Вы находитесь на странице: 1из 14

Liquid Level Controls

Contents

Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 2

General Information
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 5
Dimensions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 7

Probe Assemblies
Level Controls . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 3
Level and Resistance Controls . . . . . . . . . . . . . . . page 4
Probe Fittings . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . page 4
Probe Rod Assemblies . . . . . . . . . . . . . . . . . . . . . . page 4

Applications
Typical Control Ranges and Materials . . . . . . . . . page 9
Level and Resistance Sensing Ranges . . . . . . . page 11
Response Time . . . . . . . . . . . . . . . . . . . . . . . . . . . page 11

Selection Guide . . . . . . . . . . . . . . . . . . . . . . . . page 12

Replacement Parts . . . . . . . . . . . . . . . . . . . . . page 13

1
Liquid Level Controls
Series 13DJ3–3000

Description General Specifications


The 13DJ3 Series 3000 Conductive Power Consumption 3 watts (includes control base)
Liquid Level Control is designed to
provide a reliable level detection of Resistivity Range Typical liquid resistivity 0-60 MegOhms • centimeter (See Table 5)
conductive liquids or solids. No moving Resistance Sensing 0-15 MegOhms in six ranges
parts or floats are required. Metal probe Sensitivity Consult factory for higher ranges.)
rods are placed in the conductive liquid Maximum Probe Voltage 22.5 VAC (Ranges 1, 2, & 3), 29 VAC (Ranges 4, 5, & 6)
at the desired levels. The liquid or solid
conductive material completes the Maximum Probe Current 65 mA to .001 mA
circuit between the probe rod or rods to Solid State Output Signal 12 VDC open circuit limited to 30mA short circuit.
the metal material container. If the Terminals #5 and #2 on Control Base.
container is non-conductive (fiberglass, Speed of Response 0.003 sec. to 0.20 sec.
cement, etc.), an additional probe rod is
used as a grounding probe to complete Permissable Lead Length Up to 2,000′ (609.6m) Use #16 AWG wire minimum
the electrical circuit. Completion of the Ambient Temperature -40°C to 57°C (-40°F to 135°F)
circuit will cause the output relay to
operate. The relay contacts may be
used for pump, valve, or motor control; Resistance Sensing Control Features
audible and/or visual level indication. The 13DJ3 is also designed to be used S Very high sensitivity—up to 60
The controls will operate over a as a resistance sensing control. In this megohms cm liquid resistivity
resistivity range of 0 to 60 application the control operates as an
S Compact, all solid state, plug-in,
MegOhms-cm. This permits the sensing electronic switch which converts the
modular design for reliability with
of liquids or solids with very low minute current flow through delicate
flexibility
conductivity such as antibiotics, mechanisms or extremely light contacts
refrigerants, or sand with a moisture into a switching output capable of S DPDT EM relay and 12VDC solid
content as low as 5%. handling relatively heavy electrical state outputs (optional solid state
loads. The maximum sensitivity of the logic outputs)
In addition to high sensitivity, the control
control when used for resistance
has a fast response time and can be S Low probe voltage isolated from line
sensing is 15 megohms.
wired for electronic control latching on voltage
certain applications, allowing the use of S Fast response time
both sets of relay contacts for external
loads. S Wide selection of probe assemblies
A solid state output signal can be S All molded parts of rugged, impact
obtained from the control resistant NORYL
simultaneously with a relay output. This
S Heavy-duty easy to wire terminals
signal can be used for electronic
counting, data logging, or feeding S High voltage connections isolated
information to a computer. from low voltage
The control has protection against false S Ambient temperature range:
operation due to line voltage transients, –40°C to +57°C (–40°F to 135°F)
line voltage dropouts of 1/2 second or NORYL is a registered trademark of the General Electric
less, or during initial power up. These Company.
features allow the 13DJ3 Series 3000
Control to be used in solving the more
difficult industrial level applications.

