Академический Документы
Профессиональный Документы
Культура Документы
system between the machine and the ffault point. Also, component. These components can n be seen in Fig 3, which
the connection type and impedance of pow wer transformers shows the components and alternatiing current and the sum of
influence the magnitude of short-circuit level. these components.
During a fault in the power system, the equipment must
withstand, without impairing its performannce and without
significant loss of life, any stresses impossed by the short-
circuit currents. Moreover, the circuit breakeer must be able to
interrupt these currents, and support the cuurrents when it is
closed re-establishing a fault current in tthe case of a
permanent fault.
The fault types that can occur in a three phase electrical
system are three-phase, phase to phase, phhase to phase to
ground and phase to ground. Fig. 1 and 2 prresent the models
of representation for these faults. Fig 3: Components of cu
urrent short-circuit.
Fig 5: Assymetry factor for the first six cycles after the fault.
3
TABLE II
TRANSFORMERS PARAMETERS.
can be used to calculate the RMS (Root Mean Square) of the acceptable for routine assessments regarding the dynamic
graphs or to calculate the peak value of the short circuit from capability of equipments.
the RMS value extracted from the simulations using ASPEN
OneLiner: TABLE IV
FAULT CURRENTS FOR THE SLE SUBSTATION.
√2 (3) Fault currents simulated and calculated to bus of 23 kV of the substation
São Leopoldo
where: Solid phase-ground Solid three-phase
IRMS current RMS [A]; short-circuit (kA) - Absolute short-circuit (kA) - Absolute
IPEAK current peak [A]. Cycle X/R 37 X/R 33
error (%) error (%)
Simulated Calculated Simulated Calculated
A. Substation São Leopoldo – A.F X/R (37)
1° 47,20 46,10 2,33% 34,60 34,40 0,58%
Fig 7 shows the peak current in phase A during a solid
2° 43,10 42,70 0,93% 31,50 31,50 0,00%
three-phase fault at the 23 kV bus the substation São
3° 39,70 39,30 1,01% 29,00 29,00 0,00%
Leopoldo. From Fig. 7 it is possible to verify the existence of 4° 37,10 37,20 0,27% 27,00 27,20 0,74%
a unidirectional component that decreases exponentially with 5° 35,20 35,30 0,28% 25,40 25,50 0,39%
the time, until reaching steady state (SS). 6° 33,10 33,10 0,00% 24,00 24,10 0,42%
SS 25,20 24,00 4,76% 18,40 18,00 2,17%
Table VI presents a comparison between the values of fault B. Substation Sapucaia do Sul – A.F X/R (47)
currents derived from the asymmetry factor shown in Fig 5, Tables VIII and IX present the simulation results for the
the steady state current value extracted from ASPEN substation Sapucaia do Sul, where it can be seen that the
OneLiner software, and the fault current values obtained dynamic capacity of the swith disconnectors can be exceeded
through simulations using ATPDraw. From Table VI it is for phase-to-ground faults.
possible to verify that the absolute error varies between 0%
and 4.76% for simulations of three-phase faults and phase-
ground, when comparing the results. Considering the
magnitude of fault currents, it is considered that this error is
6
TABLE VIII case the circuit breaker needs to interrupt a higher fault
FAULT CURRENTS FOR THE SPC SUBSTATION.
current. It was also noted that some circuit breakers can be
Fault currents simulated and calculated to bus of 23 kV of the submitted to fault situations when it is needed to interrupt
substation Sapucaia do Sul fault currents above their rated capacity of interruption.
