COOLING
SYSTEM

Copyright 2011 Tesco Corporation


COOLING SYSTEM TOP DRIVE
TRAINING

 AT THE COMPLETION OF THIS SECTION YOU WILL


BE ABLE TO :

 IDENTIFY COMPONENTS
 UNDERSTAND A BASIC REFRIGERATION CIRCUIT
 IDENTIFY COOLING SYSTEM FLOW PATHS
 IDENTIFY AND TROUBLESHOOT PROBLEMS

Copyright 2011 Tesco Corporation


COOLING SYSTEM

 TOP DRIVE PUMP: supplies coolant to the top drive for


cooling gearbox and motors.

 DRIVE PUMP: supplies coolant to the power module cold


plates.

 CHILLER BYPASS PUMP: is used to bypass the chiller


circuit when the chiller is out of service for repair, coolant is
run through the modine instead.

 CIRCULATION PUMP: moves the coolant from the chiller


tank up to the chiller condenser coils. (High ambient and
1350)

Copyright 2011 Tesco Corporation


 MODINE / AKG: radiators.

 COLD PLATES: used for transferring heat away from


electronic components.

 PA44 MOTOR STATORS: have coolant passing through


them to transfer heat away from the motors, and into the
coolant lines, through the heat exchanger then returning
back to the mechanical module.

 HEAT PUMP: maintains the ambient temperature in the


power module within a range of 65 F to 75 F.

 DEHUMIDIFIER: removes moisture from the air in the


power module.
Copyright 2011 Tesco Corporation
CHILLER
 COMPRESSOR: brings (low pressure gas in) and
pumps (high pressure gas out) to condenser.(R22
refrigerant)

 CONDENSER: (high pressure gas in) turns back to


(high pressure liquid out) when it cools, going
through condenser (air cooled).

 TX VALVE: controls the flow of liquid through the


evaporator,(temperature controlled)

 EVAPORATOR: (low pressure liquid in) changed


back to (low pressure vapor out), when heated by
power module coolant.
Copyright 2011 Tesco Corporation
COOLING SYSTEM DATA

MD-500 AND CHILLER

 1 TON =12,000 BTU/HR (HEAT REMOVAL RATE)

 THE ECI-900, (2) MD-500 DRIVE REQUIRE A 10 TON CHILLER.

 THE ECI-1350, (3) MD-500 DRIVE AND HIGH AMBIENT UNITS REQUIRE A
25 TON CHILLER.

 EACH MD-500 REQUIRES 15 GPM (57 LPM) AND A HEAT REMOVAL RATE
OF 34,130 BTU /HR.(10kW)

 THE ECI-900 MD-500 DRIVE COOLANT PUMP IS DRIVEN BY A 5 HP MOTOR

Copyright 2011 Tesco Corporation


COOLING SYSTEM DATA

 THE ECI-1350 MD-500 DRIVE AND HIGH AMBIENT UNITS COOLANT


PUMP IS DRIVEN BY A 10 HP MOTOR

 THE ECI-900 DRIVE USE 2 CHILLER COMPRESSORS WITH THE WATER


TEMPERATURE THERMOSTAT (WTT) SET AT COMP#1 @68 DEG.F
(21.1DEG.C) COMP#2 : 5 DEG. APART (AUTOMATIC)

 ECI-1350 DRIVES AND HIGH AMBIENT UNITS USE 4 CHILLER


COMPRESSORS WITH THE WATER TEMPERATURE THERMOSTATS (WTT)
SET AT : COMP#1 @70DEG.F (21.1DEG.C) COMP#2 @70DEG.F
(21.1DEG.C) COMP#3 @72DEG.F (22.2DEG.C) COMP#4 @74DEG.F
(23.3DEG.C) (MULTI STAGE SYSTEM)

Copyright 2011 Tesco Corporation


COOLING SYSTEM DATA
CHILLER BYPASS
 THE ECI-900 MD-500 DRIVE CHILLER BYPASS PUMP IS DRIVEN BY A
5 HP MOTOR
 THE ECI-1350 MD-500 DRIVE AND HIGH AMBIENT UNITS CHILLER
BYPASS PUMP IS DRIVEN BY A 10 HP MOTOR

T0P DRIVE
 EACH PA44 MOTOR REQUIRES 7 GPM(26.6 LPM) OR 3.5 GPM (13.3
LPM) PER STATOR.
 THE 450 TOP DRIVE AND THE ECI-900 TOP DRIVE COOLANT PUMP IS
DRIVEN BY A 5 HP MOTOR
 THE ECI-1350 TOP DRIVE AND HIGH AMBIENT UNITS COOLANT
PUMP IS DRIVEN BY A 10 HP MOTOR

