Вы находитесь на странице: 1из 4

DATASHEET

DAC60000 SERIES
24VDC-220VDC Inverters for industrial backup systems

Modular power conversion architecture 1-24kVA


1-phase and 3-phase secured AC supply
True redundant n+1 system, hot swap modules
Natural cooled and fan cooled modules

• Modular systems and stand-alone inverters • On-line/Off-line configuration


• 6kVA and 30kVA bypass units • Complete systems solutions • AC-distribution
• Double battery bank supply solutions for power transmission backup systems
• RS-232 access for local parameters • Relays and SNMP for remote monitoring

Sales & Support: CP Power & Automation Ltd | 3 Fairfield Court | Seven Stars Industrial Estate | Coventry | CV3 4LJ | UK
Tel: +44 (0) 2476 214799
E-mail: sales@cppowerautomation.com
Internet: www.cppowerautomation.com
Powernet reserves the right to change the specification without notice Created: TRä 06.11.2012/ Updated: 01.02.2016 HLi File: DAC60000_24-220V_UK_2012-11-06.doc
DATASHEET

PARALLEL CONNECTABLE INVERTER MODULES


Type Nominal DC input Nominal Nominal Cooling Dimensions Weight
DC input Range AC output Power Without handles
DAC62132VF 24VDC 20…32VDC 230VAC, 50Hz 1000VA/600W Convection 14TE x 6U x 372mm 4 kg
DAC62232VF 24VDC 20…32VDC 230VAC, 50Hz 1200VA/800W Forced, fan 14TE x 6U x 372mm 4 kg
DAC62134VF 48/60VDC 40…72VDC 230VAC, 50Hz 1000VA/700W Convection 14TE x 6U x 372mm 4 kg
DAC62234VF 48/60VDC 40…72VDC 230VAC, 50Hz 1200VA/1200W Forced, fan 14TE x 6U x 372mm 4 kg
DAC62135VF 110/125VDC 88…150VDC 230VAC, 50Hz 1000VA/700W Convection 14TE x 6U x 372mm 4 kg
DAC62235VF 110/125VDC 88…150VDC 230VAC, 50Hz 1200VA/1200W Forced, fan 14TE x 6U x 372mm 4 kg
DAC62136VF 220/230VDC 178…275VDC 230VAC, 50Hz 1000VA/700W Convection 14TE x 6U x 372mm 4 kg
DAC62236VF 220/230VDC 178…275VDC 230VAC, 50Hz 1200VA/1200W Forced, fan 14TE x 6U x 372mm 4 kg

19” 2U MECHANICAL ADAPTERS FOR HORIZONTAL INSTALLATION


MSR7990+ DAC type 1200VA fan cooled inverter in 19” 2U installation
ADU68230+ DAC type 1200VA fan cooled inverter and AC-distribution (4 x MCB) in 19” 2U installation

STATIC SWITCH + MANUAL BYPASS


Type Description
BPU69130VF External static switch, 6000VA 230VAC, 14TE x 6U x 372mm module
MSR7990+BPU69130VF External static switch, 6000VA 230VAC, 19” x 2U x 372mm
BPU69430FR + MBP68400 External static switch and manual bypass, 30kVA 230VAC, 19” x 3U x 480mm
MBP68000 / MBP68200 See separate datasheets for 6U and 2U manual bypass solutions

ACCESSORIES
Type Description
MSR7990 19” 2U adapter for 6U 14TE inverter and static switch modules
WMA7830 Wall mounting adapter for 6U 14TE inverter, 1-3 modules can be mounted to one compact package
68200014 19” Subrack 6U 300mm for 1-6pcs of 14TE 6U models (note inverter’s depth 372mm)
88680001 19” Subrack 7U 300mm for 1-6pcs of 14TE 6U models including parallel connection cables
8868000 Wall mountable 19” Subrack 7U 475mm for 1-6pcs of 14TE 6U models, shielded enclosure
8860000 Coverplate set for empty module place in 19” 6U subrack
8760038 Communication system bus cable for 1...6 modules
876003H Communication system bus cable for 1...12 modules
8760037 RS232 computer cable for inverters or 6kVA STS, D9 pins (includes Remote monitoring software in CD)
8781832 RS232 computer cable for 30kVA STS, D15 pins (includes Remote monitoring software in CD)
8781836 Communication adapter cable between inverter system bus D9 connector and 30kVA STS D15 connector
8760039 Power cable between 6kVA static switch and inverter

