COVER SHEET

REV.NO. DATE Drawing Name PREPARED CHECKED APPROVED

1 2016.08.26 Electrical Detail Design Instruction

19/9/2016

APPRD. Electrical Detail Design Instruction DWG. NO.


CONTRACTOR

RVWD. HR-F172S-D0101-01
INDONESIA MUARA JAWA CFSPP
CHKD. DATE REV.
2X27.5MW PROJECT
DSCD. 2016.08.26 1
CONTENTS
1.General Description .................................................................................................... 1
1.1 Project Introduction ...................................................................................... 1
1.2 General climate condition ............................................................................ 1
1.3 Scope of electrical systems........................................................................... 1
1.4 Design basis .................................................................................................. 1
1.5 Codes and standards ..................................................................................... 2
2.Electrical Single Line Diagram ................................................................................... 3
2.1 General ......................................................................................................... 3
2.2 Generator & transformer system .................................................................. 4
2.3 System voltage level will be selected to the following nominal values: ...... 5
3.Ratings and Parameters of Main Equipment .............................................................. 5
4.Calculation of Short Circuit Current ........................................................................... 9
4.1 Basis Data ..................................................................................................... 9
4.2 Conclusion of Calculation ............................................................................ 9
5.Auxiliary Power Supply ............................................................................................ 10
5.1 General ....................................................................................................... 10
5.2 6.3kV Auxiliary Power Supply system ...................................................... 10
5.3 380/220V Auxiliary System ....................................................................... 10
6.Neutral Earthing Arrangement .................................................................................. 11
7.Philosophy of Electrical Equipment Layout ............................................................. 11
7.1 Layout of Oil Immersed Transformer ........................................................ 11
7.2 Layout of Auxiliary Switchgears ................................................................ 12
8.Black Start Diesel Generator and Emergency Power Supply ................................... 12
9.Lighting System ........................................................................................................ 13
9.1 General ....................................................................................................... 13
9.2 Technical Requirements ............................................................................. 14
9.3 Small power ................................................................................................ 14
9.4 Maintenance power supply system............................................................. 14
10.Earthing and Lightning Protection System ............................................................. 14
10.1 Earthing ...................................................................................................... 14
10.2 Lightning Protection ................................................................................... 15
11.Cable and Cabling System ...................................................................................... 15
11.1 General ....................................................................................................... 15
11.2 Selection of Cable Type .............................................................................. 15
11.3 Cable Tray and Conduit .............................................................................. 16
12.Cathodic Protection System .................................................................................... 16
1. General Description
1.1 Project Introduction
Indonesia Muara Jawa 2x27.5MW CFSPP project is the first phase of the power
plant and consists of 3 boilers and 2 steam turbine generators. The plant is located at
Teluk Dalam Village, Muara Jawa, East Kalimantan, Indonesia.
The power plant will be high pressure, high temperature, once through cooling
type, using the local coal as the main fuel and have the capacity of black startup.
Two of the three boilers will be supplied for operating in the normal condition
and the other one standby.
1.2 General climate condition
(1) Annual Air Temperature
Average : 27.450C
Minimum : 22.400C
Maximum : 33.500C
(2) Annual Relative Humidity
Average : 80.25%
Minimum : 69.0%
Maximum : 85.0%
(3) Wind Speed
At +0. m above mean river level
Average : 2.83 knot
Maximum : 20 knot
(4) Seismicity
Indonesian Seismic Code: Zone 2
Approximate Equivalent UBC Seismic Code : Zone 2B (0.15g Horizontal
Acceleration).
1.3 Scope of electrical systems
Description on electrical system is divided into the followings: generator and
transformer system, auxiliary power system, black start diesel generator and
emergency power supply system, 150kV substation system, cable and cable laying,
earthing/grounding system, lightning system, lighting system and others.
1.4 Design basis
1) The EPC contract between the Owner and SECPCO 3.
2) The engineering contract between SEPCO 3 and Hongrui.