2
Liquid Level Controls
Series 13DJ3–3000
Probe Assemblies

A selection of probe assemblies are required surface area at a point of for dairy and other food processing
available for a wide variety of contact with the liquid. Figure 1 shows installations. Sanitary probes do not
applications. The probe assembly typical probe assemblies. require probe tips for satisfactory
consists of a probe fitting threaded for Type 61 probe fittings are ceramic operation.
convenient installation into a tank, vat, insulated with stainless steel trim which Type 64 probe tip assemblies are
or other container; a stainless steel may be used either alone or in one of a combinations of a probe rod or
probe rod or insulated suspension wire variety of metal enclosures. Single and suspension wire of the desired length
which may be cut to the desired length double probe fittings are available. Type with a suitable probe tip and are used
for the particular installation; and a 63 sanitary probe fittings are available with all Type 61 probe fittings.
probe tip designed to provide the

Probes for Level Controls Types 61, 63, 64

Type 63GH1
and 63GH2
sanitary probe
fitting and rod
Type 61LF1
Type 61LF1 assemblies
probe fitting
probe fitting with Type
with 64MR1 suspension
Type 64CR1 Type 61LJ2
wire and tip
probe rod probe fitting Type 61BD1
and tip with probe fitting
Type 64CR1 with
probe rods Type 64CR1
and tips probe rod
and tip

3
Liquid Level Controls
Series 13DJ3–3000
Probe Assemblies

Level and Resistance Control


Output Characteristics
Bulletin Control Voltage Response Resistivity
Number Base Output Supply Type Rating Leakage Time Range
13DJ3-3000 Voltage 12DC/3.44 Ċ Ċ
120V AC
60-1600B Ċ Ċ Ċ
50/60Hz
240V AC
60-1601B Ċ Ċ Ċ
50/60Hz
8-670 DPDT 5A, 120V AC
supplied with EM 2.5A, 240V AC Ċ
control base Relay 1A, 120V DC Refer to
SPNO 1A, 265V AC Tables on page 11
8-651 1mA
Triac AC 20mA min.
SPNO 30mA,
8-652 10µA
FET AC/DC 120V AC/DC
Voltage 30mA,
63-116 Ċ
DC Output 24V DC
NPN Open 250mA,
63-115 1mA
Collector 24V DC

Probe Fittings
Bulletin Rods or Housing Fitting Maximum Maximum
Number Description Wires Used Material Pipe Thread Temperature Pressure PSI
Probe fitting with 250
61BD1-1000 1 None 1/2″
rubber cap (1,724 kPa)
61LF1-1000 Probe fitting in cast Bronze 200
1 1″
61LF1-1000M enclosure 316 Stainless Steel 149 C
149°C (1,378 kPa)
300°F 250
61LJ2-1000 Bronze
Two probe fittings in (1,724 kPa)
2 2″
cast enclosure 200
61LJ2-1000M 316 Stainless Steel
(1,378 kPa)
63GH1-1000 Special
p sanitaryy 1 Fits 1 1/2″
1/2 LAMD 13H nut
probe
b with
ith 00.91m
91 (3′) for #15 Union Ferrule
63GH2-1000 probe rod(s) supplied 2 100 C
100°C
with 3m (10′) cable None Ċ
63GJ1-1000 1 212°F
and separable Fits 2″
2 LAMD 13H nut for
63GJ2-1000 connector 2 #15 Union Ferrule

Probe Rod Assemblies


Bulletin
Number Description
64CR1-1000 316 Stainless Steel Probe Tip and 1/4″ dia. x 0.3m (12″) Probe Rod
64CR1-1001 316 Stainless Steel Probe Tip and 1/4″ dia. x 0.61m (24″) Probe Rod
64CR1-1002 316 Stainless Steel Probe Tip and 1/4″ dia. x 0.91m (36″) Probe Rod
64CR1-1003 316 Stainless Steel Probe Tip and 1/4″ dia. x 1.22m (48″) Probe Rod
64CR1-1004 316 Stainless Steel Probe Tip and 1/4″ dia. x 1.83m (72″) Probe Rod
64CR1-1005 316 Stainless Steel Probe Tip and 1/4″ dia. x 2.44m (96″) Probe Rod
64CR1-1006 316 Stainless Steel Probe Tip and 1/4″ dia. x 3m (120″) Probe Rod

