Вы находитесь на странице: 1из 28

Terminal Blocks

Fuseholders and Power Distribution Blocks

Catalog
9080CT9603R07/10
2010
Class 9080

CONTENTS
9080LBA Power Distribution Blocks Copper or Aluminum Wire . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
9080LBA and 9080LBC Power Distribution Blocks Copper Wire only or Aluminum/Copper Wire. . . . . . . . . . . . . . . . . . . . . . . . 7
9080LBC Power Distribution Blocks Copper Wire Only . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Fuseholders 30 A Rated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Fuseholders 60 A Rated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .11
Fuseholders 100 A Rated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
9080LBA and 9080LBC Power Distribution Block Approximate Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
Fuseholder Approximate Dimensions 250 V, 30 A and 60 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Fuseholder Approximate Dimensions 250 V, 100 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16
Fuseholders Approximate Dimensions 600 V, 30 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Fuseholders Approximate Dimensions 600 V, 30 A and 60 A . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18
UL Short Circuit Current Ratings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks

Family Description

Power Distribution Blocks


Available in a wide varity of sizes, these power distribution and splicer blocks are available in one, two, and three pole versions,
with either aluminum or copper lugs. Whatever your application, the class 9080 type LB blocks should have a component to meet
your needs. A wide selection of covers completes this family.
The power distribution blocks are UL component recognized and CSA approved; many blocks have been tested to achieve a
higher SCCR according to the 2005 NEC and UL508A.

Class 9080 Type LB

Fuse Holders
This family of fuse holders will accept Types H, R, CC, M and J fuses up to 200 amperes. Both 250 V and 600 V versions are
available. All Class H, R and J fuses are supplied as standard. All fuse holders are UL Listed and CSA approved.

Class 9080 Type FB

NOTE: The product lines listed below are not shown in this catalog.
Please refer to the referenced catalog included with each family.

Family Description

IEC Terminal Blocks


Depending on the application, there are several types of IEC terminal blocks:
• Spring terminal
• Screw terminal
• Insulation displacement connection

Refer to catalog 9080CT9901R7/07

NEMA Type Terminal Blocks


This family of blocks and accessories offers a wide variety of features like DIN 3 track mounting, colored blocks, terminal screws
shipped backed out, captive screws and higher density to save you both money and time. This line also includes a direct mount
block that can be panel or track mounted. Standard track comes in common lengths and breakoff styles. All blocks are UL
component recognized and CSA approved.

Refer to Catalog 9080CT9601.


Class 9080 Type G

Circuit Protectors
There are two families of circuit protectors. One will be right for your application. The Class 9080 Type GCB thermal magnetic
product is available from 0.1 A through 15 A and offers high density. The Telemecanique GB2 thermal magnetic product is
available from 0.5 A through 12 A and is available world wide.

Refer to Catalog 9080CT9601 or Catalog 9080CT9602.

2
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA Power Distribution Blocks Copper or Aluminum Wire

Class 9080 Miniature Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating - CU Wire 115 A 115 A 175 A 175 A
Current Rating - AL Wire 90 A 90 A 135 A 135 A
SCCR with Circuit Breakers See page 20 See page 20 N/A See page 21
SCCR with Fuses See page 22 See page 22 See page 22 See page 22
Main Main Main Main
Wire Range
(1) #14-2 AWG (1) #14-2 AWG (1) #14-2/0 AWG (1) #14-2/0 AWG
Lugs suitable for use with
Branch Branch Branch Branch
75° C Conductors
(1) #14-2 AWG (4) #18-10 AWG (1) #14-2/0 AWG (4) #14-4 AWG
Main Main Main Main
#3-#2 / 50 lb-in / (5.6 N-m) #3-#2 / 50 lb-in / (5.6 N-m) #6-2/0 / 120 lb-in / (13.5 N-m) #6-2/0 / 120 lb-in / (13.5 N-m)
#6-#4 / 45 lb-in / (5.1 N-m) #6-#4 / 45 lb-in / (5.1 N-m) #8 / 40 lb-in / (4.5 N-m) #8 / 40 lb-in / (4.5 N-m)
#8 / 40 lb-in / (4.5 N-m) #8 / 40 lb-in / (4.5 N-m) #14-#10 / 35 lb-in / (4.0 N-m) #14-#10 / 35 lb-in / (4.0 N-m)
#14-#10 / 35 lb-in / (4.0 N-m) #14-#10 / 35 lb-in / (4.0 N-m)
Tightening Torque
Branch Branch Branch Branch
#3-#2 / 50 lb-in / (5.6 N-m) #18-#10 / 7 lb-in / (0.8 N-m) #6-2/0 / 120 lb-in / (13.5 N-m) #14-#4 / 35 lb-in / (4.0 N-m)
#6-#4 / 45 lb-in / (5.1 N-m) #8 / 40 lb-in / (4.5 N-m)
#8 / 40 lb-in / (4.5 N-m) #14-#10 / 35 lb-in / (4.0 N-m)
#14-#10 / 35 lb-in / (4.0 N-m)
Tin Plated High Conductive Tin Plated High Tin Plated High Tin Plated High
Lug Material
AL Conductive AL Conductive AL Conductive AL
Base Material High Impact Thermoplastic High Impact Thermoplastic General Purpose Phenolic General Purpose Phenolic
-40 to 257° F -40 to 257° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 125° C -40 to 125° C -40 to 150° C -40 to 150° C

File E60616 Guide XCFR2 File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications
¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number 9080LBA161101 9080LBA161104 9080LBA162101 9080LBA162104
Clear Plastic Covers N/A N/A 9080LB21 9080LB21
1.53 x 2.29 x 0.83 in.
Block Dimensions 1.53 x 2.29 x 0.76 in. 1.78 x 2.88 x 1.13 in. 1.78 x 2.88 x 1.13 in.
38.8 x 58.2 x 21.08 mm
(D) x (H) x (W) 38.8 x 58.2 x 19.3 mm 45.2 x 73.2 x 28.7 mm 45.2 x 73.2 x 28.7 mm
(including dovetail)
Two Pole Blocks
Block Catalog Number N/A 9080LBA261104 9080LBA262101 9080LBA262104
Clear Plastic Covers N/A N/A 9080LB22 9080LB22

Block Dimensions 1.53 x 2.29 x 1.46 in.


1.78 x 2.88 x 1.94 in. 1.78 x 2.88 x 1.94 in.
N/A 38.8 x 58.2 x 37.08 mm
(D) x (H) x (W) 45.2 x 73.2 x 49.3 mm 45.2 x 73.2 x 49.3 mm
(including dovetail)
Three Pole Blocks
Block Catalog Number 9080LBA361101 9080LBA361104 9080LBA362101 9080LBA362104
Clear Plastic Covers N/A N/A 9080LB23 9080LB23
1.53 x 2.29 x 2.1 in.
Block Dimensions 1.53 x 2.29 x 2.03 in. 1.78 x 2.88 x 2.75 in. 1.78 x 2.88 x 2.75 in.
38.8 x 58.2 x 53.34 mm
(D) x (H) x (W) 38.8 x 58.2 x 51.6 mm 45.2 x 73.2 x 69.9 mm 45.2 x 73.2 x 69.9 mm
(including dovetail)

3
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA Power Distribution Blocks Copper or Aluminum Wire