1
3) The Minutes of the design kickoff meeting between SEPCO 3 and Hongrui
4) The river water analysis report.
5) The Indonesian laws and regulations.
6) The related codes and standards.
1.5 Codes and standards
Technical Codes ,Rules and Standards issued as follows:
IEC 60034 Rotating electrical machines
IEC 60044 Instrument transformers
IEC 60050 International electrotechnical vocabulary
IEC 60072 Dimensions and output series for rotating electrical machines
IEC 60076 Power transformers
IEC 60085 Thermal evaluation and classification of electrical installation
IEC 60099 Surge arresters
IEC 60137 Insulating bushings for alternating voltages above 1000V
IEC 60146 Semiconductor converters
IEC 60214 On-load tap-changers
IEC 60255 Coal handling control system
IEC 60265 High-voltage switches
IEC 60269 Low-voltage fuses
IEC 60282 High-voltage fuses
IEC 60296 Fluids for electrotechnical applications – Unused mineral insulating oils
for transformers and switchgears
IEC 60439 Low voltage switchgear and controlgear assemblies
IEC 60478 Stabilized power supplies, DC output
IEC 60470 High-voltage alternating current contactors and contactor-based
motor-starters
IEC 60686 Stabilized power supplies, AC output
IEC60687
Alternating current static watt-hour meters for active energy(classes 0.2 S and 0.5 S)
IEC 60694 Common specifications for high voltage switchgear and controlgear
standards

2
IEC 60715 Dimensions of low voltage switchgear and controlgear
IEC 60870 Telecontrol equipment and system
IEC 60896 Stationary lead-acid batteries
IEC 60947 Low-voltage switchgear and controlgear
IEC 61641 Enclosed low-voltage switchgear and controlgear assemblies
IEC 61850 Communication networks and system in substation
IEC 61869 Instrument transformers
IEC 62040 Unin
terruptible power systems
IEC 62271 High voltage switchgear and controlgear
IEC 62305 Protection against lightning
IEEE 80 Guide for Safety in AC Substation Grounding
IEEE 665 Guide for Generating Station Grounding
2. Electrical Single Line Diagram
2.1 General
Rated voltage levels and grounding mode:

ITEM VOLTAGE LEVEL AND GROUNDING MODE


VARIATION

150kV system 150kV±10% Solidly grounded

Generator 10.5kV±5% Through an earthing


transformer with resistor
on secondary windings

MV auxiliary power 6.3kV±5% Grounded through low


system Resistor

LV auxiliary power system 0.38/0.22kV±5% Solidly grounded

2×33MW coal fired turbine generator units will be installed in this phase, the project
including two generators, three boilers, one of the three boilers will be standby for the
others. The two units will be evacuated to 150kV power system.
Generator transformer of each unit will deliver power to the plant 150 kV switchyard,
by means of overhead conductors at the incoming 150kV gantry of respective
3
generator bay.
Three phase two-winding transformer of 41.25MVA rating with OLTC will be used
to step up the generated voltage to 150 kV.
One unit auxiliary transformer (UAT) will be adopted for each unit , the unit auxiliary
transformer will be off-circuit tap changing (OCTC) two winding type.
One generator circuit breaker (GCB) will be applied for each unit and will be located
between generator and generator transformer. Start-up/standby transformer will not be
used in this project, start-up/standby power will be delivered from 150kV power grid
system through generator transformer with GCB in open condition. Unit auxiliary
transformers will be directly fed from generator busduct. The secondary voltage of the
UATs will be 6.6kV.
Overhead ACSR conductors of suitable rating will be used to connect the generator
transformers with the 150kV switchyard. All the equipments in the 150kV switchyard
will be selected as per 40kA short-circuit current level as given in the contract.
The proposed 150kV switchyard will be in front of the transformer yard. It will have
five bays with double bus scheme. Two outgoing line bays, two transformer incoming
bays and one bus coupler bay will consist 150kV switchyard.
The Switchyard Control building will be located within the switchyard boundary and
will have control&relay room, HV test room, battery room, DC distribution board
room, low voltage switchgear room, etc.
2.2 Generator & transformer system
The generators proposed for the plant are of three phase, horizontal mounted,
two-pole cylindrical rotor type, with the rated power of 33MW, power factor of 0.8
lagging to 0.95 leading, terminal voltage of 10.5kV and speed of 3000rpm. The
turbine generator will have the typical air cooling system.
Generator excitation system is static excitation system, including excitation
transformer, static Rectifier, redundancy AVR with power system stabilizer function.
Each turbo generator unit would be connected to generator transformer by segregated
phase busduct for feeding power into the 150kV HV grid.
The generator transformer will be three-phase, mineral oil filled, ONAN/ONAF
cooled, on-load tap changer, 41.25MVA, 157.5±8x1.25/10.5kV voltage ratio and YN
d11 vector group.
The unit auxiliary transformer will be tapped off from the generator busduct between
generator and generator transformer to supply the 6.3 kV unit switchgear boards. The
unit auxiliary transformer will be three phase, ONAN/ONAF cooling with OCTC,
15MVA, voltage ratio is 10.5 ±2 x2.5%/6.6kV and vector group is D-yn1.Each unit
auxiliary transformer will be sized capacity to supply 100% plant auxiliary load and
will act as standby to each other in case of any fault on either of the unit auxiliary

4
transformer. MV cables will be used for connecting unit auxiliary transformers with
6.3kV switchgears.
2.3 System voltage level will be selected to the following nominal values:
Power grid :150 kV
Generation voltage :10.5kV
Voltage for AC auxiliaries :6.3kV, 380/220V
3. Ratings and Parameters of Main Equipment
Ratings and Main Parameters of Generator:

WX16Z-044LL
1 Model No.
T

2 Rated Output MW 33

3 Rated Power Factor 0.8(lagging)

4 Rated terminal voltage kV 10.5

5 Rated Frequency Hz 50

6 Rated Speed r/min 3000

Excitation Voltage at rated


7 V 184.5
output.

Excitation Current at rated


8 A 924.3
output

9 Connection Type Y

10 Cooling type Air

11 Excitation type Static Excitation

Direct axis synchronous


12 reactance % 211.1
(unsaturated)

5
X′du
13 Direct axis transient % 24.5
reactance (unsaturated)

X″d
14 Direct axis sub-transient % 15.0
reactance (saturated)

X″du
15 Direct axis sub-transient % 19.1
reactance (unsaturated)

Parameters of Generator Transformer:

Three phase
1 Type
oil-immersed

2 Rated capacity MVA 41.25

157.5±8x1.25%/10.5k
3 Ratio
V

4 Tap OLTC

5 Vector Group Yn,d11

6 Impedance Voltage Hz 14%

Parameters of Unit Transformer:

Three phase
1 Type
oil-immersed

2 Rated capacity MVA 15

3 Ratio 10.5±2x2.5%/6.6kV

4 Tap OCTC

6
5 Vector Group Dyn1

6 Impedance Voltage Hz 10.5%

Parameters of 150kV Circuit Breaker:

1 Rated Voltage kV 150

2 Rated Current A 1250

3 Type SF6

Rated short circuit breaking


4 kA 40
current

Rated short circuit making


5 kA 100
current

Rated short-duration
6 power-frequency withstand kV 325
voltage(Common)

Rated short-duration
power-frequency withstand
7 kV 375
voltage(Access the isolating
distance)

Rated lightning impulse


8 kV 750
withstand voltage(Common)

Rated lightning impulse


9 withstand voltage(Access the kV 860
isolating distance)

Parameters of 150kV Disconnecting Switch:

1 Rated Voltage kV 150

2 Rated Current A 1250

Rated short circuit breaking


3 kA 40
current

7
Rated short circuit making
4 kA 100
current

Rated short-duration
5 power-frequency withstand kV 325
voltage(Common)

Rated short-duration
power-frequency withstand
6 kV 375
voltage(Access the isolating
distance)

Rated lightning impulse


7 kV 750
withstand voltage(Common)

Rated lightning impulse


8 withstand voltage(Access the kV 860
isolating distance)

Parameters of 150kV Current Transformer:

1 Rated Voltage kV 150

300-600/5A
2 Ratio
500-1000/5A

Outdoors headstand
3 Type
type

Rated short time thermal


4 kA 40
current

5 Rated dynamic current kA 100

Parameters of 150kV Potential Transformer:

1 Rated Voltage kV 150

(150/√3)/(0.1/√3)/(0.1/
2 Ratio √3)/(0.1/√3)/(0.1)kV
(150/√3)/(0.1/√3)kV

8
Outdoors fold mounted
3 Type type capacitor voltage
transformer

Rated short time thermal


4 kA 40
current

5 Rated dynamic current kA 100

Parameters of 150kV Lightning Arrester:

1 Rated Voltage kV 150

3 Type ZnO

Lightning impulse residual


4 kA 416
voltage

10kA of 8/20 micro sec


5 Nominal Discharge Current kA
wave

4. Calculation of Short Circuit Current


4.1 Basis Data
The short circuit current of 150kV switchgear will be 40kA. Impedance voltage Of
GT and UAT will be 14% and 10.5% respectively.
4.2 Conclusion of Calculation

System 3 ph. Short circuit (kA)