4
Liquid Level Controls
Series 13DJ3–3000

Wiring Diagrams

Low Level Alarm Low Level Alarm


Self-latching With Push Button Reset
LINE VOLTAGE LINE VOLTAGE

INC 2NC INC 2NC


ALARM IN0 2N0 ALARM IN0 2N0
IC 2C IC 2C
L1 L2 L1 L2

13DJ3- MODEL 3000 13DJ3- MODEL 3000


PLUGĆIN PLUGĆIN
CONTROL MODULE CONTROL MODULE

1 8 1 8 N.C. RESET
2 7 2 7 SWITCH
3 0 3 0
RANGE 4 5
RANGE 4 5
RESISTOR RESISTOR

Single probe low level alarm. The relay is deĆenergized with Single probe low level alarm with electronic latching & push button reset. The
probe immersed and energized with probe out of liquid. Connections are relay is deĆenergized with probe immersed
shown for operation on ranges 1, 2 & 3. and energized with probe out of liquid. Connections are shown for ranges 1, 2 &
For operation on ranges 4, 5 & 6, connect range resistor to 3. For operation on ranges 4, 5 & 6 connect range resistor to terminal 4" instead
terminal 4" instead of terminal 3." of terminal 3."

High Level Alarm High Level Alarm


Self-latching With Push Button Reset
LINE VOLTAGE LINE VOLTAGE

INC 2NC INC 2NC


ALARM IN0 2N0 ALARM IN0 2N0
IC 2C IC 2C
L1 L2 L1 L2

13DJ3- MODEL 3000 13DJ3- MODEL 3000


PLUGĆIN PLUGĆIN
CONTROL MODULE CONTROL MODULE

1 8 1 8
2 7 2 7 N.C. RESET
3 0 3 0
SWITCH
+ RANGE
RANGE 4 5 *VOLTAGE 4 5
RESISTOR RESISTOR
OUTPUT
-
12VDC

Single probe high level alarm. The relay is deĆenergized with Single probe high level alarm with electronic latching & push button reset. The
probe immersed and energized with probe out of liquid. Connections are shown relay is deĆenergized with probe immersed
for operation on ranges 1, 2 & 3. and energized with probe out of liquid. Connections are shown for ranges 1, 2 &
For operation on ranges 4, 5 & 6, connect range resistor to 3. For operation on ranges 4, 5 & 6 connect range resistor to terminal 4" instead
terminal 4" instead of terminal 3." of terminal 3."

* 30mA max (not short circuit protected)

5
Liquid Level Controls
Series 13DJ3–3000

Wiring Diagrams
Pump Up Constant Level Control Pump Down Constant Level Control
LINE VOLTĆ LINE VOLTAGE
AGE

INC 2NC INC 2NC


PUMP IN0 2N0 PUMP IN0 2N0
IC 2C IC 2C
L1 L2 L1 L2

13DJ3- MODEL 3000 13DJ3- MODEL 3000


PLUGĆIN PLUGĆIN
CONTROL MODULE CONTROL MODULE

1 8 1 8
2 7 2 7
3 0 3 0
+
RANGE 4 5 *VOLTAGE RANGE 4 5
RESISTOR OUTPUT RESISTOR
-
12VDC

A double probe installation, used for pumpĆup constant level control. The relay is deĆenerĆ A double probe installation, used for pumpĆdown constant level control. The relay is enerĆ
gized when the upper probe is immersed and does not energize until the liquid drops below gized when the upper probe is immersed and deĆenergized when the liquid drops below the
the lower probe. Connections are shown for ranges 1, 2 & 3. For operation on ranges 4, 5 lower probe. Connections are shown for ranges 1, 2 & 3. For operation on ranges 4, 5 & 6
& 6 connect range resistor to terminal 4" instead of terminal 3." connect ground to terminal 4" instead of terminal 3."

