Inspection & Testing of


TRANSFORMER

Nana Heryana
nana@konversi.ee.itb.ac.id

nana@konversi.ee.itb.ac.id
LPKEE-ITB 1

POWER TRANSFORMER INSPECTION AND TEST PLAN

ACTIVITY
DOCUMENTS
DESCRIPTION PROCESS DESCRIPTION/INSPECTION End
PJIT MIGAS REFERENCE
User
Pre-Inspection Inform the client regarding the Certification H --- H  Owner specifications
Meeting Agencies scope of work.  Applicable
code/standard
Design Appraisal  Drawing R --- R  Owner Specification
 General Specification R --- R  Code or Standard
 Calculation R --- R
Factory  Identification of Component and Material V --- H  Procedure
Acceptance
Test (FAT)  Temperature Rise Test W W W  Code or Standard
 Lightning Impulse Voltage Withstand Test W W W
 Switching Impulse Test W W W
 Heat Run Test W W W
 Vector Group Test W W W
 Transformer Turning Ratio Test W W W
 Insulation Resistance Test W W W
 Short Circuit Withstand Test W W W
 Magnetizing Current Test W W W
 Positive Sequence Impedance Test W W W
 Zero Sequence Impedance test W W W
 Tap Changer Test W W W
 Noise Level W W W
 Current Transformer Test W W W

nana@konversi.ee.itb.ac.id
LPKEE-ITB 2

1
2/28/2014

POWER TRANSFORMER INSPECTION AND TEST PLAN

For oil type ---


 Check the cooling fans rotate freely by W W W
hand and are mounted as per the
manufacture's drawings (for oil type)
ACTIVITY
DOCUMENTS
DESCRIPTION PROCESS DESCRIPTION/INSPECTION End
PJIT MIGAS REFERENCE
User
 Gas Detector Relay Test W W W
 Oil Temperature Indicator Test W W W
 Oil Level Indicator Test W W W
 Cooling Fan Test W W W
 Insulating Oil Test W W W
 Standard Oil Test W W W

nana@konversi.ee.itb.ac.id
LPKEE-ITB 3

POWER TRANSFORMER INSPECTION AND TEST PLAN


Pre-  Verify nameplate of equipt. with the data W W
Commissioning sheet W --- W
Test, On-Site  Check the transformer layout based on
classification area
 Check the size, type, identification and W --- W
termination of all cables to be connected,
according the design drawing
 Inspect for physical damages W --- W
 Check the bolt nuts & screws are properly W --- W
install
 Check the transformer sections are W --- W
properly aligned, leveled and bolted
 Earthing Measurement Test W --- W
For Oil Type
 Check the cooling equipment installed W --- W
properly
 Check the components are installed W --- W
specified and properly (as gauges,
pressure relay, etc)
 Check the transformer thoroughly for oil W --- W
leaks
 Check the transformer tank/casing is W --- W
grounded properly
 Check that crystals in silica gel breather W --- W
are mostly blue
Commissioning  Performance Test W W H Test Sheet Pre-
Test, Final Insp. Commissioning Test
Procedure

nana@konversi.ee.itb.ac.id
LPKEE-ITB 4

2
2/28/2014

INSPECTION AND TEST PLAN FOR POWER TRANSFORMER


DISTRIBUTION RE-CERTIFICATION
ACTIVITY
DOCUMENTS
DESCRIPTION PROCESS DESCRIPTION INSPECTION End
PJIT MIGAS REFERENCE
User
 Assessment Report R R H  Owner
Document  Re-engineering report *) R R H Specification
Review  Drawing R - H  Code or
 Previous certificate SKPP R - H Standard
 Operation & Maintenance Manuals R - H
 Log Book Maintenance R - H
 Verify nameplate of equipment with the data sheet V - W  Procedure
Site Inspection  Check the Transformer Layout based on V - W  Drawing
classification area V - W  Owner
 Inspect for physical damages V - W Specification
 Check temperature of ambient air as the cooling V - W
 Check the bolt nuts and screws V - W
 Check the transformer tank/casing is grounded R/W - W
properly R/W - W
 Noise level R/W - W
 Insulation resistance measurement R/W - W
 Earthing Measurement R/W - W
 Standard oil test R/W V W
 Gas analysis (if required) R/W V W
 No Load Test R/W V W
 Short Circuit Test R/W V W
 Polarization Index (PI) measurement
 Residual Life Assessment (RLA) base on IR & PI

nana@konversi.ee.itb.ac.id
LPKEE-ITB 5

Transformer Inspection
National fire protection association (NFPA) National Electrical Testing Association (NETA)