1 150kV 40

2 10.5kV(Generator side) 16.46

3 10.5kV(Grid side) 21.36

4 6.3kV 19.4

5 380V 43.7(maximum)

More detail short circuit calculation information please refer to


“HR-F172S-D0101-04 SHORT-CIRCUIT CALCULATION”
9
5. Auxiliary Power Supply
5.1 General
This project will adopt 6.3kV and 0.38/0.22kV auxiliary power supply system.
The 6.3kV system neutral point will be earthed via resistor. LV dry type transformer
and motors rated equal or above 160kW will be connected to 6.3kV. There will be
6.3kV unit switchgear for each unit to supply unit load and one 6.3kV station board
for power supply station and standby boiler load. LV power system will be
non-separated power system and lighting system: 380 /220V, 50 Hz 3-phase solidly
earthed low voltage network. Loads up to 160 kW will be connected to LV system.
5.2 6.3kV Auxiliary Power Supply system
Unit auxiliary load like FWP, CW Pump, ID Fan, SA Fan, etc will be fed from 6.3kV
unit switchboards. Station load will be fed from 6.3kV station switchboard.
Motor above 1000 kW will be fed from 6.3kV vacuum circuit breaker (VCB)
switchboard and other MV motors will be fed from fuse-vacuum contactor (FC)
switchboard. All MV motors will have space heater for avoiding condensation during
idle hours.LV transformer above 1250 kVA will be fed from 6.3kV vacuum circuit
breaker switchboard and other LV transformers will be fed from fuse-vacuum
contactor switchboard.
VCBs will be used for all transformer incomer & bus coupler feeders, based upon the
calculations, the fault level of 6.3kV auxiliary bus will be 25kA.
5.3 380/220V Auxiliary System
There will be five LV transformers for power supply in the whole plant and one
standby LV transformers to supply standby power source for the LV transformers.
380/220V auxiliary system will have PC-MCC connection type.
PC will have single busbar with subsection connection. Standby power will be fed
from LV standby transformers.
Normally MCC will have one section with two separately incomers.
The LV auxiliary transformers will be of three phase, epoxy cast resin/resin
encapsulated AN cooling dry type; the neutrals of 380V side are solidly earthed. PCs
will be single front fully drawout type, MCCs will be single front fully drawout type
and DBs will be single front fixed type.
Circuit breaker with rated current more than 630A will be provided with air circuit
breaker and other circuits will be provided with moulded case circuit breakers. Air
circuit breaker will be three pole, spring charged, horizontal drawout type, suitable for
manual and electrical operation.
L.V switchgears, PCs, MCCs, DBs, will be indoor, metal clad, suitable for clean but
hot, humid and tropical atmosphere. Degree of protection will be higher than IP 31.
10
Degree of protection of outdoor equipment will be IP 55 class. The form of
switchgear will be Form 4a at least which is according to IEC.
Sheet steel used for construction of the switchboards will be minimum 2 mm thick for
structural load bearing members, doors, covers and partitions.
All control, interlock facilities including remote CB status indication and remote
operation from center control room will be provided for essential PC and MCC
circuits.
For crane / hoist circuit, a local disconnector will be furnished.
Important LV motors with capacity greater than 30kW will have soft starters.
V.T.s will be protected by fuses and will be draw out type.
6. Neutral Earthing Arrangement
Electrical power system will include 150kV, 10.5kV, 6.3kV, 380V/220V.
The neutral of 150kV system will be solidly earthed, HV neutrals of GT will be
solidly earthed too.
The neutral of 10.5kV system will be non-effectively earthed, neutrals of generator is
connected through resistance via a single phase grounding transformer.
The neutral of 6.3kV system will be earthed through low resistance, LV neutrals of
UAT will be connected through resistance. The rated current of the Neutral
Grounding Resistor (NGR) is 200A.
The neutral of 380V system will be solidly earthed. Neutrals of all the LV
transformers will be solidly earthed. LV power system adopts TN-C system and
lighting system adopts TN-C-S, “C” means neutral and protective functions combined
in a single conductor (PEN conductor) and “S” means protective function provided by
a conductor separate from the neutral conductor or from the earthed line (or, in a.c.
systems, earthed phase) conductor.
7. Philosophy of Electrical Equipment Layout
7.1 Layout of Oil Immersed Transformer
All transformer yard layouts will be prepared rationally. While making transformer
yard layouts, including Generator Transformer (GT) and Unit auxiliary Transformer
(UAT), the following aspects will be considered:
a) Reliability of Generator outline circuit
b) Angle / length of the 150kV overhead lines will be minimal.
c) Fire protection requirements
d) Equipment overhaul /transportation requirements
e) Combined consideration with the transformers and other facilities, i.e. the C.W.
11
tubes etc.
f) Fire walls.
Based on the above, the Layout of GT will be lined up in parallel with the A-row of
Turbine Building. The UAT will be located between the GT and the Turbine-building.
Fire Wall will be set between the GT and UAT.
7.2 Layout of Auxiliary Switchgears
6.3kV unit switchgears will be located in steam turbine house at 0.0m.
380V unit switchgear and station switchgears will also be located in steam turbine
house at 0.0m.
380V emergency/normal switchgear will be located in steam turbine house at 0.0m.
DM plant LV PC switchgears will be located in electrical distribution room at DM
plant house.
Coal handling PC switchgears will be located in the CHP and electric distribution
room.
Ash and dust handling PC will be located in air compressors house.
Other auxiliary buildings will be provided with MCC as needed.
8. Black Start Diesel Generator and Emergency Power Supply
Black start diesel generator (BSDG) sets will be provided in this project , terminal
voltage of BSDG will be 6.6kV.6.3kV BSDG switchboard will be provided and
connected with 6.3kV station switchboard. Two NOs 1800kW BSDG will be
provided. One of them will also act as emergency diesel generator. The neutral point
of BSDG will be earthed through low resistance.
BSDG will be manual control model, controlled by local or remote at center control
room. After BSDG start-up, the operator close the BSDG circuit breaker and
bus-couple breaker by manual to supply the power to 6.3kV station bus and 6.3kV
unit bus waiting for start. BSDG will be provided with auto synchronization device
and should automatic synchronize with each other to parallel operating.
The low voltage emergency power supply will start within 20 sec after failure of the
normal supply through dedicated step-down transformer. One set breaker will be set
at the HV side of the emergency transformer used to disconnect the circuit for
maintenance, the breaker will be controlled locally and remote at center control room.
In normal operation (normal network available), LV emergency MCC will be
supplied by the normal power system. The neutral of emergency power system will be
solidly earthed.
The emergency power network will be designed with automatic control device. In
case of the normal power supply failure, automatic device start one set of BSDG.
After the BSDG start-up, the control device sent signals to trip working power
12
incomer and standby power incomer circuit breaker, close BSDG circuit breaker and
emergency power incomer breaker to restore emergency MCC bus power.
9. Lighting System
9.1 General
The lighting system will provide light in the power station as per the recommended
lux levels. The appropriate lux levels will be maintained throughout the plant during
various conditions.
A number of miniature circuit breaker outgoing feeders will be provided to supply
power to various lighting panel located in different floors of power house and other
buildings.
The following subsystem will be supplied:
(i)Normal AC lighting system
(ii)Emergency AC lighting system
(iii)Emergency DC lighting system
(iv)Emergency exit indication lighting system
Lux levels in specific areas will be based on following requirement:
1) Illuminance value requirement in central control room
a.A working surface illuminance of 350 Lux
b.A working area illuminance of 250 Lux.
c.An illuminance of 200 Lux for mess rooms.
d.An illuminance of 150 Lux for access areas.
2) Operation floor of turbine house illuminance of 200 Lux.
3) Generator terminal room illuminance of 100 Lux.
4) 0.0m floor of turbine house illuminance of 100 Lux.
5) Boiler equipment operation area and the burner area illuminance of 100 Lux.
6) Control rooms in auxiliary building illuminance of 200 Lux.
7) Road lighting requirement:
An average illuminance of 20 lux will be provided for roads, paths and external
compounds, including switchyard, unless otherwise directed by the owner.
8) Emergency lighting
An illuminance of 50 lux will be provided in the diesel generator rooms and any other
plant area where operational functions are required to be performed during an