Class 9080 Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating-CU Wire 310 A 335 A 335 A 350 A
Current Rating-AL Wire 250 A 270 A 270 A 270 A
SCCR w/Circuit Breakers N/A See page 20 See page 21 See page 21
SCCR with Fuses N/A See page 22 See page 22 See page 22
Wire Range Main Main Main Main
Lugs suitable for use (1) #6 - 350 MCM (1) #6 - 400 MCM (1) #6 - 500 MCM (2) #14 - 2/0 AWG
with Branch Branch Branch Branch
75° C Conductors (1) #6 - 350 MCM (4) #14 - #2 AWG (6) #14 - #2 AWG (6) #14 - #4AWG
Main Main Main Main
#6-350 MCM / 275 lb-in / #6-400 MCM / 275 lb-in / #6-400 MCM / 275 lb-in / #6-2/0 / 120 lb-in / (13.5 N-m)
(31.0 N-m) (31.0 N-m) (31.0 N-m) #8 / 40 lb-in / (4.5 N-m)
Branch Branch Branch #14-#10 / 35 lb-in / (4.0 N-m)
Tightening Torque #6-350 MCM / 275 lb-in / #3-#2 / 50 lb-in / (5.6 N-m) #3-#2 / 50 lb-in / (5.6 N-m) Branch
(31.0 N-m)
#6-#4 / 45 lb-in / (5.1 N-m) #6-#4 / 45 lb-in / (5.1 N-m) #14-#4 / 35 lb-in / (4.0 N-m)
#8 / 40 lb-in / (4.5 N-m) #8 / 40 lb-in / (4.5 N-m)
#14-#10 / 35 lb-in / (4.0 N-m) #14-#10 / 35 lb-in / (4.0 N-m)
Lug Material Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
-40 to 302°F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150°C -40 to 150° C -40 to 150° C -40 to 150° C

File E60616 Guide XCFR2 File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications
¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number 9080LBA163101 9080LBA163104 9080LBA163106 9080LBA163206
Clear Plastic Covers 9080LB31 9080LB31 9080LB31 9080LB31
Block Dimensions 2.61 x 4.00 x 1.94 in. 2.61 x 4.00 x 1.94 in. 2.61 x 4.00 x 1.94 in. 2.61 x 4.00 x 1.94 in.
(D) x (H) x (W) 66.3 x 101.6 x 49.3 mm 66.3 x 101.6 x 49.3 mm 66.3 x 101.6 x 49.3 mm 66.3 x 101.6 x 49.3 mm
Two Pole Blocks
Block Catalog Number 9080LBA263101 9080LBA263104 9080LBA263106 9080LBA263206
Clear Plastic Covers 9080LB32 9080LB32 9080LB32 9080LB32
Block Dimensions 2.61 x 4.00 x 3.47 in. 2.61 x 4.00 x 3.47 in. 2.61 x 4.00 x 3.47 in. 2.61 x 4.00 x 3.47 in.
(D) x (H) x (W) 66.3 x 101.6 x 88.1 mm 66.3 x 101.6 x 88.1 mm 66.3 x 101.6 x 88.1 mm 66.3 x 101.6 x 88.1 mm

Three Pole Blocks


Block Catalog Number 9080LBA363101 9080LBA363104 9080LBA363106 9080LBA363206
Clear Plastic Covers 9080LB33 9080LB33 9080LB33 9080LB33
Block Dimensions 2.61 x 4.00 x 5.00 in. 2.61 x 4.00 x 5.00 in. 2.61 x 4.00 x 5.00 in. 2.61 x 4.00 x 5.00 in.
(D) x (H) x (W) 66.3 x 101.6 x 27.0 mm 66.3 x 101.6 x 127.0 mm 66.3 x 101.6 x 127.0 mm 66.3 x 101.6 x 127.0 mm

4
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA Power Distribution Blocks Copper or Aluminum Wire

Class 9080 Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating-CU Wire 420 A 335 A 380 A 380 A
Current Rating-AL Wire 340 A 270 A 310 A 310 A
SCCR w/Circuit Breakers N/A See page 20 See page 20 See page 20
SCCR with Fuses See page 22 See page 22 See page 22 See page 22
Main Main Main Main
Wire Range
(1) #4-600 MCM (1) #6-400 MCM (1) #4-500 MCM (1) #4-500 MCM
Lugs suitable for use with
Branch Branch Branch Branch
75° C Conductors
(1) #4-600 MCM (8) #14-2 AWG (6) #14-2/0 AWG (12) #14-2 AWG
Main Main Main Main
#4-600 MCM #6-400 MCM #4-500 MCM #4-500 MCM
500 lb-in (56.5 N-m) 275 lb-in (31.0 N-m) 375 lb-in (42.3 N-m) 375 lb-in (42.3 N-m)

Tightening Torque Branch Branch Branch Branch


#4-600 MCM #3-#2 50 lb-in (5.6 N-m) #6-2/0 120 lb-in (13.5 N-m) #3-#2 50 lb-in (5.6 N-m)
500 lb-in (56.5 N-m) #6-#4 45 lb-in (5.1 N-m) #8 40 lb-in (4.5 N-m) #6-#4 45 lb-in (5.1 N-m)
#8 40 lb-in (4.5 N-m) #14-#10 35 lb-in (4.0 N-m) #8 40 lb-in (4.5 N-m)
#14-#10 35 lb-in (4.0 N-m) #14-#10 35 lb-in (4.0 N-m)
Lug Material Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
-40 to 302° F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150° C -40 to 150° C -40 to 150° C -40 to 150° C

File E60616 Guide XCFR2 File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications
¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number 9080LBA164101 9080LBA164108 9080LBA165106 9080LBA165112
Clear Plastic Covers 9080LB41 9080LB41 9080LB51 9080LB51
Block Dimensions 2.90 x 4.75 x 2.29 in. 2.90 x 4.75 x 2.29 in. 3.12 x 5.50 x 3.17 in. 3.12 x 5.50 x 3.17 in.
(D) x (H) x (W) 80.3 x 120.7 x 57.2 mm 80.3 x 120.7 x 57.2 mm 79.2 x 139.7 x 80.5 mm 79.2 x 139.7 x 80.5 mm
Two Pole Blocks
Block Catalog Number N/A 9080LBA264108 9080LBA265106 9080LBA265112
Clear Plastic Covers N/A 9080LB42 9080LB52 9080LB52
Block Dimensions 2.90 x 4.75 x 4.17 in. 3.12 x 5.50 x 5.85 in. 3.12 x 5.50 x 5.85 in.
N/A
(D) x (H) x (W) 80.3 x 120.7 x 104.6 mm 79.2 x 139.7 x 149.4 mm 79.2 x 139.7 x 149.4 mm
Three Pole Blocks
Block Catalog Number 9080LBA364101 9080LBA364108 9080LBA365106 9080LBA365112
Clear Plastic Covers 9080LB43 9080LB43 9080LB53 9080LB53
Block Dimensions 2.90 x 4.75 x 6.05 in. 2.90 x 4.75 x 6.05 in. 3.12 x 5.50 x 8.54 in. 3.12 x 5.50 x 8.54 in.
(D) x (H) x (W) 80.3 x 120.7 x 152.4 mm 80.3 x 120.7 x 152.4 mm 79.2 x 139.7 x 216.9 mm 79.2 x 139.7 x 216.9 mm

5
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA Power Distribution Blocks Copper or Aluminum Wire

Class 9080 Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating-CU Wire 620 A 760 A 760 A 760 A
Current Rating-AL Wire 500 A 620 A 620 A 620 A
SCCR w/Circuit Breakers N/A N/A N/A N/A
SCCR with Fuses See page 22 See page 22 See page 22 See page 23
Main Main Main Main
Wire Range
(2) #4 - 350 MCM (2) #4 - 500 MCM (2) #4 - 500 MCM (2) #4 - 500 MCM
Lugs suitable for use with
Branch Branch Branch Branch
75° C Conductors
(2) #4 - 350 MCM (2) #4 - 500 MCM (8) #14 - 2/0 AWG (12) #14-4 AWG
Main Main Main Main
#6-350 MCM / 275 lb-in / #4-500 MCM / 375 lb-in / #4-500 MCM / 375 lb-in / #4-500 MCM / 375 lb-in /
(31.0 N-m) (42.3 N-m) (42.3 N-m) (42.3 N-m)
Tightening Torque Branch Branch Branch Branch
#6-350 MCM / 275 lb-in / #4-500 MCM / 375 lb-in / #6-2/0 / 120 lb-in / (13.5 N-m) #14-#4 / 35 lb-in / (4.0 N-m)
(31.0 N-m) (42.3 N-m) #8 / 40 lb-in / (4.5 N-m)
#14-#10 / 35 lb-in / (4.0 N-m)
Lug Material Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL Tin Plated High Conductive AL
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
-40 to 302° F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150° C -40 to 150° C -40 to 150° C -40 to 150° C