General Inspection items Frequency


Load Current Hourly or use recording meters

Voltage Hourly or use recording meters

Liquid Level Hourly or use recording meters

Temperature Hourly or use recording meters

Protective devices Yearly


Protective Alarm Monthly
Ground Connections Every 6 months

nana@konversi.ee.itb.ac.id
LPKEE-ITB 6

3
2/28/2014

Transformer Inspection
National fire protection association (NFPA) National Electrical Testing Association (NETA)

General Inspection items Frequency


Tap Changer Every 6 months

Lightning arrester Every 6 months

External inspection Every 6 months

Internal inspection 5-10

Auxiliary equipments Annually

nana@konversi.ee.itb.ac.id
LPKEE-ITB 7

Transformer Inspection
National fire protection association (NFPA) National Electrical Testing Association (NETA)

General Inspection items Frequency


Break-down voltage Annually
Color Annually
Power factor test Annually
Moisture content Annually
Gas-analysis test Annually

nana@konversi.ee.itb.ac.id
LPKEE-ITB 8

4
2/28/2014

Transformer Inspection
National fire protection association (NFPA) National Electrical Testing Association (NETA)

General Inspection items Frequency


Winding
Insulation Resistance Annually
Power factor Annually
Polarization Index (PI) Annually
Hi-Potential voltage (AC/DC) Five years or more
Induced voltage Five years or more
Polarization recovery voltage Annually

nana@konversi.ee.itb.ac.id
LPKEE-ITB 9

FUNGSI MINYAK TRAFO

• Media Isolator
• Media Pendingin
• Media/ alat untuk
memadamkan busur api
• Perlindungan terhadap
korosi

nana@konversi.ee.itb.ac.id

5
2/28/2014

MINYAK TRAFO

• MINYAK MINERAL
• MINYAK SINTETIK
• Pemilihan bergantung
tempat/lingkungan
– Askarel minyak sintetik yang
tidak dapat terbakar (Cocok
untu industri kimia), dari sisi
kesehatan berbahaya.
nana@konversi.ee.itb.ac.id

INSPEKSI MINYAK TRAFO

1. Appearance (Kejernihan
Penampilan)]
2. Kinematic Viscosity; tahanan cairan
semakin rendah konduktivitas
termalnya semakin bagus.
3. Density ( Masa jenis)
4. Water Content Kandungan Air max
50 ppm

nana@konversi.ee.itb.ac.id

6
2/28/2014

INSPEKSI MINYAK TRAFO

5. Dielectric Dissipation Factor ( faktor


kebocoran dielektrik) tinggi DDF
rendah tahanan jenis minyak. max
0,005
6. Resistivity ( Isolator >109W-m)
7. Flash point ( titik nyala ; titik sebelum
uap menjadi api 1400C)
8. Pour point ( Titik tuang, titik terendah
dimana minyak masih mengalir) -90C
1) -300C 2)

1) International standard IS 335-1983 , 2)British Standard BS 148-1972

nana@konversi.ee.itb.ac.id

INSPEKSI MINYAK TRAFO


9. Breakdown Voltage ( Tegangan Tembus) 30 kV
10. Netralization Number ( Angka kenetralan) max
0,03 mg KOH/gm
11. Oxidation Stability ( kemantapan Oksidasi) :
Proses oksidasi menyebabkan bertambahnya
kecenderungan minyak untuk membetuk asam
dan kotoran zat yang akan membentuk endapan.
Asam akan menyebabkan korosi, kotoran
engakibatkan transfer panas terganggu max 0,4
mg KOH/gm 1) 0,03 mg KOHgm

