DPP2U SERIES

P O W E R I N G T E C H N O L O G Y
DC DISTRIBUTION PANELS
20 Pluggable Breakers & Dual 450A Inputs

DESCRIPTION
UNIPOWER’s DPP2U Series circuit breaker
panels provide distribution and overload
protection for 1 to 20 circuits with circuit
breakers that can be field installed/exchanged
using a supplied puller tool. The panels are
only two mounting positions (3.5 inches) high.

Standard models provide up to 20 breakers


dual-bus 900A (10A/10B) distribution and
alarm capabilities. The A and B sections of
the dual-bus panel are fully isolated, can be
E210994 LVD2006/95/EC
separately configured for 12 or 24/48 volts and ROHS2011/65/EU
are polarity neutral. Breaker capacities range
from 2.5 to 200 amperes. Optional single-bus STANDARD DUAL FEED CONFIGURATIONS
450A models are also available. AMPS
MODEL VOLTS INPUT MAX. # TOTAL
EACH
NUMBER EACH FEED FEEDS BREAKERS AMPS
Breaker and power fail alarms are indicated FEED
by a dual color LED (green/red) and Form C DPP2U-A1-B1 48/24 - 48/24 10 A side
relay contacts for each bus. DPP2U-A6-B6 12 - 12 2 & 450 900
DPP2U-A1-B6 48/24 - 12 10 B side
Rear accessed load cables connect via 2-hole
anti-rotation posts. All connections are OPTIONAL SINGLE FEED CONFIGURATIONS
straight on for easy installation. AMPS
MODEL VOLTS INPUT MAX. # TOTAL
EACH
NUMBER EACH FEED FEEDS BREAKERS AMPS
FEED
FEATURES DPP2U-A1-B1-S 48/24
1 20 450 450
 48/24V and 12V or Dual Voltage DPP2U-A6-B6-S 12

 POLARITY NEUTRAL
 450A bus bar inputs (900A total) BREAKER ORDERING GUIDE 1
 Dual Feed (optional Single Feed) AMPS PART NUMBER AMPS PART NUMBER
 “Mid-Trip” circuit breaker function 2.5 348-1441-0020 50 348-1441-0500
 Circuit Breaker ‘puller’ included 5 348-1441-0050 60 348-1441-0600
 Tapered entry for easy insertion 10 348-1441-0100 80 348-1441-0800
 NO or NC alarm contacts 15 348-1441-0150 100 348-1441-1000
 Alarm LEDs 20 348-1441-0200 125 2 775-1524-0000
 Power Fail form-C alarm 25 348-1441-0250 150 2 775-1524-0010
 19" & 23" universal mounting brackets 30 348-1441-0300 200 2 775-1524-0020
 Rear panel safety cover standard 40 348-1441-0400
NOTES:
1. Breakers need to be ordered individually and are shipped separately.
THREE YEAR WARRANTY 2. Require two positions. Includes paralleling bars to connect output load terminals.
3. Breakers are magnetic-hydraulic plug-in type with auxiliary contacts (Normally
Open) and mid-trip function. Only the following types may be installed.
2.5A to 100A:
SAFETY CERTIFICATIONS CBI D-Frame Series single pole, D-2A23XANBSXXXXLXB-XXXXXWDVAX2-X
or
UL60950-1 2nd Edition Carling C-Series Handle single pole, CT1-B2-14-XXX-A11-MJ
CSA22.2, No. 60950-1 2nd Edition 125A to 200A:
EN60950-1 2nd Edition CBI D-Frame Series, parallel pole, D-2A23XBNBSXXXXLAM-XXXXXWDVAX3-X
or
Carling C-Series Handle Parallel pole, CT2-P2-04-XXX-A11-MK
www.unipowerco.com
NORTH AMERICA CALL: +1-954-346-2442 • EUROPE CALL: +44 1903 768200
1.25
(31.8)

0.57
(14.5)

