Академический Документы
Профессиональный Документы
Культура Документы
Abstract—We propose an objective formulation of the impulse II. REQUIREMENTS OF AN ANALYSIS SYSTEM
analysis problem from a signal analysis viewpoint. The winding
response is quintessentially that of a deterministic network to a In proposing any new method for analysis, the following con-
finite energy signal, with breakdown and partial discharge being ditions need be met. It must:
inherently nonlinear events. A significant improvement to the ac- • be capable of addressing different waveforms at reduced
quisition of waveforms is demonstrated by a virtual instrument ap- and full voltage;
proach. It retains the advantages of the time- and frequency-do- • objectively distinguish partial discharge from failure;
main methods. The drawbacks of the transfer function method are
highlighted and a new piecewise linear approach is proposed for • reproduce existing results in a comparable or better
analysis. Experiments on a discrete lumped parameter model of manner;
the winding are used to validate the PXI based instrument. • be consistent implying that results are valid for simple
Index Terms—Breakdown, extrapolation, impulse test, partial
breakdown events.
discharge, virtual instrument.
III. SIGNAL ANALYSIS PRELIMINARIES
The standard 1.2/50 lightning impulse (LI) excitation,
I. INTRODUCTION which is usually produced from a Marx generator can be written
in the form
of voltages from a Marx generator. The procedure is covered where “a” and “b” are adjusted to produce a 1.2/50 wave-
in standards such as IEC 60076—pt.IV [1]. As a winding is a form. Similarly, the wave shape chopped on the tail (CLI) can
complex structure from a dielectric viewpoint, failure detection be written in the form
during the test is fairly involved. This can be gauged from the
fact that both IEC and ANSI have separate guidelines for failure (2)
identification. The earliest approach involved the visual compar-
Both the signals are finite energy deterministic signals with
ison of current and voltage records obtained on impulse oscil-
loscopes. The drawbacks with this approach were the need to
(3)
have identical wave shapes at reduced and full voltage, and the
subjective nature of comparison. Digital techniques [2], [3] have
been increasingly used for recording waveforms during impulse For such signal, a Fourier transform exists and one can compute
testing. In principle, subjective evaluations could be avoided the frequency domain equivalent as
with such records. However, it is observed that the responses of
the winding to varying wave shapes such as the standard light- (4)
ning impulse (LI) and chopped impulse (CLI) cannot be com-
pared with time domain records alone. The transfer function By Parseval’s relation, it is also known that
approach [4] was proposed to overcome these drawbacks. The
method is not yet mandatory as per standards and some prob- (5)
lems do exist with the method.
Irrespective of the methods of acquisition, limitations exist in Tolerances exist on the front and tail of the LI and the time
the failure identification techniques. They are: to chop of the CLI. Fig. 1(a) shows the typical LI with a peak
• lack of an objective criterion for distinguishing PD from value of 1 V and Fig. 1(b) shows its normalized frequency do-
breakdown; main equivalent. Fig. 2(a) and (b) shows corresponding wave-
• lack of objective identification criteria for breakdown with forms for the CLI. The excitation in the frequency domain as
LI and CLI waveforms. shown in Figs. 1(b) and 2(b) gives an indication of the absolute
In this work, we proceed from first principles and propose an frequencies involved. The frequency domain records have been
approach based on signal analysis. normalized such that the maximum value of each waveform oc-
curs at 0 dB.
Manuscript received June 29, 2006. This work was supported by the MHRD, The device under test is a transformer winding and for the
India. Paper no. TPWRD-00361-2006. frequencies of interest can be considered as a lumped param-
The authors are with the Department of Electrical Engineering, IIT Madras,
Chennai, India (e-mail: tamilpalani@iitm.ac.in; jshankar@ee.iitm.ac.in). eter model of the form of Fig. 3 [5], [6]. IEC-60076 treats the
Digital Object Identifier 10.1109/TPWRD.2007.900089 device as a single-input single-output (SISO) system with the
0885-8977/$25.00 © 2007 IEEE
1310 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007
Fig. 8. Block diagram of lightning impulse test measuring system (DUT: de-
vice under test).
Fig. 13. Unfaulted current, i(t), through the resistive network (excitation 10 V Fig. 16. Computed transfer functions from Figs. 14 and 15.
LI).
Fig. 14. Current in the resistive network with fault at various time instants.
Fig. 18. Transfer function with conventional and PWL approach (t = 5 s).
Fig. 15. Frequency-domain representation of Fig. 14. . As shown in Fig. 18, this transfer func-
tion matches what one would expect for the circuit.
from what is intuitively obvious for such a circuit. Although X. GENERALIZATION OF THE PWL APPROACH
one can identify a change in transfer function, the answer does TO R-L CIRCUITS
not permit further analysis. In order to retain the utility of the We now extend the analysis to the case of R-L circuit. The
transfer function, we proceed on the following lines. low frequency equivalent of the 10-section physical model is
We estimate a current from the value of after the shown in Fig. 19. Here we replace R1 and R2 of Fig. 12 with
fault. In other words, we estimate a current that would flow R-L elements of value 0.1R and 0.1L and 0.9R and 0.9L with
in the circuit if the fault occurred at . This is shown in R, L being 180 and 25 mH. In this case, a switch is placed
Fig. 17 as . The new transfer function is now computed as across the 0.1R, 0.1L combination. This R-L model is evident
1314 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007
Fig. 24. Front panel of proposed instrument for LI tests (Legend, A: applied impulse. B: response with reduced and full level impulse. C: FFT of B. D: LPF
response of B. E: BPF response of B. E: HPF response of reduced level and PD invoked between two nodes. G: FFT of D. H: FFT of E. I: FFT of F. J: reduced
transfer function of LPF response. K: full level extrapolated transfer function of LPF response).
is the transfer function determined from the estimated values of this context. Fault simulation studies [9], [10] form the basis of
and . the analysis tool. The major analysis changes proposed by us
The virtual instrument is now modified to display estimated which forms a far more comprehensive approach, as opposed to
transfer functions. The two new windows J and K are shown in the transfer function method of [2], [19] or the wavelet method
Fig. 24 in Appendix B. A further advantage of this method is of [20], [21] can be summarized as follows:
that the transfer functions computed at the output of filter F1 • we compute , the frequency domain current;
permit a comparison between the chopped and standard LI. • we evaluate the response across three band of filters F1, F2,
and F3;
• breakdown can be identified by the estimated transfer func-
XII. DISCUSSION
tion, rather than current response alone;
The hardware and analysis tool developed here is a culmi- • the location of breakdown can be estimated using the esti-
nation of a series of intermediate steps and is to be viewed in mated response across F2 [17].
1316 IEEE TRANSACTIONS ON POWER DELIVERY, VOL. 22, NO. 3, JULY 2007
The location of partial discharge can be obtained from a cor- where is quality factor. The NEB for such a filter is
relation based study of the response across F3 [22]. The com- where is the cutoff of the filter. As the first stage filter is low
parison of chopped wave test with that of the LI was shown in pass, it will have a lower NEB than a system with no filter. The
[23]. The recognition of these faults, including identification of variance due to quantisation is given by [27]
nonlinear elements within, can be automated based on the re-
sponses obtained in the virtual instrument [24]. As an additional (A.6)
feature, the instrument can be adapted for recognizing winding
deformations during short-circuit tests [25]. where is the quantization step
[13] P. H. Morshius and F. H. Kreuger, “Transition from streamer to [23] S. Jayalalitha and V. Jayashankar, “Fuzzy logic based impulse test
townsend mechanisms in dielectic voids,” J. Phys. D., Appl. Phy., no. analysis,” in Proc. IEEE Mid-Summer Workshop on Soft Computing
23, pp. 1562–1568, 1990. in Industrial Application-SMCia/05, Espoo, Finland, Jun. 2005.
[14] J. M. Wetzer and Vanderlaan, “Pre-breakdown current basic interpreta- [24] S. Jayalalitha and V. Jayashankar, “Fuzzy logic based fault classifi-
tion and time resolved measurements,” IEEE Trans. Elect. Insul., vol. cation of impulse test records,” IEEE Trans. Power and Energy, vol.
24, no. 2, pp. 247–255, Apr. 1989. 126-B, no. 4, pp. 481–488, Apr. 2006.
[15] S. Degeneff, “A general method of determining resonance in trans- [25] A. Palani and V. Jayashankar, “An adaptive high resolution measuring
former windings,” IEEE Trans. Power App. Syst., vol. 96, no. 2, pp. system for characterizing transformers subjected to broadband excita-
423–430, 1977. tion,” in Proc. IEEE Int. Conf. TENCON’2005, Melbourne, Australia,
[16] P. T. M. Vaessen and N. V. Kema, “Transformer model for high fre- Nov. 2005, Paper no. 32854902.
quencies,” IEEE Trans. Power Del., vol. 3, no. 4, pp. 1761–1768, Oct. [26] P. A. Ramon and G. W. John, Analog Signal Processing. Singapore:
1988. Wiley, 1999, pp. 509–512.
[17] M. Gopalakrishnan, M. A. Paneerselvam, C. Kumaravelu, R. B. Shree- [27] S. Franco, Design With Operational Amplifiers and Analog Integrated
shankar, and V. Jayashankar, “Identification and location of breakdown Circuits. India: Tata McGraw-Hill, 2002.
in windings,” in IEEE Annu. Rep., Conf. Electrical Insulation and Di-
electric Phenomena (CEIDP-2003), Oct. 2003, pp. 518–521.
[18] A. Palani, S. Jayalalitha, N. Madhumohan, and V. Jayashankar, “Clas-
sification of impulse faults in transformers using adaptive filtering ap-
proach,” in Proc. 10th INSUCON Int. Conf., Birmingham, U.K., May
2006, pp. 211–216.
[19] J. Christian and K. Feser, “Procedures for detecting winding displace-
ments in power transformers by the transfer function method,” IEEE A. Palani received the B.E. degree in instrumentation and control engineering
Trans. Power Del., vol. 19, no. 1, pp. 214–220, Jan. 2004. from the University of Madras, Chennai, India, in 1999 and the M.E. degree
[20] S. N. Fernando and M. R. Raghuveer, “Detection of temporary faults in mechatronics engineering from Anna University, Chennai, in 2002. He is
during impulse tests using wavelets,” in IEEE Annu. Rep. Conf. currently pursuing the Ph.D. degree in the Department of Electrical Engineering,
Electrical Insulation and Dielectric Phenomena (CEIDP—2003), Oct. Indian Institute of Technology, Madras, Chennai.
2003, pp. 478–481.
[21] S. K. Pandey and L. Satish, “Multiresolution signal decompostion:
a new tool for fault detection in power transformers during impulse
tests,” IEEE Trans. Power Del., vol. 13, no. 4, pp. 1194–1200, Oct. V. Jayashankar (M’06) received the B.Tech., M.S., and Ph.D. degrees in 1982,
1998. 1991, and 1995, respectively.
[22] S. Jayalalitha and V. Jayashankar, “A correlation method for detection From 1994 to 2000, he was with the National Institute of Ocean Technology,
of partial discharges in transformers,” IEEE Trans. Power Del., vol. 21, Chennai, India. Currently, he is an Associate Professor in the Department of
no. 1, pp. 531–532, Jan. 2006. Electrical Engineering, Indian Institute of Technology, Madras, Chennai.