Вы находитесь на странице: 1из 1

JE-H(St)HRH Bd fire warning cable, FE 180/E 30 to E 90, halogen-free

Technical data Cable structure Properties


Ⴠ Special insulation for cores and outer jacket Ⴠ Bare solid copper conductor, 0,8mmø Ⴠ No fire propagation
according to DINVDE0815. Compound Ⴠ Special core insulation halogen-free, Ⴠ Low smoke density
to DINVDE0207 part23 HI1, flame cross-linked polymer to DINVDE0207 Ⴠ Not for purposes of high current and
resistant part23, HI1, flame retardant (E90 with power installation as well as underground
Ⴠ Insulation integrity 180min tested to special foil wrapping over conductor) laying
DINVDE0472 part814 and IEC60331 Ⴠ 2 cores twisted to pair and each 4 pairs Ⴠ FE180: Insulation integrity for 180
Ⴠ Functionality E 90 min layed up in bunches, the bunches stranded minutes. Tests to DINVDE0472 part814
Ⴠ Loop resistance max. 73 Ohm/km in layers IEC60331.
Ⴠ Operating voltage (peak voltage) Ⴠ Glass-fibre taped Insulation integrity under direct flame
max. 225 V (not for purposes of high Ⴠ Screening with alu-laminated polyester tape propagation for the test period of 180
current and power installation) and solid copper drain wire 0,8mmø minutes.
Ⴠ Test voltage Ⴠ Inner sheath, flame retardant polyolefin Ⴠ E30: Functionality of electrical cable
core/core 500 V compound to DIN VDE 0207 part 24 HM3 systems for minimum 30 minutes. Test to
core/screen 2000 V Ⴠ Galvanized steel wire braided screen DIN4102 part12.
Ⴠ Insulation resistance Ⴠ Special outer jacket HM2 to DINVDE0207 The functionality for 30 minutes assures
min. 100 MOhm x km part24, flame resistant when persons and animals are to be saved
Ⴠ Mutual capacitance Ⴠ Outer jacket red (RAL3000) with imprint from a burning building. 30minutes
max. 120 nF/km at 800 Hz  "BRANDMELDEKABEL" secures the functional performance of the
Ⴠ Minimum bending radius Tests fire warning and alarm systems, safety and
approx. 6x cable ø Ⴠ Flame test to VDE0482-332-3, BS4066 spare lighting, passenger lifts with
Ⴠ Caloric load values part3/ DINEN60332-3/ IEC60332-3 evacuation circuits, except the cables which
see Technical Informations (equivalent DINVDE0472 part804 test are installed within the ladder shafts and
methodC) engine rooms.
Ⴠ Corrosiveness of combustion gases Ⴠ E90: Functionality of electrical cable
according to VDE0482 part267/ systems for minimum 90 minutes. Test
DINEN50267-2-2/ IEC60754-2 (equivalent method to DIN4102 part12.
DINVDE0472 part813) The functionality for 90 minutes assures
Ⴠ Smoke density according to VDE0482 the functional performance of
part1034-1+2 / IEC61034-1+2 / water-pressure-rising stations for the
DINEN61034-1+2 / BS7622 part1+2 supply to avoid smoke and heat in
 (equivalent DINVDE0472 part816) safety-stairs and inner rooms, ladder shafts
Ⴠ LS0H = Low Smoke Zero Halogen-free. and engine rooms for fire brigade lifts,
emergency lifts for sickbeds in hospitals
and the fire brigade lifts.

Note
Ⴠ E 30 to E 90
Functionality is dependant on installation
technique.
Q


Application
Flame resistant, halogen-free, static screened installation cables for telecommunication purpose. The static screen prevents strong interference
impulse.
Suitable for fixed installation everywhere, where in case of fire human life and material assets are to be protected and a safety conciousness
take a special significance, e.g. in industrial complexes, public buildings, hotels, airports, under ground railway networks, hospitals.
= The product is conformed with the EC Low-Voltage Directive 2006/95/EG.


 


Part no. No.pairs x Outer Ø Cop. Weight Part no. No.pairs x Outer Ø Cop. Weight
cross-sec. approx. weight approx. cross-sec. approx. weight approx.
mm mm kg/km kg/km mm mm kg/km kg/km
34075 2 x 2 x 0,8 10,5 25,0 150,0 34080 20 x 2 x 0,8 26,9 206,0 870,0
34076 4 x 2 x 0,8 14,8 45,0 275,0 34072 32 x 2 x 0,8 35,0 326,0 1360,0
34077 8 x 2 x 0,8 21,1 85,0 545,0 34073 40 x 2 x 0,8 41,0 407,0 1800,0
34078 12 x 2 x 0,8 22,7 126,0 602,0 34074 52 x 2 x 0,8 44,0 529,0 2038,0
34079 16 x 2 x 0,8 25,0 166,0 734,0


Dimensions and specifications may be changed without prior notice. (RQ02)