DPP2U SERIES DC DISTRIBUTION PANELS - 2

5.98 SPECIFICATIONS
(151.9) Typical at 25oC Unless Otherwise Noted.

INPUT/OUTPUT ENVIRONMENTAL
Panel Capacity Operating Temp. Range........................................................................................................-10°C to +70°C
@35°C.............................................................................................................................................450A per Bus Storage Temp. Range............................................................................................................-40°C to + 85°C
@40°C........................................................................................................................................... 400A per Bus Humidity......................................................................................................0% to 95%, Non-Condensing
@50°C............................................................................................................................................320A per Bus
@70°C........................................................................................................................................... 200A per Bus PHYSICAL SPECIFICATIONS
Configuration.......................................................................450A Single Bus with 1 to 20 Breakers Case Material........................................................................................................................................................Steel
.900A Dual Bus 1 to 10 Breakers Each Bus Finish....................................................................................................................................... Powder Coat Black
OUTLINE OF SAFETY COVER
Breaker Capacity ....................................................................................................................... 2.5A to 200A
1
Case Dimensions, Inches (mm)...............................................................3.45 H x 17.16 W x 5.98 D
4.60 Voltage
1 (blue dotted line) 17.16 (87.6 x 435.9 x 151.9)
(116.8) 24/48V Version..................................................................................................................................21-60VDC (435.9)
Safety Cover extension, Inches (mm).................................................................................... 8.1 (205.7)
12V Version....................................................................................................................................... 10.5-15VDC Weight (approx.).................................................................................................................. 12.5INPUT
lbs. (5.67 kg.)
B - BUS INPUT B - BUS OUTPUT FEED
Polarity.........................................................................................Neutral, Positive or Negative Ground
A - BUS OUTPUT FEED A - BUS
3 Rack Mounting.............................................................................................................................. 19 or 23 Inch
7)
FEED FEED
0 stud 0.22 0.25
(5.6)
h = 0.50 (12.7),
ALARMS
0.42
10
(6.4)
9 8 7 6 5 4 3 2 1 10 9 8
CONNECTIONS 7 6 5 4 3 2 1

(15.88) spacing Alarm


(10.7) Indicator ....................................................................................................Dual Color LED Per Bus Input Connections....................................................................................................................................Bus Bar
LED Status Indication......................................................................................................... Green = Normal Output Connections.........................................................................................1/4-20 Stud, 2-hole lugs
..Red = CB Trip Alarm Chassis Ground Connection........................................................................1/4-20 Stud, 2-hole lugs
Off = No Power Alarm Relay Connections..................................................Spring Clamp Terminals,16-26AWG
Alarm Relays............................................................................................Form C Contacts for each Bus
Notes:
3.50 SAFETY
1. See ordering guide to specify.

ALM-A
ALM-B

(88.9) Safety.................................................................UL60950-1 2nd Ed., CSA22.2 No. 60950-1 2nd Ed.,


NO-C-NC NO-C-NC
EN60950-1 2nd Ed.
NEBS................................................................................................................GB-1098-CORE, GR-63-CORE
1.25
(31.8)

B - BUS RETURN Alarm connector A - BUS RETURN


0.60 0.57
FRONT VIEW
(15.2) (14.5)

5.98
A - ALM B - ALM
(151.9)
1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
A BUS - 450A MAX/100A MAX PER CB B BUS - 450A MAX/100A MAX PER CB

A - BUS FEED BREAKERS B - BUS FEED BREAKERS

NOTES:
1. 125A, 150A & 200A breakers utilize two positions and must have blank spaces either side.
2. 80A & 100A breakers must have blank spaces either side.
17.16

REAR VIEW
(435.9)

B - BUS INPUT B - BUS OUTPUT FEED A - BUS OUTPUT FEED A - BUS INPUT
FEED FEED
stud 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
= 0.50 (12.7),
15.88) spacing
ALM-A
ALM-B

NO-C-NC NO-C-NC

B - BUS RETURN Alarm connector A - BUS RETURN


0.60
(15.2)
NOTE: Single feed models DPP2U-A1-B1-S and DPP2U-A6-B6-S have both left and right side input bus bars fitted. It is only necessary to
connect the input feed to one side for correct operation. The unused side is directly connected to the live input feed and can be
used for supplying additional panels. The total load must not exceed 450A on any one pair of bus bars in the chain.

UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • sales@unipowerco.com
A - ALM North America: +1 954-346-2442 • Europe: +44 1903 768200 B - ALM

1 2 3 4 5 6 7 8 9 10 1 2 3 4 5 6 7 8 9 10
DPP2U SERIES DC DISTRIBUTION PANELS - 3

DIMENSIONS
ALL DIMENSIONS IN INCHES (mm).

