Вы находитесь на странице: 1из 9

IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO.

3, JULY 2007 1309

Virtual Instrument for Lightning Impulse Tests


A. Palani and V. Jayashankar, Member, IEEE

Abstract—We propose an objective formulation of the impulse II. REQUIREMENTS OF AN ANALYSIS SYSTEM
analysis problem from a signal analysis viewpoint. The winding
response is quintessentially that of a deterministic network to a In proposing any new method for analysis, the following con-
finite energy signal, with breakdown and partial discharge being ditions need be met. It must:
inherently nonlinear events. A significant improvement to the ac- • be capable of addressing different waveforms at reduced
quisition of waveforms is demonstrated by a virtual instrument ap- and full voltage;
proach. It retains the advantages of the time- and frequency-do- • objectively distinguish partial discharge from failure;
main methods. The drawbacks of the transfer function method are
highlighted and a new piecewise linear approach is proposed for • reproduce existing results in a comparable or better
analysis. Experiments on a discrete lumped parameter model of manner;
the winding are used to validate the PXI based instrument. • be consistent implying that results are valid for simple
Index Terms—Breakdown, extrapolation, impulse test, partial
breakdown events.
discharge, virtual instrument.
III. SIGNAL ANALYSIS PRELIMINARIES
The standard 1.2/50 lightning impulse (LI) excitation,
I. INTRODUCTION which is usually produced from a Marx generator can be written
in the form

T HE impulse test on a transformer is a routine test for trans-


formers of 132 kV and above. The test procedure has a
fairly long history and involves the application of a sequence
(1)

of voltages from a Marx generator. The procedure is covered where “a” and “b” are adjusted to produce a 1.2/50 wave-
in standards such as IEC 60076—pt.IV [1]. As a winding is a form. Similarly, the wave shape chopped on the tail (CLI) can
complex structure from a dielectric viewpoint, failure detection be written in the form
during the test is fairly involved. This can be gauged from the
fact that both IEC and ANSI have separate guidelines for failure (2)
identification. The earliest approach involved the visual compar-
Both the signals are finite energy deterministic signals with
ison of current and voltage records obtained on impulse oscil-
loscopes. The drawbacks with this approach were the need to
(3)
have identical wave shapes at reduced and full voltage, and the
subjective nature of comparison. Digital techniques [2], [3] have
been increasingly used for recording waveforms during impulse For such signal, a Fourier transform exists and one can compute
testing. In principle, subjective evaluations could be avoided the frequency domain equivalent as
with such records. However, it is observed that the responses of
the winding to varying wave shapes such as the standard light- (4)
ning impulse (LI) and chopped impulse (CLI) cannot be com-
pared with time domain records alone. The transfer function By Parseval’s relation, it is also known that
approach [4] was proposed to overcome these drawbacks. The
method is not yet mandatory as per standards and some prob- (5)
lems do exist with the method.
Irrespective of the methods of acquisition, limitations exist in Tolerances exist on the front and tail of the LI and the time
the failure identification techniques. They are: to chop of the CLI. Fig. 1(a) shows the typical LI with a peak
• lack of an objective criterion for distinguishing PD from value of 1 V and Fig. 1(b) shows its normalized frequency do-
breakdown; main equivalent. Fig. 2(a) and (b) shows corresponding wave-
• lack of objective identification criteria for breakdown with forms for the CLI. The excitation in the frequency domain as
LI and CLI waveforms. shown in Figs. 1(b) and 2(b) gives an indication of the absolute
In this work, we proceed from first principles and propose an frequencies involved. The frequency domain records have been
approach based on signal analysis. normalized such that the maximum value of each waveform oc-
curs at 0 dB.
Manuscript received June 29, 2006. This work was supported by the MHRD, The device under test is a transformer winding and for the
India. Paper no. TPWRD-00361-2006. frequencies of interest can be considered as a lumped param-
The authors are with the Department of Electrical Engineering, IIT Madras,
Chennai, India (e-mail: tamilpalani@iitm.ac.in; jshankar@ee.iitm.ac.in). eter model of the form of Fig. 3 [5], [6]. IEC-60076 treats the
Digital Object Identifier 10.1109/TPWRD.2007.900089 device as a single-input single-output (SISO) system with the
0885-8977/$25.00 © 2007 IEEE
1310 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 1. LI excitation in time and frequency domain.