File E60616 Guide XCFR2 File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications
¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number 9080LBA165202 9080LBA1652021 9080LBA165208 9080LBA165212
Clear Plastic Covers 9080LB51 9080LB51 9080LB51 9080LB51
Block Dimensions 3.12 x 5.50 x 3.17 in. 3.12 x 5.50 x 3.17 in. 3.12 x 5.50 x 3.17 in. 3 .12 x 5.50 x 3.17 in.
(D) x (H) x (W) 79.2 x 139.7 x 80.5 mm 79.2 x 139.7 x 80.5 mm 79.2 x 139.7 x 80.5 mm 79.2 x 139.7 x 80.5 mm
Two Pole Blocks
Block Catalog Number 9080LBA265202 9080LBA2652021 9080LBA265208 9080LBA265212
Clear Plastic Covers 9080LB52 9080LB52 9080LB52 9080LB52
Block Dimensions 3.12 x 5.50 x 5.85 in. 3.12 x 5.50 x 5.85 in. 3.12 x 5.50 x 5.85 in. 3.12 x 5.50 x 5.85 in.
(D) x (H) x (W) 79.2 x 139.7 x 149.4 mm 79.2 x 139.7 x 149.4 mm 79.2 x 139.7 x 149.4 mm 79.2 x 139.7 x 149.4 mm
Three Pole Blocks
Block Catalog Number 9080LBA365202 9080LBA3652021 9080LBA365208 9080LBA365212
Clear Plastic Covers 9080LB53 9080LB53 9080LB53 9080LB53
Block Dimensions 3.12 x 5.50 x 8.54 in. 3.12 x 5.50 x 8.54 in. 3.12 x 5.50 x 8.54 in. 3.12 x 5.50 x 8.54 in.
(D) x (H) x (W) 79.2 x 139.7 x 216.9 mm 79.2 x 139.7 x 216.9 mm 79.2 x 139.7 x 216.9 mm 79.2 x 139.7 x 216.9 mm

6
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA and 9080LBC Power Distribution Blocks Copper Wire Only or Aluminum/Copper Wire

Class 9080 Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating-CU Wire 175 A 150 A 175 A 255 A
Current Rating-AL Wire 135 A N/A N/A N/A
SCCR w/Circuit Breakers See page 20 See page 21 See page 21 N/A
SCCR with Fuses See page 22 N/A See page 23 N/A
Wire Range Main - (1) #14-2/0 AWG Main - (1) #18-1/0 AWG Main - (1) #14-2/0 AWG Main - (1) #6-250 MCM
Lugs suitable for use with 75° C
Conductors Branch - (6) #14-#4 AWG Branch - (1) #18-1/0 AWG Branch - (4) #14-#4 AWG Branch - (1) #6-250 MCM

Main: Main Main Main


#6-2/0 / 120 lb-in / (13.5 N-m) #3-1/0 / 50 lb-in /(5.6 N-m) #6-2/0 120 lb-in (13.5 N-m) #6-250 MCM /
#8 / 40 lb-in (4.5 N-m) #6-#4 / 45 lb-in / (5.1 N-m) #8 40 lb-in (4.5 N-m) 375 lb-in (42.3 N-m)
#14-#10 / 35 lb-in (4.0 N-m) #8 / 40 lb-in / (4.5 N-m) #14-#10 35 lb-in (4.0 N-m)
#18-#10 / 35 lb-in / (4.0 N-m)
Tightening Torque
Branch Branch Branch Branch
#14-#4 / 35 lb-in / (4.0 N-m) #3-1/0 / 50 lb-in / (5.6 N-m) #14-#4 35 lb-in (4.0 N-m) #6-250 MCM /
#6-#4 / 45 lb-in / (5.1 N-m) 375 lb-in (42.3 N-m)
#8 / 40 lb-in / (4.5 N-m)
#18-#10 / 35 lb-in / (4.0 N-m)
Lug Material Tin Plated High Conductive AL Tin Plated High Conductive CU Tin Plated High Conductive CU Tin Plated High Conductive CU
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
-40 to 302° F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150° C -40 to 150° C -40 to 150° C -40 to 150° C
File E60616 Guide XCFR2 File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications
¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number N/A 9080LBC162101 9080LBC162104 9080LBC163101
Clear Plastic Covers N/A 9080LB21 9080LB21 9080LB31
Block Dimensions 1.78 x 2.88 x 1.13 in. 1.78 x 2.88 x 1.13 in. 2.61 x 4.00 x 1.94 in.
N/A
(D) x (H) x (W) 45.2 x 73.2 x 28.7 mm 45.2 x 73.2 x 28.7 mm 66.3 x 101.6 x 49.3 mm
Two Pole Blocks
Block Catalog Number N/A N/A 9080LBC262104 N/A
Clear Plastic Covers N/A N/A 9080LB22 N/A
Block Dimensions 1.78 x 2.88 x 1.94 in.
N/A N/A N/A
(D) x (H) x (W) 45.2 x 73.2 x 49.3 mm
Three Pole Blocks
Block Catalog Number 9080LBA362106 9080LBC362101 9080LBC362104 9080LBC363101
Clear Plastic Covers 9080LB23 9080LB23 9080LB23 9080LB33
Block Dimensions 2.10 x 2.90 x 5.38 in. 1.78 x 2.88 x 2.75 in. 1.78 x 2.88 x 2.75 in. 2.61 x 4.00 x 5.00 in.
(D) x (H) x (W) 53.3 x 73.7 x 136.7 mm 45.2 x 73.2 x 69.9 mm 45.2 x 73.2 x 69.9 mm 66.3 x 101.6 x 127.0 mm

9080FBDIN3 N/A N/A N/A

DIN 3 (35 mm) Track Adapter


7
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBC Power Distribution Blocks Copper Wire Only

Class 9080 Standard

Maximum Voltage Rating 600 600 600 600


Service Class C C C C
Current Rating-CU Wire 380 A 350 A 760 A 760 A
Current Rating-AL Wire N/A N/A N/A N/A
SCCR w/Circuit Breakers N/A See page 21 N/A N/A
SCCR with Fuses See page 23 See page 23 See page 23 See page 23
Main Main Main Main
Wire Range
(1) #4 - 500 MCM (2) #14 - 2/0 AWG (2) #4 - 500 MCM (2) #4 - 500 MCM
Lugs suitable for use with
Branch Branch Branch Branch
75° C Conductors
(6) #14-2 AWG (6) #14 - #4 AWG (8) #14 - 2/0 AWG (12) #14-2 AWG
Main Main Main
Main
#4-500 MCM - #4-500 MCM - #4-500 MCM -
#6-2/0 120 lb-in (13.5 N-m)
375 lb-in (42.3 N-m) 375 lb-in (42.3 N-m) 375 lb-in (42.3 N-m)
#8 40 lb-in (4.5 N-m)
Branch
#14-#10 35 lb-in (4.0 N-m)
Tightening Torque #3-#2 50 lb-in (5.6 N-m) Branch Branch
Branch
#6-#4 45 lb-in (5.1 N-m) #6-2/0 120 lb-in (13.5 N-m) #3-#2 50 lb-in (5.6 N-m)
#14-#4 35 lb-in (4.0 N-m)
#8 40 lb-in (4.5 N-m) #8 40 lb-in (4.5 N-m) #6-#4 45 lb-in (5.1 N-m)
#14-#10 35 lb-in (4.0 N-m) #14-#10 35 lb-in (4.0 N-m) #8 40 lb-in (4.5 N-m)
#14-#10 35 lb-in (4.0 N-m)
Tin Plated High Tin Plated High Tin Plated High Tin Plated High
Lug Material
Conductive CU Conductive CU Conductive CU Conductive CU
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
-40 to 302° F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150° C -40 to 150° C -40 to 150° C -40 to 150° C

File E60616 Guide XCFR2 ¨ File 070361 / Class 6228-01 RoHS Compliant Marked
Certifications

