PSV Identification
Customer Requisition # Job # Job Description
PT. Duta Instrument Alfa Sakti +11976
Tag # Tag Description P / ID NACE
+11979 No
ASME Code Fluid State Resolved ASME Area Resolved API Area Rupture Disk Coeff.
ASME Sec. VIII Liquid (Mass) 0.010552 in² 0.009497 in² No Rupture Disk, 1
Operating Pressure Set Pressure Constant Back P. Variable Back P. Cold Diff. Test P.
13.5 Bar G 15 Bar G 0 Bar G 0 Bar G 15 Bar G
Operating Temp. Relief Temp. Operating to Set % Over Pressure Percent Over P.
26 °C 26 °C 90 % 1.5 Bar G 10 %
26DA10L-120
API Letter API Area ASME Area
D 0.110 in² 0.150 in²
Size Rating Facing
Inlet: 1.0 in 150 # RF
Outlet: 2.0 in 150 # RF
Valve Design Cap Constrn Test Gag
Conventional Screwed Cap No
Max. Rel. Cap. React. Force Noise
28430 lb/hr 0.007054 lbs -
Materials
Body (1)
Carbon Steel (SA-216 Gr. WCB)
Bonnet (2)
Carbon Steel (SA-216 Gr. WCB)
Nozzle (5)
316 SS
Disc (4)
Dimensions 316 SS
42 lb 19 in 4 1/2 in 316 SS
4 1/8 in 1/
2 in 1 3/16 in Chrome Alloy
Bellows (15)
N/A
Name Plate Capacity
Air Water Steam
- 57 US gpm -
Tag Notes
We assume :
1. Operating Pressure = 13.5 BarG, 10% lower than Set. Pressure (15 BarG)
1. Operating Pressure = 13.5 BarG, 10% lower than Set. Pressure (15 BarG)
2. Operating Temp. = 26 degC
3. Constant Back Pressure = 0 BarG
4. Variable Back Pressure = 0 BarG
5. % Allowable = 10% (Blocked Discharge)
6. Liquid Flow Rate = 2000 lb/hr
7. Liquid Relieving Temperature = 26 degC
8. Specific Gravity of Liquid = 1
9. Viscosity of Liquid = 1 Cp
Please customer to verify and confirm for data above.
SizeMaster 4.3.2.13, DB: D:\DATA SIZE MASTER\SM JAS 2013-lf End of 26DA10L-120 Valve Reference Drawing
Tag +11976: +11979 - Data Sheet
PSV Identification
Tag # Tag Description Tag Status P / ID Discharge To Revision #
+11979 Valve Selected 0
Plant # Drawing # Index # Issue For Service Inlet Line # Outlet Line # Revised By
System Admin
Sizing Basis
ASME Code Cause of Over Pressure Fluid State Rupture Disk Coeff. NACE
ASME Sec. VIII Blocked Discharge Liquid (Mass) No Rupture Disk, 1 No
Process Parameters
MAWP - Bar G Max. Design T. - °C Min. Design T. - °C
Operating Operating Constant Back
13.5 Bar G 26 °C 0 Bar G
Pressure Temp. P.
Set Pressure 15 Bar G Relief Temp. 26 °C Variable Back P. 0 Bar G
Operating to Set % 90 % Percent Over P. 10 % Over Pressure 1.5 Bar G
Atm Pressure 1.0133 Bar Abs Relief Pressure 17.513 Bar Abs Cold Diff. Test P. 15 Bar G
Non-Compressible State
Fluid Type Liquid Specific Gravity 1 sp gr Viscosity Type Absolute
Req. Flow Cap. 2000 lb/hr Viscosity 1 Centipoise
Calculated Area 0.010552 in² Reynolds # 28918
Resolved ASME Area: 0.010552 in² (Resolved by Maximum) Resolved API Area: 0.009497 in²
Model Selection
Manufacturer Farris API Letter D Inlet Size 1.0 in Outlet Size 2.0 in
Model Number 26DA10L-120 API Area 0.110 in² In. Rating 150 # Out. Rating 150 #
Valve Design Conventional ASME Area 0.150 in² In. Facing RF Out. Facing RF
Cap Constrn Screwed Cap Test Gag No Quantity 1 NACE No
Name Plate Capacity (Water): 57 US gpm
Model Materials
Body Carbon Steel (SA-216 Gr. WCB) Bonnet Carbon Steel (SA-216 Gr. WCB)
Nozzle 316 SS Disc 316 SS
Guide 316 SS Spring Chrome Alloy
Bellows N/A
Sizing Scenarios
Fluid Cause of Relief Load Noise Noise Required
Scenario Max Rel Cap Relief T. React. Force
State Over P. Capacity Atm (dBa) Flare (dBa) Area
Blocked
Case A Liquid 2000 lb/hr 28430 lb/hr 26 °C 0.007054 lbs - - 0.010552 in²
Discharge
Tag Notes
We assume :
1. Operating Pressure = 13.5 BarG, 10% lower than Set. Pressure (15 BarG)
2. Operating Temp. = 26 degC
3. Constant Back Pressure = 0 BarG
4. Variable Back Pressure = 0 BarG
5. % Allowable = 10% (Blocked Discharge)
6. Liquid Flow Rate = 2000 lb/hr
7. Liquid Relieving Temperature = 26 degC
8. Specific Gravity of Liquid = 1
9. Viscosity of Liquid = 1 Cp
Please customer to verify and confirm for data above.
SizeMaster 4.3.2.13, DB: D:\DATA SIZE MASTER\SM JAS 2013-lf End of +11979 Data Sheet