FP007h

SECTIONNEURS POUR POSTES D'EXTERIEUR


DISCONNECTORS FOR OUTDOOR SUBSTATIONS

SR16200 SR16201 SBE / SB18160 SP16700 / PE ST90 / ST36001 / STE


A coupure centrale A double coupure A coupure verticale Pantographe / Semi-pantographe Sectionneur de terre
Center break Double break Vertical break Pantograph / Semi-pantograph Earthing switch

Ur Ir Ik/tk 1s Ur Ir Ik/tk 1s Ur Ir Ik/tk Ur Ir Ik/tk 3s Ur Ik/tk 1s

24 kV 24 kV
36 kV
≤2000 A ≤ 40 kA 36 kV ≤8000 A ≤ 80 kA 36 kV ≤ 90 kA
38 kV
38 kV 38 kV

52 kV ≤2000 A ≤ 40 kA 52 kV ≤4000 A ≤ 63 kA 52 kV ≤2000 A ≤ 31.5 kA 52 kV ≤ 40 kA

72.5 kV ≤3150 A ≤ 40 kA 72.5 kV ≤4000 A ≤ 63 kA 72.5 kV ≤4000 A ≤ 50 kA 72,5 kV ≤3150 A ≤ 40 kA 72.5 kV ≤ 40 kA

100 kV ≤3150 A ≤ 40 kA 100 kV ≤4000 A ≤ 63 kA 100 kV ≤4000 A ≤ 50 kA 100 kV ≤3150 A ≤ 40 kA 100 kV ≤ 40 kA

123 kV ≤3150 A ≤ 50 kA 123 kV ≤4000 A ≤ 63 kA 123 kV ≤4000 A ≤ 63 kA 123 kV ≤4000 A ≤ 63 kA 123 kV ≤ 63 kA

145 kV ≤3150 A ≤ 50 kA 145 kV ≤4000 A ≤ 63 kA 145 kV ≤4000 A ≤ 63 kA 145 kV ≤4000 A ≤ 63 kA 145 kV ≤ 63 kA

170 kV ≤4000 A ≤ 50 kA 170 kV ≤4000 A ≤ 63 kA 170 kV ≤4000 A ≤ 63 kA 170 kV ≤4000 A ≤ 63 kA 170 kV ≤ 63 kA

245 kV ≤4000 A ≤ 50 kA 245 kV ≤4000 A ≤ 63 kA 245 kV ≤4000 A ≤ 63 kA 245 kV ≤4000 A ≤ 63 kA 245 kV ≤ 63 kA

300 kV ≤4000 A ≤ 63 kA 300 kV ≤4000 A ≤ 63 kA 300 kV ≤ 63 kA

362 kV ≤4000 A ≤ 63 kA 362 kV ≤4000 A ≤ 63 kA 362 kV ≤ 63 kA

420 kV ≤4000 A ≤ 63 kA 420 kV ≤4000 A ≤ 63 kA 420 kV ≤ 63 kA

550 kV ≤4000 A ≤ 63 kA 550 kV ≤4000 A ≤ 63 kA 550 kV ≤ 63 kA

Conforme aux spécifications de la norme CEI. As per IEC standards.


Isolateurs porcelaine, ligne de fuite: 25 mm / kV*. Porcelain isolators*, creepage distance : 25 mm per kV*.
Fonctionnement sous glace : 10 mm*. Operated under icing condition : 10 mm thickness*.
* Valeurs standards. Pour toute autre demande, merci de bien vouloir nous consulter. * Standard values. For further inquiries, please consult us.

Options : Options :

Sectionneur de terre combiné. Associated earthing switch.


Dispositif de coupure et d'établissement de courants de transfert de barres. Making and breaking device for tranfer currents.
Dispositif de coupure et d'établissement de courants induits pour sectionneur Making and breaking device for inductive currents for earthing switch.
de terre.

Organes de manoeuvre : Operating device:


Commandes motorisées Electrical operating mechanism (E.O.M.)
Commandes manuelles Manual operating mechanism (M.O.M)
FP007h

ORGANES DE MANOEUVRE POUR SECTIONNEURS DE POSTES D'EXTERIEUR


OPERATING DRIVES FOR OUTDOOR SUBSTATIONS DISCONNECTORS

électriques / electrical manuelles / manual

MR41R MR41E R77E T70

Manoeuvre monopolaire (non tringlée) ou multipolaire (tringlée) Manoeuvre monopolaire (non tringlée) ou multipolaire (tringlée)
One pole operation or ganged pole operation. One pole operation or ganged pole operation.
Manoeuvre électrique à distance / Electrical remote operation Manoeuvre manuelle locale / Manual local operation
Manoeuvre électrique locale / Electrical local operation
Manoeuvre manuelle secours locale / Surge local manual operation
Sélecteur de position verrouillable / Lockable changeover switch
Par rotation de l'arbre de transmission / Par rotation de l'arbre de Par déplacement vertical
Rotative movement of driving output shaft transmission / Rotative de l'arbre / Vertical translation
movement of driving output of driving output shaft
shaft
Temps de manoeuvre ≤ 10 sec. Temps de manoeuvre ≤ 8 sec.
(options 4 sec. ) / Operation time (options 4 sec. ) / Operation time
≤ 10 sec. (options 4 sec.) ≤ 8 sec. (options 4 sec.)
Nombre de manoeuvres garanties 1000, 2000, 10000 cycles selon
applications) / Number of guaranted operations 1000, 2000, 10000
cycles as per requested applications).
Moteur à démultiplication variable, à transmission de Levier à manoeuvre Levier à manoeuvre verticale /
mouvement irréversible / Motor with variable reduction ratio and horizontale / Vertical operator lever
irreversible transmission movement Horizontal operator lever
Tension d'alimentation disponibles : 48 Vcc à 220 Vcc et 110 Vca à 400 Levier longueur 1000 mm à A double poignée, rayon de
Vca / Available motor feeding voltages : 48 Vdc to 220 Vdc and 110 Vac simple poignée / Operator débattement du levier 500 mm
to 400 Vac lever length 1000 mm with one / Operator lever radius 500 mm
handle with two handles
Protection moteur par relais Protection du module par contrôle
thermique (option MCB) électronique (option MCB)
Motor protected by thermal relay Module protected by electronic
(MCB upon request) control (MCB upon request)
Nombre de contacts auxiliaires : Nombre de contacts auxiliaires : Nombre de contacts : 4O+4F (option 8O+8F) /
4O+4F (option 8O+8F et 12O+12F) 8O+8F (option 16O+16F) / Number of contacts: 4NO+4NC (8NO+8NC upon request)
Number of auxiliary contacts : Number of auxiliary contacts : 8NO+
4NO+4NC (8NO+8NC and 12NO 8NC (16NO+16NC upon request)
+12NC upon request)

Ensemble électromécanique monté en coffret en acier inoxydable. / Contacts auxiliaires montés en coffret en aluminium / Auxiliary
The all electro-mechanism system is housed in a stainless steel cabinet. contacts are housed in an aluminium cabinet.

Degré de protection IP43 (option Degré de protection IP44 (option Degré de protection IP43 (option IP54) / Degree of protection:
IP54) / Degree of protection: IP43 IP55) / Degree of protection: IP44 IP43 (IP54 upon request)
(IP54 upon request) (IP55 upon request)

Résistance de chauffage non Résistance de chauffage Résistance de chauffage non thermostatée / Heating resistor,
thermostatée / Heating resistor, thermostatée / Heating resistor with without thermostat
without thermostat thermostat