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Block Catalog Number 9080LBC163106 9080LBC163206 9080LBC165208 9080LBC165212
Clear Plastic Covers 9080LB31 9080LB31 9080LB51 9080LB51
Block Dimensions 2.61 x 4.00 x 1.94 in. 2.61 x 4.00 x 1.94 in. 3.12 x 5.50 x 3.17 in. 3.12 x 5.50 x 3.17 in.
(D) x (H) x (W) 66.3 x 101.6 x 49.3 mm 66.3 x 101.6 x 49.3 mm 79.2 x 139.7 x 80.5 mm 79.2 x 139.7 x 80.5 mm
Two Pole Blocks
Block Catalog Number 9080LBC263106 9080LBC263206 N/A N/A
Clear Plastic Covers 9080LB32 9080LB32 N/A N/A
Block Dimensions 2.61 x 4.00 x 3.47 in. 2.61 x 4.00 x 3.47 in.
N/A N/A
(D) x (H) x (W) 66.3 x 101.6 x 88.1 mm 66.3 x 101.6 x 88.1 mm
Three Pole Blocks
Block Catalog Number 9080LBC363106 9080LBC363206 9080LBC365208 9080LBC365212
Clear Plastic Covers N/A 9080LB33 9080LB53 9080LB53
Block Dimensions 2.61 x 4.00 x 5.00 in. 2.61 x 4.00 x 5.00 in. 3.12 x 5.50 x 8.54 in. 3.12 x 5.50 x 8.54 in.
(D) x (H) x (W) 66.3 x 101.6 x 127.0 mm 66.3 x 101.6 x 127.0 mm 79.2 x 139.7 x 216.9 mm 79.2 x 139.7 x 216.9 mm

8
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders 30 A Rated

Class 9080 Class H Fuses Class R Fuses

Maximum Voltage Rating 250 600 250 600


Wire Range
#14 to #10 AWG #14 to #10 AWG #14 to #10 AWG #14 to #10 AWG
(based on 75° C wire)
Solid or Stranded Solid or Stranded Solid or Stranded Solid or Stranded
Wire Type
Copper Wire Copper Wire Copper Wire Copper Wire
Pressure Wire Pressure Wire Pressure Wire Pressure Wire
Lug Termination
Connector Connector Connector Connector
Copper Alloy Copper Alloy Copper Alloy Copper Alloy
Clip Material
Tin Plated Tin Plated Tin Plated Tin Plated
Clip Type Reinforced Reinforced Reinforced Reinforced
Base Material High Impact Thermoplastic General Purpose Phenolic High Impact Thermoplastic General Purpose Phenolic
Recommended Tightening
25 lb-in (2.8 N-m) 25 lb-in (2.8 N-m) 25 lb-in (2.8 N-m) 25 lb-in (2.8 N-m)
Torque
-40 to 257° F -40 to 302° F -40 to 257° F -40 to 302° F
Temperature Rating
-40 to 125° C -40 to 150° C -40 to 125° C -40 to 150° C
Fuse Size (Via. x Length) 9/16" x 2" 13/16" x 5" 9/16" x 2" 13/16" x 5"
AIC Rating in accordance
10,000 10,000 200,000 200,000
with UL512

Certifications File E40747 Guide IZLT ¨ File 70360/ Class 6225-01 RoHS Compliant Marked

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Catalog Number 9080FB1211 9080FB1611 9080FB1211R 9080FB1611R
1.38 x 3.00 x 1.12 in. 1.69 x 6.25 x 1.63 in. 1.38 x 3.00 x 1.12 in. 1.69 x 6.25 x 1.63 in.
Dimensions (D) x (H) x (W)
35.1 x 76.2 x 28.4 mm 42.9 x 159.0 x 41.4 mm 35.1 x 76.2 x 28.4 mm 42.9 x 159.0 x 41.4 mm
Two Pole Blocks
Catalog Number 9080FB2211 9080FB2611 9080FB2211R 9080FB2611R
1.38 x 3.00 x 1.91 in. 1.69 x 6.25 x 2.94 in. 1.38 x 3.00 x 1.91 in. 1.69 x 6.25 x 2.94 in.
Dimensions (D) x (H) x (W)
35.1 x 76.2 x 48.5 mm 42.9 x 159.0 x 74.7 mm 35.1 x 76.2 x 48.5 mm 42.9 x 159.0 x 74.7 mm
Three Pole Blocks
Catalog Number 9080FB3211 9080FB3611 9080FB3211R 9080FB3611R
1.38 x 3.00 x 2.95 in. 1.69 x 6.25 x 4.25 in. 1.38 x 3.00 x 2.95 in. 1.69 x 6.25 x 4.25 in.
Dimensions (D) x (H) x (W)
35.1 x 76.2 x 74.9 mm 42.9 x 159.0 x 108 mm 35.1 x 76.2 x 74.9 mm 42.9 x 159.0 x 108 mm

9080FBDIN3 N/A 9080FBDIN3 N/A

DIN 3 (35 mm) Track Adapter

9
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders 30 A Rated

Class 9080 Class M Fuses Class CC Fuses Class J Fuses

Maximum Voltage Rating 600 600 600


Wire Range
#14 to #10 AWG #14 to #10 AWG #14 to #2 AWG
(based on 75° C wire)
Solid or Stranded Solid or Stranded Solid or Stranded
Wire Type
Copper Wire Copper Wire Copper Wire
Pressure Wire Pressure Wire Box Lug
Lug Termination
Connector Connector Connector
Copper Alloy Copper Alloy Copper Alloy
Clip Material
Tin Plated Tin Plated Tin Plated
Clip Type Standard Standard Reinforced
Base Material High Impact Thermoplastic High Impact Thermoplastic High Impact Thermoplastic
Recommended Tightening Torque 25 lb-in (2.8 N-m) 25 lb-in (2.8 N-m) 25 lb-in (2.8 N-m)
-40 to 257° F -40 to 257° F -40 to 257° F
Temperature Rating
-40 to 125° C -40 to 125° C -40 to 125° C
Fuse Size (Dia. x Length) 13/32" x 1 1/2" 13/32" x 1 1/2" 13/16"x2 1/4"
AIC Rating in accordance
100,000 200,000 200,000
with UL512

File E40747 / Guide IZLT2 File E40747 / Guide IZLT


Certifications
¨
File 070360 File 70360
Class 6225-01
¨
Class 6225-01

RoHS Compliant RoHS Compliant

Marked Marked

Flammability Rating UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Catalog Number 9080FB1611M 9080FB1611CC 9080FB1611J
1.29 x 3.13 x 0.85 in. 1.29 x 3.13 x 0.85 in. 1.95 x 3.38 x 1.16 in.
Dimensions (D) x (H) x (W)
32.8 x 79.5 x 21.6 mm 32.8 x 79.5 x 21.6 mm 49.5 x 85.7 x 29.4 mm
Two Pole Blocks
Catalog Number 9080FB2611M 9080FB2611CC 9080FB2611J
1.29 x 3.13 x 1.60 in. 1.29 x 3.13 x 1.60 in. 1.95 x 3.38 x 2.20 in.
Dimensions (D) x (H) x (W)
32.8 x 79.5 x 40.6 mm 32.8 x 79.5 x 40.6 mm 49.5 x 85.7 x 56.0 mm
Three Pole Blocks
Catalog Number 9080FB3611M 9080FB3611CC 9080FB3611J
1.29 x 3.13 x 2.35 in. 1.29 x 3.13 x 2.35 in. 1.95 x 3.38 x 3.25 in.
Dimensions (D) x (H) x (W)
32.8 x 79.5 x 59.7 mm 32.8 x 79.5 x 59.7 mm 49.5 x 85.7 x 82.5 mm

9080FBDIN3 9080FBDIN3 DIN 3 Track Mounting is standard.

