Lightning Protection System Design and

Products

The first step in designing a lightning protection system is Risk Assessment. Axis has used the guidelines
of IEC 62305 Part 2 to design a Risk Assessment Software that allows you to assess the risks and
determine the Class of Lightning Protection System (LPS) for your structure. This software uses
parameters unique to your structure to help you determine the best and most efficient protection
system.

Based on this, you can now design the external and internal protection systems for your building. The
External protection system would include an Air Termination, Down Conductor and an Earth
Termination System. For internal protection, one would use surge protection devices and equipotential
bonding.

Air Termination

The positions of the Air Termination can be decided based on the rolling sphere method, the protective
angle method and the mesh method. The rolling sphere method can even be used to define the zones of
protection for structures with complex geometry. The radius for the sphere is determined directly from
the Class of LPS.

The Protection Angle method is used for simple structures but only up to a certain height as determined
by the class of LPS.

The Mesh Method is best used for flat surfaces where the air termination conductors are to be placed at
the roof edges and where no other metallic structure will be above the air termination system.

Axis Air Termination Rods, made from high grade electrolytic Copper, provide the highest conductivity
that allows the flow of lightning strikes without any damage to the structure or equipment.

Non-Conventional Air Termination Systems

According to IEC-62305, the zone of protection determined for an air termination system shall be
defined only by the physical size of the system. There is no conclusive evidence that this zone can be
enhanced, as claimed by manufacturers of Early Streamer Emission technologies. Thus, no IEC Standard
recognizes the ESE technology.

Down Conductors

Down conductors, connected to the Air termination system with suitable Axis products, should take the
most direct route down the structure, with spacing between each one defined by the Class of LPS. Axis
Copper Clad Steel Down Conductors are specially developed to offer the high mechanical strength of
steel and the current carrying capacity of Copper. Since IEC 62305 also allows the use of re bars inside
concrete structures as down conductors under certain conditions, Axis offers specially designed
products to use this technology effectively.

Earth Termination

An Earth Electrode should provide low electrical resistance with the earth to allow for the dissipation of
currents. It should also be resistant to corrosion because it will be buried underground for a long period
of time.

Worldwide, one of the most popular Earth Electrodes are copper bonded earth rod, which comply with
IEC 62561 Part 2. Since electricity is a surface phenomenon, the copper layer allows for a conductive
path while the inner core of high strength steel provides the strength required for driving the rod inside
the ground. Axis Copper Bonded Earth Rods have been are approved by Utilities across the world and
continue to be popular due to their consistently high quality.

Internal LPS

The two major components of internal LPS are Equipotential bonding and surge protection devices
(SPD’s). The purpose of Equipotential Bonding equipment is to bring all the metallic parts and
equipment in a structure to the same Voltage Potential, to avoid hazards to human life or other damage.
SPD’s protect electronic devices by breaking the circuit in case of an equipment or system fault.
Conclusion

Since 1994, Axis has continued to manufacture and supply high quality lightning protection and earthing
equipment internationally. We have a proven track record of high quality protection. Our customers
include Utilities, Government Organizations and Private Projects across the globe.