Fig. 5. Modal equivalent circuit of 400-kV transformer [Glaninger’86].

To simulate PD the classical “ ” model is used with the


time of discharge “ ” being of the order of tens of ns to 5 [7].
A nonlinear element is required to simulate arresters. Which are
sometimes placed across sections of the winding. The values of
Ls, Rs, Cs, and Cg are derived from the geometry of the winding.

IV. FORMULATION OF THE PROBLEM


Although a number of papers have appeared in the recent
Fig. 2. CLI excitation in time and frequency domain.
times on impulse testing, the drawback with several of them is an
inconsistent formulation. For example, several do not consider
all classes of faults, or involve hypothetical fault models with no
experimental results or do not state the resolution of the method.
Recently a comprehensive fault model [8] was proposed to cater
to all faults that can occur during imputes tests. Experimental
results to corroborate the model were demonstrated in [9]. It
is well known that a lumped parameter model can be used to
characterize the high frequency behavior of a winding [10]. We
hence formulate the impulse analysis problem in the following
manner. “Given a lumped parameter model of a winding, sub-
ject to a class of inputs, and a set of fault models, the objective
of analysis is to identify if the device withstood the test, break-
down occurs or discharge occurs or a nonlinear element exists
within”, measuring system for LI.

V. MEASURING SYSTEM FOR LI TESTS


The current standard for the LI test treats the winding as an
SISO system. Here, the applied voltage is the excitation and the
Fig. 3. Lumped parameter model of a winding.
winding current is the response. Since the input is a finite
energy signal across a deterministic model, the response is
also a finite energy signal. Its energy can be computed in time
and frequency domain.
Consider the modal equivalent of a 400-kV transformer re-
ported by Glaninger [11], as shown in Fig. 5. It is energized
with a pulse, 1.2/50 LI. The current response
is as shown in Fig. 6. The frequency domain equivalent of the
current is shown in Fig. 7. The resonance and anti-resonance
Fig. 4. Schematic representation of faults. frequencies of the winding marked as and
respectively. The distribution of energy
until (9 kHz) is 94.808%, from to (between
stimulus as v(t) and the response is i(t). In order to study anal- 10 to 80 kHz) is 5.094% and after is 0.098%.
ysis methods, faults are placed across any two nodes or a node to The main aim of impulse test analysis is to identify break-
ground. The types of faults are shown in Fig. 4. In brief, break- down events and hence it would be appropriate to acquire sig-
down is simulated by a switch, which closes at “ ” and stays nals associated with breakdown as accurately as possible. With
“ON” for the duration of the response. present digitizers, it is feasible to sample low frequency signal
PALANI AND JAYASHANKAR: VIRTUAL INSTRUMENT FOR LI TESTS 1311

Fig. 8. Block diagram of lightning impulse test measuring system (DUT: de-
vice under test).

Fig. 6. A 400-kV transformer winding current for a 01000 kV LI.

Fig. 9. Ten section physical model of a winding with discrete elements.

LabVIEW environment provides such a facility. Thus our pro-


posal is to incorporate an analog front end with programmable
filters. This is followed by three A/D converters with different
resolutions. A further stage of digital filtering follows the A/D
converter helps to reduce noise level. This filter can now have a
much higher order approaching ideal brick wall.

