6" FEM NST X 4" MALE NST

HOSE THREAD COUPLING


DRILL FOUR
3/4" HOLES FOR 4" FEM NST HOSE THRD x
6"Ø NST HOSE

2'-0"
24" MOUNTING (TYP.) 2 1/2"Ø MALE HOSE THRD
CONNECTION

6"Ø STEEL
90° BEND
6"Ø HOLE FOR SUCTION
AND VENT PIPE. 4"Ø 2 1/2"Ø HOSE
SUCTION PIPE CAP W/ CHAIN
HOLE FOR FILL PIPE.

24"
FILL PIPE
LOCATION
1/4" STEEL
PLATE (TYP.) 6"Ø RISER

24" MIN.
CLAMP WELDED
TO PIPE
SUCTION, FILL AND VENT PIPES
SCALE 1:25 PIPE SUPPORT REQUIRED IF
HORIZONTAL RUN EXCEEDS 3FT.

3'-0" 3'-0"

6"Ø STEEL
90° BEND

12 FEET (3.6m) MAX.


1/2" HARDENED BOLTS
GROUTED INTO TANK

6"Ø SCH. 40 STEEL

18" MIN.
VENT PIPE SUCTION PIPE SCREEN WELDED 6"Ø SCH 40
LOCATION LOCATION OVER OPENING STEEL PIPE

DEPTH VARIES
APPROVED PRECAST
REINFORCED CONCRETE
24" Ø STANDARD MANHOLE ANTI-VORTEX STORAGE TANK. MINIMUM

6"
FRAME AND COVER. LID TO BE PLATE CAPACITY 25,000 CAN
LOCKING TYPE. 1" HARDENED BOLTS
GROUTED INTO TANK GALLONS (30,000USG).
PIPE EXTENDS THROUGH CONCRETE
AND IS MORTARED IN PLACE
3/4" (19mm) Ø GALV. STEEL RUNGS PROVIDE STANDARD MANHOLE
AT 12" (300mm) ON CENTRE FROM
FLOOR TO CEILING OF TANK
ACCESSWAY TO TANKAGE.
EXTEND TO GRADE LEVEL IF
VENT PIPE DETAIL
TANK IS BURIED. SCALE 1:25

6"
DOUBLE 2 1/2" N.S.T. CLAPPERED
SIAMESE CONNECTION
MINIMUM 12" OF 3/4" MINUS COMPACTED CRUSH
TOP VIEW BASE OVER UNDISTURBED SUB-BASE
SCALE 1:50
4"Ø SCH. 40 STEEL

ELEVATION

18" MIN.
PIPE SLEEVE OVER 1"Ø ANCHOR BOLTS
48" ON CORNERS. INTERIM PIPE SLEEVE
SUPPORTS PLACED MIDWAYS AS SHOWN.

6"
6"Ø HOLE FOR SUCTION
AND VENT PIPE.

48"
PIPE EXTENDS THROUGH CONCRETE
AND IS MORTARED IN PLACE

FILL PIPE DETAIL 1/4" STEEL PLATE (TYP.)


SCALE 1:25
NOTES:
1. ALL METAL PIPING COMPONENTS SHALL BE ASSEMBLED BY WELDING, PAINTED WITH
INTERNAL SUPPORT COLUMN
(IF REQUIRED)
CORROSION PROTECTANT COAT AND RED ENAMEL PAINT COAT. ANTI-VORTEX PLATE PLAN
2. RECOMMENDED INSIDE DIMENSIONS 20.5 FT. (6.25m) WIDE x 20.5 FT. (6.25m) LONG x SCALE 1:50
9,85 FT. (3.0m) DEEP.

TITLE:
HIGHLANDS FIRE DEPT. FD-2A
1564 Millstream Road Water Storage Tank Detail
Victoria, B.C. V9E 1G6
E. Hall (250) 479-1814 * W. Hall (250) 474-2633
Fax (250) 474-3677
LARGE CISTERN ASSEMBLY
DATE: 16 July 2000 SCALE: AS SHOWN
SIDE VIEW REVISED: MARCH 20, 2001 by MK
SCALE 1:50 REVISED: MARCH 4, 2001 by MK DRAWN: M. Kristiansen APPROVED: