NOJA-5028-01

Restrict Trip Mode Basic Guide

GuideGuideModule
The MODE pushbutton on the HMI panel allows the device “Control” mode to be set to either Local or Remote. When in Local
mode, controls can only be executed locally and when in Remote mode, controls can only be executed by remote applications.

The exception to this is an Open control, which can be executed locally or remotely, independent of the device “Control” mode.
The user can now restrict this by enabling “Restrict Trip Mode”. When “Restrict Trip Mode” is enabled, if the device is in Remote
Control mode, local trip (or Open) commands are blocked and if the device is in Local Control mode, remote trip commands are
blocked.

“Restrict Trip Mode” can be set via Logic and SGA.

To configure “Restrict Trip Mode” via Logic follow the steps below:

1. In CMS, ensure you are Online with the relay.


2. Upload Settings from the relay.
3. Copy uploaded settings to the device in CMS.
4. Configure one of the available logic channels so that “Restrict Trip Mode” is turned on by a valid condition e.g. when
the OSM is connected.
5. Save settings and download it to the relay. Check the Change Log to ensure the new functionality is activated.

Figure 1 Enabling Restrict Trip Mode using Logic

Note: All communication interfaces including I/O and communication ports can be configured as either Local or Remote. As such
control commands issued through any of these ports may be classified as Local even though they are issued by a remote
application.

Figure 3: Configuring Control Mode on Communication Port

NOJA Power Switchgear Pty Ltd


16 Archimedes Place, Murarrie, 4172, Qld, Australia
phone: +61 7 3907 8777 fax: +61 7 3399 6777
email: sales@nojapower.com.au
web: www.nojapower.com.au
NOJA-5028-01
Restrict Trip Mode Basic Guide

GuideGuideModule
DNP3 Protocol

The following status codes are provided for the DNP3 protocol in response to a binary Trip/Close command.

Comms Port Device Control Trip and Close Restrict Trip Control related
Scenarios Description
Control Mode Mode Commands Mode Status Code
1 Remote Remote Trip/Close ON/OFF Success (0) Request accepted
Request not accepted due to mismatch
2 Remote Local Close OFF/ON Local (7) between the Comms and device Control
modes
3 Remote Local Trip OFF Success (0) Request accepted
Request not accepted due to mismatch
4 Remote Local Trip ON Local (7) between the Comms and device Control
modes
5 Local Local Trip/Close ON/OFF Success (0) Request accepted
Request not accepted due to mismatch
6 Local Remote Close ON/OFF Local (7) between the Comms and device Control
modes
7 Local Remote Trip OFF Success (0) Request accepted
Request not accepted due to mismatch
8 Local Remote Trip ON Local (7) between the Comms and device Control
modes

IEC Protocol

The following table displays the response of “C_SC” or “C_DC” to a command Trip/Close.

Comms Port Device Control Trip and Close Restrict Trip C_SC or C_DC response to
Scenarios Description
Control Mode Mode Commands Mode Trip/Close command
1 Remote Remote Trip/Close ON/OFF COT: <7> with positive flag Request accepted
Request not
2 Remote Local Close OFF/ON COT: <7> with negative flag
accepted
3 Remote Local Trip OFF COT: <7> with positive flag Request accepted
Request not
4 Remote Local Trip ON COT: <7> with negative flag
accepted
5 Local Local Trip/Close ON/OFF COT: <7> with positive flag Request accepted
Request not
6 Local Remote Close ON/OFF COT: <7> with negative flag
accepted
7 Local Remote Trip OFF COT: <7> with positive flag Request accepted
Request not
8 Local Remote Trip ON COT: <7> with negative flag
accepted