1) International standard IS 335-1983 , 2)British Standard BS 148-1972

nana@konversi.ee.itb.ac.id

7
2/28/2014

Inspection & Testing of


TRANSFORMER

Testing of Transformer

DGA RDC PI TTR TAN δ DIRANA

Analisis

nana@konversi.ee.itb.ac.id
LPKEE-ITB 15

Dissolved Gas Analysis (DGA)


• DGA berfungsi untuk
mendeteksi jumlah
combustible gas
• Pengambilan sample
dilakukan saat trafo
beroperasi

BACK

nana@konversi.ee.itb.ac.id
LPKEE-ITB 16

8
2/28/2014

Pengukuran Resistansi Belitan (RDC)

• RDC berfungsi untuk analisis keseimbangan


belitan
Auto Current Ranging from 10
MA to 40 Amps
Digital Resistance Reading
from 1 micro-ohm to 500
ohms
Auto discharge circuit for
operator safety
Built-in 2.5" Thermal Printer,
computer interface
Stores 48 records of 63
readings
Weighs less than 30 lbs.

BACK

nana@konversi.ee.itb.ac.id
LPKEE-ITB 17

dc Winding Resistance Test


• Pengujian ini mengukur resistansi dc dari belitan
fasa-fasa , fasa-netral.
• Semua pengujian dilakukan pada suhu 75 C untuk
mendapatkan hasil yang sesungguhnya.
• Nilai pengujian jika dibandingkan dengan hasil
pengujian pabrik boleh mempunyai beda sekira 2 %
saja, jika nilainya lebih besar maka maka dapat
diyakini sambungan belitan ke terminal, tap changer
tidak baik.

Rtest (234.5  75)


R75C 
234.5  winding temp. C
nana@konversi.ee.itb.ac.id
LPKEE-ITB 18

9
2/28/2014

Polarization Index
• PI berfungsi
mengetahui
kualitas isolasi
• Reff. Standard IEEE 43
:2000

BACK

nana@konversi.ee.itb.ac.id
LPKEE-ITB 19

Insulation Resistance Test


Insulation Resistance biasa disebut sebagai test Megger
Pengukuran Insulation resistance menurut Standard IEEE
dan NEMA – MG 1, PART: 20

TEGANGAN KERJA MESIN YANG DIUKUR V - TEST

Machine dng. Tegangan Kerja 240 – 2400 V 500 Vdc


Machine dng. Tegangan Kerja 3000 – 4800 V 2500 Vdc
Machine dng. Tegangan Kerja 5200 - 13800 V 2500 or 5000 Vdc
Semua DC Machine 500 Vdc,
500 Vdc, Max 1000
Semua Winding Rotor dengan Rated Voltage > 100 V
V dc

Insulation Resistance Minimum:


( UN + 1) MΩ
nana@konversi.ee.itb.ac.id
LPKEE-ITB 20

10
2/28/2014

Contoh Data Pengujian Mesin Listrik < 1 KV

Jenis Pengujian Kondisi Standar Referensi Remark (Catatan)


Tahanan Isolasi
IR (Min) 146.5 MΩ >5 MΩ IEEE Std 43-2000 masih memenuhi
standar
Nilai DAR tidak
Paul Gill
DAR (Min) 1,23 >1,25 memenuhi best
Handbook practice
PI masih
PI (Min) 2.65 >2 IEEE Std 43-2000 memenuhi
standar
Max deviation =
RDC +/- 5 % IEEE Std 62-1995 Belitan seimbang
0.282%

nana@konversi.ee.itb.ac.id

Contoh Data Pengujian Mesin Listrik 6.3 KV

Jenis Pengujian Kondisi Standar Referensi Remark (Catatan)

IR masih
IEEE Std 43-
IR (Min) 2.06 GΩ > 100 MΩ memenuhi standar
2000

Nilai DAR
Paul Gill
DAR (Min) 1.56 >1.25 memenuhi best
Handbook practice
PI masih memenuhi
IEEE Std 43-
PI (Min) 3.75 >2 standar
2000

