1. CALCULO DE LA POTENCIA INSTALADA O CARGA INSTALADA ( C.I.

PRIMERA PLANTA 119.74 M2 AREA TECHADA 231.94


SEGUNDA PLANTA 112.20 M2 AREA LIBRE 180.26
AZOTEA 52.00 M2 AREA TOTAL 300.00
283.94 M2

CI.1 - CARGA INSTALADA PARA ALUMBRADO Y TOMACORRIENTES

CI.1 = AREA TECHADA * CARGA UNITARIA


CI.1 = 231.94 X 25
CI.1 = 5798.5 WATT

CI.2 - CARGA INSTALADA PARA PEQUEÑOS USOS NO CONTEMPLDOS EN CI.1

CI.2 = 1500 WATT

CI.3 - CARGA INSTALADA PARA CARGAS MOVILES

CI.3 = 2000 WATT

CI.4 - CARGA INSTALADA PARA AREAS LIBRES

CI.4 = AREA LIBRE * 5


CI.4 = 180.26 X 5
CI.4 = 901.3 WATT

CI.5 - CARGA INSTALADA PARA COCINAS ELECTRICAS

1 COCINAS DE 4 HORNILLAS MAS HORNO = 8000


CI. 5 = 8000 X 1
CI.5 = 8000 WATT

CI.6 - CARGA INSTALADA PARA CALENTADOR DE AGUA O THERMA

1 THERMAS DE 35 LITROS = 750


CI. 5 = 750 1
CI.6 = 750 WATT

CI.7 - CARGA INSTALADA PARA ARTEFACTOS DE COCINA

1 BATIDORA = 200
1 CAFETERA = 800
1 HORNO MICROONDA = 1500
1 OLLA ARROCERA = 1400
1 REFRIGERADORA = 200
1 LICUADORA = 500
CI.7 = 4600 WATT

CI.8 - CARGA INSTALADA PARA OTROS ARTEFACTOS

1 ASPIRADORAS = 500
2 COMPUTADORAS = 600
1 EQUIPOS DE SONIDO = 40
1 LAVADORAS = 800
1 PLANCHA = 1000
5 TELEVISOR = 900
1 SECADORA DE ROPA = 1500
2 VENTILADOR = 200
CI,8 = 5540 WATT

CI,T - CARGA INSTALADA TOTAL

CI.T = 29089.8 WATT

2. CALCULO DE MAXIMA DEMANDA

MD.1 - MAXIMA DEMANDA PARA TOMACOORIENTES Y LUMINARIAS MAS AREAS LIBRES

MD.1 = ( CI.1 + CI. 4) * FACTOR DE DEMANDA


MD.1 = 6699.8 X 35%
MD.1 = 2344.93 WATT

MD.2 - MAXIMA DEMANDA PARA PEQUEÑOS USOS Y TIPO DE CARGA

MD.2 = ( CI.2+ CI.3) * FACTOR DE DEMANDA


MD.2 = 3500 X 0.30
MD.2 = 3499.70 WATT

MD.3 - MAXIMA DEMANDA PARA LA COCINA

MD.3 = ( CI.5) * FACTOR DE DEMANDA


MD.3 = 8000 X 80%
MD.3 = 6400.00 WATT

MD.4 - MAXIMA DEMANDA PARA EL CALENTADOR DE AGUA O THERMA


MD.4 = ( CI.6) * FACTOR DE DEMANDA
MD.4= 750 X 100%
MD.3 = 750.00 WATT

MD.5 - MAXIMA DEMANDA PARA ARTEFACTOS DE COCINA

MD.5 = ( CI.7) * FACTOR DE DEMANDA


MD.5 = 4600 X 43%
MD.3 = 1978.00 WATT

MD.6 - MAXIMA DEMANDA PARA OTROS ARTEFACTOS

MD.5 = ( CI.8) * FACTOR DE DEMANDA


MD.5 = 5540 X 36%
MD.3 = 1994.40 WATT

MD,T - MAXIMA DEMANDA TOTAL

MD.T = 16967.03 WATT

3. CALCULO DEL CALIBRE DEL CONDUCTOR POR INTENSIDAD DE CORRIENTE

INTENSIDAD

I =16967.03/(√3 𝑥 220 𝑥0.9)

I= 49.47 A

INTENSIDAD DE DISEÑO

ID= 1NTENSIDAD X FACTOR DE DISEÑO


ID= 49.47 X 1.25
ID= 61.84 A

4. SELECCIÓN DEL TIPO Y LSA SECCION DEL CONDUCTO

TIPO DE CABLE = TW
CALIBRE EN MM2 = 16
CALIBRE EN AWG = 6
5. VERIFICACION POR CAIDA DE TENSION

K = √3
Id = 61.84
S = 0.0175
L = 8.42
S = 16.00
Cos = 1

∆�=√3 𝑋 61.84 𝑋 (0.0175 𝑋 8.42)/16 𝑋 1

ΔV = 0.986 V

0.986 < 5.5 V OK !!


1 X 16 mm² TW + 1 - 16 mm²
PVC 25 mm Ø Pesado

6. CIRCUITOS ESPECIALES

A) COCINA
𝐼 = 𝑊/(𝐾 𝑥 � 𝑥 𝐶𝑜𝑠 ∅)

W = 8000
K = TRIFASICO = √3
V = 220
��� ∅ = 0.9

𝐼 = 8000/(√3 𝑥 220 𝑥 0.9)

I = 23.33 A

C. N. E → Incrementar en 20%

Id = 1.2 X 23.33
Id = 27.99 A ≈ 28 A
6 mm² TW = 35 A OK!!

VERIFICACION POR CAIDA DE TENSION

K = √3
Id = 23.33 X 1.12 = 26.13
S = 0.0175
L = 7.62
S = 6.00
Cos = 1

∆�=√3 𝑥 23.33 𝑥 (0.0175 𝑥 7.62)/6 𝑥 1

ΔV = 0.898 V

0.898 < 3.3 V OK !!


2 - 1 X 6 mm² TW

A) CALENTADOR DE AGUA O THERMA


𝐼 = 𝑊/(𝐾 𝑥 � 𝑥 𝐶𝑜𝑠 ∅)

W = 750
K = MONOFASICO = 1
V = 220
��� ∅ = 0.9

𝐼 = 750/(1 𝑥 220 𝑥 0.9)

I = 3.79 A

C. N. E → Incrementar en 20%

Id = 1.2 X 3.79
Id = 4.54 A ≈ 5A

1.5 mm² TW = 10 A OK!!

VERIFICACION POR CAIDA DE TENSION

K = 1
Id = 3.79 X 1.12 = 4.24
S = 0.0175
L = 9.56
S = 1.50
Cos = 1

∆�=1 𝑥 4.24 𝑥 (0.0175 𝑥 9.56)/1.5 𝑥 1

ΔV = 0.473 V 2-2,5mm2 TW

0.473 < 3.3 V OK !!


2 - 1,5mm2 ≈ 2-2,5mm2 TW
PVC – 15 mm∅ L – 2 x 2,5 mm2 TW +1 x 2,5 mm2