FLOW SWITCHES
 THE TOP DRIVES AND MD-500 COOLANT RETURN LINES CONTAIN
FLOW SWITCHES, IF THERE IS NO FLOW THE TOP DRIVE WILL NOT
RUN (NO FLOW NO GO)
Copyright 2011 Tesco Corporation
COOLING SYSTEM DATA
GOULDS PUMP MODEL AND APPLICATIONS

 1SVC1J6LO: 450 HP TOP DRIVE AND DRIVE PUMPS, 900 HP TOP


DRIVE AND CHILLER BYPASS PUMPS.

 2SVC1L6NO: 1350 HP AND 900 HP HIGH AMBIENT PACKAGE TOP


DRIVE AND CHILLER BYPASS PUMPS.

 3SVB1J6DO: 900 HP DRIVE PUMP.

 4SVB1L6DO: 1350 HP AND 900 HP HIGH AMBIENT PACKAGE


DRIVE PUMP.

Copyright 2011 Tesco Corporation


TEMPERATURE LIMITS
 2 STATOR THERMISTOR/MOTOR:
YELLOW WARNING 266 °F (130 C)
RED SHUTDOWN 284 °F (140C) (TOP DRIVE)
 CCB SENSOR:
YELLOW WARNING 122 °F (50C)
RED SHUTDOWN 131 °F (55 C) (HEAT PUMP)
 PRE REGULATOR SENSOR:
YELLOW WARNING 122 °F (50C)
RED SHUTDOWN 131 °F (55 C) (CHILLER)
 INVERTER SENSOR:
YELLOW WARNING 122 °F (50C)
RED SHUTDOWN 131 °F (55 C) (CHILLER)

Copyright 2011 Tesco Corporation


COOLING SYSTEM ECI 900

Copyright 2011 Tesco Corporation


TOP DRIVE COOLING
SYSTEM

3SV

1SV

1SV

Copyright 2011 Tesco Corporation


TOP DRIVE COOLING
SYSTEM

Copyright 2011 Tesco Corporation


COOLING SYSTEM
ECI 900 HIGH AMBIENT

4SV

2SV

2SV

Copyright 2011 Tesco Corporation


COOLING SYSTEM ECI 1350

4SV

2SV

2SV

Copyright 2011 Tesco Corporation


COOLING SYSTEM
ECI 1350 HIGH AMBIENT

4SV

2SV

2SV

Copyright 2011 Tesco Corporation


CHILLER TOP DRIVE
COOLANT TANK COOLANT TANK
145 GAL/548L 145 GAL/548L

COOLANT (UCARTHERM)
50/50 GLYCOL MIX
Copyright 2011 Tesco Corporation
TOP DRIVE COOLANT PUMP CHILLER BYPASS PUMP
AND MOTOR AND MOTOR

PUMP OUTLETS

PUMP INLETS Copyright 2011 Tesco Corporation


DRIVE PUMP AND MOTOR

Copyright 2011 Tesco Corporation


CHILLER CIRCULATION PUMP INLET FROM RESERVOIR

CHILLER CIRCULATION PUMP


Copyright 2011 Tesco Corporation
COOLANT PUMPS

Copyright 2011 Tesco Corporation


SERVICE LOOP (HOSE REEL)

Copyright 2011 Tesco Corporation


TOP DRIVE HYDRAULIC QUICK COUPLERS

INLET

INLET

TOP DRIVE COOLANT QUICK COUPLERS


Copyright 2011 Tesco Corporation
MALE COUPLER

FEMALE COUPLER

TOP DRIVE COOLANT PLUMBING


Copyright 2011 Tesco Corporation
COOLANT PASSAGES IN PA44 MOTOR
Copyright 2011 Tesco Corporation
ECI 1350

COOLING LINES OUT FROM MOTOR STATORS

CAUTION** FITTINGS OUT OF MOTOR MAY HIT QUILL IF NOT THE


CORRECT ONES
Copyright 2011 Tesco Corporation
COOLING LINES INTO MOTOR STATORS

MINIMUM FLOW
3.5GPM(13.2L) /STATOR.
7GPM(26.5L) /MOTOR
Copyright 2011 Tesco Corporation
THIRD MOTOR INTLET COOLING LINES ECI 1350