OUTLINE OF SAFETY COVER


4.60
(blue dotted line)
(116.8)

0.76 1.13
(19.3) (28.7)
0.21 0.22 0.25 OUTLINE OF SAFETY COVER
(5.3) 0.56 0.37 (5.6) 0.42 (6.4)
(14.2) (9.4) (10.7) 4.60
(blue dotted line)
ø 0.306 (7.8)
(116.8)
0.49 (12.5) x
0.31 (7.9) slot 0.76 1.13
(19.3) (28.7)
0.21 0.22 0.25
(5.3) 0.56 0.37 (5.6) 0.42 (6.4)
(14.2) 3.50
(9.4) (10.7)
ø 0.90
0.306
(22.9)
(7.8) (88.9)

1.725 0.49 (12.5) x


(43.82) 1.25
0.31 (7.9) slot (31.8)
0.500 0.625
(12.70) (15.88)

Chassis GND
(1/4-20 THREAD) 0.90 0.57 3.50
(22.9) (14.5) (88.9)
0.750
(19.05) 1.725
(43.82) 1.25
0.500 0.625 (31.8)
(12.70) (15.88)

Chassis GND 5.98


(1/4-20 THREAD) (151.9) 0.57
(14.5)
4.642
(117.91) 0.750
(19.05)

5.98
(151.9)
4.642
(117.91)
3.45 17.16
(87.6) (435.9)

B - BUS INPUT B - BUS OUTPUT FEED A - BUS OUTPUT FEED A - BUS INPUT
FEED FEED
0.63 0.76 1/4-20 stud 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
(16.0) (19.3) length = 0.50 (12.7),
0.625 (15.88) spacing

3.45
CONNECTIONS 17.16
(87.6) (435.9)

OUTPUT TERMINAL DETAIL B - BUS INPUT ALARM CONNECTOR DETAIL


B - BUS OUTPUT FEED A - BUS OUTPUT FEED A - BUS IN
ALM-A
ALM-B

FEED FEED
NO-C-NC NO-C-NC
0.63 0.76 1/4-20 stud 10 9 8 7 6 5 4 3 2 1 10 9 8 7 6 5 4 3 2 1
(16.0) (19.3) length = 0.50 (12.7),
ALM-A
ALM-B

NO-C-NC NO-C-NC
0.625 (15.88) spacing

Shorting Bus (-S Models) B - BUS RETURN Alarm connector NO-C-NC NO-C-NC
A - BUS RETURN
1/4-20 stud 0.60
length = 0.38 (9.7), (15.2)
0.625 (15.88) spacing
Connectors are Phoenix Contact spring clamp type.
ALM-A
ALM-B

Wires (16-26AWG) do not require any termination.


NO-C-NC NO-C-NC

NO-C-NC NO-C-NC

A - ALM B - ALM

Shorting Bus (-S Models) 1 2 3 4 5 6 7 B -8BUS9 RETURN


10 1 2 3 Alarm
4 5 connector
6 7 8 9 10 A - BUS RETURN
A BUS - 450A MAX/100A MAX PER CB B BUS - 450A MAX/100A MAX PER CB
1/4-20 stud 0.60
length = 0.38 (9.7), (15.2)
0.625 (15.88) spacing
A - BUS FEED BREAKERS B - BUS FEED BREAKERS

POWER CONNECTIONS
Input Lug Connections A - ALM B - AL

Max. wire size of 350 kcmil, Panduit LCC350-14BW-X or 2501 kcmil


2 3
FLEX 4
Conductor,
A BUS - 450A
5 6 7
MAX/100A MAX PER CB
8
Panduit
9 10
LCCX250-14B-X.
1 2 3 4 5 6 7
B BUS - 450A MAX/100A MAX PER CB
8 9 10

Load Lug Connections A - BUS FEED BREAKERS B - BUS FEED BREAKERS

Max. wire size of #2 AWG FLEX Conductor, Panduit LCDXN2-14A-E or LCDXN2-14AF-E (90deg angle).

See product manual for more detailed information about making connections to this distribution unit:
dpp2u-ds-revG-0917.indd

www.unipowerco.com/pdf/dpp2u-man.pdf.

© 2017 UNIPOWER LLC


This document is believed to be correct at time of publication and Unipower LLC accepts no responsibility for consequences from printing errors or inaccuracies. All specifications subject to change without notice.

UNIPOWER LLC • 3900 Coral Ridge Drive, Coral Springs, Florida 33065, USA • sales@unipowerco.com
North America: +1 954-346-2442 • Europe: +44 1903 768200

Вам также может понравиться