IEEE Std 62-


RDC Max deviation = 0.031 % +/- 5 % Belitan seimbang
1995
DDF = 10.380 x 10-3 < 6 x 10-3 Kantung udara
(voids) pada isolasi
Tan δ Tip Up Mean DDF = 9.631 x 10- VDE 0530
< 3 x 10-3 melebihi standar
3

nana@konversi.ee.itb.ac.id

11
2/28/2014

Faktor Koreksi
Berdasarkan standar IEEE 43 tahun 2000 nilai resistansi tersebut harus
dikoreksi ke suhu 40°C dengan formula seperti pada persamaan :

R C  Resistansi yang sudah dikoreksi


RC  RM  Kt R M  Resistansi pengukuran
K T = Faktor koreksi

 40  T  /10
K t   0,5  dengan T adalah suhu pengukuran dalam
°C saat penujian dilakukan.

nana@konversi.ee.itb.ac.id

Insulation Resistance Test


Megohmmeter reading should be maintained for
a period of 1 min. Make the following readings
for two-winding transformers:
• a. High-voltage winding to low-voltage winding
and to ground
• b. High-voltage winding to ground
• c. Low-voltage winding to high-voltage winding
and to ground
• d. Low-voltage winding to ground
• e. High-voltage winding to low-voltage winding

nana@konversi.ee.itb.ac.id
LPKEE-ITB

12
2/28/2014

Insulation Resistance Test

nana@konversi.ee.itb.ac.id
LPKEE-ITB

Insulation Resistance Test

nana@konversi.ee.itb.ac.id
LPKEE-ITB

13
2/28/2014

Polarization Index (PI)

PI adalah salah satu cara yang digunakan untuk


mengetahui quality winding akibat pengaruh
lingkungan, seperti penyerapan air, pengotoran
debu, dllmerupakan perbandingan pengukuran Arus
Bocor pada pengukuran dalam 10 menit terhadap 1 menit

Pengukuran R IS 10 menit
PI =
Pengukuran R IS 1 menit

nana@konversi.ee.itb.ac.id
LPKEE-ITB

Polarization Index (PI)


Nilai parameter PI menurut IEEE Transaction 43

Lower than 1.0 = Dangerous R Insulation Test Instrument

1.0 to 1.4 = Poor


1.5 to 1.9 = Questionable
2.0 to 2.9 = Fair
3.0 to 4.0 = Good
Over than 4.0 = Excellent

Jika PI kurang dari 2.0 menunjukkan bahwa isolasi winding


terlalu banyak menyerap uap air atau terdapat penumpukan
kotoran konduktive.
PI s/d 1.5 dapat dikategorikan aman jika:
RIS > ( 1000 + 1 MΩ)

nana@konversi.ee.itb.ac.id
LPKEE-ITB

14
2/28/2014

Polarization Index (PI)


Cara Pengukuran PI yang lain adalah dengan cara perbandingan pengukuran Arus
Bocor pada pengukuran dalam 1 menit terhadap ½ menit
Pengukuran R IS 1 menit
PI =
Pengukuran R IS 1/2 menit
Nilai parameter PI menurut IEEE Transaction 43
Lower than 1.0 = Poor
1.1 to 1.24 = Questionable
1.25 to 1.35 = Fair
1.4 to 1.5 = Good
≥ 1.5 = Excellent
Jika PI kurang dari 1.25 menunjukkan bahwa isolasi winding terlalu banyak
menyerap uap air atau terdapat penumpukan kotoran konduktive.

nana@konversi.ee.itb.ac.id
LPKEE-ITB

Transformer Turn Ratio (TTR)


• TTR berfungsi untuk mendeteksi adanya
hubungsingkat pada belitan trafo
Reff. IEEE C57.12.00-1993

Highest ratio: 0.8 - 15,000


Built-in 4.5" thermal printer
Excitation current measuring
Phase angle measuring
Computer interface
Name-plate turns ratio calculation
Computed % error based on
measured and calculated ratio
Automated phase switching