* 30mA max (not short circuit protected)

For insulated tanks, a grounded third probe must be added as shown.


If an additional wire is run between the control ground and the third
probe, it should be grounded at the control.

Pump Down Constant Level Control


LINE VOLTAGE

INC 2NC
PUMP IN0 2N0
IC 2C
L1 L2

13DJ3- MODEL 3000


PLUGĆIN
CONTROL MODULE
1 8
2 7
3 0
RANGE 4 5
RESISTOR

A double probe installation, used for pumpĆdown constant level control. The relay is
energized when the upper probe is immersed and deĆenergized when the liquid drops
below the lower probe. Connections are shown for ranges 1, 2 & 3. For operation on
ranges 4, 5 & 6 connect range resistor to terminal 4" instead of terminal 3."

For insulated tanks, a grounded third probe must be added as shown.


If an additional wire is run between the control ground and the third
probe, it should be grounded at the control.

6
Liquid Level Controls
Series 13DJ3–3000

Dimensions—mm (inches)
NEMA 1 #61–3322–3 NEMA 3, 4, 5, 12 & 13
3.938
.875 (22.2)
#61–4090
(100)
* * 4 .375
(101.6) (9.5)

5.938
(150.8)
8.25
5.25 7.25 (209.5)
(133.4) (184.1)
.188 8.75
(4.8) (222.2)
9.5
* * (241.3)

.812 .375
(20.6) (9.5) .688
4.875 (17.5)
(123.8)
5.938 .312 (7.9)
(150.8) HOLE (4)

6.25 .625 (15.9)


(158.7)

*
.875 DIA. (22.2)
3.875
(98.4)
8 K.0.'S TOTAL
* 4.875
(123.8)
.375 1.063
(9.5) TYP.
1.188 (27)
(30.2)

Open Type .531 2.375


(13.5) (60.3)
.031 EITHER MAY BE USED FOR
(.8) THIRD MOUNTING HOLE .375
(9.5)

5.25
(133.3)

4.781 #8 SCREW
(121.4) TERMINALS
(16)

4 MTG. HOLES
.185 DIA.
(2.54)
2.25
.25 1.25 (57.1)
(31.7)
2.5 3.625
(63.4) (92.1)
3.125 WITH INSTALLED PLUGĆIN MODULE
(79.4)

7
Liquid Level Controls
Series 13DJ3–3000

Dimensions—mm (inches)
61 Series Probe Assemblies
2.875 DIA.
(73)

1.812
(46)
L H
1.812 (46)

3.5
(88.9)

.5 (12.7) VIEW WITH


1/2-14 NPT COVER REĆ

ÉÉÉ
MOVED
2.125 DIA. VIEW WITH
(54)

ÉÉÉ
COVER REĆ
3.125 DIA.
MOVED
(76.2)

ÉÉÉ ÇÇÇÇ
1/2-14
1/2-14 NPSC

ÉÉÉ ÇÇÇÇ
NPSC
1/4-20 NC2 2.437
(61.9)
1

ÉÉÉ ÇÇÇÇ
(25.4) WEEP HOLES
(3) 2.438

ÉÉÉ ÇÇÇÇ
.375 (9.5) (61.9)

ÇÇÇÇ
.625 (15.9)
.812 (20.6) 1-11 1/2

ÇÇÇÇ
NPT
.625 (15.9)
2-11 1/2
61BD1 61LF1 NPT

61LJ2

63 Series Probe Assemblies 64 Series Probe Assemblies


PROBE WIRE
#13-H UNION NUT TO CONTROL
(SUPPLIED BY CUSTOMER)

