Вы находитесь на странице: 1из 1

DESIGN OF STP PLANT.

Total occupancy considered – 712

Water requirements as per NBC – 45 LPCD

Total water required - 32040 Lltrs /day.

Expected waste water to STP – 85% of the total water requirement.

Proposed – STP Capacity - 27.5 kl Rounded upto 30 kld.

Length Width Height Area Volume


SL.No Description Of Equipment
(M) (M) (M) ( Sqm) ( CUM)
STP TANK CAPACITIES - 30 KL
1 Bar Screen Chamber 1.5 1 1 1.5 1.5
2 Receiving Tank /Equalization Tank 3 2 2 6 12
3 Anoxic Tank 1.5 1.5 4 2.25 9
4 SBR Aeration Tank - 1 2 2 4 4 16
5 Sludge Tank 2 2 2 4 8
6 Decant Tank 3 2 2 6 12
7 Final treated water tank 4 3 2.5 12 30
TOTAL AREA/VOLUME 35.75 88.5