ESTUDIO DE RESISTIVIDAD DEL TERRENO
FECHA:
No. DOCUMENTO: MC-018-E-103
1.- OBJETIVO
2.- CALCULOS
3.- BIOGRAFIA
4.- ANEXOS
2 de 34
A
ELABORÓ: ASA
REVISÓ JLCH
APROBÓ AEPS
FECHA: 25-Jul-13
ÑO
TIVIDAD DE LA MALLA
3 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
1.- OBJETIVO
El objetivo del Estudio es determinar el valor de reisistividad del terreno en el área donde se ampliará la SE de 115 kV para ela
Memoria de cálculo de la malla de tierras correspondiente.
El método de medición utilizado es el de Wenner de las cuatro puntas. En este método se tienen cuatro puntas enterradas a lo
línea recta separadas a la misma distancia a, enterrados a una profundidad b.
b
a a a
El voltaje entre los dos electrodos internos es medido y dividido por la corriente que circula entre los otros dos electrodos (exter
un valor de resistencia R. La resistividad se obtiene utilizando la siguiente fórmula:
4 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
5 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
4 aR
2a a
1
a 2 4b 2 a2 b2
Donde :
Donde :
A = 28.00762335 A = 28.00762335
In
3.422 X 10 ⁻⁴
In
234 + 450
0.20201564
0.3 X 0.00393 X 1.7241 234 + 46
6 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
0.001512963
En donde :
If = Corriente asimetrica efectiva de falla = 28.00762335 kA
tc = Tiempo de de falla = 0.25 s
ar = Coeficiente térmico de resistividad = 0.00393 1/°C
rr = Resistividad relativa del cobre = 1.7241 mW.cm
TCAP = Factor de capacidad térmica = 3.422 J/(cm3 °C)
Tm = Temperatura máxima de los conectores = 450 C
o
Por lo que el area del conductor capaz de drenar la corriente de corto circuito es:
A = 65.9352 mm2
7 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
Medidor de resistencia de tierras de la marca Kyoritsu modelo 4106, no. de serie W0303807 con vigencia de calibración hasta
de 2014. Se anexa Informe de calibración.
Se efectuaron dos pruebas, cada una consistente de cuatro mediciones a lo largo de una línea recta, separando los electrodos
metros. Se anexa dibujos de localización de puntos de prueba y Reporte de resultados del Medidor de resistencia de tierras.
TABLA DE RESULTADOS
8 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
0.09 *
1
CS 1 S
2h S 0.09
Cs =
1 --
0.09 X 1-
50.00
5000
2 X 0.1 + 0.09
Cs =
1 --
0.09 X 0.99
0.29
Cs =
1 -- 0.3072413793 = 0.6927586207
0.116
E step50Kg 1000 6 C s s
ts
0.116
E touch50Kg 1000 1.5 C s s
ts
9 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
0.116
E touch50Kg 1000 No. 5 C s s MC-018-E-114
1.DOCUMENTO:
ts
Es = 5054 V
Et = 1437 V
donde:
Cs = Factor de reducción 0.693
rs = Resistividad de la capa de acabado 5000 Wm
ts = Duracion de la corriente de choque 0.25 s
r = Resistividad promedio del terreno 50.00 Wm
hs = Espesor de la capa de acabado 0.1 m
10 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
Debido a que como el potencial de la malla de tierra remota GPR es mayor con respecto a la maxima tension permitida de toqu
determinar las tensiones de reticula y de paso para la subestación
La maxima tension de toque encontrada dentro de un lazo o reticula de una malla es segun la formula 80 de la norma 80 de la
siguiente formula:
K m K i ρ IG
Em
Lm
Em = 1325.0 V
1 D2 D 2h 2 h Kii 8
Km
ln
ln
2 16hd 8Dd 4d Kh 2n 1
Km = 1
2π
In
16
x
12 ²
0.5 x 0.01325
+
12 +
8 x 12
2x 0.5 ²
x 0.0133
-
0.5
4 x 0.01325
+
1
1.22474In
8
2 x 10.8858
Km = 1
2π
In
144
0.106
+
169
1.272
-
0.5
0.053 +
0.8164966
In
8
65.2560096
11 de 34
D
d
h
Kii
Kh
n
Km =
=
=
=
=
=
=
V k
Km = 0.1591549431 In
Km = 0.1591549431 In
PROYECTO:
AREA:
No. PROYECTO :
DOCUMENTO:
No. DOCUMENTO:
1358.5
1481.91824
Km = 0.1591549431 5.5873670664
Km = 0.8892570875
+ 132.86
INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II
018
MXFALT-II-2734
MC-018-E-114
- 9.434
-1.7137255686
0.88926
12 de 34
+ 0.8164966 In
=
12
= 0.01325 m
= 0.5
1
= 1.2247449
0.12259407
= 10.885816 cond.
