NORTH RISER INV-R-y

U.N.O DC
GOOD LIFT LIFT 1
MSSB-25-LS-01
(LIFE SAFETY)
T/O 3 ISOLATOR
PV PANELS CABLE SCHEDULE NOTES
MSSB-25-ESS-02 HSSB-L25-ESS-1 15kA & MSSB-25-NESS-03
SUB-FDCIE-2 SUB-EWCIE-2 DB-PV DB-H-L25 1. THIS DRAWING SHALL BE READ IN CONJUNCTION WITH THE ELECTRICAL SERVICES SPECIFICATION, THE ARCHITECTURAL
(79A/125A)/
NOTE 17 CABLE DRAWINGS AND ALL OTHER RELEVANT SERVICES DRAWINGS.
LEVEL 25 250A LEVEL 25 INV-25-y
SOUTH CABLE SIZE
RISER DC
PV PANELS
NUMBER 2. REFER TO THE LEGEND
SOUTH RISER SOUTH RISER SOUTH RISER SOUTH RISER SOUTH RISER SOUTH RISER ISOLATOR
30
T/O 1 5 x 4x1C 300mm² Cu FIRE RATED 3. UNLESS OTHERWISE INDICATED, SUBMAIN CABLES INSTALLED ON THE CABLE LADDERS SHALL BE SPACED IN ACCORDANCE
10kA & MSSB-24-LS-01 WITH AS3008 TO ACHIEVE A DERATING FACTOR OF NO LESSTHAN 1.0.
(40A/40A)/ 2 7 x 4x1C 500mm² Cu FIRE RATED + 4 x 240mm² Cu EARTH
SOUTH RISER DC BATTERY
LEVEL 24 250A LEVEL 24 ISOLATOR STORAGE 4. UNLESS OTHERWISE NOTED, ALLOW 25% SPACE POLES ON EACH CIRCUIT BREAKER CHASSIS AND EACH SECTION OF SITE
3 4x1C 35mm² Cu XLPE/PVC + 16mm² Cu EARTH
MAIN SWITCHBOARD IN ADDITION TO THOSE SHOWN ON THE DRAWINGS.
30 3
T/O DB-H-L23 4 4x1C 50mm² Cu XLPE/PVC + 25mm² Cu EARTH
T/O 5. SUPPLY AND INSTALL ENGRAVED RED WARNING LABELS AS REQUIRED AND IN ACCORDANCE WITH ALL RELEVANT
15kA & DC NOTE 18
10kA & MSSB-23-LS-01 (79A/125A)/
5 2 x 4x1C 500mm² Cu XLPE/PVC + 2 x 150mm² Cu EARTH AUSTRALIAN STANDARDS INCLUDING THE FOLLOWING:
(40A/40A)/ ISOLATOR "WARNING-DANGER"
LEVEL 23 250A LEVEL 23 6 NOT IN USE
250A "415VOLTS BEHIND"
"LIVE BUSBARS"
30 LIFT 2 LIFT 3 LIFT 4 LIFT 5 7 4x1C 70mm² Cu XLPE/PVC + 50mm² Cu EARTH
T/O 6. MAIN SWITCHBOARD EARTHING ARRANGEMENTS SHALL COMPLY WITH THE MULTIPLE EARTH NEUTRAL SYSTEM (MEN)
4 4 4 8 8 4x1C 95mm² Cu XLPE/PVC + 50mm² Cu EARTH
10kA & MSSB-22-LS-01 AS REQUIRED BY AS3000.
(40A/40A)/ 9 2000A COPPER BUSDUCT
LEVEL 22 250A LEVEL 22 7. ALL CIRCUIT BREAKERS WITHIN THE ELECTRICAL DISTRIBUTION SYSTEM SHALL DISCRIMINATE IN ACCORDANCE WITH

SECTION

SECTION
TYPE M2 TYPE M2 TYPE M2 TYPE M2 TYPE M2 10 1x4C 25mm² Cu XLPE/PVC + EARTH AS3000 REQUIREMENTS.

