Вы находитесь на странице: 1из 1

PSV Calculation Report - Liquid Relief Sizing Case

PSV General Data

Item 100 PSV 001 Design Code ASME VIII

Service Design Temperature 80.00 °C

Fluid 1 @Main Phase Liquid Fire Case False

Body Mat'l Carbon Steel Sizing Method Liquid Emergency Thermal Expansion

PSV Type Balanced-Bellow Rupt. Disk False Discharge To Process

Fluid Properties @ Relieving PRD Coefficients

Kv 0.989 Kw 1.000
8 0
Spec Gravity 0.9964 Viscosity 0.6514 cP
Kd 0.650 Kc 1.000
0 0

Process Data @ Relieving

Superimposed Const. 1.01 barA


Back Press.
Relieving Flow 518.31 kg/h Var. 0.00 barA

Relieving Temp 40.00 °C Builtup Back Press 0.50 barG

Set Pressure 12.00 barG Total Back Press 0.50 barG

Over Pressure 10.0 % Max. Allowable Back Press: 6.00 barG

PRDSizing Results

Calculated Orifice 0.04 cm² Selected Orifice 0.71 cm² % Used 6.3 %

Selected Capacity 8229.04 kg/h Orifice Designation 1 "# 150 D 2 "# 150

Inlet / Outlet Lines Sizing Results

Eq. Calc. Calc. Max Avg


N.D. I.D. Rough.
Sch. Length Flow DP DP vel.
(in) (in)
mm m kg/h bar bar m/s

INLET 0.05 0.02 518.31

OUTLET 0.05 423.00 518.31

Calculation Notes

Record 1 of 1 6/13/2018 10:23:34 PM

Вам также может понравиться