VI. VALIDATION OF PROPOSED INSTRUMENT


In order to validate the proposed hardware, it is necessary
Fig. 7. Normalized winding current of 400-kV transformer. to perform controlled measurements. We hence construct a
physical model of a uniform layer winding. The validity of this
model has been proved by a number of investigators [15], [16].
with good vertical resolution. It would thus be appropriate to This consists of discrete inductors, capacitances to ground and
acquire the low frequency response with a separate digitizer. In capacitance across sections. The 10-node physical model is
order to decide on the cut off frequency, one can study the cur- shown in Fig. 9. Here, Rs (18 ) represents the resistance of
rent response in the frequency domain as seen in Fig. 7. The first the winding, Ls (2.5 mH) its leakage inductance, Cs (150 pF)
anti-resonant frequency forms a natural separation of low and capacitance across sections and Cg (850 pF) ground capaci-
high frequency responses. Thus one could choose the cutoff of tance, which would complete the equivalent circuit. The main
this filter to be below . From an analysis of the PD events advantage of the discrete element model is that controlled
in literature [12], [13] and [14] it is known that PD events can experiments involving breakdown and partial discharge are
occur from 1 ns to a few microseconds ( ). Hence it would be possible. It is energized with an exponentially decaying voltage,
appropriate to have one digitizer that can sample at the highest v(t) (with a peak value of 10V) similar to the standard 1.2/50
frequencies. The choice is dictated by available hardware and LI wave shape. The winding current (which is the response
with existing technology 1 GSa/s at 8 bits seems feasible with of the system) is monitored in a current viewing resistor, Rm.
many oscilloscopes. A high-pass filter can be utilized so that Figs. 10 and 11 show the time-domain and frequency-domain
high temporal resolution is possible. It is known that the location responses of excitation and winding current.
of the poles shift during breakdown events. Hence an interme- The energy distribution of current in the physical model is
diate band pass filter would complete the requirement. In effect • (upto 20 kHz) ;
we are proposing a hardware acquisition with three analog fil- • to (20 to 114.5 kHz) ;
ters in the front end. The schematic of the proposed instrument • Greater than (114 to 500 kHz) .
is shown in Fig. 8. F1, F2, and F3 are three analog filters, of the The low-frequency response provides a good indication of
Bessel type. A1, A2 and A3 are analog gain stages. Three A/D breakdown as was shown in the earlier section. It is known that
converters with different resolutions and sampling rates follows the location of the fault can be estimated based on changes in
the analog section. The improvement due to this scheme are de- the resonant frequency [17]. Hence, band pass filter F2 provides
scribed in Appendix A. an indication of the location of the fault. Some events such as
Analysis involves time and frequency domain computation. It partial discharge or minor structural deformations affect the cur-
would be convenient if the instrument incorporated with a bus rent signal at high frequency region. Hence, filter F3 is designed
based architecture such as a PXI bus with software support. A to acquire such events.
1312 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 12. Simulating breakdown across resistive elements.

In order to demonstrate the utility of the instrument, fault


studies are conducted. To simulate breakdown, a wire is placed
across the two nodes 4–5 of the model. The front panel of the
Fig. 10. Stimulus and winding current through 10-section discrete element virtual instrument as in Fig. 24 shows the current in the model
physical model. with and without breakdown (BD), in window B. The response
across the LPF (F1) is shown in window D. The corresponding
frequency domain record is shown in window G. The response
of band pass filter with and without fault is shown in window E.
The shift of resonant frequencies is evident in window H.
In order to simulate PD, an arbitrary function generator con-
nected to an analog switch, which is placed across the capac-
itor “a” of the “abc” model of Fig. 4. Here, ` ' ,
` ' and ` ' . The time and frequency records
with and without partial discharge are shown in window F and
I. From I it is evident that the presence of PD changes the high
frequency response of the winding.

VIII. IMPROVEMENTS IN IMPULSE ANALYSIS


In the previous section, experimental investigations were
Fig. 11. Normalized frequency domain equivalent of Fig. 10. done by shorting a wire across nodes in order to simulate
breakdown. In practice breakdown occurs after a finite time
from the initiation of excitation. This was seen in the examples
shown in [10]. This has a very significant influence on the esti-
On the basis of Section V, the physical model under consider-
mation of parameters during the impulse test. For example, the
ation, F1 cutoff frequency is 3 kHz, F2 is a BPF with lower and
computation of the transfer function [2] implicitly assumes that
upper cutoffs of 10 kHz and 130 kHz, and F3 is a HPF with a
the device under test continues to be linear during breakdown.
cutoff of 120 kHz. The resolutions of the three digitizers A/D1,
We demonstrate the limitations of this approach in Section IX.
A/D2 and A/D3 that follow the front end analog filters are dif-
ferent and are chosen in accordance with optimal requirements.
The low frequency digitizer has a resolution of 24 bits with a IX. LIMITATION OF THE TRANSFER FUNCTION METHOD
maximum sampling of 102 kSa/s. The second digitizer which We show the limitations of the transfer function approach by
typically has a bandwidth of 500 kHz has a vertical accuracy of considering a simple resistive circuit with two elements. We ini-
12 bits with a sampling of 1.2 MSa/s. The third digitizer has a tially consider a circuit with two resistors R1 and R2 each of
bandwidth of 100 MHz and is sampled at 200 MSa/s. 10 , as shown in Fig. 12. A LI voltage of 10 V is applied
across them and the current through them noted. The current
VII. RECOGNITION BREAKDOWN AND PARTIAL DISCHARGE is shown in Fig. 13. Let be the current in the circuit when
energized by . The transfer function .
The design as proposed in Fig. 8 was implemented on a PXI Let be the current with a break down at 5 . The break-
system. Fig. 24 in Appendix B shows the front panel of the pro- down is simulated with an analog switch that closes at 5 and
posed instrument. The three digital filters following analog fil- stays closed for the duration of the response. Similarly faults
ters are implemented in LabVIEW. The cutoff of the three filters are created at 20 , 30 etc. and these currents are shown
is adapted to the resonant behavior of the winding. Windows in in Fig. 14. The normalized frequency domain representation of
Fig. 24 are marked . Here, A shows the applied LI currents with no fault, , and is
input and B and C show the time and frequency domain views of shown in Fig. 15.
the winding current without filter as in the conventional method. The transfer functions computed with faulted waveform are
Windows D, E, and F show the responses across F1, F2, and F3. . From Fig. 16 we see that the transfer
The corresponding frequency domain views are in G, H, and I. function is modulated by the fault and the response is different
PALANI AND JAYASHANKAR: VIRTUAL INSTRUMENT FOR LI TESTS 1313

Fig. 13. Unfaulted current, i(t), through the resistive network (excitation 10 V Fig. 16. Computed transfer functions from Figs. 14 and 15.
LI).

Fig. 17. PWL approach to extrapolate the 5 s faulted response.

Fig. 14. Current in the resistive network with fault at various time instants.

Fig. 18. Transfer function with conventional and PWL approach (t = 5 s).

Fig. 15. Frequency-domain representation of Fig. 14. . As shown in Fig. 18, this transfer func-
tion matches what one would expect for the circuit.

from what is intuitively obvious for such a circuit. Although X. GENERALIZATION OF THE PWL APPROACH
one can identify a change in transfer function, the answer does TO R-L CIRCUITS
not permit further analysis. In order to retain the utility of the We now extend the analysis to the case of R-L circuit. The
transfer function, we proceed on the following lines. low frequency equivalent of the 10-section physical model is
We estimate a current from the value of after the shown in Fig. 19. Here we replace R1 and R2 of Fig. 12 with
fault. In other words, we estimate a current that would flow R-L elements of value 0.1R and 0.1L and 0.9R and 0.9L with
in the circuit if the fault occurred at . This is shown in R, L being 180 and 25 mH. In this case, a switch is placed
Fig. 17 as . The new transfer function is now computed as across the 0.1R, 0.1L combination. This R-L model is evident
1314 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

Fig. 19. Low-frequency model of a winding.

Fig. 22. PWL approach for R-L networks.

Fig. 20. Time-domain response across filter F1 (DUT: 10-section physical


model).

Fig. 23. Transfer functions computed for Fig. 22.

The current with being the excitation and the


transfer function are computed in a similar manner. Fig. 22
shows the current for fault at 5 . The current is
then estimated from . The enlarged view of current before
and after the fault is also shown in same plot. The transfer
function, is then estimated and is shown in Fig. 23. It can
be appreciated that the estimation of is a simplified form
of a model reference approach. Here only the low frequency
parameters R, L are estimated. This is generally possible to a
high degree of accuracy. This eliminates the drawback of the
model reference approach which requires a model for the entire
Fig. 21. Transfer functions computed for Fig. 20. range of frequencies [8].

XI. IMPROVED VIRTUAL INSTRUMENT


because at low frequencies, Cs and Cg would have impedances, We have shown that the estimated transfer function forms
which are substantially larger than R, L. As far as identification a basis of identifying breakdown when initiation of faults oc-
of breakdown is concerned, the response across the first filter curs after a finite time. We define the following terms—reduced
F1 is significant [18]. We can prove that the response across transfer function (RTF) and full transfer function (FTF):
this filter does not change with the low frequency (R-L) equiv-
alent circuit as opposed to the complete (Rs-Ls-Cg-Cs) circuit. (6)
Fig. 20 shows the response across F1 for each of these circuits
for LI excitation.
where and are the current and voltage at the reduced
Fig. 20 shows that the response across F1 is exactly identical
level and
to that across the R-L elements alone. Fig. 21 shows the transfer
function computed for response across F1 with the R-L and RLC
(7)
circuits.
PALANI AND JAYASHANKAR: VIRTUAL INSTRUMENT FOR LI TESTS 1315

Fig. 24. Front panel of proposed instrument for LI tests (Legend, A: applied impulse. B: response with reduced and full level impulse. C: FFT of B. D: LPF
response of B. E: BPF response of B. E: HPF response of reduced level and PD invoked between two nodes. G: FFT of D. H: FFT of E. I: FFT of F. J: reduced
transfer function of LPF response. K: full level extrapolated transfer function of LPF response).

is the transfer function determined from the estimated values of this context. Fault simulation studies [9], [10] form the basis of
and . the analysis tool. The major analysis changes proposed by us
The virtual instrument is now modified to display estimated which forms a far more comprehensive approach, as opposed to
transfer functions. The two new windows J and K are shown in the transfer function method of [2], [19] or the wavelet method
Fig. 24 in Appendix B. A further advantage of this method is of [20], [21] can be summarized as follows:
that the transfer functions computed at the output of filter F1 • we compute , the frequency domain current;
permit a comparison between the chopped and standard LI. • we evaluate the response across three band of filters F1, F2,
and F3;
• breakdown can be identified by the estimated transfer func-
XII. DISCUSSION
tion, rather than current response alone;
The hardware and analysis tool developed here is a culmi- • the location of breakdown can be estimated using the esti-
nation of a series of intermediate steps and is to be viewed in mated response across F2 [17].
1316 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007

The location of partial discharge can be obtained from a cor- where is quality factor. The NEB for such a filter is
relation based study of the response across F3 [22]. The com- where is the cutoff of the filter. As the first stage filter is low
parison of chopped wave test with that of the LI was shown in pass, it will have a lower NEB than a system with no filter. The
[23]. The recognition of these faults, including identification of variance due to quantisation is given by [27]
nonlinear elements within, can be automated based on the re-
sponses obtained in the virtual instrument [24]. As an additional (A.6)
feature, the instrument can be adapted for recognizing winding
deformations during short-circuit tests [25]. where is the quantization step

XIII. CONCLUSION (A.7)


A virtual instrument was developed for analysis of impulse
test records in transformers. The front-end hardware has three where is the number of bits of ADC.
analog filters that precede three digitisers with varying resolu- For the three ADC converters of 8, 16 and 24 bits
tion. Breakdown and partial discharge events can be identified
clearly. A new piecewise linear approach is suggested for evalu- (A.8)
ating the transfer function when breakdown occurs after a finite
time. The location of breakdown, as well as partial discharge, (A.9)
can be identified based on further analysis of the records.
(A.10)
APPENDIX A
IMPROVEMENTS OF SNR OF MEASURMENT The variance of quantization noise which is the denominator
In order to quantify the improvements with the proposed front of (A.3) thus reduces considerably. This results in improved
end (Fig. 9), we introduce the notion of signal to noise ratio SNR for the measurement.
(SNR) of the measurement process. Any measured signal based
on sampling can be expressed of the form APPENDIX B
(A.1) Fig. 24 shows the proposed virtual instrument for LI tests.