BMS
EMS EMS EMS EMS

EMS
EMS
30 3
T/O DB-H-L21 M M M M M
T/O 11 4x1C 150mm² Cu XLPE/PVC + 95mm² Cu EARTH 8. REFER TO CIRCUIT BREAKER SCHEDULE WITHIN SPECIFICATION FOR ADDITIONAL DETAILS.
15kA &
10kA & MSSB-21-LS-01 (79A/125A)/ 125A/250A 125A/250A 125A/250A 125A/250A XX/YY 12 NOT IN USE
(40A/40A)/ 9. CIRCUIT BREAKER SHALL BE SIZED AS REQUIRED FOR FINAL CUIRCUITS.
LEVEL 21 250A LEVEL 21 250A 250A 250A 250A 250A
250A
13 NOT IN USE 10. ENSURE SWITCHBOARD FITS WITHIN INDICATED LOCATION PRIOR TO FABRICATION.
30 DB-H-L25-LIFTS (HIGH RISE LIFT DB) 400A TP, N, E Cu INTERNAL BUSBARS (INSULATED) 14 NOT IN USE
T/O • FORM 3b TO AS 3439 (NO 'i' OR 'h' CONFIGURATIONS ACCEPTABLE) 11. ENSURE ALL LABELS ARE SCREW FIXED. ADHESIVE LABELING WILL NOT BE ACCEPTED.
10kA & MSSB-20-LS-01 • 15kA FAULT LEVEL (MINIMUM) FOR 1 SECOND 15 3 x 4x1C 240mm² Cu XLPE/PVC + 1 x 240mm² Cu EARTH
(40A/40A)/ • ELECTRIC ORANGE EXTERNAL, WHITE INTERNAL 12. NAMING CONVENTION FOR DISTRIBUTION BOARDS
LEVEL 20 250A LEVEL 20 • SHEET METAL MINIMUM 2mm THICKNESS 500A 16 7 x 4x1C 300mm² Cu FIRE RATED + 3 x 240mm² Cu EARTH
• IP42 TENANT :
30 • TOP ENTRY/EXIT
17 4x1C 185mm² Cu FIRE RATED + 185mm² Cu EARTH DB-LR-Ty-Lx-NESS;
T/O y DENOTES TENANT 'S' FOR SOUTH RISER OR 'N' FOR NORTH RISER,
18 1x2C 16mm² Cu FIRE RATED + EARTH x DENOTES FLOOR LEVEL I.E L3 DENOTES LEVEL 3 AND NESS DENOTES FED FROM NON-ESSENTIAL SUPPLY.
10kA & MSSB-19-LS-01
(40A/40A)/ FOR EXAMPLE.
19 4x1C 95mm² Cu FIRE RATED + 50mm² Cu EARTH DB-LR-TN-L13-NESS EQUATES TO DB IN LOW RISE, NORTH RISER, ON LEVEL 13 AND FED FROM NON ESSENTIAL SUPPLY.
LEVEL 19 250A LEVEL 19
DB-HR-Ty-Lx;
20 NOT IN USE
30 3 LEVEL 25 y DENOTES TENANT 'S' FOR SOUTH RISER OR 'N' FOR NORTH RISER,
T/O DB-H-L18 21 4x1C 35mm² Cu FIRE RATED + 16mm² Cu EARTH x DENOTES FLOOR LEVEL I.E L25 DENOTES LEVEL 25 AND FEEDS FROM BOTH ESSENTIAL AND NON-ESSENTIAL SUPPLIES.
T/O
15kA & FOR EXAMPLE.
10kA & MSSB-18-LS-01
(40A/40A)/
(79A/125A)/
SOUTH SOUTH
22 1x2C 25mm² Cu FIRE RATED DB-HR-TN-L14 EQUATES TO DB IN HIGH RISE, NORTH RISER ON LEVEL 14 AND FEEDS FROM BOTH ESSENTIAL AND NON-
LEVEL 18 250A LEVEL 18 NORTH RISER ESSENTIAL SUPPLIES.
250A RISER RISER
U.N.O 23 2 x 4x1C 185mm² Cu XLPE/PVC + 185mm² Cu EARTH
HYDRAULIC SERVICES :
30 24 4x1C 240mm² Cu XLPE/PVC + 120mm² Cu EARTH HSSB-Lx-w-y; WHERE x DENOTES LEVEL NUMBER, w DENOTES 'NESS' FOR NON-ESSENTIAL SUPPLY OR 'ESS' FOR ESSENTIAL
T/O
SUPPLY AND y DENOTES BOARD REFERENCE NUMBER
10kA & MSSB-17-LS-01 25 NOT IN USE FOR EXAMPLE.
(40A/40A)/
LEVEL 17 LEVEL 17 26 4x1C 120mm² Cu XLPE/PVC + 95mm² Cu EARTH HSSB-LB4-NESS-1 EQUATES TO HYDRAULIC SERVICES DB ON BASEMENT 4 FED FROM THE NON ESSENTIAL SUPPLY AND
250A
THE BOARD'S REFERENCE IS NUMBER 1.
30 27 2 x 4x1C 240mm² Cu XLPE/PVC + 185mm² Cu EARTH
RETAIL :
T/O
28 1x4C 10mm² Cu XLPE/PVC + EARTH DB-R-y; WHERE y DENOTES RETAIL TENANCY NUMBER
10kA & MSSB-16-LS-01 FOR EXAMPLE
(40A/40A)/ 29 4x1C 25mm² Cu XLPE/PVC + 16mm² Cu EARTH DB-R-3 EQUATES TO RETAIL TENANCY 3
LEVEL 16 250A LEVEL 16 LEVEL 16
30 1x4C 10mm² Cu FIRE RATED + EARTH HOUSE SERVICES :
30 3
T/O DB-H-L15 DB-H-x; WHERE x DENOTES FLOOR LEVEL I.E L03 DENOTES LEVEL 3
LIFT 6 T/O 31 2 x 4x1C 185mm² Cu FIRE RATED + 150mm² Cu EARTH FOR EXAMPLE.
15kA & LIFT 7 LIFT 8 LIFT 9 LIFT 10 LIFT 11
10kA & MSSB-15-LS-01 DB-H-L03 EQUATES TO HOUSE DB ON LEVEL 3.
(40A/40A)/
(79A/125A)/ 32 4x1C 240mm² Cu FIRE RATED + 120mm² EARTH
LEVEL 15 250A LEVEL 15
250A COMMERCIAL/COMMUNITY SERVICES :
33 3 x 4x1C 185mm² Cu XLPE/PVC + 2x185mm² EARTH
DB-Cw-x-y; WHERE w DENOTES 'O' FOR COMMERCIAL OR 'U' FOR COMMUNITY,
30 34 2 x 4x1C 150mm² Cu XLPE/PVC + 1x150mm² EARTH x DENOTES FLOOR LEVEL I.E L03 DENOTES LEVEL 3 AND y DENOTES BOARD REFERENCE NUMBER
T/O FOR EXAMPLE.
10kA & MSSB-14-LS-01 35 3 x 4x1C 400mm² Cu XLPE/PVC + 2x400mm² Cu EARTH DB-CU-B4-1 EQUATES TO COMMUNITY DB ON LEVEL B4 AND BOARD REFERENCE 1.
(40A/40A)/
LEVEL 14 250A LEVEL 14 36 4x1C 300mm² Cu XLPE/PVC + 150mm² Cu EARTH INVERTERS :
INV-x-y; WHERE x DENOTES LEVEL NUMBER AND y DENOTES BOARD REFERENCE NUMBER
30 37 1x2C 35mm² Cu FIRE RATED FOR EXAMPLE
T/O INV-25-1 EQUATES TO INVERTER LOCATED ON LEVEL 25 WITH BOARD REFERENCE NUMBER 1.
38 1x4C 16mm² Cu FIRE RATED + EARTH
10kA & MSSB-13-LS-01
(40A/40A)/ 39 4x1C 300mm² Cu FIRE RATED + 150mm² EARTH 13. CONTRACTOR SHALL SUPPLY AND INSTALL SURGE PROTECTION DEVICE AS FOLLOWING AT EACH INCOMING SUPPLY OF
LEVEL 13 250A LEVEL 13 THE MSB AND MDB.
40 4x1C 120mm² Cu FIRE RATED + 70mm² EARTH SPD.EN 6143-11/IEC 614311.
30 3
TYPE 1/CLASS 1 AND TYPE 2/CLASS 2 COMBINED SURGE AND LIGHTNING ARRESTOR, 3Ø.
T/O DB-H-L12 41 4x1C 50mm² Cu FIRE RATED + 25mm² EARTH
T/O 100kA RMS 2250kA PEAK SHORT CIRCUIT FAULT WITHSTAND.
15kA &
10kA & MSSB-12-LS-01 MANUFACTURER : DEHN DV_M_TNC-255_FM.
(40A/40A)/
(79A/125A)/ 42 3150A COPPER BUS DUCT CATALOGUE NUMBER : 951305.
LEVEL 12 250A LEVEL 12
250A PROVIDE AND INSTALL REMOTE SIGNALING CONTACT WIRED TO LABELLED TERMINALS AND THROUGH TO SCADA
43 1x2C 10mm² Cu PVC/PVC + EARTH SYSTEM.
30 44 9 x 4x1C 400mm² Cu XLPE/PVC + 4x240mm² Cu EARTH
T/O 14. ALL FIRE RATED CABLES SHALL BE INSTALLED ON 2HR FIRE RATED CERTIFIED CABLE LADDER AND SUPPORT SYSTEMS.
10kA & MSSB-11-LS-01
(40A/40A)/ 15. INSTALL ALL METERING FUSES AND SHORTING LINKS IN DEDICATED METERING COMPARTMENT. INSTALL ALL BMS/EMS
LEVEL 11 250A LEVEL 11 TERMINALS IN SEPARATE DEDICATED COMPARTMENT.