13
emergency.
The supply will be from normal PCC/MCC for normal lighting and emergency
lighting in main power house will be from EMCC, emergency lights supplied by
battery will be installed at the entrance of central control room, battery room, other
entrances of important places and auxiliary workshop far away from main power
house.
9.2 Technical Requirements
(i) There will be fluorescent fixtures are adopted in the control rooms and other
important areas, The fixtures will have high luminescent efficiency and are
convenient for maintenance.
(ii)HID industrial grade flood lights will be used to illuminate switchyards,
transformer yard and similar areas. HID roadway luminaries will be used to illuminate
all plant roads and approaches. The operation of roadway luminaries will be
controlled by integral photocells or astronomic time clock. All other area lighting
level will be maintained as per contract document.
The voltage drop from the lighting panel to the farthest lighting fixture will be
considered using the following criteria:
(i)Normal lighting circuits: 5%
(ii)Other lighting circuits (outside lighting, roadway lighting, lighting voltage 24V
etc.): 10%
9.3 Small power
All Socket circuit will be provided with earth leakage circuit breaker(ELCB).
220 V switched, flush mounted, sockets will be provided in plant areas to supply
power for equipment used for maintenance and in offices and similar areas where
standard 220V equipment is normally used.
9.4 Maintenance power supply system
380/220V working electric power outlet boxes will be supplied in the powerhouse and
other workshops.
The outlet boxes wiIl be supplied in each floor and/or room of various plant buildings
and turbine building from 380/220 V MCCs.
10. Earthing and Lightning Protection System
10.1 Earthing
The station grounding system will be so designed that the actual step and touch
voltages are well within the maximum safe values for the site. The design will be
done in compliance with IEEE guide.
In the grounding system, outdoor grounding grid usesφ22GAL. round steel
14
conductor and 50X8 mm flat steel will be used as indoor grounding grid.
Sizes of underground conductor will be selected based on unrestricted ground fault
current and maximum duration of fault clearing time will be 1 sec. Connections to
individual equipment will be sized based on the fault clearing time. More information
please refer to HR-F172S-D0103-02 GROUNDING CALCULATION.
Main Plant Grounding grid and switchyard grounding grid will be inter-connected at
least two locations.
All exposed conductive parts of electrical equipment, valve actuators, cable glands &
armour etc. will be effectively earthed.
10.2 Lightning Protection
The lightning protection of the power station, chimney will be done as per IEC
guidelines and codes of practice for lightning protection. A separate earthing system
will be set for chimney.
Lightning rods will be installed on 150kV switchyard gantry. Lightning rods will also
be installed at fuel oil tank area.
Zno lightning arresters will be installed on 150kV switchyard outgoing feeders and
Zno lightning arresters will also be set on the HV side of GT.
11. Cable and Cabling System
11.1 General
Power cable conductor sizes will be determined based on the following conditions:
maximum conductor temperatures under sustained condition; three phase short
circuit/earth fault conditions; voltage regulation under steady state; motor starting
conditions and automatic disconnection time for protection.
When a fault is cleared by backup protection in a non-fuse protected circuit, the cable
insulation should remain intact, safe and well functional.
11.2 Selection of Cable Type
Following types of cables will be used for different services of the plant :
a) 6.3 kV System Power Cable
All 6.3kV cables must be of stranded copper/aluminum conductor, XLPE insulated,
PVC sheathed, flame-retardant type. The cables will be suitable for 6.3kV resistance
earthed system.
b) LV Power Cable
All LV power cables must be of 0.6/1kV grade aluminum conductor, XLPE insulated,
PVC sheathed, flame-retardant type. The cables will be suitable for directly earthed
system.