THIRD MOTOR OUTLET COOLING LINES

Copyright 2011 Tesco Corporation


ECI 1350

MOTOR INLET COOLING LINES

Copyright 2011 Tesco Corporation


HEAT EXCHANGER INLET FROM KAMAN MOTORS

GEARBOX OIL AND TOP DRIVE COOLANT HEAT EXCHANGER

HEAT EXCHANGER OUTLET BACK TO MECHANICAL MODULE


Copyright 2011 Tesco Corporation
TO PA44 MOTORS FROM MECHANICAL MODULE

FROM PA44 MOTORS BACK


TO TANK

OUTLET TO MECHANICAL MODULE


Copyright 2011 Tesco Corporation
FLOW SWITCH

OUTLET TO POWER MODULE

OUTLET TO TOP DRIVE

RETURN FROM TOP DRIVE


RETURN FROM POWER MODULE
Copyright 2011 Tesco Corporation
COOLANT FILTERS
(10 MICRON)

Copyright 2011 Tesco Corporation


DRIVE COOLING SYSTEM

The cooling system is designed to cool down the DRS drive(s) electronic
components and circuit boards by circulating a glycol-based antifreeze
coolant through the Drive cold plates.

Its main components are located in Mechanical and Power module:

• Heat Pump and

• Standard 10 Ton or High Ambient 25 Ton Chiller

Copyright 2011 Tesco Corporation


DRIVE COOLING SYSTEM

CHILLER

HEAT PUMP

Copyright 2011 Tesco Corporation


DRIVE COOLING SYSTEM

Copyright 2011 Tesco Corporation


POWER MODULE COOLING LINES TO COLD PLATES

MINIMUM FLOW
5 GPM(19L) /COLD PLATE.
15 GPM(57L) /MD500
Copyright 2011 Tesco Corporation
FROM HEAT
PUMP

TO HEAT
PUMP

Copyright 2011 Tesco Corporation


Copyright 2011 Tesco Corporation
CHILLER AND HEAT PUMP

It is critical for the electronic components to maintain certain ambient


temperature and humidity levels within the building and inside the drive
cabinets to prevent condensation.

The power module has a dedicated, self-contained cooling system,


called Heat Pump, which is basically an AC unit that controls both
temperature and humidity according to preset levels.

The Heat Pump is installed inside the Power Module.

Copyright 2011 Tesco Corporation


HEAT PUMP

Copyright 2011 Tesco Corporation


HEAT PUMP REFRIGERANT CAPACITY
(3.5lbs-5lbs)
FILL CONNECTIONS (HEAT PUMP)

HEAT PUMP LOCATION

Copyright 2011 Tesco Corporation


WHEN MAKING REPAIRS TO CHILLER CIRCUIT
BASIC REFRIGERATION USE DRY N2 TO
CYCLE
PREVENT COPPER OXIDE FROM FORMING IN PIPING (BLACK)
HEATING REFRIGERANT

COOLING REFRIGERANT

HIGH PRESSURE VAPOR, HIGH PRESSURE LIQUID, LOW PRESSURE LIQUID/ VAPOUR, LOW PRESSURE VAPOUR.
Copyright 2011 Tesco Corporation
CHILLER CIRCUIT

LOW PRESSURE LIQUID/


VAPOUR, TURNS TO A
LOW PRESSURE VAPOUR
WHEN HEATED IN THE
EVAPORATOR WITH THE
POWER MODULE COOLANT
(LIQUID HEATED)

HIGH PRESSURE
VAPOR, TURNS TO A
HIGH PRESSURE
LIQUID WHEN COOLED
BY THE CONDENSOR
(AIR COOLED)

CPR

CPR

HIGH PRESSURE VAPOR, HOT GAS BYPASS HIGH PRESSURE LIQUID, LOW PRESSURE LIQUID/ VAPOUR, LOW PRESSURE VAPOUR,
Copyright 2011 Tesco Corporation
DISCHARGE LINE
(GAS) (HIGH PRESSURE)

(HIGH PRESSURE CUT OUT SWITCH)

Copyright 2011 Tesco Corporation


CONDENSER

CONDENSER REFRIGERANT IN
(GAS) (HIGH PRESSURE)

