STRUCTURAL DESIGN OF STICK CURTAIN
WALLING - Sample calculations
Example 1
Design a transom for a curtain wall with
mullions spaced at 1.2m centre to centre
(transom length of, say, 1.15m) and transoms
spaced at 1.6m. The wall is glazed with 6/12/6
double glazed units.
Vertical loading
The transom must be designed to carry the dead
load of the glass. The dimensioned assembly,
together with the resulting bending moment and
shear stress distribution in the transom due to
dead loads, is illustrated in Figure 1.
where:
This document has been printed from the CWCT ‘Cladding Forum’, access to which is restricted to subscribing Members of
the Centre for Window & Cladding Technology. Information about the availability of CWCT publications and membership is
available at our website – www.cwct.co.uk – or from the address at the end of this note.
Structural design of curtain walling - sample calculations TN27
The design bending moment in the transom due The limiting stress po depends on the grade of
to the weight of the glass is given by: aluminium and can be obtained from BS 8118
Table 4.2. The most common grade of
M = fPL/4 = (1.22831.15)/4 = 98Nm. aluminium for curtain wall sections is 6063
alloy in temper T6 for which the limiting stress
The design shear force is: is 160N/mm2. For design purposes this value is
reduced by dividing by a safety factor m which
V = fP = 340N takes the value 1.2 from Table 3.3 of BS8118.
2/8
Structural design of curtain walling - sample calculations TN27
3/8
Structural design of curtain walling - sample calculations TN27
assumed to be unaffected (Clause 4.5.4, point loads) (see Technical Note 2 Introduction
BS 8118: Part 1). to wind loading on cladding and Figure 2).
4/8
Structural design of curtain walling - sample calculations TN27
384 EI
Mmax = (160/1.2) 6.3104/22.7
where:
= 370 NmOK
W is the total load, in N,
Check for buckling
other terms as previously defined.
web =0.6 d/t = 0.6 18.5/2.1 = 5.3
5 1088 (1150) 3
max
5mm
flange = b/t = 45.8/2.1 = 21.8 384(70 10 3 )(6.3 10 4 )
Combined loading
(p A )
VRS
v v The above calculations have considered the
m effects of dead and wind loads separately. As
these loads can act at the same time it is
where: necessary to check the effect of combining the
loads. The full procedure is given in BS 8118
Av = 0.8 N D t
clause 4.8 however in this case the following
condition should be satisfied
where:
M xdesign M ydesign
D is the overall depth of web measured to the 1
outer surfaces of flanges, 28 mm, M x max M y max
t is the web thickness, 2.1 mm,
substituting values determined above gives
N is the number of webs, 2,
5/8
Structural design of curtain walling - sample calculations TN27
188 98
0.68 OK
370 587
Example 2
Design a mullion which spans over two floors
(say, 6.4m) to resist a wind load of 1600 Pa (1.6
kN/m2) and the dead loads transferred from the
connecting transoms in Example 1. Assume a
uniform distribution of wind loading on the
facade.
Loading
The dimensioned assembly, together with the
resulting bending moment and shear stress
distribution in the mullion due to the applied
wind load, is illustrated in Figure 3. This
loading is assumed to be uniformly distributed
along the length of the mullion. Assuming it is
supported at the top, the mullion is also subject
to tension due to dead loads.
= (1.23.2) 1600
= 6144 N
Stresses
The most highly stressed cross-section occurs at Figure 3 Live loading on curtain walling
the intermediate support where the bending mullion
moment is given by:
Mmax = (160/1.2) 165104/64 = 3438 Nm
M = f WL/8 = (1.2 6144 3.2)/8 = 2950 Nm.
Check for buckling
This is also the region of peak shear force, given
by: web =0.5 d/t = 0.5 86/2.1 = 20.5
6/8
Structural design of curtain walling - sample calculations TN27
7/8
Structural design of curtain walling - sample calculations TN27
where:
131 10 3 N
8/8