DIN 3 (35 mm) Track Adapter

10
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders 60 A Rated

Class 9080 Class H Fuses

Maximum Voltage Rating 250 600 600


Wire Range
#14 to #2 AWG #14 to #2 AWG #14 to #2 AWG
(based on 75° C wire)
Solid or Stranded Solid or Stranded Solid or Stranded
Wire Type
Copper or Aluminum Wire Copper or Aluminum Wire Copper Wire
Lug Termination Box Lug Connector Box Lug Connector Box Lug Connector
Copper Alloy Copper Alloy Copper Alloy
Clip Material
Tin Plated Tin Plated Tin Plated
Clip Type Reinforced Reinforced Reinforced
Base Material High Impact Thermoplastic General Purpose Phenolic General Purpose Phenolic
#2 to #3 AWG 50 lb-in (5.6 N-m) #2 to #3 AWG 50 lb-in (5.6 N-m) #2 to #3 AWG 50 lb-in (5.6 N-m)
#4 to #6 AWG 45 lb-in (5.1 N-m) #4 to #6 AWG 45 lb-in (5.1 N-m) #4 to #6 AWG 45 lb-in (5.1 N-m)
Recommended Tightening Torques
#8 AWG 40 lb-in (4.5 N-m) #8 AWG 40 lb-in (4.5 N-m) #8 AWG 40 lb-in (4.5 N-m)
#10 to #14 AWG 35 lb-in (4.0 N-m) #10 to #14 AWG 35 lb-in (4.0 N-m)) #10 to #14 AWG 35 lb-in (4.0 N-m)
-40 to 257° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 125° C -40 to 150° C -40 to 150° C
Fuse Size (Dia. x Length) 13/16" x 3" 1 1/16" x 5 1/2" 1 1/16" x 5 1/2"
AIC Rating in accordance
10,000 10,000 10,000
with UL512

Certifications File E40747 Guide IZLT ¨ File 70360/ Class 6225-01 RoHS Compliant Marked

Flammability Rating L94V-0 UL94V-0 UL94V-0


One Pole Blocks
Catalog Number 9080FB1221 9080FB1621 N/A
2.01 x 4.83 x 1.48 in. 2.12 x 6.75 x 1.95 in.
Dimensions (D) x (H) x (W) N/A
51.1 x 123.0 x 37.7 mm 53.8 x171.4 x 49.5 mm
Two Pole Blocks
Catalog Number 9080FB2221 9080FB2621 9080FB2621C
2.01 x 4.83 x 2.86 in. 2.12 x 6.75 x 3.51 in. 2.12 x 6.75 x 3.51 in.
Dimensions (D) x (H) x (W)
51.1 x 123.0 x 72.7 mm 53.8 x171.4 x 89.2 mm 53.8 x171.4 x 89.2 mm
Three Pole Blocks
Catalog Number 9080FB3221 9080FB3621 N/A
2.01 x 4.83 x 4.23 in. 2.12 x 6.75 x 5.08 in.
Dimensions (D) x (H) x (W) N/A
51.1 x 123.0 x 108.0 mm 53.8 x171.4 x 129.0 mm

11
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders 60 A Rated

Class 9080 Class R Fuses Class J Fuses

Maximum Voltage Rating 250 600 600


Wire Range
#14 to #2 AWG #14 to #2 AWG #14 to #2 AWG
(based on 75° C wire)
Solid or Stranded Solid or Stranded Solid or Stranded
Wire Type
Copper or Aluminum Wire Copper or Aluminum Wire Copper or Aluminum Wire
Lug Termination Box Lug Connector Box Lug Connector Box Lug Connector
Copper Alloy Copper Alloy Copper Alloy
Clip Material
Tin Plated Tin Plated Tin Plated
Clip Type Reinforced Reinforced Reinforced
Base Material High Impact Thermoplastic General Purpose Phenolic High Impact Thermoplastic
#2 to #3 AWG 50 lb-in (5.6 N-m) #2 to #3 AWG 50 lb-in (5.6 N-m) #2 to #3 AWG 50 lb-in (5.6 N-m)
#4 to #6 AWG 45 lb-in (5.1 N-m) #4 to #6 AWG 45 lb-in (5.1 N-m) #4 to #6 AWG 45 lb-in (5.1 N-m)
Recommended Tightening Torques
#8 AWG 40 lb-in (4.5 N-m) #8 AWG 40 lb-in (4.5 N-m) #8 AWG 40 lb-in (4.5 N-m)
#10 to #14 AWG 35 lb-in (4.0 N-m) #10 to #14 AWG 35 lb-in (4.0 N-m) #10 to #14 AWG 35 lb-in (4.0 N-m)
-40 to 257° F -40 to 302° F -40 to 257° F
Temperature Rating
-40 to 125° C -40 to 150° C -40 to 125° C
Fuse Size (Dia. x Length) 13/16" x 3" 1 1/16" x 5 1/2" 1 1/16" x 2 3/8"
AIC Rating in accordance
200,000 200,000 200,000
with UL512

Certifications File E40747 Guide IZLT ¨ File 70360/ Class 6225-01 RoHS Compliant Marked

Flammability Rating UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Catalog Number 9080FB1221R 9080FB1621R 9080FB1621J
2.01 x 4.83 x 1.48 in. 2.12 x 6.75 x 1.95 in. 2.09 x 4.07 x 1.67 in.
Dimensions (D) x (H) x (W)
51.1 x 123.0 x 37.7 mm 53.8 x 171.4 x 49.5 mm 53.0 x 103.0 x 42.4 mm
Two Pole Blocks
Catalog Number 9080FB2221R N/A 9080FB2621J
2.01 x 4.83 x 2.86 in. 2.09 x 4.07 x 3.20 in.
Dimensions (D) x (H) x (W) N/A
51.1 x 123.0 x 72.7 mm 53.0 x 103.0 x 81.2 mm
Three Pole Blocks
Catalog Number 9080FB3221R 9080FB3621R 9080FB3621J
2.01 x 4.83 x 4.23 in. 2.12 x 6.75 x 5.08 in. 2.09 x 4.07 x 4.72 in.
Dimensions (D) x (H) x (W)
51.1 x 123.0 x 108.0 mm 53.8 x171.4 x 129.0 mm 53.0 x 103.0 x 120.0 mm

12
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders 100 A Rated

Class 9080 Class H Fuses Class R Fuses

Maximum Voltage Rating 600 600 250 600


Current Rating 100 100 100 100
Wire Range
#6 to 2/0 AWG #6 to 2/0 AWG #6 to 2/0 AWG #6 to 2/0 AWG
(based on 75° C wire)
Solid or Stranded Solid or Stranded Solid or Stranded Solid or Stranded
Wire Type
Copper Wire Cu or Al Wire Cu or Al Wire Cu or Al Wire
Lug Termination Box Lug Connector Box Lug Connector Box Lug Connector Box Lug Connector
One piece Aluminum One piece Aluminum
One piece Aluminum
Clip Material Copper Alloy Tin Plated w/ Copper Spring w/ Copper Spring
w/ Stainless Steel Spring
Tin Plated Tin Plated
Clip Type Reinforced Reinforced Reinforced Reinforced
Base Material General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic General Purpose Phenolic
Recommended Tightening
120 lb-in (13.6 N-m) 120 lb-in (13.6 N-m) 120 lb-in (13.6 N-m) 120 lb-in (13.6 N-m)
Torques
-40 to 302° F -40 to 302° F -40 to 302° F -40 to 302° F
Temperature Rating
-40 to 150° C -40 to 150° C -40 to 150° C -40 to 150° C
Fuse Size (Dia. x Length) 1" x 7 7/8" 1" x 7 7/8" 1" x 5 7/8" 1" x 7 7/8"
AIC Rating in accordance
10,000 10,000 20,000 20,000
with UL512

File E40747 Guide IZLT File 70360 / Class 6225-01 RoHS Compliant Marked
Certifications ¨

Flammability Rating UL94V-0 UL94V-0 UL94V-0 UL94V-0


One Pole Blocks
Catalog Number N/A N/A 9080FB1231R 9080FB1631R
2.44 x 6.12 x 1.93 in. 2.60 x 8.12 x 2.10 in.
Dimensions (D) x (H) x (W) N/A N/A
62.0 x 155.5 x 49.0 mm 66.0 x 206.2 x 53.3 mm
Two Pole Blocks
Catalog Number N/A N/A 9080FB2231R N/A
2.44 x 6.12 x 3.49 in.
Dimensions (D) x (H) x (W) N/A N/A N/A
62.0 x 155.5 x 88.6 mm
Three Pole Blocks
Catalog Number 9080FB3631C 9080FB3631 9080FB3231R 9080FB3631R
2.6 x 8.12 x 5.73 in. 2.60 x 8.12 x 5.73 in. 2.44 x 6.12 x 5.05 in. 2.60 x 8.12 x 5.73 in.
Dimensions (D) x (H) x (W)
66.0 x 206.2 x 145.5 mm 66.0 x 206.2 x 145.5 mm 62.0 x 155.5 x 128.3 mm 66.0 x 206.2 x 145.5 mm

13
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
9080LBA and 9080LBC Power Distribution Block Approximate Dimensions
9080LBA/9080LBC9080LBa/LBC

A1 A2 A3 J- Mounting Hole Dia.