CONDENSER REFRIGERANT OUT


(LIQUID) (HIGH PRESSURE)
Copyright 2011 Tesco Corporation
HOT GAS BYPASS VALVE

LINE TO EVAPORATOR

EQUALIZER LINE

HOT GAS BYPASS SOLENOID

PROVIDES A MEANS TO BYPASS HIGH PRESSURE REFRIDGERANT TO THE SYSTEMS LOW


PRESSURE SIDE IN ORDER TO MAINTAIN A GIVEN MINIMUM SUCTION PRESSURE, AND TO
BALANCE THE SYSTEM CAPACITY TO THE LOAD DEMAND Copyright 2011 Tesco Corporation
LINE TO EVAPORATOR FROM HOT GAS BYPASS VALVE
Copyright 2011 Tesco Corporation
COMPRESSOR HEATER

CHILLER REFRIDGERANT LEVEL GAUGE


(HIGH PRESSURE LIQUID) (R22)

Copyright 2011 Tesco Corporation


TX VALVE

TX VALVE BULB
OUT (B) IN

REMOTE BULB

EQUALIZER LINE
(A)

THE THERMO EXPANSION VALVE REGULATES THE FLOW OF LIQUID REFRIGERANT


INTO THE EVAPORATOR IN EXACT PROPORTION TO THE RATE OF EVAPORATION OF
THE LIQUID REFRIGERANT. THE TX VALVE RESPONDS TO (A) THE TEMPERATURE OF
THE GAS REFRIGERANT LEAVING THE EVAPORATOR AND (B) THE PRESSURE AND THE
SPRING IN THE EVAPORATOR. THIS CONTROLLED FLOW PREVENTS LIQUID
REFRIGERANT FROM RETURNING TO THE COMPRESSOR. Copyright 2011 Tesco Corporation
P1

AS TEMPERATURE AT
BULB INCREASES THE
PRESSURE INCREASES
BULB
AT P1 AND OPENS
P2 EXPANSION VALVE.
WORKING AGAINST
OUTLET PRESSURE P2
AND SPRING P3

P3 P1 = P2 + P3
VALVE IS EQUALIZED

P1 GREATER THAN P2 + P3
VALVE WILL OPEN

P1 LESS THAN P2 + P3
VALVE WILL CLOSE
Copyright 2011 Tesco Corporation
OR REFRIGERANT IN
(LOW PRESSURE)

EVAPORATOR

REFRIGERANT OUT
OW PRESSURE)

Copyright 2011 Tesco Corporation


LOW PRESSURE CUT OUT LINE TO ADJUSTABLE SWITCHES
Copyright 2011 Tesco Corporation
DISCHARGE LINES
(GAS) (HIGH PRESSURE)

SUCTION LINES
(GAS) (LOW PRESSURE)

Copyright 2011 Tesco Corporation


CHILLER COMPRESSORS AND EVAPORATORS LOCATION

COOLER

WARMER

CHILLER REFRIGERANT CAPACITY ECI 1350 OR HIGH


AMBIENT PACKAGE (30lbs) Copyright 2011 Tesco Corporation
CHILLER EVAPORATOR LOCATION

EVAPORATOR REFRIGERANT OUT


(GAS)
EVAPORATOR REFRIGERANT IN
(LIQUID)
Copyright 2011 Tesco Corporation
TX VALVES

Copyright 2011 Tesco Corporation


ECI 900 CHILLER COMPRESSORS LOCATION

CPR VALVES PROTECT COMPRESSORS FROM OVERLOAD

WARMER

COOLER

LIQUID LINE DRIERS MAX. 1-2 DEG.BETWEEN INLET AND OUTLET


Copyright 2011 Tesco Corporation
ECI 900 HIGH AMBIENT, ECI 1350

OVERHEAD CHILLER CONDENSER COILS

LIQUID LINE DRIER MAX. 1-2 DEG.BETWEEN INLET AND OUTLET

Copyright 2011 Tesco Corporation


900 CHILLER

SUCTION PRESSURE SHOULD BE 60-80 PSI

DISCHARGE PRESSURE SHOULD BE 250-300 PSI (NORMAL)

Copyright 2011 Tesco Corporation


In Summary…
• The Top Drive system has three separate sources for
cooling.
1. Top Drive cooling fan
2. Drive Module Chiller
3. Power Module Heat Pump

• Through correct maintenance, operation, and


inspection of these components we can ensure no
damage is done to the equipment due to
condensation or overheating.
• By ensuring the chiller coolant is maintained at least 4
to 5 degrees above the ambient temperature of the
power module and the PA44 motors do not achieve
130 degrees C, we can expect full utilization of all the
components for extended durations.
Copyright 2011 Tesco Corporation