1/4-20 NC2

POLARIZED .312 (7.9) HEX NUT,


CONNECTOR NO. 316 S.S.
(TO PREVENT 1.25
INTERCHANGING (31.8) 61-3285 .75
OF PROBE WIRES) *NOTE: ADAPTER (19)
FOR TYPES 63GJ1 NO. 316 S.S. 1/4-20 UNC
AND 63GJ2 7/16 HEX (11.1)
USE 2″ FITTINGS
PROBE
INSULATOR 58-66
FOR TYPES 63GH1
.281 DIA. (7.1)
AND 63GH2
NO. 16 S.S.
USE 1 1/2″ FITTINGS
WIRE,
LENGTH TO BE INSULATED A" DIM.
SPECIFIED BY WITH GEON .25 DIA.
CUSTOMER (6.35)
#15 UNION FERRULE
(SUPPLIED BY CUSTOMER) 61-3284
.875 DIA. (22.2)
PROBE TIP
NO. 316 S.S. .562 DIA.
INSULATED (14.3)

SOLDER FERRULE 6
TO TANK FOR (152.4)
MOUNTING 2
1.125 (50.8)
FITTING PROBE (28.6)
(CUT TO LENGTH
INSULATOR ON INSTALLATION)
(TO PREVENT
PROBE RODS
FROM TOUCHING)

TYPE 63GJ1 TYPE 63GJ2 64CR1


63GH1 63GH2

8
Liquid Level Controls
Series 13DJ3–3000
Applications

Typical Control Ranges and Probe Materials


Concentration Resistivity Range Suitable Probe
Typical Liquid (% by Weight) (ohms cm) Ê Control Range Material Ë
Acetate Acid 5-50 600-1,300 2 HC
Ammonia 6.4-15 1,000-2,000 2 SS
Ammonium Chloride 5-25 2-10 1 HB, HC
Ammonium Iodide 10-50 2-12 1 SS
Ammonium Nitrate 5-50 3-20 1 SS
Ammonium Sulfate 5-30 5-20 1 HC
Antibiotics 200,000-2 MΩ 5 SS
Barium Chloride 10-25 5-15 1 SS
Barium Nitrate 4.2-8.4 30-50 1 SS
Beer 200-2,000 1 or 2 SS
Butyric Acid 1-20 1,000-2,000 2 SS
Cadium Bromide 5-30 35-100 1 SS
Cadium Chloride 5-50 30-60 1 SS
Cadium Iodide 5-45 30-160 1 SS
Cadium Nitrate 5-48 10-20 1 SS
Cadium Sulfate 5-36 20-70 1 SS
Calcium Chloride 5-35 5-15 1 SS
Calcium Nitrate 6-50 10-20 1 SS
Copper Chloride 10-35 10-15 1 HB, HC
Cupric Nitrate 10-35 10-15 1 SS
Cupric Sulfate 2.5-17.5 20-100 1 SS
Distilled Water 20,000-200,000 3 SS
Formic Acid 5-60 100-200 1 SS
Hydrobromic Acid 5-15 2-5 1 HB
Hydrochloric Acid 5-40 1-5 1 HB
Hydrofluoric Acid 5-30 3-20 1 M, HC
Hydroiodic Acid 5 8 1 SS
Lead Nitrate 20-30 15-20 1 SS
Lithium Carbonate 0.2 300 1 SS
Lithium Chloride 5-40 5-15 1 SS
Lithium Hydroxide 1.25-7.5 4-12 1 SS
Lithium Iodide 10-25 5-20 1 SS
Lithium Sulfate 5 25 1 SS
Magnesium Chloride 5-28 10-20 1 M
Magnesium Nitrate 10-17 10-12 1 SS
Magnesium Sulfate 5-25 20-40 1 SS
Mercuric Bromide 0.223-0.422 40,000-60,000 3 SS
Milk 200-2,000 1 or 2 SS
Nitric Acid 5-60 1-5 1 SS
Oxalic Acid 3.5-7 12-20 1 SS
Phosphoric Acid 10-87 5-20 1 HC
Potassium Acetate 10-30 4-18 1 SS
Potassium Bromide 10-36 2-10 1 SS
Potassium Carbonate 5-50 5-20 1 SS
Potassium Chloride 5-20 4-18 1 SS
Potassium Cyanide 3-6 1-20 1 SS

