are the same as the overflow values in
the meter, i.e. they are the recorder’s values. The units will be kWh or kvarh. The size
of the records will be 8 whole digits (99.999.999)
The units in which any power and energy data is transmitted by the communications
protocol will be kW, kWh, and/or kvarh, independent of what is being displayed.
Types of screen.
There are three types of screen.
09-09-2003 12:23:10
Q1 1+2+3+ T534 NBC
The data lines consist of two fields: one is the code and the other the value of the data.
9 characters are reserved for the code field and the remainder for the value field until
the 20 display characters have been used.
1.18.1.01 000000003
1.18.2.01 000000009
L
L L1 L11 (Actual)
L11 (Actual)
(Main)
(Raíz) (Contract
(Contrato 1)
L12(Closure
L12 (Cierre 1)
1)
L13(Closure
L13 (Cierre 2)
2)
L14
L14(Closure 3)
(Cierre 3)
L15
L15(Closure 4)
(Cierre 4)
L16
L16(Closure 5)
(Cierre 5)
L17
L17(Closure 6)
(Cierre 6)
L2
L2 L21 (Actual)
(Contract 2)
(Contrato 2)
L22
L22(Closure
(Cierre 1)1)
L23
L23(Closure
(Cierre 2)2)
L24
L24(Closure
(Cierre 3)3)
L25
L25(Closure
(Cierre 4)4)
L26
L26(Closure
(Cierre 5)5)
L27
L27(Closure
(Cierre 6)6)
L3
L3 (Actual)
L31 (Actual)
(Contract)3
(Contrato 3)
L32
L32(Closure 1)
(Cierre 1)
L33
L33(Closure 2)
(Cierre 2)
L34
L34(Closure 3)
(Cierre 3)
L35
L35(Closure 4)
(Cierre 4)
L36
L36(Closure 5)
(Cierre 5)
L37
L37(Closure 6)
(Cierre 6)
L4 L40
L40(Indicators)
(Indicadores)
(Information)
(Información)
L41
L41(Contracted
(Parámetrosparameters)
contratados)
L42
L42(Transformation ratios)
(Relaciones trasnformación)
L43
L43(Current
(Valoresvalues)
en curso)
L44
L44(Instant
(Valoresvalues)
instantáneos)
L45
L45(Communications)
(Comunicaciones)
L46
L46(Identifiers)
(Identificadores)
L47
L47(Output constants)
(Constantes de salida)
L48
L48(Change
(Cambiotime)
horario)
Manufacturer's
Información Model
Modelo
Information
Fabricante
Series
Número number
de serie
Date
Fechaof de
manufacture
fabricación
Installation screen
Pantalla instalación
Cirwatt
EstadoStatus
Cirwatt
Language
Idioma
Display contrast
Contraste display
CIRWATT INSTALLATION MANUAL Page no. 8
The ABSOLUTE option (ABS) displays absolute values for active and reactive energy,
as well as power excesses and maximum demands.
The INCREMENTAL option (INC) displays the incremental values from the last bill
closure for active and reactive energy, power excesses and maximum demands.
If no option is selected, a short press will move on to showing Absolute data values as
a default.
CIRWATT INSTALLATION MANUAL Page no. 9
The codes for the incremental value codes are shown below:
The information is displayed in exactly the same way as in screen L12, but field F will
have the value 02 instead of 01.
• For example: 1.18.1.02 Æ Absolute active energy consumed, from period 1,
penultimate bill closure.
The information is displayed in exactly the same way as in screen L12, but field F will
have the value 03 instead of 01.
• For example: 1.18.1.03 Æ Absolute active energy consumed, from period 1, bill
closure 3.
CIRWATT INSTALLATION MANUAL Page no. 13
The information is displayed in exactly the same way as in screen L12, but field F will
have the value 04 instead of 01.
• For example: 1.18.1.04 Æ Absolute active energy consumed, from period 1, bill
closure 4
The information is displayed in exactly the same way as in screen L12, but field F will
have the value 05 instead of 01.
• For example: 1.18.1.05 Æ Absolute active energy consumed, from period 1, bill
closure 5.
