DESIGN OF CRASH BARRIER

Vehicle impact force (Ls) = 25


Unit Weight of concrete = 25
Height of impact force above pavement surface (He) = 600

Figure 1. Section of a barrier-friction slab system for calculation of sliding


In order to obtain the weight of the barrier-friction slab system, the detail calculation is conducted below

Table 1. Calculation of Barrier-friction slab system weight

Longitudi
nal Vertical
distance, distance,
Item Section X Y Area Weight (W)
(m) (m) (Sq.m) KN/m
1 0.175 0.5 0.0875 2.19
2 0.05 0.5 0.0125 0.31
3 0.05 0.85 0.0213 0.53

Concrete
Sensitivity: LNT Constructionand
(Barrier Internal Use
friction slab)
#
4 0.225 0.35 0.0788 1.97
Concrete 5 0.175 0.25 0.0219 0.55
(Barrier and 6 0.175 0.1 0.0175 0.44
friction slab) 7 0.45 0.635 0.2858 7.14
8 0.35 0.35 0.0613 1.53
9 0.1 0.195 0.0195 0.49
10 0.1 0.365 0.0365 0.91
11 2 0.25 0.5000 12.50
12 1.7 0.05 0.0850 1.87
13 1.7 0.15 0.1275 3.19
14 1.7 0.25 0.2125 5.31
Soil (Pavement 15 1.7 0.3 0.5100 9.18
layers) 16 0.35 0.35 0.0613 1.10
Total W= 47.01

SLIDING CHECK

tanΦr 0.674509
P = W tanΦr = 31.707 KN
Ls = 25 kN safe
P is static resistance
W is weight of the barrier-friction slab system and overburden soil on it
Φr is soil-friction slab interface friction angle = angle of internal friction of reinforced fill =

AREA OF STEEL

As per IRC 6-2010 cl 206.6.5 Table 3


As per IRC6-2010 item 5- table 3
As per IRC 6-2010 P1 (normal containment)
Grade of Concrete M 40
modular ration m = 10
σst= Stress in Steel = 240 N/mm2
σcb = Stress in Concrete = 13.33 N/mm2
K = 0.35709
j = 0.88097
Q = 2.09669
d = 225-16/2-40 = 167 mm effective depth within 300mm from paved su

As Per Item 4 table 3


Mr= 15 kNm/m
Ast required= 4.2481679657 cm^2
Provide dia 16 @ 200 mm C/C
Ast provided= 10.0530964915 cm^2

# Sensitivity: LNT Construction Internal Use


As per IRC6-2010 item 5- table 3
Mr = 7.5 kNm/m
Ast required= 2.1240839829 cm^2
Provide dia 12 @ 250 mm C/C
Ast provided= 4.5238934212 cm^2

# Sensitivity: LNT Construction Internal Use


KN/m (force as per IRC: 6 -2010 table 3 moment of resistance 15kNm/m with 600mm lever arm)
kN/cu.m
mm

ulation is conducted below

# Sensitivity: LNT Construction Internal Use


34

th within 300mm from paved surface

# Sensitivity: LNT Construction Internal Use