9
Liquid Level Controls
Series 13DJ3–3000
Applications

Typical Control Ranges and Probe Materials (continued)


Concentration Resistivity Range Suitable Probe
Typical Liquid (% by Weight) (ohms cm) Ê Control Range Material Ë
Potassium Fluoride 5-40 5-15 1 SS
Potassium Hydroxide 5-40 2-5 1 M
Potassium Iodide 10-55 5-18 1 SS
Potassium Nitrate 10-20 5-12 1 SS
Potassium Oxalate 10 11 1 SS
Potassium Sulfate 10 12 1 M
Potassium Sulfide 5-50 2-10 1 SS
Propionic Acid 5-30 900-1,200 2 M
Refrigerants 2MΩ-20MΩ 5 or 6 SS
Silver Nitrate 10-60 5-20 1 SS
Sodium Acetate 20-30 15-18 1 SS
Sodium Carbonate 5-15 10-20 1 SS
Sodium Chloride 5-25 5-15 1 SS
Sodium Hydroxide 20-50 5-20 1 M
Sodium Iodide 10-40 5-20 1 SS
Sodium Nitrate 10-30 7-12 1 SS
Sodium Sulfate 10-15 8-12 1 SS
Sodium Sulfide 2-18 5-20 1 SS
Strontium Chloride 10-20 5-12 1 SS
Strontium Nitrate 10-40 10-15 1 SS
Sulfuric Acid 5-50 1-10 1 HC
Synthetic Latex 2MΩ-20MΩ 6 SS
Tapwater 2,000-20,000 3 SS
Zinc Chloride 10-40 10-15 1 M
Zinc Sulfate 5-30 20-100 1 SS
Ê Measured at normal room temperature
Ë Suitable Probe Materials
SS = 316 Stainless Steel (standard)
M = Monel
HB = Hastelloy B2
HC = Hastelloy C

10
Liquid Level Controls
Series 13DJ3–3000
Applications

Level and Resistance Sensing Ranges


Liquid Resistivity Resistance Range Maximum Maximum Typical
Range (ohms/cm) Sensing Resistor Volts Current Solutions
j - Orange
Acids
j - Orange
1 0 - 600 0 - 150Ω 22.5 VAC 65 mA Bases
j - Brown
Salts
330Ω
j - Red
Beer
j - Violet
2 600 - 6,000 150 - 1,500Ω 22.5 VAC 8.33 mA Milk
j - Red
Water
2,700Ω
j - Red
Water
j - Violet
3 6,000 - 60,000 1,500 - 15,000Ω 22.5 VAC .83 mA Alcohols
j - Orange
Distilled Water
27,000Ω
j - Red
Alcohols
j - Violet
4 60,000 - .6MΩ 15,000 - 150,000Ω 29 VDC .1 mA Ammonia
j - Yellow
Distilled Water
270,000Ω
j - Red
j - Violet Antibiotics
5 .6MΩ - 6MΩ 150,000 - 1.5MΩ 29 VDC .01 mA
j - Green Refrigerants
2.7MΩ
j - Red
j - Violet Refrigerants
6 6MΩ - 60MΩ 1.5 - 15MΩ 29 VDC .001 mA
j - Blue Synthetic Latex
27MΩ
Note: All range resistors are 1/2 W ± 10% except Range 1, which is 2 W.