REV.:
ELABORÓ:
REVISÓ
APROBÓ
FECHA:
LM L C
LM =
LM =
LM =
Lr
LR
Lx
Ly
=
=
=
=
=
V k
Ki 0.644 0.148 n
Ki = 0.644
Ki = 2.2551008407
Ki = 2.2551008407
913
913
913
LM = 1059.6863988983
Lc
+
1.55 1.22
+
1.55
PROYECTO:
AREA:
No. PROYECTO :
DOCUMENTO:
No. DOCUMENTO:
0.148
1.55
x
1.6031300426
10.886
1.22
1.22
LM = 1059.6863988983 m
Kh
donde :
1
h
ho
; Kh
Kh = 1.2247448714
n n a nb n c n d
=
Lr
L2 x L2 y
INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II
018
MXFALT-II-2734
MC-018-E-114
51
91.5
1 +
L
R
3.05
²+
0.0435492152
0.5
1
=
=
13 de 34
48
913
3.05
91.5
51
48
²
91.5
m
m
m
m
= 1.224745
0.5 m
1 m
= 10.885816 cond
91.5
REV.:
ELABORÓ:
REVISÓ
APROBÓ
FECHA:
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
donde:
2L c 2 913
na =
198
= 9.22222222
Lp
Lp 198 198
nb = = = 1.0520711235
4 A 4 2000 178.8854382
0. 7 A
2000
L x L y Lx Ly 0.7 0.5719
nc =
51 x 48 51 48 =
2448
= 1.12253991
A 2000 2000
Dm 70 70
nd = = = 0.9994902
L2 x L2 y 51 ²+ 48 ² 70.035705
14 de 34
Es
Ks
s
=
n ma x e
n n a nb n c n d
n =
r = Resistividad promedio
Ks = Factor de geometria
= 1
π
0.3702
2
D h
PROYECTO:
AREA:
No. PROYECTO :
DOCUMENTO:
No. DOCUMENTO:
na
nb
nc
nd
Es
n
=
=
=
=
=
9.2222222222
1.0520711235
1.122540
0.999490186
10.885816491
Ls
D
conductores
conductores
conductores
conductores
conductores
1
2.2551
762.53
0.5
+
Es = 767.68448452 V
K
1 1
2h
1
1
50.00
12
INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II
018
MXFALT-II-2734
MC-018-E-114
+
0.9995 = 10.885816491
14003.81
1
0.5
+
15 de 34
913
198
2000
51
48
70
= 766.68448452
1
12
1
m
m
m ²
m
m
m
El voltaje entre pies sobre el piso exterior inmediato a la red ( de acuerdo a la norma 80 de la IEEE formula 92) se calcula de la
K s K i IG
50.00
0.3702
2.2551
14003.81 A
762.53
1 -
Wm
0 .5 n 2
0.5
10.89 - 2
REV.:
ELABORÓ:
REVISÓ
APROBÓ
FECHA:
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
Ks = 0.31831 1 + 0.08
+ 0.0833 0.997886
Ks = 0.3702444256
Ks = 0.3702444256
K mK iIG t S
L
157 0.235 S C S
16 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
Ls = 762.525 m
Em = 1325 V
Es = 768 V
K m K iI G ts
L
157 0 . 235 s C s
L > 723.04 m
17 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.:
AREA: 018 ELABORÓ:
No. PROYECTO : MXFALT-II-2734 REVISÓ
DOCUMENTO: APROBÓ
MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS
FECHA:
No. DOCUMENTO: MC-018-E-114
3.- BIBLIOGRAFÍA
4.3.- ANSI/IEEE Std 80 – 2000 IEEE Guide for Safety in AC Substation Grounding
18 de 34
A
ASA
JLCH
AEPS
28-Jun-13
la corriente que circula entre los otros dos electrodos (externos) para dar
guiente fórmula:
19 de 34
A
ASA
JLCH
AEPS
28-Jun-13
28.00762335
2.44285714
20 de 34
A
ASA
JLCH
AEPS
28-Jun-13
21 de 34
A
ASA
JLCH
AEPS
28-Jun-13
22 de 34
A
ASA
JLCH
AEPS
28-Jun-13
PASO
8
10.8858 - 1
23 de 34
A
ASA
JLCH
AEPS
28-Jun-13
24 de 34
A
ASA
JLCH
AEPS
28-Jun-13
NTERRADO
25 de 34
A
ASA
JLCH
AEPS
28-Jun-13
Harper 1997.
ation Grounding
aciones Eléctricas
26 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.: A
AREA: 018 ELABORÓ: ASA
No. PROYECTO : MXFALT-II-2734 REVISÓ JLCH
DOCUMENTO: MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS APROBÓ AEPS
FECHA: 28-Jun-13
No. DOCUMENTO:MC-018-E-114
4.- ANEXOS
27 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.: A
AREA: 018 ELABORÓ: ASA
No. PROYECTO : MXFALT-II-2734 REVISÓ JLCH
DOCUMENTO: MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS APROBÓ AEPS
FECHA: 28-Jun-13
No. DOCUMENTO:MC-018-E-114
28 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.: A
AREA: 018 ELABORÓ: ASA
No. PROYECTO : MXFALT-II-2734 REVISÓ JLCH
DOCUMENTO: MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS APROBÓ AEPS
FECHA: 28-Jun-13
No. DOCUMENTO:MC-018-E-114
29 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.: A
AREA: 018 ELABORÓ: ASA
No. PROYECTO : MXFALT-II-2734 REVISÓ JLCH
DOCUMENTO: MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS APROBÓ AEPS
FECHA: 28-Jun-13
No. DOCUMENTO:MC-018-E-114
30 de 34
PROYECTO: INCREMENTO DE CAPACIDAD PLANTA ALTAMIRA II REV.: A
AREA: 018 ELABORÓ: ASA
No. PROYECTO : MXFALT-II-2734 REVISÓ JLCH
DOCUMENTO: MEMORIA DE CALCULO DEL SISTEMA DE TIERRAS APROBÓ AEPS
FECHA: 28-Jun-13
No. DOCUMENTO:MC-018-E-114
31 de 34