30 16. ALL ACB's AND MCCB's PROVIDED AT MAIN SWITCHBOARDS (MSB-1, MSB-2, MSB-GEN) SHALL BE ELECTRONIC TYPE.
T/O REFER TO CIRCUIT BREAKER SCHEDULE IN THE SPECIFICATION FOR FURTHER DETAILS.
10kA & MSSB-10-LS-01
(40A/40A)/ 17. APPROXIMATELY 186kW SOLAR PV SYSYTEM ACROSS LEVEL 25 AND ROOF LEVEL, PROVIDING SOLAR PANELS ARE RATED
LEVEL 10 250A LEVEL 10 AT 360W. THE CONTRACTOR SHALL ALLOW TO ENGAGE A SPECIALIST TO DESIGN, SUPPLY, INSTALL, TEST AND
COMMISSIONING A COMPLETE SYSTEM WORKING SYSTEM.
30 3 PROVIDE ALL NECESSARY EQUIPMENT AND POWER DISTRIBUTION REQUIRED TO FEED THE ENERGY GENERATED BY THE
T/O
T/O DB-H-L09 LEGEND SYSTEM INTO THE POWER DISTRIBUTION NETWORK. THIS IS TO INCLUDE, BUT IS NOT LIMITED TO:
15kA &
10kA & MSSB-09-LS-01 (79A/125A)/ xx DENOTES TRIP SETTING yy DENOTES TRIP UNIT SIZE A. SOLAR PANELS
(40A/40A)/
LEVEL 09 250A LEVEL 09 B. AC/DC CABLING
250A
C. AC/DC SWITCHGEAR AND CIRCUIT PROTECTION
30 D. SURGE DIVERTERS
xxA|yyA E. EARTHING
T/O CIRCUIT BREAKER SIZING
zzA F. INVERTERS COMPLETE WITH MODULATION CONTROL TO TAILOR THE OUTPUT OF THE PV SYSTEM TO THAT OF THE
10kA & MSSB-08-LS-01
(40A/40A)/ BUILDING.
LEVEL 08 250A LEVEL 08 G. NON-EXPORT CONTROLS TO SATISFY THE REQUIREMENTS OF CITIPOWER AND FUTURE PV INSTALLATIONS ON OTHER
zz DENOTES FRAME SIZE BUILDINGS OF THE SITE.
H. COORDINATION WITH POWER SOURCE CONTROL REQUIREMENTS.
30
I. EQUIPMENT TO PROVIDE COMPLIANCE WITH CITIPOWER POWER QUALITY REQUIREMENTS.
T/O
J. BMS INTERFACES
10kA & MSSB-07-LS-01 K. METERING
(40A/40A)/
LEVEL 07 LEVEL 07 L. BATTERY STORAGE (LITHIUM TECHNOLOGY PREFERRED) FINAL LOCATION AND CAPACITY OF BATTERY STORAGE
SHALL
250A
BE AGREED WITH CLIENT.
30 3
T/O DB-H-L06 PV SPECIALIST IS TO FULLY COORDINATE WITH THE ELECTRICAL CONTRACTOR DURING TENDER TO ESTABLISH WHO WILL
T/O
15kA & BE PROVIDING AND INSTALLING WHICH ELEMENTS OF PLANT.
10kA & MSSB-06-LS-01 (79A/125A)/
(40A/40A)/
250A THE DESIGN AND DOCUMENTATION SHALL COMPLY WITH THE CLEAN ENERGY COUNCIL GRID–CONNECTED SOLAR PV
LEVEL 06 250A LEVEL 06
SYSTEMS “DESIGN GUIDELINES FOR ACCREDITED INSTALLERS” AND LOCAL POWER AUTHORITY REQUIREMENTS.

