Design for Seismic Tie Beams

Per ACI 318-08 section 21.12.3.2 – “Grade beams designed to act as horizontal ties between pile caps or
footings shall be proportioned such that the smallest cross-sectional dimension shall be equal to or greater
than the clear spacing between connected columns divided by 20 but need not be greater than 18 inches.
Closed ties shall be provided at a spacing not to exceed the lesser of one half the smallest orthogonal cross-
sectional dimension and 12 inches.”

But ACI is not telling us that what force these tie beams should be designed for, so here is the IBC 2009
section to tell us that:

IBC2009 section 1809.13 for shallow foundations and 1810.3.13 for deep foundations:

for SDC C, D, E or F, ties shall be capable of carrying, in tension or compression, a force equal to the lesser of
the product of the larger pile cap or column design gravity load times the seismic coefficient, Sds,divided by
10, and 25 percent of the smaller pile or column design gravity load. (there is more in this section so please
read the code before applying this to your case)