BACK

nana@konversi.ee.itb.ac.id
LPKEE-ITB 30

15
2/28/2014

Transformer Turns Ratio (TTR) Test

• Menentukan rasio belitan dan polaritas trafo


pada waktu yang sama.
• Mengkonfirmasi rasio, polaritas dan vektor
sesuai name plate.
• Menentukan rasio dan polaritas ( bukan pada
tegangan ratingnya)
• Test meliputi semua tap dalam keadaan
tanpa beban
• ANSI 57.12-00, bagian 6.1 : hasil harus
berkisar 0.5 persen dari name plate,
• TTR dengan ketelitian 0.1 persen diterima
sebagai referensi

nana@konversi.ee.itb.ac.id
LPKEE-ITB

Alternative Test for TTR

nana@konversi.ee.itb.ac.id
LPKEE-ITB 32

16
2/28/2014

Alternative Test for TTR

nana@konversi.ee.itb.ac.id
LPKEE-ITB 33

Tan Delta Test


• Tan delta berfungsi untuk mendeteksi adanya
kantung udara (voids) pada isolasi Reff. VDE 0530

DOBLE M4000
BACK

nana@konversi.ee.itb.ac.id
LPKEE-ITB 34

17
2/28/2014

Tan Delta Test


Dissipation Power Factor
Sistim isolasi mesin listrik secara alamiah akan mengalami
penurunan sesuai dengan usianya, namun demikian
percepatan penurunannya sangat dipengaruhi oleh
berbagai factor, a.l: gesekan, thermal stresses, mechanical
stresses, kantong udara didalam isolasi, kwalitas lapisan
semi conductive pada isolasi, dll.
Salah satu kriteria yang paling penting untuk mengetahui
kwalitas dalam sistim isolasi mesin listrik adalah hubungan
sebab akibat dari factor disipasi power factor dengan
tegangan kerja. Dissipation power factor di test pada
tegangan 0.2 Un s/d 1.0 Un dengan interval tegangan
sebesar 0.2 Un .

nana@konversi.ee.itb.ac.id

Tan Delta Test


Nilai Dissipation Power Factor (Tan. Δ ) menurut VDE 0530

Tan δ0.6 – Tan δ 0.2


Tan δ 0.2 = = Max 3.0 x 10 -3
2

∆ Tan δ 0.2 = Max = 6.0 x 10 -3

Kenaikan “power factor” menunjukkan adanya kenaikan


jumlah kantong2 udara (voids) yang ada di dalam isolasi
dan atau menunjukkan adanya kenaikan tahanan pada
lapisan semiconductor, kenaikan tahanan tersebut dapat
disebabkan oleh: loose contacts ke dinding slot
adanya kerusakan semiconductor

nana@konversi.ee.itb.ac.id

18
2/28/2014

Tan Delta Test


Coil with many
Power Factor on the Void Winding
Dielectric Power Factor voids

12

10

∆ Tan δ

Power Factor
Tan D

Coil with few

Tan δ
6 voids

0
0,2 0,4 0,6 0,8 1,0
100%
25% 50%
U/Un ---------->
Line to Ground Voltage Test

Kenaikan hasil pengukuran Tan Δ menunjukan adanya kenaikan kantong


udara, penyerapan uap air, aktivitas partial discharge, dll.

Kantong2 udara yang terbentuk didalam lapisan isolasi akan menjadi tempat penimbunan uap air dan merupakan
tempat terbentuknya “PD” , aktivitas PD akan mengikis permukaan isolasi, lama-kelamaan isolasi akan menjadi
terbuka. Jika ditemukan hasil uji Tan Δ sudah tinggi, sebaikanya cepat2 dilakukan perbaikan isolasi winding

nana@konversi.ee.itb.ac.id

Dielectric Response Analysis (DIRANA)