B G

D E D E E D F

1 Pole 2 Pole 3 Pole A1 A2 A3 B C D E F G H J

LBA161101 N/A LBA361101


0.76 1.40 2.03 2.29 1.53 0.38 0.64 0.19 1.93 0.32 0.201
LBA161104 LBA261104 LBA361104
LBA162101 LBA262101 LBA362101
LBA162104 LBA262104 LBA362104
LBC162101 N/A 1.13 1.94 2.75 2.88 1.78 0.56 0.81 0.31 2.25 0.24 0.205
LBC362101
LBC162104 LBC262104 LBC362104
LBA163101 LBA263101 LBA363101
LBA163104 LBA263104 LBA363104
LBA163106 LBA263106 LBA363106
LBA163206 LBA263206 LBA363206 1.94 3.47 5.00 4.00 2.61 0.97 1.53 0.31 3.38 0.40 0.203
LBC163101 N/A LBC363101
LBC163106 LBC263106 LBC363106
LBC163206 LBC263206 LBC363206
LBA164101 N/A LBA364101
2.28 4.16 6.04 4.75 2.92 1.14 1.88 0.31 4.13 0.51 0.200
LBA164108 LBA264108 LBA364108
LBA165202 LBA265202 LBA365202 3.17 5.85 8.54 5.50 3.12 1.58 2.69 0.38 4.75 0.50 0.265
LBA1652021 LBA2652021 LBA3652021
LBA165106 LBA265106 LBA365106
LBA165112 LBA265112 LBA365112
LBA165212 LBA265212 LBA365212
LBC165208 N/A LBC365208
LBC165212 N/A LBC365212

.218 x .375 USE A #8 SELF TAPPING SCREW


[5.5 x 9.5] FOR MOUNTING COMPONENT
SLOT
.265 x .375
[6.7 x 9.5] .50
SLOT 13

1.00 2.90
25.4 73.7
1.45
36.8
1.07
4.63 27
117.5
4.77 .50
121 13
5.37
136.4 DIN Rail Adapter

.60
15.2
2.10
53.4

.38 in.
Dimensions:
9.5 [mm]
LBA362106

14
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholder Approximate Dimensions 250 V, 30 and 60 A

.22/5.6 DIA. HOLE THRU


.22/5.6 DIA. HOLE THRU .22/5.6 DIA. HOLE THRU 2 PLACES
4 PLACES 2 PLACES

1.25 1.50
1.50
[31.8] [38.1]
[38.1]

3.00

250 V

250 V
.50 3.00 3.00

30 A
30 A
250 V 30 A
[13] [76.2] [76.2] [76.2]

.75 .19 .33 1.25


.22 2.50
[19] [4.8] [8.4] [31.7]
[5.7] [63.5]
1.91
1.12 [48.5] 2.95
[28.4] [74.9]

.82 .82
[21] .82
[21] [21]

1.38 1.38 1.38


[35.1] [35.1] [35.1]
.53 .53 .53
[13] [13] [13]

FB1211 FB2211 FB3211


FB1211R FB2211R FB3211R
30 A

.218/5.54 DIA.
C BORE.400/10.16 DIA. X .63/16 DEEP

1.24 4.83 250V. 60A.250V. 60A. 1.24 4.83 250V. 60A.250V. 60A.250V. 60A. 1.24 4.83
250V. 60A. [31.4] [123] [123]
[31.4] [123] [31.4]

1.80 1.80 1.80


[45.8] [45.8] [45.8]

.49 .50 .50


.49 .50 [12] [13] .49 .01
[13] [13] [13] [13] [.3]
1.48 1.33 1.33 1.33
[37.7] [33.7] [33.7]
[33.7]
2.86 4.23
[72.7] [108]

1.21 1.21 1.21


[30.8] [30.8] [30.8]

2.01 2.01 2.01


[51.1] [51.1] [51.1]
.62 .62 .62
[16] [16] [16]

FB1221 FB2221 FB3221


FB1221R FB2221R FB3221R

in.
Dimensions:
[mm]
60 A

15
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholder Approximate Dimensions 250 V, 100 A

.28/[7.1]DIA. HOLE THRU .28/[7.1] DIA. HOLE THRU .28/[7.1] DIA. HOLE THRU
.53/[13.5] DIA. C'BORE .53/[13.5] DIA. C'BORE .53/[13.5] DIA. C'BORE
X .59/[15.0] DEEP X .53/[15.0] DEEP X .59/[15.0] DEEP
98066 98066 98066 98066 98066 98066

2/0-14 2/0-14 2/0-14 2/0-14 2/0-14 2/0-14


CU9AL CU9AL CU9AL CU9AL CU9AL CU9AL

6.12
[155.5]
GAUGE GAUGE
STRIP STRIP GAUGE
STRIP
250V 100A 2.37 6.12 250V 100A 250V 100A 2.37 6.12 2.37
[60.3] [155.5] [60.3] [155.5] 250V 100A 250V 100A 250V 100A [60.3]
STRIP STRIP
GAUGE GAUGE

98066
1.87 98066 98066
1.87 98066 98066 98066
1.87
[47.5] [47.5] [47.5]
2/0-14 2/0-14 2/0-14 2/0-14 2/0-14 2/0-14
CU9AL CU9AL CU9AL CU9AL CU9AL CU9AL

.62 .62
.61 .62 .61 TYP .61 TYP
[15.5] [15.8] [15.5] [15.8] [15.5] [15.8]
1.56 1.56
[39.6] TYP 1.44
1.44 1.44 TYP
[36.5] [39.6]
[36.5] [36.5]

2.44 2.44 2.44


[62.0] [62.0] [62.0]
.86
[21.8]
250V 100A
.86
[21.8]
.86
1.93 3.49 5.05 [21.8]
[49.0] [88.6] [128.3]

FB1231R FB2231R FB3231

100 A

.28 [7.1] DIA. THRU


.59 [14.96] DIA. C'BORE
X .64 [16.2] DEEP

.87 STRIP
[22.1] GAUGE

600V.100A. 600V.100A. 600V.100A.


4.25
[108]
STRIP
GAUGE 8.12
[206.2]

1.94
[49.3]

.61 1.81
[15.5] [46.0]
1.55
[39.5]

2.60
[66.0]

5.73
[145.5] .87
[22.1]

FB3631
FB3631R in.
Dimensions:
[mm]
100 A

16
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholder Approximate Dimensions 600 V, 30 A

30 A
1 Pole 2 Pole 3 Pole
.85 1.60 2.35
[21.6] [40.6] [59.7]
.375 .750 1.500
[9.5] [19.1] [38.1]

1.56
[39.6]
TYP.
3.13
[79.5]

.24 .42 .42 .750 .172 x .218 SLOTS TYP.


[6.1] [10.6] [10.6] [19.1]
[4.4] x [5.5]

.50
[13] 1.290
[32.8]

FB1611M FB2611M FB3611M

.85 1.60 2.35


[21.6] [40.6] [59.7]
.375 .750 1.500
[9.5] [19.1] [38.1]

1.56
[39.6]
TYP. 3.13
[79.5]

.24 .42 .42 .750 .172 x .218 SLOTS TYP.