30 18. EQUIPMENT SHOWN WITHIN DASHED BOX ARE FUTURE PROVISION ONLY. ALLOW FOR CONNECTION OF FUTURE
T/O BATTERY STORAGE ONLY (BATTERIES NOT WITHIN SCOPE OF WORKS).
10kA & MSSB-05-LS-01
(40A/40A)/
LEVEL 05 250A LEVEL 05

30
T/O
10kA & MSSB-04-LS-01
(40A/40A)/
LEVEL 04 250A LEVEL 04

30 3
T/O DB-H-L03
T/O
15kA &
10kA & MSSB-03-LS-01 (79A/125A)/
(40A/40A)/
LEVEL 03 250A LEVEL 03
250A

30
T/O
10kA & MSSB-02-LS-01
(40A/40A)/
LEVEL 02 250A LEVEL 02

MSB-GEN (GENERATOR SWITCHBOARD)


MSSB-01-LS-01
REFER TO DRAWING 2MQ_ED_00007 L13 L14 (LIFE SAFETY) HSSB-L01-ESS-1 MSSB-01-NESS-02 MSSB-01-NESS-03 HSSB-L01-NESS
SUB-FDCIE-1 SUB-EWCIE-1
LEVEL 01 LEVEL 01

DB-PAV
T/O DB-R-C (MELBOURNE SQUARE
15kA & (RETAIL COMMON) PAVILLION)
(125A/125A)/ DB-H-L00
250A 3
LEVEL 00 LEVEL 00

DB-EOT
(END OF TRIP)
MSSB-B1-NESS-01

LEVEL B1 LEVEL B1

T/O
15kA &
(125A/125A)/ DB-H-LB2
250A 3
LEVEL B2 LEVEL B2

MSSB-B3-LS-01 DB-CP
(LIFE SAFETY) (CAR PARK) HSSB-B3-ESS-1 MSSB-B2/3-NESS-01 HSSB-B3-NESS-1
2

LEVEL B3 SPARE CAPACITY SPARE CAPACITY LEVEL B3


CAPABLE OF HOUSING 1 OFF 250A MCCBs CAPABLE OF HOUSING 1 OFF 250A MCCBs
(FRAME SIZE) INCLUDING METERING AND (FRAME SIZE) INCLUDING METERING AND
41 38 41 38 40 18 39 18 19 17 41 EMS TERMINALS 37 37 24 15 EMS TERMINALS 3 29 11 7 36 34 3 35 3 29 36 3 3 3 3 4 27 8 3 4 29 7

GENERATOR LIFE SAFETY ESSENTIAL (MAINS & EPP) ESSENTIAL SERVICES (MAINS & EPP) METERED SECTION (MAINS)
FUTURE UPS
SUPPLY SECTION TYPE M2
(EPP) TYPE M2 TYPE M2 TYPE M2 TYPE M2 EMS
EMS EMS EMS EMS
EMS TYPE M2 M
M M M M
EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2
EMS
TYPE M2 M EMS
TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2 EMS TYPE M2
M M M M M 20A|20A M 20A|20A M M M M 20A|20A 20A|20A M M M M M M M M M M M M M M M M M M M M M
125A 125A 125A 125A
BMS 320A|400A
63A|125A 32A|40A 63A|125A 32A|40A 125A|250A 250A|250A 250A|250A 200A|250A 63A|125A XX|YY 320A|400A 800A|1000A XX|YY XX 63A 63A|63A 160A|250A 100A|160A 320A|400A 80A|100A 800A|1250A 63A|100A 63A|100A 250A|250A 63A|125A 63A|125A 63A|125A 63A|125A 63A|125A 400A|400A 160A|250A 63A|100A 100A|100A 63A|63A 80A|100A
160A 160A 160A 160A M 400A
250A 250A 250A 250A 250A 250A 250A 400A 250A 250A 400A 1000A 250A 250A 100A 125A 250A 250A 400A 125A 1250A 125A 125A 250A 250A 250A 250A 250A 250A 400A 250A 125A 160A 125A 125A
200A 200A 200A 200A