• DIRANA berfungsi untuk


mengetahui kelembaban
(moisture content) isolasi

Reff. IEEE 62-1995


OMICRON electronics Corp BACK

nana@konversi.ee.itb.ac.id
EU-ITB 38

19
2/28/2014

Description of Condition Monitoring test of


Power Transformer
1. Capacitance and Tan Delta test of Bushing & winding : To detect
insulation condition.
2. Frequency Response Analysis : To detect any winding movement.
3. Winding resistance test : To check winding condition.
4. Turns Ratio test : To check inter turn fault.
5. Magnetic Balance test : To check core condition.
6. Excitation Current : To detect core related defect.
7. IR & PI Value Measurement test : To check insulation condition.
8. Oil test as per IS: 1866 : To check oil condition & characteristic.
9. DGA (oil test) : To detect internal thermal fault
10. Furan (oil test) : To detect condition of paper insulation
11. Domino oil test (on line test) : To detect moisture in oil & paper
12. Core Insulation test : To detect insulation condition of Core to Tank

nana@konversi.ee.itb.ac.id
LPKEE-ITB 39

High-Potential Voltage Test

• The DC hi-pot test is applied at above the


rated voltage of a transformer to evaluate the
condition of winding insulation.
• The DC high-voltage test is not recommended
on power transformers above 34.5 kV; instead
the AC hi-pot test should be used.

nana@konversi.ee.itb.ac.id
LPKEE-ITB

20
2/28/2014

High-Potential Voltage Test


• Reference to VDE 0530 part 1.
• Hi-pot test diaplikasikan antara winding dengan ground mesin, dan
winding yang tidak di test harus di ground kan
• Hi-pot test dilakukan untuk new winding
• Hi-pot test dilakukan dengan tegangan a.c dengan gelombang sinus
dan frequency antara 40 s/d 60 cycle per second
• Besar tegangan uji dimulai dengan tegangan tidak lebih dari ½ dari full
voltage test, Waktu yang diperlukan untuk menaikan tegangan dari
tegangan awal s/d tegangan full +/- 10 detik
• Mesin polyphase dengan rated lebih dari 1 kVA, jika dimungkinkan
setiap phase winding di test terhadap ground
• “Acceptance” test tidak dianjurkan untuk diulang, jika dikehendaki
maka pengulangan test untuk test kedua dan seterusnya tegangan test
hanya 80% dari tegangan test penuh.

nana@konversi.ee.itb.ac.id
LPKEE-ITB

High-Potential Voltage Test


• Hi-pot test untuk mesin yang diperbaiki. Mesin yang
di rewinding total di test seperti mesin baru dengan
tegangan uji 100% Rewinding partial di test dengan
tegangan uji sebesar 80% dari tegangan test penuh.
• Test dilakukan jika semua part dalam kondisi bersih
dan kering
• Untuk mesin yang di overhaul, Hi-pot test dapat
dilakukan jika ada persetujuan antara pihak user
dengan workshop

nana@konversi.ee.itb.ac.id
LPKEE-ITB

21
2/28/2014

High-Potential Voltage Test


• Jika dikehendaki (dng perjanjian khusus) Besar
tegangan uji untuk mesin yang di overhaul
• UT = 500 V test applied for UN < 100 V
• UT = 1.5 U,
• with minimum 1000 V, for UN ≥ 100 V
• UT = test voltage
• UN = Voltage rated of machine
• Hi-pot test dilakukan selama 60 second dan selama
dilakukan test tidak boleh terjadi flash-over atau
break down.

nana@konversi.ee.itb.ac.id
LPKEE-ITB

High-Potential Voltage Test


Secondary winding (rotor) of induction or
synchronous motor

Non reversing 1000V + 2U (voltage rotor in


motor open circuit)
Reversed motor 1000V + 4 U (voltage rotor in
open circuit)

Exciter 1000 + 2U (exciter voltage),


min. 1500 V

nana@konversi.ee.itb.ac.id
LPKEE-ITB 44

22
2/28/2014

High-Potential Voltage Test

nana@konversi.ee.itb.ac.id
LPKEE-ITB

Open-Circuit Test

VOC ,IOC and POC

nana@konversi.ee.itb.ac.id
LPKEE-ITB 46

23
2/28/2014

Short-Circuit Test

VSC ,ISC , and POC

nana@konversi.ee.itb.ac.id
LPKEE-ITB 47

TERIMA KASIH