Nuclear safety related systems and components that are essential to:
Emergency RX shutdown
CTMT isolation
RX core cooling
CTMT RX heat removal
Or otherwise essential in preventing significant release of radioactive material to environment are defined as Class-1E load.
Class-1E electrical systems are designed in accordance with:
HAF-0207-88 & reference to R.G-1.32-77, R.G-1.75-74.
IEEE standard 308-1990.
10-CFR-50
Question 9: DEP-J
1-D (DEP-A)
2-D (DEP-B)
ELA (EMA)
Loads
BOP
JOP-1~4
T/G Motor
MFWP-A/B/C lube oil pump # 02
Dump oil pump A/B
TX lighting, CI UPS, CIDC # 01 & # 02
The main function of Generator excitation system is to supply DC power supply for exciting the rotor of the main generator.
Functions
Provide and regulate the Gen Stator voltage with limits.
Provide and regulate reactive power.
Ensure stability of the power system.
Voltage
Phase Sequence
Frequency
Question 14:
Line-1 Line-2
DS133 DS213
220kV Bus # 1
DS111
CB13
CB12 CB21 CB22
CB11
DS132
DS121 DS211 DS222
DS112
DS113
220kV Bus # 2
M T/F 132kV from
Wan Buchran
Voltage : 260V
P.f : 0.2
Fly wheel: Function is to accommodate system surges / fluctuations for 1.2 sec.
In normal operation both sets are synchronized and supply system voltage.
80%
D.K
CNPP
100% 50%
Zone Reach Time
I 80% ~20 m sec
II 150% 500~700 m sec
III -20% ~7 m sec
Question 26:
At 48.6Hz Sheikh Muhamamdi C.B will open to handing over load 220~250MW to CNPP.
At 51.3Hz, CB11 & CB12 will open for LDA Mode.
Question 27:
GCB, IPB, Main T/F, Head lines, surge arrestor, line arrestor, GIS (CB, isolator, earth switch, fast earthing switch, CT, PT, Bus-1, Bus-
2) CVTs, Line trap (PLC) line arrestor.
Cooling fans
Bushings 220kV
Lower oil tank
Upper oil tank
Insulator installation
Iron core
Low voltage leads out
High voltage leads out
T/F oil
High voltage winding
Low voltage winding
Moisture absorber
Question 30:
Advantages
Stable up to 500ºC
Inert metallic parts / contact longer life
No oxidation & deterioration
Electro -ve gas
Decomposition product SF-2 / SF-4 recombination during arc extinction
Diclectric – strength in 2-3 times that of air
Redration in switchgear size
Disadvantage
Moisture contents produce serious problems
Alarm Reset
Low gas pressure 0.45MPa 0.5MPa
Low gas pressure 0.40MPa 0.45MPa
(Block closing & opening)
Air alarms
Alarm Reset
Low air pressure 1.25MPa 1.5MPa
Low air pressure 1.20MPa 1.4MPa
(Block closing & opening)
Question 34:
In case of Zone-1 tripping close 1st CB after 05 sec, close 2nd CB after 30 sec.
In case of one pole opening of CB if fault exists open other two pole to convert 1-phase fault into 3-phase fault.
Question 35: Temp limitation for Main, S/D & Aux T/Fs
Oil Temperature
T/F Alarm (ºC) Manual Trip (ºC)
Main 80 95
Step down 75 85
Auxiliary 75 85
Coil Temperature
T/F Alarm (ºC) Manual Trip (ºC)
Main 115 120
Step down 90 100
Auxiliary 90 100
3-Isolator (02 lines & 01 main T/F) are provided with Stub-bus protection on opening of isolator with respective CB is at close
position, stub protection will open the CB.
Communication
PLC SCADA
Protection permissive (Zone-I)
Digital parameters
GCB, GIS (CB + Isolator), Rx-Trip CB
132kV GIS (CB + Isolator)
Analog parameters
Line MW/MVAR
Main T/F MW/MVAR/MWth
Pulsing Energy Signal
Question 38:
The Main T/F is provided with Gas explosion protection (Buchholz Relay).
In case of fire inside the T/F, Buchholz relay will actuate with low density gas protection actuation working alarm will be given out,
but the trip will not be actuated when gas density reaches set value. Following actions will be taken by protection system generator
protection.
FTD operate (fast mode)
Open CB-11 & CB-12.
Open GCB.
6kV circuit breakers are vacuum circuit breakers. The vacuum has high dielectric strength. Arc-time constant of vacuum is lowest.
Arc is interrupted at zero current.
2. Decoupling Mode
If during high speed T/F the CB to be switched-off should not be switched-off for same reason, the closed CB is open again via
scanning when both CB closed for time > 0.1sec.
Rectifier
Inverter
Static Switch
Battery
Isolating T/F
AC main Supply
AC 220V output
Regulating T/F
UPS Mode
On main
On battery
Bypass main
Maintenance bypass
Cylinder body
Other engine parts
Lube oil
Intake air (during S/D and low load operation)
Frequency : 50±1 Hz
Terminal Voltage : 6.3kV±315V
SI
Loop – 70%, less voltage
0.5 sec – delay EDG startup
3.5 sec – loop sequence
MCR (manual)
V/Hz = 1.1Alarm
V/Hz = 1.2Trip
The limit of V/Hz protection is to limit over-saturation of flux density in iron cores of Gen and transfer. At V/Hz ≥ 1.05, the limit
action will decrease the exciting and value to V/Hz, if it can not be limited yet, the protection will trip the Gen at 1.2 value.
IBP compressor is used to provide & maintain compressed air to insulated bus phase to avoid moisture contents up to 30% FP.
220kV CB
Spring to close & air to open
Quenching medium is SF-6
GCB
Is hydraulically operated
Quenching medium is SF-6
EDG cooling water system
Design for 1000 hrs continuous operation at rated load & 02 hours within 24 hours at 110% over load.
The volume of close cycle coolant ensure 2.25min operation at rated load without external cooling water (closed cycle is cooled by
WES).
Loads:
Engine cylinder body
Turbo-charger carrier housing
Temp > 75ºC thermostat starts operating, full open at 90ºC.
> 95ºC engine will shutdown.
EMA EMB
610 610B
620B 620
600 EMG
~ EEG001DG ~ EEG801DG ~
6kV Bus EEG401DG
(ESB 670CB)
6.3/400V
(ESB 970TM) (4500kVA)
~ ~ ~
ESB804DG ESB803DG ESB802DG