Вы находитесь на странице: 1из 2

Project: ETAP Page: 4

Location: 16.0.0C Date: 03-05-2018


Contract: SN: 4359168

Engineer: Study Case: CD Revision: Base

Filename: rftgg Study: Steady-State Temperature

Analysis Results (Ductbank section Study)


0.00
Conductor Energized Rdc @ Dielectric Conductor
per Conductor Final Temp. Losses Losses Current Temp.
No. Cable ID Conduit/Location ID Cable per Cable µOhm/m Watt/m Yc Ys Watt/m Amp °C

1 Loop 2-QC2 feeder 1-1 Cond1815 3 3 155.90 0.064 0.011 0.018 16.271 185.50 81.32

2 Loop 2-QC2 feeder 1-2 Cond1815 3 3 155.90 0.064 0.011 0.018 16.271 185.50 81.32

3 Loop 3-RE12-feeder 1 Cond12 3 3 153.35 0.064 0.011 0.018 19.174 203.00 76.27

4 Loop 4-RMG feeder 1 Cond15 3 3 150.66 0.064 0.012 0.018 9.351 143.00 70.92

5 Loop 5-ERT10-Feeder 1 Cond16 3 3 150.28 0.064 0.012 0.018 12.270 164.00 70.17

6 Loop 6-TR6 Feeder-1 Cond17 3 3 157.82 0.064 0.011 0.017 30.391 252.00 85.14

7 Loop 6-TR6 Feeder-2 Cond11 3 3 157.13 0.064 0.011 0.018 30.259 252.00 83.76

8 Loop1-QC1- feeder 1-1 Cond14 3 3 158.41 0.064 0.011 0.019 22.306 215.50 86.32

9 Loop1-QC1- feeder 1-2 Cond14 3 3 158.41 0.064 0.011 0.019 22.306 215.50 86.32

10 Loop7-AA2-Feeder 1 Cond13 3 3 145.53 0.064 0.013 0.019 0.453 32.00 60.75

Yc = Increment of AC/DC resistance ratio due to AC current skin and proximity effect
Ys = Increment of AC/DC resistance ratio due to losses of circulation and eddy current effect in shield, sheath and armor
Project: ETAP Page: 5

Location: 16.0.0C Date: 03-05-2018


Contract: SN: 4359168

Engineer: Study Case: CD Revision: Base

Filename: rftgg Study: Steady-State Temperature

Summary (Ductbank section Study)


0.00
Current Temp.
No. Cable ID Conduit/Location ID Size Amp °C

1 Loop 2-QC2 feeder 1-1 Cond1815 240 185.50 81.32

2 Loop 2-QC2 feeder 1-2 Cond1815 240 185.50 81.32 2.00


3 Loop 3-RE12-feeder 1 Cond12 240 203.00 76.27 3.00
4 Loop 4-RMG feeder 1 Cond15 240 143.00 70.92 4.00
5 Loop 5-ERT10-Feeder 1 Cond16 240 164.00 70.17 5.00
6 Loop 6-TR6 Feeder-1 Cond17 240 252.00 85.14 6.00
7 Loop 6-TR6 Feeder-2 Cond11 240 252.00 83.76 7.00
8 Loop1-QC1- feeder 1-1 Cond14 240 215.50 86.32 8.00
9 Loop1-QC1- feeder 1-2 Cond14 240 215.50 86.32 9.00
10 Loop7-AA2-Feeder 1 Cond13 240 32.00 60.75 10.00

F Indicates fixed cable size in cable sizing calculations or fixed cable ampacity in uniform ampacity calculation
* Indicates a cable temperature exceeding its limit
# Indicates a cable temperature exceeding its marginal limit

Вам также может понравиться