where is the current in the absence of noise and is


REFERENCES
a noise term. With a sampling-based system, will have a
contribution from quantization. Expression A.1 can be written [1] IEC-60076: International Standard Part 1–5, Edition 2.1,2000-04,
2000.
in the frequency domain as [2] R. Malewski, E. Gokenbach, R. Maeier, and K. H. FellmannClaudi,
“Five years of monitoring the impulse test of power transformers with
(A.2) digital recorders and the transfer function method,” in CIGRE, 1992,
pp. 1–6, Paper 12-201.
[3] E. Hanique, “A transfer function is a reliable tool for comparison of full
One measure of the SNR of the process can be defined to be and chopped lightning impulse tests,” IEEE Trans. Power Del., vol. 9,
no. 3, pp. 1261–1266, Jul. 1994.
[4] R. Malewski and B. Poulin, “Impulse testing on power transformers
(A.3) using the transfer function method,” IEEE Trans. Power Del., vol. 3,
no. 2, pp. 476–489, Apr. 1988.
[5] K. Karsai, D. Kerenyi, and L. Kiss, Large power transformers. New
This follows because is finite energy and is the vari- York: Elsevier, 1987.
ance of the noise. With the introduction of the three analog filters [6] S. V. Kulkarni and S. A. Khaparde, Transformer Engineering—Design
and Practice. New York: Marcel Dekker, 2004.
in the front end, the SNR considerably improves. To prove this, [7] C. Kumaravelu, R. Sarathi, V. Jayashankar, S. Usa, and K.
we need the notion of the noise equivalent bandwidth (NEB) of a Udayakumar, “Partial discharge during impulse tests,” in IEEE
system. It can defined as area under the actual power gain curve Annu. Rep., Conf. Electrical Insulation and Dielectric Phenomena
(CEIDP—2003), Oct. 2003, pp. 616–619.
equals that of the theoretical rectangular power-gain curve with [8] S. Arunkumar, V. Sandeep, S. Shankar, M. Gopalakrishnan, K.
width B and height of a convenient value [26]. Udayakumar, and V. Jayashankar, Proc. Inst. Elect. Eng., Sci. Meas.
NEB is mathematically represented as Tech., vol. 151, no. Issue 1, pp. 25–30, Jan. 2004.
[9] V. Jayashankar, C. Kumaravelu, A. Palani, S. Usa, and K.
Udayakumar, “Modelling faults during impulse testing of trans-
(A.4) formers,” in IEEE—International conference on Power System
Transients (IPST-2005), Montreal, QC, Canada, Jun. 2005, Paper no.
IPST05-119.
where is the transfer function of the system and is the [10] V. Jayashakar, A. Palani, S. Usa, and K. Udayakumar, “Simulations of
gain. The transfer function of a second-order Bessel low-pass faults during impulse tests,” IEEE Trans. Power Del., vol. 20, no. 1, pp.
524–525, Jan. 2005.
filter is given as [11] P. Glaninger, “Modal analysis as a means of explaining the oscillatory
behavior of transformers,” Brown Boveri Rev. 1–85, pp. 41–49, 1986.
(A.5) [12] E. O. Forster, “Progress in the understanding of electrical breakdown
in condensed matter,” J. Phys. D., Appl. Phys., vol. 23, pp. 1506–1514,
1990.
PALANI AND JAYASHANKAR: VIRTUAL INSTRUMENT FOR LI TESTS 1317

