STRUCTURAL DESIGN OF ROOF FOR GATEHOUSE NO.

03

ASSUMPTION S & DATA:

1. Design Codes

a) BS : 5950 : Part 1 : 2000 - structural use of steel

2. Material

a) py = 275 MPa - steel design strength ( S 275 )

3. Loadings:

Load 1:DL1 (Self weight)

Load on Roof

DL 2 (weight of 20mm Plywood)

ɣ =540 Kg/m³

w2 = (1.051m) (0.020 m) (540 Kg / m3) (9.8)

w = 0.111 KN /m

DL 3 (weight of 100mm Rigid Insulation)

W3 = (0.306) (1.051) = 0.322 KN/m

DL 4 (weight of 3mm steel sheeting)


ɣ =79 KN/m³
W4 = (079KN/m³)(1.051)(0.003)= 0.250 KN/m

DL 5 (weight of 4mm steel sheeting)


ɣ =79 KN/m³
W = (079KN/m³)(1.051)(0.004)= 0.332 KN/m

W=w2+w3+w4+w5 = 1.015 KN/m

Concentrated Load on Main Beam P1= (3.60)(1.015)/2 = 1.830 KN

Ceiling Load

Panel 1
DL 6 (weight of 19mm Ceiling cover)
ɣ =540 Kg/m³
W(SH)= (540Kg/m³)(9.8)(0.019)= 0.1KN/m²

DL 7 (weight of 5mm Galvanized Metal Barrier)


ɣ =79 KN/m³
W = (79KN/m³)(0.005)= 0.395 KN/m²
DL 8(weight of 19mm Plywood)
ɣ =540 Kg/m³
W = (540Kg/m³)(9.8)(0.019)= 0.1 KN/m²

W= w6 + w7 +w8
W = 0.592 KN/M²

LOAD ON BEAM = (0.592 KN/M²)(1.711 m)/3 = 0.34 KN/m²

Load 2 : Roof Live Load ( w= 0.6 KN/m²)

W09 = (1.051 m)( 0.60 KN/m²)


W09= 0.630 KN/m

Load 3: Wind Load Calculation

NET WIND PRESSURE = - 2.50 Kpa

Load Combination

1. 1.0 DL1 + 1.0 LL + 1.0 wL


2. 1.2 DL1 + 1.6 wL + 1.0LL
DESIGN OF STEEL ROOF FOR GATEHOUSE NO.03

Check for Strength

*Use RHS for the Side Beams (refer to STAAD output)


400 x 200 x 10 mm GR. S275

*Use SHS for Main Beams (refer to STAAD output)


150x 150 x 8.8 mm

*Use C-Channel for Bracing (refer to STAAD output)


152 x 76 x 18 Kg /m

* Use CHS Ø323.9 x 12.75 mm for the column (refer to STAAD output)

*Use 142 Z 15 for Purline

Check for Deflection

δmax = 8.989 mm - max deflection due to load

δallow = 7892 δallow = 21.92 mm OR 20mm WHICH IS LESSER- allowable deflection

360

δallow > δmax Therefore SAFE.


STRUCTURAL DESIGN OF ROOF FRAME FOR GATEHOUSE NO.03
2ND MODLE