Response Time (seconds)


Solid State Output Relay Output
Range On Off On Off
1 0.003 0.060 0.012 0.070
2 0.0035 0.060 0.013 0.070
3 0.004 0.060 0.014 0.070
4 0.006 0.060 0.018 0.070
5 0.023 0.060 0.033 0.070
6 0.190 0.190 0.200 0.200

11
Liquid Level Controls
Series 13DJ3–3000

Selection Guide
1. Select 13DJ3–3000
2. Select Control Base
SeriesNumber Voltage Supply Description
60-1600B 120 VAC Open Type
60-1610B 50/60 Hz NEMA 1 Enclosure
60-1601B 230 VAC Open Type
60-1611B 50/60 Hz NEMA 1 Enclosure
For NEMA 3, 4, 12, and 13; order open type base and 61-4090 enclosure.

3. Select Probe Fitting


SeriesNumber Description Rods or Wires Used
61BD1-1000 Probe fitting with rubber cap
61LF1-1000 1
Probe fitting in cast enclosure
61LF1-1000M
61LJ2-1000 Two probe fittings in
2
61LJ2-1000M cast enclosure
Note: 61 Series probe fittings require suitable Series 64 probe tips and probe rod or suspension wires shown below.
63GH1-1000 1
63GH2-1000 Special sanitary probe with 0.91m (3′)
(3 ) probe rod(s) supplied with 2
63GJ1-1000 3m (10′) cable and separable connector 1
63GJ2-1000 2

4. Select Probe Rod Assemblies for 61 Series Probe Fittings


SeriesNumber Description
64CR1-1000 Probe Tip and 1/4″ dia. x 0.3m (12″) Probe Rod
64CR1-1001 Probe Tip and 1/4″ dia. x 0.61m (24″) Probe Rod
64CR1-1002 Probe Tip and 1/4″ dia. x 0.91m (36″) Probe Rod
64CR1-1003 Probe Tip and 1/4″ dia. x 1.22m (48″) Probe Rod
64CR1-1004 Probe Tip and 1/4″ dia. x 1.83m (72″) Probe Rod
64CR1-1005 Probe Tip and 1/4″ dia. x 2.44m (96″) Probe Rod
64CR1-1006 Probe Tip and 1/4″ dia. x 3m (120″) Probe Rod

12
Liquid Level Controls
Series 13DJ3–3000
Replacement Parts

Replacement Parts
Part Number Description Application
3-170 Rubber Cap For 61BD1
21-49-1 For 63GH2 - 63GJ2
Connector and 3m (10′) Cable Assembly
21-50 For 63GH1 - 63GJ1
Separates double probes when the long probe
31-224 1 1/2″ diameter Teflon Spacer
exceeds 30″ (76.2cm)
33-287 1/4-20 UNC Hex Nut Used with 64CR1 probe assemblies
58-66 Insulation Suspension Wire Used when the required probe length exceeds 3m (10′)
61-3284 316 SS 5/8″ diameter Suspension Wire Probe Tip Used when the required probe length exceeds 3m (10′)
61-3285 316 SS Adaptor Connects suspension wire to 61 Series probes
61-3288 316 SS 9/16″ diameter Probe Tip Required on all probe rods for rated sensitivity
61-3519 Resistor Package For 13DJ3-3000

61BD1 Model 1000 Also Used in 61LF1–61LJ2 all Models

No. 3-170
Rubber Cap

Suspension Wire
Adaptor and Probe Tip Assembly

Suspension Wire
Adaptor
No. 61-3285

Part No. 33-287

Probe Rod

Suspension Wire
No. 58-66
Order Separately
and Specify
Required Length

*Part No.
31-224

Probe Tip
No. 61-3288
Probe Tip Assembly
No. 61-3284

*Available as Optional Extra with Double Probe Assemblies,


When Either Rod Exceeds 30 Inches in Length.

13