[6.1] [10.6] [10.6] [19.1]
[4.4] x [5.5]

.50
[13] 1.290
[32.8]

FB1611CC FB2611CC FB3611CC

in.
Dimensions:
[mm]

17
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders Approximate Dimensions 600 V, 30 A and 60 A

.20/5.08 DIA. THRU .265 [6.7] DIA. THRU .265 [6.7] DIA THRU .265 [6.7] DIA THRU
C'BORE SLOT .50 [12.7] X .94 [23.8] C'BORE .50 [12.7] DIA. C'BORE .50 [12.7] DIA.
X .44 [11.2] DP. X .44 [11.8] DP. X .44 [11.8] DP.

.34
[8.7]

600V 3.13 6.25 600V 3.13 6.25 600V 3.13 6.25


30A [79.4] [159] 30A [79.4] [159] 30A [79.4] [159]
.31
[7.9]

1.56 1.56 1.56


[39.7] [39.7] [39.7]

.51 .62 .38 .62


[13] [16] .25 .62 .03
[9.7] [16] [6.5] [16]
1.63 [.8]
1.56 3.13
[41.4] [39.6] [79.2]
2.94 4.25
[74.7] [108]

1.13 1.13 1.13


[28.6] [28.6] [28.6]

1.69 1.69 1.69


[42.9] [42.9] [42.9]
.69 .69 .69
[18] [18] [18]

FB1611 FB2611 FB3611


FB1611R FB2611R FB3611R

in.
Dimensions:
60 A [mm]

1.95 3.51 5.08


(49.5) (89.2) (129)

.281 D.
(7.1) 3.12
(79.2)
6.75
.50 D. (171.4)
(12.7)

1.81
(46)

.62 .66 1.56 3.12


(15.7) (16.8) (39.6) (79.2)
1.56 1.29 3.12
(39.6) (32.8) (79.2)

2.12
(53.8)

.27 .77
(6.8) (19.6)

FB1621 FB2621 FB3621


FB1621R FB2621C FB3621R
30 A
18
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Fuseholders Approximate Dimensions 600 V, 30 A and 60 A

30 A
.30 [7.5] .57 [14/5] TYP. [5.6 X 20.1]

1.69
[42.9]
30A 30A
600V 600V
3.38
[85.8] 30A 30A
600V 600V

1.04 [26.5]
TYP. 3.25 2.21 1.16
[82.5] [56.1] [29.5]

1.95
[49.5]
.71 [17.9]

FB3611J FB2611J FB1611J

60 A
.265 x .325 Slot
[6.7 x 8.3]
1.67 3.20 4.72
TYP.
(42.4) (81.2) (120)

4.07 4.07 4.07


(103) (103) (103)
2.03 2.03 2.03
(51.7) (51.7) (51.7)

.45 .45 .45


(12) (12) (12)
.76 1.53 .76 1.53 1.53 .76
(19) (38.8) (19) (38.8) (38.8) (19)

1.37
(34.9)

2.09 2.09 2.09


(53.0) (53.0) (53.0)
.57 .57 .57
(14) (14) (14)

.13
TYP
(3.2)

FB1621J FB2621J FB3621J

in.
Dimensions:
[mm]

19
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
UL Short Circuit Current Ratings
U

Table 1: 9080LBA and 9080LBC Power Distribution Blocks Short Circuit Current Ratings with Circuit Breakers

Suitable Conductors MCM / AWG Overcurrent Protection Circuit Breaker


Cat No.
CU Required

SCCR, RMS
Line Load Mfr. Type Max A Volts Max
Sym A
JDL36250 250 18 kA
JGL36250 250 35 kA
2-6 2 -6 Square D
JJL36250 250 65 kA
9080LBA161101 JLL36250 250 65 kA
480
9080LBA361101 HDL36100 100 18 kA
HGL36100 100 35 kA
8-10 8-10 Square D
HJL36100 100 65 kA
HLL36100 100 65 kA

JDL36250 250 18 kA
JGL36250 250 35 kA
JJL36250 250 65 kA
9080LBA161104
JLL36250 250 65 kA 480
9080LBA261104 8- 10 4) 14 Square D
HDL36100 100 18 kA
9080LBA361104
HGL36100 100 35 kA
HJL36100 100 65 kA
HLL36100 100 65 kA

JDL36250 250 18 kA
JGL36250 250 35 kA
9080LBA362106 2/0 -6 6) 4- 10 Square D JJL36250 250 65 kA 480
JLL36250 250 65 kA
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA165106
JJL36250 250 65 kA
9080LBA265106 2/0 -4 6) 8 Square D 480
JLL36250 250 65 kA
9080LBA365106
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA165112
JJL36250 250 65 kA
9080LBA265112 2/0 -4 12) 2 -8 Square D 480
JLL36250 250 65 kA
9080LBA365112
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA164108
JJL36250 250 65 kA
9080LBA264108 2/0 -6 6) 2 - 10 Square D 480
JLL36250 250 65 kA
9080LBA364108
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA163104
JJL36250 250 65 kA
9080LBA263104 2/0 -4 4) 2 -8 Square D 480
JLL36250 250 65 kA
9080LBA363104
JDL36250 250 18 kA

20
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
UL Short Circuit Current Ratings

Table 1: 9080LBA and 9080LBC Power Distribution Blocks Short Circuit Current Ratings with Circuit Breakers
(continued)

Suitable Conductors MCM / AWG Overcurrent Protection Circuit Breaker


Cat No.
CU Required

SCCR, RMS
Line Load Mfr. Type Max A Volts Max
Sym A
JGL36250 250 35 kA
9080LBA163206
JJL36250 250 65 kA
9080LBA263206 2) 1/0 -8 6) 4- 10 Square D 480
JLL36250 250 65 kA
9080LBA363206
JDL36250 250 18 kA

JGL36250 250 35 kA
JJL36250 250 65 kA
2) 2/0 -2 6) 4-8 Square D
JLL36250 250 65 kA
9080LBC163206
JDL36175 175 18 kA
9080LBC263206 480
JGL36175 175 35 kA
9080LBC363206
JJL36175 175 65 kA
2) 4-6 6) 10-12 Square D
JLL36175 175 65 kA
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBC162101 JJL36250 250 65 kA
1/0 -8 1/0 -8 Square D 480
9080LBC362101 JLL36250 250 65 kA
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA163106
JJL36250 250 65 kA
9080LBA263106 2/0 -6 6) 2 - 10 Square D 480
JLL36250 250 65 kA
9080LBA363106
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBA162104
JJL36250 250 65 kA
9080LBA262104 2/0 - 10 4) 4- 10 Square D 480
JLL36250 250 65 kA
9080LBA362104
JDL36250 250 18 kA

JGL36250 250 35 kA
9080LBC162104
JJL36250 250 65 kA
9080LBC262104 2/0 -8 4) 4-8 Square D 480
JLL36250 250 65 kA
9080LBC362104
JDL36250 250 18 kA

21
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
UL Short Circuit Current Ratings

Table 2: 9080LBA and 9080LBC Power Distribution Blocks Short Circuit Current Ratings with Fuses

Suitable Conductors
Catalog Number Fuse Type / Amperage
MCM / AWG CU

Volts
1 Pole 2 Pole 3 Pole Line Load J T RK1 RK5 G CC SCCR
Max
2-6 2-6 200 200 200 100 60 30 100 kA 600
9080LBA161101 N/A 9080LBA361101
8-10 8-10 100 100 100 – 60 30 100 kA 600

2-6 10-14 200 200 200 100 60 30 200 kA 600


9080LBA161104 9080LBA261104 9080LBA361104
8-10 10-14 100 100 100 30 60 30 100 kA 600

9080LBA162101 9080LBA262101 9080LBA362101 2/0-6 2/0-6 300 300 200 100 60 30 65 kA 600

9080LBA162104 9080LBA262104 9080LBA362104 2/0-6 4-14 200 200 200 100 60 30 100 kA 600

– – – – 60 – 100 kA 600
N/A N/A 9080LBA362106 2/0-6 4-14
200 200 200 100 – 30 200 kA 600

9080LBA163101 9080LBA263101 9080LBA363101 N/A

400-3/0 2-8 400 400 400 100 60 30 100 kA 600


9080LBA163104 9080LBA263104 9080LBA363104
2/0-6 2-14 200 200 200 100 60 30 100 kA 600

400 400 400 200 – 30 200 kA 600


400-3/0 2-8
600 – – – 60 – 100 kA 600
9080LBA163106 9080LBA263106 9080LBA363106
200 200 200 100 – 30 200 kA 600
2/0-6 2-14
– – – – 60 – 100 kA 600

