Вы находитесь на странице: 1из 2

Power Factor & Phase Angle Meters

Featrues
True power system design compliants
ANSI-IEEE, IEC & VDE standards
High over capability to assure reliable operation
High accuracy 0.5%
Display with super rate LED
Applied rules & standards
Measuring & conversion IEC 688
Dielectric strenth IEC 688
Impulse & Surge test ANSIc37.90/1989, IEC 255-3
Adaptability=powersystm IEC 0110
Measuring reliability VDE 3540
Specification
Model MP & ML Power factor and Phase angle meters, designed of a balance type with universal & flexible application
feature, can be applied to measure single phase 2 or 3 wires, 3 phase 3 wires & 3 phase 4 wires only under the
specified terminal connection. The units accept ac voltage & current inputs with detection of phase relation between the
measured phase voltage & phase current of power factor COSØ for MP & phase angle for ML. The designed specifica-
tions compliant ANSI, DIN & VDE standards with full protection for unusual surge intrusion and input over assuring
reliable operation.
Specification
Accuracy (23± 3°C) 0.5%fs + 0.2° > 20% input current, 0.5%fs + 0.4° >10% input current
Stability Temperature coefficient <50 ppm per degree c, long term draft <0.2% per year
Display & resolution 0.56” super rate LED, 0.001-0.999 for PF, 0.010-360.0 degree for phase angle
Response time Sample rate 1 of per sec. typically
Input over Current input:3xrating-continuous, 10x rating-30 sec., 25x rting-3 sec.
Voltage input : max continuous 750V or 1.5 rating which ever great
Frequency 47-70 Hz
Dielectric strength 2.5KVrms/1 min, all terminals to case, 2KVrms/1 min input vs power terminals
Surge test ANSI C37.90/1989, IEC 255-3 (1989)
Impulse Voltage 1.2x50us 4KV, oscillation wave 0.5us-100KHz 3KV or 1Mhz-0.25 ms 2.5KV
operating condition Temperature range -10 to 55°C, 0-99% RH non-condensed, storage -25 to 70°C
Auxiliary poer AC ± 15% < 6 VA DC ±20% < 6 watt
Order form
System Function Models
1 phase 2 wires Power Factor MP
3 phase 3 wires
3 phase 4 wires Phase Angle ML
Frame ( in mm)
96x48 U
110x110 O
Auxiliary power
AC 110 V & 220V S
DC Option 12 V 1
DC Option 24 V 2
DC Option 48 V 3
DC Option 125 V 4
Voltage & Current Input
Defined range Effective rang
75-135V/0.5-5A 50-160V/0.2-0.75A 1 50-300V A
180-500V/0.5-5A 150-600V/0.2-7.5A 2 100-500V B
75-135V/0.1-1A 50-160V/0.05-1.5A 3 V-V input for phase angle
180-500V/0.1-1A 150-600V/0.05-1.5A 4 only
90-300V/2-20A 60-330V/0.5-25A 5
180-500V/2-20A 150-600V/0.5-25 6
Terminal connection........... Model MP / ML
Terminals 11(+),12(-),for DC power option

1phase 2 wires 3 phase 3 wires

Ms MI Pm Pn As AI Cs Cl P a Pb Pc

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
m n AC110V a b c AC110V
AC 220V AC 220V
Aux. Power Aux. Power
M A
N B
Source Load C
Source Load

3 phase 4 wires Ousi 3 phase 4 wires

As AI Bs BI Cs CI P a Pb Pc Pn As AI Bs BI Cs CI P a Pn

1 2 3 4 5 6 7 8 9 10 11 12 1 2 3 4 5 6 7 8 9 10 11 12
a b c n AC110V a n c AC110V
AC 220V AC 220V
Aux. Power Aux. Power
A A
B B
C C
N Source Load N Source Load

V - V input for phase angle only

+ - + -
1 2 3 4 5 6 7 8 9 10 11 12
V1 V2 AC110V
AC 220V
Aux. Power