REFER TO EMS TYPE M2 1250A TP, N, E Cu INTERNAL BUSBARS (INSULATED) 1250A TP, N, E Cu INTERNAL BUSBARS (INSULATED) EMS TYPE M2 2000A TP, N, E Cu INTERNAL BUSBARS (INSULATED)
FAULT CURRENT LIMITING FUSE 200A|250A EMS TYPE M2 63A|100A XX|YY XX|YY
2MQ_ED_00007 M M
FAULT CURRENT LIMITING FUSE 250A 125A 250A 250A
FOR FURTHER DETAIL M
FAULT CURRENT LIMITING FUSE R W B R W B EMS TYPE M2 TYPE M2 EMS EMS TYPE M2 EMS TYPE M2
N N M M M M
R W B M.E.N
BMS NOTE 13
C/W INTERMEDIATE 'OFF' POSITION BMS C/W INTERMEDIATE 'OFF' POSITION ATS N N E
1250A 1250A 1000/1250A 900/1250A
SEGREGATED LIFE SAFETY ESSENTIAL SECTION 3-POLE ATS 3-POLE SEGREGATED SEGREGATED
R W B R W B NORMALLY 1250A 1250A SPARE CAPACITY TO MAIN EARTH BAR
1000/2000A METERING BMS/EMS
• FORM 3b TO AS 3439 (NO 'i' OR 'h' CONFIGURATIONS ACCEPTABLE) CLOSED 3-POLE 3-POLE
• 50kA FAULT LEVEL (MINIMUM) FOR 1 SECOND
N N 2000A SECTION TERMINAL CAPABLE OF HOUSING 2 OFF 250A MCCBs (FRAME SIZE)
POSITION
• TOP ENTRY/EXIT
2000A TP, N, E Cu INTERNAL R W B R W B SECTION INCLUDING METERING AND EMS TERMINALS FOR EACH
BUSBARS (INSULATED) MECHANICAL LOCK 1600/2000A
• RED EXTERNAL STRUCTURED FINISH 2000A N N
NOTE 13 2000A
• IP42 3200A TP, N, E Cu INTERNAL BUSBARS (INSULATED) 2000A TP, N, E Cu INTERNAL BUSBARS (INSULATED)
FUTURE LOAD BANK CONNECTION POINT MSB-1 (METERED SECTION)
WITHIN SEGREGATED COMPARTMENT PROTECTION RELAY
2000A NOTE 13 • FORM 3b TO AS 3439 (NO 'i' OR 'h' CONFIGURATIONS ACCEPTABLE)
1250A TP, N, E Cu INTERNAL BUSBARS (INSULATED) CTs IN DEDICATED
• 50kA FAULT LEVEL (MINIMUM) FOR 1 SECOND
TYPE M4 COMPARTMENT
1250A TP, N, E Cu INTERNAL BUSBARS (INSULATED) M POWER ANALYSER
• ELECTRIC ORANGE EXTERNAL STRUCTURED FINISH
1000/1250A • SHEET METAL MINIMUM 2mm THICKNESS
1250A • IP42
TO GENERATOR CONTROL PFR TYPE M1 • TOP ENTRY/EXIT
SEGREGATED GENERATOR SUPPLY SECTION M SUPPLY AUTHORITY SEGREGATED ESSENTIAL SERVICES ESSENTIAL SECTION PRIMARY
2000A TP, N, E Cu INTERNAL BUSBARS (INSULATED)
PROTECTION
• FORM 3b TO AS 3439 (NO 'i' OR 'h' CONFIGURATIONS ACCEPTABLE) METERING SECTION FUTURE CABLING TO AHF • FORM 3b TO AS 3439 (NO 'i' OR 'h' CONFIGURATIONS ACCEPTABLE)
RELAY
• 50kA FAULT LEVEL (MINIMUM) FOR 1 SECOND • 50kA FAULT LEVEL (MINIMUM) FOR 1 SECOND
2000A TP, N, E Cu INTERNAL BUSBARS (INSULATED) 3150A
• TOP ENTRY/EXIT • TOP ENTRY/EXIT
LOCKABLE 8 29
• RED EXTERNAL STRUCTURED FINISH • RED EXTERNAL STRUCTURED FINISH
1 MAIN ISOLATOR
• IP42 • IP42
HSSB-B4-ESS-1 MSSB-B4-NESS-01
LEVEL B4 FUTURE ACTIVE HARMONIC FILTER LEVEL B4
AHF
2MVA CITIPOWER CITIPOWER SHALL ADVISE SCCD
TRANSFORMER LV CIRCUIT BREAKER SIZE WITHIN SUBSTATION.
11kV/400V

A
F
C
I
S
S
U
E
O AFC ISSUE CM KY 06.09.18
N AFC ISSUE CM KY 31.08.18 TWO MELBOURNE QUARTER ELECTRICAL SCHEMATICS -SHEET 1
M AFC ISSUE CM KY 28.06.18
L AFC ISSUE CM KY 18.06.18
K
J
IFC ISSUE
AFT ISSUE
CM
CM
KY
KY
18.05.18
13.04.18
ELECTRICAL SERVICES
I IFT ISSUE CM KY 09.03.18
H ISSUE FOR PRICING CM KY 07.02.18
N.T.S 31281 2MQ_ED_00005 O
REV DESCRIPTION DRAWN APP'D DATE ARCHITECT/CLIENT PROJECT TITLE SCALE @ A0 PROJECT No DRAWING No REV