(2)2/0-2 4-8 400 400 400 100 60 30 100 kA 600


9080LBA163206 9080LBA263206 9080LBA363206
(2)4-6 10-14 300 300 200 100 60 30 100 kA 600

600 600 – – – – 50 kA 600


9080LBA164101 N/A 9080LBA364101 600-2 600-2
400 400 400 200 60 30 100 kA 600

400-3/0 2-8 400 400 400 200 60 30 100 kA 600


9080LBA164108 9080LBA264108 9080LBA364108
2/0-6 2-14 200 200 200 100 60 30 100 kA 600

450 450 400 200 60 30 100 kA 600


9080LBA165202 9080LBA265202 9080LBA365202 (2)350-4 (2)350-4
600 600 – – – – 50 kA 600

9080LBA1652021 9080LBA2652021 9080LBA3652021 (2)500-4 (2)500-4 600 600 400 200 60 30 100 kA 600

500-3/0 2/0-6 400 400 400 100 60 30 100 kA 600


9080LBA165106 9080LBA265106 9080LBA365106
2/0-4 8-14 200 200 200 100 60 30 100 kA 600

500-3/0 2-8 400 400 400 200 60 30 100 kA 600


9080LBA165112 9080LBA265112 9080LBA365112
2/0-4 2-14 200 200 200 100 60 30 100 kA 600

(2)500-250 2/0-4 600 600 400 200 60 30 100 kA 600


9080LBA165208 9080LBA265208 9080LBA365208 600 600 – – – – 50 kA 600
(2)4/0-4 2/0-10
400 400 400 200 60 30 100 kA 600

22
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
UL Short Circuit Current Ratings

Table 2: 9080LBA and 9080LBC Power Distribution Blocks Short Circuit Current Ratings with Fuses (continued)

Suitable Conductors
Catalog Number Fuse Type / Amperage
MCM / AWG CU

Volts
1 Pole 2 Pole 3 Pole Line Load J T RK1 RK5 G CC SCCR
Max
600 600 600 N/A N/A N/A 50 kA 600
(2)500-250 4-8
400 400 400 200 60 30 100 kA 600
9080LBA165212 9080LBA265212 9080LBA365212
600 600 N/A N/A N/A N/A 50 kA 600
(2)4/0-4 4-14
400 400 400 200 60 30 100 kA 600

9080LBC162101 N/A 9080LBC362101 N/A

9080LBC162104 9080LBC262104 9080LBC362104 2/0-6 4-14 200 200 200 100 60 30 100 kA 600

9080LBC163101 N/A 9080LBC363101 N/A

500-3/0 2-8 400 400 400 200 60 30 100 kA 600


9080LBC163106 9080LBC263106 9080LBC363106
2/0-4 2-14 200 200 200 100 60 30 100 kA 600

(2)2/0-2 4-8 400 400 400 100 60 30 100 kA 600


9080LBC163206 9080LBC263206 9080LBC363206
(2)4-6 10-14 200 200 200 100 60 30 100 kA 600

(2)500-250 2/0-4 600 600 400 200 60 30 100 kA 600


9080LBC165208 N/A 9080LBC365208 600 600 N/A N/A N/A N/A 50 kA 600
(2)4/0-4 2/0-6
400 400 400 200 60 30 100 kA 600

600 600 600 – – – 50 kA 600


(2)500-250 2-8
400 400 400 200 60 30 100 kA 600
9080LBC165212 N/A 9080LBC365212
600 600 – – – – 50 kA 600
(2)4/0-4 2-14
400 400 400 200 60 30 100 kA 600

23
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks
Index of Catalog Numbers

Index of Catalog Numbers

9080FB1211 9 9080LB21 3, 7 9080LBA362101 3


9080FB1211R 9 9080LB22 3, 7 9080LBA362104 3
9080FB1221 11 9080LB23 3, 7 9080LBA362106 7
9080FB1221R 12 9080LB31 4, 7, 8 9080LBA363101 4
9080FB1231R 13 9080LB32 4, 8 9080LBA363104 4
9080FB1611 9 9080LB33 4, 7, 8 9080LBA363106 4
9080FB1611CC 10 9080LB41 5 9080LBA363206 4
9080FB1611J 10 9080LB42 5 9080LBA364101 5
9080FB1611M 10 9080LB43 5 9080LBA364108 5
9080FB1611R 9 9080LB51 5, 6, 8 9080LBA365106 5
9080FB1621 11 9080LB52 5, 6 9080LBA365112 5
9080FB1621J 12 9080LB53 5, 6, 8 9080LBA365202 6
9080FB1621R 12 9080LBA161101 3 9080LBA3652021 6
9080FB1631R 13 9080LBA161104 3 9080LBA365208 6
9080FB2211 9 9080LBA162101 3 9080LBA365212 6
9080FB2211R 9 9080LBA162104 3 9080LBC162101 7
9080FB2221 11 9080LBA163101 4 9080LBC162104 7
9080FB2221R 12 9080LBA163104 4 9080LBC163101 7
9080FB2231R 13 9080LBA163106 4 9080LBC163106 8
9080FB2611 9 9080LBA163206 4 9080LBC163206 8
9080FB2611CC 10 9080LBA164101 5 9080LBC165208 8
9080FB2611J 10 9080LBA164108 5 9080LBC165212 8
9080FB2611M 10 9080LBA165106 5 9080LBC262104 7
9080FB2611R 9 9080LBA165112 5 9080LBC263106 8
9080FB2621 11 9080LBA165202 6 9080LBC263206 8
9080FB2621C 11 9080LBA1652021 6 9080LBC362101 7
9080FB2621J 12 9080LBA165208 6 9080LBC362104 7
9080FB3211 9 9080LBA165212 6 9080LBC363101 7
9080FB3211R 9 9080LBA261104 3 9080LBC363106 8
9080FB3221 11 9080LBA262101 3 9080LBC363206 8
9080FB3221R 12 9080LBA262104 3 9080LBC365208 8
9080FB3231R 13 9080LBA263101 4 9080LBC365212 8
9080FB3611 9 9080LBA263104 4
9080FB3611CC 10 9080LBA263106 4
9080FB3611J 10 9080LBA263206 4
9080FB3611M 10 9080LBA264108 5
9080FB3611R 9 9080LBA265106 5
9080FB3621 11 9080LBA265112 5
9080FB3621J 12 9080LBA265202 6
9080FB3621R 12 9080LBA2652021 6
9080FB3631 13 9080LBA265208 6
9080FB3631C 13 9080LBA265212 6
9080FB3631R 13 9080LBA361101 3
9080FBDIN3 7, 9, 10 9080LBA361104 3

24
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks

25
© 1993 – 2010 Schneider Electric 08/2010
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Terminal Blocks

26
08/2010 © 1993 – 2010 Schneider Electric
All Rights Reserved

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com
Schneider Electric USA, Inc. Square D® and Schneider Electric® are trademarks or registered trademarks of Schneider Electric
8001 Knightdale Blvd. or its affiliates. Other trademarks used herein are the property of their respective owners.
Knightdale, N.C. 27545, USA
1-888-Square D 9080CT9603R0710 © 1993 – 2010 Schneider Electric All Rights Reserved
1-888-778-2733 9080CT9603R09/08 Dated 4/2009
www.schneider-electric.us 9080CT9603 Dated 2/1997
08/2010

Courtesy of Steven Engineering, Inc.-230 Ryan Way, South San Francisco, CA 94080-6370-Main Office: (650) 588-9200-Outside Local Area: (800) 258-9200-www.stevenengineering.com

Вам также может понравиться