AC-DISTRIBUTION
See separate datasheets for AC-distribution solutions

The Inverter packing includes following:


6
1) Inverter
1
2) AC output connector (finger protected screw terminals)
3) DC input cable 3m 2.5mm2
4) User manual 2
5) Grounding cable 3m 2.5mm2 8

The Static Switch packing includes: 7 3


6) Static Switch
7) Mains Input cable 2m 4,5 mm2
8) AC output cable 2m 4,5 mm2
9) Grounding cable 2m 6mm2

To be ordered separately 10
10) RemoteMonitor software in CD and
Remote monitoring cable PC-Inverter(s) 5, 9 12 11
11) Communication system bus cable
12) Power cable static switch – inverters 1m 1,5 mm2

Powernet reserves the right to change the specification without notice Created: TRä 06.11.2012/ Updated: 01.02.2016 HLi File: DAC60000_24-220V_UK_2012-11-06.doc
DATASHEET

SPECIFICATION 24VDC 48/60VDC 110/125VDC 220/230VDC


INVERTERS 1000VA 1200VA 1000VA 1200VA 1000VA 1200VA 1000VA 1200VA

ELECTRICAL
Input voltage 20-32 VDC 40-72 VDC 88-150 VDC 178-275 VDC
User programmable (PC/RS-232) start-up and shut down voltage limits and delays
Input current, max continuous 37 A 50 A 22 A 35 A 10 A 16 A 5A 8A
Input current, max 5 sec peak 75 A 75 A 50 A 50 A 22 A 22 A 11 A 11 A
Inrush current < 30 A < 20 A < 10 A < 10 A
Output voltage Nominal 230 VAC sine wave, user programmable 200-240V, floating output
Output frequency Nominal 50 Hz, user programmable 40 - 70 Hz, crystal locked
Nominal output power 1000VA / 1200VA / 1000VA 1200VA / 1000VA 1200VA / 1000VA / 1200VA /
600W 800W / 700W 1200W / 700W 1200W 700W 1200W
Overload, 5 seconds 1200 W 1700 W 1700 W 1700 W
Overload, 60 seconds 110% for all models, max time can be limited shorter
Number of restart attempts and delays are user programmable
Output current, nominal 4.4 A 5.2 A 4.4 A 5.2 A 4.4 A 5.2 A 4.4 A 5.2 A
Max short circuit current, 1-4 sec 13 A 13 A 13 A 13 A 13 A 13 A 13 A 13 A
Efficiency 85 % 83 % 90 % 90 % 90 %
Load power factor range Full power rating from 0 inductive to 0 capacitive
Total harmonic distortion, resistive load <2%
Crest factor >3 > 2.7 >3 > 2.7 >3 > 2.7 >3 > 2.7
Static regulation, 0…100% load 3%
Transient recovery < 0.3 ms
Psofometric noise, input N/A < 2 mV N/A N/A
Isolation Input-Chassis 1500 VAC (2000 VCD)
Input-Output 3000 VAC (4000 VDC)
Output-Chassis 1500 VAC (2000 VDC)
Protection Output current limiting
Overload and short circuit proof
Internal input and output fuses
DC input fuse (external fuse needed) max C 63A max C 40A max C 25A max C 16A

STANDARDS
Safety EN 60950-1
EMC 48/60VDC inverters: EN 55022B, EN61000-6-3, EN61000-6-2, ETS 300 132-2, BTNR 2511
24VDC, 110/125VDC and 220VDC inverters: EN 55022A, EN61000-6-4, EN61000-6-2
Static Switch: As 48/60V inverters except immunity:
EN61000-4-3 radiated immunity according to EN61000-6-1, other immunity standards EN61000-6-2