[13] P. H. Morshius and F. H. Kreuger, “Transition from streamer to [23] S. Jayalalitha and V. Jayashankar, “Fuzzy logic based impulse test
townsend mechanisms in dielectic voids,” J. Phys. D., Appl. Phy., no. analysis,” in Proc. IEEE Mid-Summer Workshop on Soft Computing
23, pp. 1562–1568, 1990. in Industrial Application-SMCia/05, Espoo, Finland, Jun. 2005.
[14] J. M. Wetzer and Vanderlaan, “Pre-breakdown current basic interpreta- [24] S. Jayalalitha and V. Jayashankar, “Fuzzy logic based fault classifi-
tion and time resolved measurements,” IEEE Trans. Elect. Insul., vol. cation of impulse test records,” IEEE Trans. Power and Energy, vol.
24, no. 2, pp. 247–255, Apr. 1989. 126-B, no. 4, pp. 481–488, Apr. 2006.
[15] S. Degeneff, “A general method of determining resonance in trans- [25] A. Palani and V. Jayashankar, “An adaptive high resolution measuring
former windings,” IEEE Trans. Power App. Syst., vol. 96, no. 2, pp. system for characterizing transformers subjected to broadband excita-
423–430, 1977. tion,” in Proc. IEEE Int. Conf. TENCON’2005, Melbourne, Australia,
[16] P. T. M. Vaessen and N. V. Kema, “Transformer model for high fre- Nov. 2005, Paper no. 32854902.
quencies,” IEEE Trans. Power Del., vol. 3, no. 4, pp. 1761–1768, Oct. [26] P. A. Ramon and G. W. John, Analog Signal Processing. Singapore:
1988. Wiley, 1999, pp. 509–512.
[17] M. Gopalakrishnan, M. A. Paneerselvam, C. Kumaravelu, R. B. Shree- [27] S. Franco, Design With Operational Amplifiers and Analog Integrated
shankar, and V. Jayashankar, “Identification and location of breakdown Circuits. India: Tata McGraw-Hill, 2002.
in windings,” in IEEE Annu. Rep., Conf. Electrical Insulation and Di-
electric Phenomena (CEIDP-2003), Oct. 2003, pp. 518–521.
[18] A. Palani, S. Jayalalitha, N. Madhumohan, and V. Jayashankar, “Clas-
sification of impulse faults in transformers using adaptive filtering ap-
proach,” in Proc. 10th INSUCON Int. Conf., Birmingham, U.K., May
2006, pp. 211–216.
[19] J. Christian and K. Feser, “Procedures for detecting winding displace-
ments in power transformers by the transfer function method,” IEEE A. Palani received the B.E. degree in instrumentation and control engineering
Trans. Power Del., vol. 19, no. 1, pp. 214–220, Jan. 2004. from the University of Madras, Chennai, India, in 1999 and the M.E. degree
[20] S. N. Fernando and M. R. Raghuveer, “Detection of temporary faults in mechatronics engineering from Anna University, Chennai, in 2002. He is
during impulse tests using wavelets,” in IEEE Annu. Rep. Conf. currently pursuing the Ph.D. degree in the Department of Electrical Engineering,
Electrical Insulation and Dielectric Phenomena (CEIDP—2003), Oct. Indian Institute of Technology, Madras, Chennai.
2003, pp. 478–481.
[21] S. K. Pandey and L. Satish, “Multiresolution signal decompostion:
a new tool for fault detection in power transformers during impulse
tests,” IEEE Trans. Power Del., vol. 13, no. 4, pp. 1194–1200, Oct. V. Jayashankar (M’06) received the B.Tech., M.S., and Ph.D. degrees in 1982,
1998. 1991, and 1995, respectively.
[22] S. Jayalalitha and V. Jayashankar, “A correlation method for detection From 1994 to 2000, he was with the National Institute of Ocean Technology,
of partial discharges in transformers,” IEEE Trans. Power Del., vol. 21, Chennai, India. Currently, he is an Associate Professor in the Department of
no. 1, pp. 531–532, Jan. 2006. Electrical Engineering, Indian Institute of Technology, Madras, Chennai.

Вам также может понравиться