Solid phase-ground Solid three-phase This situation may occur when there is the maximum
short-circuit (kA) - Absolut short-circuit (kA) - Absolut asymmetry at the time of the fault;
Cycle X/R 47 e error X/R 39 e error • in relation to the dynamic capacity of the equipments, it
(%) (%) was noted that some can have its capacity exceeded. These
Simulated Calculated Simulated Calculated
equipments may be submitted to electromechanical efforts
1° 24,40 23,70 2,87% 19,80 19,80 0,00%
beyond its capacity, causing a reduction of its useful life,
2° 22,50 22,30 0,89% 18,20 18,40 1,10%
or even not supporting such an effort. As quoted in this
3° 21,00 21,00 0,00% 16,90 17,00 0,59%
paper, the X/R ratio of the system has increased over time,
4° 19,80 20,00 1,01% 15,80 16,10 1,90%
making it important to monitor the capacity of the
5° 18,70 19,00 1,60% 14,90 15,30 2,68% equipment already installed and the future equipments.
6° 17,80 18,00 1,12% 14,10 14,40 2,13% This paper presented curves for different asymmetry factors
SS 12,90 12,30 4,65% 10,10 10,30 1,98% and also for different cycles after the fault, validated through
simulations in ATPDraw. The curves can be used in studies
TABLE IX that do not require more complex simulations.
DYNAMIC AND INTERRUPTION CAPACITY.
This work presents an analysis of the behavior of short-
Dynamic capacity of the substation Sapucaia do circuit currents during the transient period, where the
Sul asymmetry can significantly influence the magnitude of the
current. The study shows the importance of evaluating the
Rated Dynamic Breaking short-circuit asymmetrical currents during the project and
Equipament Voltage Current Capacity sizing the equipments, which should support the efforts caused
(kV) (kA) (kA) by these currents, or still the evaluation of existing equipment
Circuit breaker 138 81 45 when there is an expansion of the system that can raise the
Circuit breaker 23 63 35 short-circuit power.
Switch disconnectors 138 80 ***
V. REFERENCES
Switch disconnectors 23 20 ***
1. KAGAN, N., OLIVEIRA, C, C, B., ROBBA, E, E. Introduction to
Current transformers 138 40 *** Electric Power Distribution Systems. São Paulo, SP: Edgard Blücher
Current transformers 23 50 *** Ltda, 2005. 328p.
2. CODI. Protection of Distribution Power Systems. 2.vol. Rio de Janeiro,
Through the simulation results for the studied system, it was RJ: Campus/Eletrobrás, 1982. 232p.
3. ZANETTA JR., L, C. Electromagnetic Transients in Power Systems.
possible to verify that some equipments can be submitted to São Paulo, SP: Edusp, 2003. 711p.
short-circuit currents above its dynamic or interruption 4. SINDER, D. Methods of calculating the transient recovery voltage for
capacity, when considering asymmetric currents evaluated in the analysis of overcoming high voltage circuit breakers. 2007.
Dissertation (Master in Engineering) - Graduate Program in Electrical
the first cycles after fault occurrence with the maximum Engineering, Federal University of Rio de Janeiro, Rio de Janeiro, 2007.
asymmetry. 5. RAMOS, M. J. S. Analysis of Short-circuit Asymmetrical Currents in
Power Distribution Systems. Graduate Program in Electrical
IV. CONCLUSION Engineering, University of Vale of Rio of Sinos, São Leopoldo, 2011.
6. ANDERSON, P, M. Analysis of Faulted Power Systems. Piscataway,
This work presents a study on the behavior of short-circuit NJ: Wiley-IEEE Press, 1973. 534p.
transient in electrical systems, the asymmetric fault currents
and asymmetry factor for different X/R ratios. Simulations
were performed using ATPDraw, applying three-phase and
phase-to-ground faults at different buses of the system studied.
Some conclusions are listed in the following:
• it was observed that even with a X/R lower than 10, the
asymmetry factor for the first cycle is significant, resulting
in a short-circuit asymmetric current above the
symmetrical current magnitude. When the relation X/R is
lower than or equal to 1, the asymmetry factor for the first
cycle is at most 7% greater than the symmetrical current,
and this percentage rapidly increases until a X/R equal to
20;
• increasing the relation X/R, it was verified that the
asymmetrical current remains in the system for a longer
time because the time constant is also increased, and in this