ALARMS, INDICATIONS AND CONTROLS


LED-Indications Input ON
Output ON
Output loading, 4 levels: >5%, >30%, >50%, >80%
Overload / Fault
Relay alarms 2 relay contacts:
Fault in system summary alarm (module failure, DC input low etc)
Primary supply failure (system with bypass) or Output ON indication (system without bypass)
Relay contact ratings: 24-48VDC: 60VDC/1A, 110VDC: 125VDC/0.4A, 220VDC: 250VDC/0.2A
Remote monitoring through RS-232 Status information: For example input and output voltage, power, temperature, faults etc.
(Remote monitoring software) Parameter adjustment: For example input voltage limits, output voltage, over load, faults etc.

MECHANICAL
Dimensions See first page
Connectors in front panel Input DC connector: Anderson SB506331 G4
Output: Finger protected AC-connector, Wieland ST18/3S2
Enclosure Steel casing IP20

ENVIRONMENTAL
Operating temperature / Humidity 0…+45 oC full power 0…+45 oC full power -10…+45 oC full power -10…+45 oC full power
+45…+60 oC reduced power, derating -2%/C typically, no condensation
Cooling Natural Fan cooling Natural Fan cooling Natural Fan cooling Natural Fan cooling
(Fans are redundant and monitored) convection convection convection convection
Altitude Full power up to 2000m, derating -2% / 100m, max altitude 3000m

Powernet reserves the right to change the specification without notice Created: TRä 06.11.2012/ Updated: 01.02.2016 HLi File: DAC60000_24-220V_UK_2012-11-06.doc
DATASHEET

CONFIGURATIONS & SYSTEM ARCHITECTURES

Stand-alone Parallel connection Parallel with external static switch


On-line and Off-line applications

SPECIAL SYSTEMS

Dual Redundant 3-phase system


Double battery system Same inverter modules

EXPANDING SYSTEM
More power needed or unit replacement
No need to shut down system output
1) Connect cables: DC cable, AC cable, System bus
2) Turn new unit on
- Automatically enters system
- Automatically adapts system parameters (voltage, frequency etc.)
- Automatically turns output on if the system output is on

COMPLETE INVERTER SYSTEMS, AC- AND DC-DISTRIBUTION


MCB distribution panels, Schuko outlets
IEC320 outlets
Customized inverter system configurations

REMOTE MONITORING SOFTWARE AND SNMP


Continuous status information from all units:
- Output on/standby, voltage, current, power, loading per cent
- Input voltage and current, Internal temperatures, faults
Parameter adjustment (without turning system output off):
- Inverter start up and shut down input voltage limits, reaction delays
- Output voltage and frequency, number of restart attempts
- Bypass synchronising frequency range, accepted voltage ranges etc.
History file reading for last 30-40 events per module
Remote monitoring by SNMP

RELIABILITY
Real redundancy - No single failure may fail the system Recovery and monitoring procedures in hardware and software
No external controller - Stands disturbances in system bus
- No other master slave dependence but synchronising - Stands accidental system bus disconnecting for seconds
- If synchronising master fails, next unit starts sending the - Stands wrong connections of cables
synchronising data - If one unit fails other units alarm
Rugged system bus structure with galvanic isolation - Voting procedures for recognising and filtering wrong
Automatic bus address configuring operation
- No need for address setup by user Automatic fast shut down of failed unit
- No malfunctions because of wrong setup - Disconnecting from AC bus in 10 ms
Self tests and diagnostics - Automatic watch dog restart if processor hangs up
- Full automatic power stage test every time inverter is started - Unit automatically turns output off if synchronising lost for
- Continuous monitoring of internal operations too long time
- Error counters (RS-232) for troubleshooting
- Recognising of wrong connections (cable not connected, Internal history file in each inverter, last 30-40 system and unit
wrong AC bus polarity) specific events

Powernet reserves the right to change the specification without notice Created: TRä 06.11.2012/ Updated: 01.02.2016 HLi File: DAC60000_24-220V_UK_2012-11-06.doc

Вам также может понравиться