15
A.C & D.C circuit will not use the same cable. Separate cables will be used for power,
control & interlock, metering and measurements, C.T., V.T.
Flame-retardant cables will be used in the safely trip, shut down the plant, fire
detection , fire-fighting system, emergency communication, DC system, UPS system,
audible alarm and other important circuits and they should be tested to satisfy the
flame retardant property requirement at the highest test temperature condition in IEC
60331.
Armoured cable will be used for direct buried application and unarmoured cables used
for the following applications:
a) Power circuits installed in protective conduit or trench.
b) Short lengths of control and instrumentation cable.
c) Special signal cables for data communication etc.
All cables will be subjected to tests as per relevant standards of IEC.
11.3 Cable Tray and Conduit
Cable tray and conduits will be hot dip galvanized steel.
12. Cathodic Protection System
Cathodic protection will comply with the requirements of BS CP 1021(Code of
Protection for Cathodic Protection) and NEMA MR-20 (Semi Conducting Rectifiers
Cathodic protection Units). Impressed current method will be provided as cathodic
protection.
The cathodic protection system will be provided in conjunction with the appropriate
plant material selection, for the plant listed below:
- Intake screen and trash racks
- Pump casings
- Condenser Water Boxes
- All other corrodible portions of water system, pipework and valves.

16