The information is displayed in exactly the same way as in screen L12, but field F will
have the value 06 instead of 01.
• For example: 1.18.1.06 Æ Absolute active energy consumed, from period 1, bill
closure 6.
All data screens that depend on this screen have the value 2 in group B of the code.
Data is displayed with zeros to the left to fill up the length of the display.
• For example: 2.16.2 Æ Absolute, current maximum demand for period 2 and for
contract 2.
Data is displayed with zeros to the left to fill up the length of the data field display.
• For example: 2.18.2.01 Æ Absolute active energy consumed, from period
2,penultimate bill closure from contract 2.
4.3.3.3.- Screen L23, L24, L25, L26, L27 (CONTRACT 2: CLOSURES 02 TO 06)
This shows recorded information on values from contract 2 from the closures prior to
the last closure. It acts in the same way as screens L13 L17 changes the group B code
from 1 to 2.
The codes for the incremental value variables are shown below:
4.3.7.1.- Model:
This screen identifies the model of the equipment. (See section 2.-METER MODEL).
CIRWATT v1.5b
410-UT5C-15C-00
CIRWATTCIRWATT
ESTADO STATUS
OPERATION OK!OK!
FUNCIONAMIENTO
CIRWATT INSTALLATION MANUAL Page no. 22
4.3.7.6.- Language
This screen indicates the pre-set language for the equipment.
LANGUAGE:
IDIOMA:
SPANISH
CASTELLANO
4.3.7.7.- Contrast
The % display contrast is shown on this screen.
DISPLAY CONTRAST
CONTRASTE DISPLAY
75%
Battery:
Type: Lithium.
Life: 10 years.
Operation without battery Maximum 96 hours
nor voltage:
Clock:
Type: Quartz oscillator/Mains frequency
Margin: < 0.5 s per day at 25 ºC
230
327
22
150
! give access to pieces that are dangerous when touched. The equipment
must not be used until it is fully installed.
R1 RS-232 or RS-485
Communications
Upper board
21 Relay output 1
22 Relay output 1
23 Relay output 2
24 Relay output 2
21 22 23 24 25 26 27 28 29 30 31
25 Relay output 3
26 Relay output 3
27 Input contact 1
28 Input contact 2
R1
29 Input contact 3
1 3 4 5 6 7 8 9 11
30 Input contact 4
2
31 Input common contact
R1 RS-232 or RS-485
Communications
Upper board
21 Relay output 1
21 22 23 24 25 26 27 28 29 30 31
22 Relay output 1
23 Relay output 2
24 Relay output 2
2 5 8 11
25 Relay output 3
26 Relay output 3
R1 27 Input contact 1
1 3 4 6 7 9 10 12
28 Input contact 2
29 Input contact 3
30 Input contact 4
31 Input common contact
CASING
terminal
CASING
7.- MAINTENANCE
The only maintenance required by the CIRWATT is replacing the battery when it
has run out.
It is advised that the battery is changed when the number of hours of use
has reached its average working life (10 years).
The hours of use may be easily checked via the display.
It has 1 series port (Plus the optical port): R1: RS-232 or RS-485 port (according to
model: ) for on site or remote communications Æ Reading and setting
Connection to a PC
RJ Cirwatt RS-232 RS-485
Connector CIRWATT P.C. (DB9) CIRWATT Converter (DB9)
1 – GND 5 – GND 1 – GND 5 – GND
2 – RX 3 – Tx 2 –Tx/Rx (-) 2 – Tx/Rx (-)
3 – TX 2 – Rx 3–Tx/Rx (+) 1 – Tx/Rx (+)
4 –CTS 7 – CTS
1 2 3 4 5 6
Front view
5 – RTS 8 – RTS
6 – GND 5 – GND 6 – GND 5 – GND
The battery reference number is written on the cover that holds the battery (CR2477N)
CIRWATT INSTALLATION MANUAL Page no. 29
C.- Quadrants
Below is a chart showing the power sign and its corresponding energy quadrant used
by the CIRWATT meter.
Reactive
consumed
nd nd st
2 1
st 2 1
Quadrant Quadrant Quadrant Quadrant
th rd
3
rd 4 3 4
th