Академический Документы
Профессиональный Документы
Культура Документы
sivacon
The Obvious Solution
for Global Challenges – SIVACON
Type testing in low-voltage switchgear To this end, Siemens has picked com-
is increasingly becoming an issue of petent, local switchgear manufacturers
prime importance worldwide. In future, and has appointed them SIVACON
there will be no other solution. But Technology Partners.
how far does one really have to go to a
accomplish a type test? Often too far. Your SIVACON Technology Partner will
receive the concentrated know-how
But that is now a thing of the past. of Siemens at terms and conditions
With the “SIVACON Technology Partner” that only a local vendor is able to
concept, Siemens is bringing the versa- offer. For you, this means: SIVACON
tile and type-tested SIVACON low- including type testing – faster, more
voltage switchboard to your door. flexibly and at lower cost than ever
before.
2
Versatile with Safety –
Type-tested components
for power distribution
pages 4–5
Always Flexible –
SIVACON adapts to
your requirements
pages 6–7
Circuit-Breaker Design –
Compact, reliable and user-friendly
pages 10–11
Fixed-Mounted Design –
Economical, reliable and variable
pages 12–14
Technical Data –
At a glance
page 19
3
Versatile with Safety –
Type-Tested Components for Power Distribution
units.
4
SIVACON Features • Modular structure of
• Type-tested standard modules device compartments
(TTA) • Single-front and back-to-back
• Standardized busbar position at installation
the top of the cubicle • Cable lead-in from above or below
• 3- and 4-pole busbar system • Cable connection from the front
up to 7400 A or rear
• Rated peak withstand current
Ipk up to 375 kA
• Deep switchgear compartment
for universal installation
5
Always Flexible –
SIVACON Adapts to your Requirements
0
20
/1
00
10
0
20
00
/1
0
00
10
80
10
0/
80
0
80
0
60
2600
2200
2200
6
SIVACON for
Power Center
All Applications
ln to 7400 A
in the
lcw to 150 kA
Low-Voltage Network
lpk to 375 kA
Subdistribution board
ln to 3200 A
lcw to 80 kA
lpk to 200 kA
Loads
7
Frame and Enclosure –
Dimensionally Accurate and Stable
Surface Treatment:
Optionally powder-coated, wet-
painted or sendzimir-galvanized
Material:
Frame and enclosure are manufac-
tured from sheet steel in the
following thicknesses:
Frame: 2.5 mm
Enclosure: 2.0 mm
Degrees of Protection to
IEC 60529
IP 30, IP 31, IP 40, IP41, IP 42
naturally ventilated
IP 40, IP 54 unventilated
Side panel
Top view 2 mm
8
Variable Busbar System –
The Answer to Diverse Requirements
Busbar System
00
00
0
0
00
80
12
80
80
0
12
12
60
10
Optimum connection
compartments for high safety
11
Fixed-Mounted Design –
Economical, Reliable and Variable
12
600/800/1000
up to 630 A/feeder
Cable feeders in
compartment design
The compartment design with its indi-
vidual sub-section for every circuit breaker
offers increased active safety for
installation and personnel protection.
• Individual sub-sections with doors
for each circuit breaker
• Circuit breaker 3VL with or without
plug-in socket
• High form of internal separation
up to Form 4 Type 7 acc. to
BS EN 60439 (gland box per functional
unit)
• Optimum connection conditions in
the rear cable connection compartment
Cable connection
compartment at the
rear with one cable
gland box per
functional unit,
internal separation
Form 4 Type 7 acc.
to BS EN 60439
00
/12
00
10
800
13
up to 630 A/feeder
Fixed-Mounted Design –
Economical, Reliable and Variable
In-line fuse-switch
disconnector
3NJ4
14
800 600/800/1000
Capacitor module,
100 kvar (chokeless) 15
800 800
16
Plug-in switch disconnector 3NJ6 1000/1200
with 250-A fuses featuring supply-
side plug-in contacts up to 630 A/feeder
Cubicle for Customised Solutions –
Plenty of Space for Flexibility
17
600–1000 1000
Type-Tested Switchgear and Controlgear Assembly (TTA) –
Signed, Sealed and Delivered Safety
Standards and specifications Type-tested low-voltage switchgear IEC 60439-1, DIN EN 60439-1
and control gear assembly (TTA) (VDE 0660 Part 500)
Testing of response to internal faults IEC 61641, VDE 0660 Part 500, Supplement 2
(arcing faults)
19
Siemens AG
www.siemens.com/sivacon
Low Voltage Controls and Distribution Division
Subject to change without prior notice 12/02 | Order No. E20001-A30-P309-V1-7600 | DISPO 27606 | 21C7748 DMPT.52.2.08 PA 12022.0 | Printed in Germany