Академический Документы
Профессиональный Документы
Культура Документы
DESIGN
MANUAL
FOURTH EDITION
Contributors:
Published by
by
and
All rights reserved. No part of this publication may be reproduced, stored in a computer or retrieval system or
transmitted in any form or by any means, electronic, mechanical, photocopy, fax, recording or otherwise, without
the prior written consent of the Masonry Institute of America or the International Code Council.
ISBN-10: 0-940116-44-8
ISBN-13: 978-0-940116-44-3
Library of Congress Cataloging-in-Publication Data
Printed in the United States of America
Portions of this publication are reproduced, with permission, from the 2006 International Building Code, 2006
edition copyright © International Code Council.
This book was prepared in keeping with current information and practice for the present state of the art of
masonry design and construction.
The authors, publisher and all organizations and individuals who have contributed to this book cannot assume or
accept any responsibility or liability, including liability for negligence, for errors or oversights in this data and
information and in the use of such information.
CHAPTER 7 VENEER--------------------------------------------------------------------------------------61
7.1 General-------------------------------------------------------------------------------------------------------------------------61
7.2 Shelf Angles-------------------------------------------------------------------------------------------------------------------62
7.3 Flashing-------------------------------------------------------------------------------------------------------------------------62
7.4 Weep Holes-------------------------------------------------------------------------------------------------------------------63
7.5 Connectors---------------------------------------------------------------------------------------------------------------------64
7.5.1 Wall Ties-------------------------------------------------------------------------------------------------------------64
7.5.2 Anchors--------------------------------------------------------------------------------------------------------------65
CHAPTER 14 VENEER--------------------------------------------------------------------------------289
14.1 General-------------------------------------------------------------------------------------------------------------------------289
14.2 Structural Support Backup Materials-----------------------------------------------------------------------------------290
14.2.1 Structural Masonry Backup-------------------------------------------------------------------------------------290
14.2.2 Structural Concrete Backup------------------------------------------------------------------------------------291
14.2.3 Wood Stud Backup-----------------------------------------------------------------------------------------------291
14.2.4 Steel Stud Backup------------------------------------------------------------------------------------------------292
TABLE OF CONTENTS xiii
14.3 Shelf Angles-------------------------------------------------------------------------------------------------------------------293
14.4 Flashing-------------------------------------------------------------------------------------------------------------------------294
14.5 Weep Holes--------------------------------------------------------------------------------------------------------------------294
14.6 Expansion Joints-------------------------------------------------------------------------------------------------------------295
14.7 System Detail Requirements----------------------------------------------------------------------------------------------295
14.7.1 General Requirements-------------------------------------------------------------------------------------------296
14.7.1.1 Definitions------------------------------------------------------------------------------------------------------296
14.7.1.2 Installation------------------------------------------------------------------------------------------------------297
14.7.2 Adhered Veneer----------------------------------------------------------------------------------------------------298
14.7.2.1 Thin Brick------------------------------------------------------------------------------------------------------298
14.7.2.2 Honeycomb Stone--------------------------------------------------------------------------------------------299
14.7.2.3 Terra Cotta-----------------------------------------------------------------------------------------------------299
14.7.2.4 Adhered Veneer Installation-------------------------------------------------------------------------------299
14.7.3 Anchored Veneer--------------------------------------------------------------------------------------------------301
14.7.3.1 Stone Veneer--------------------------------------------------------------------------------------------------304
14.7.3.2 Block Veneer, Concrete Units----------------------------------------------------------------------------307
14.8 Typical Details-----------------------------------------------------------------------------------------------------------------308
14.8.1 Roof/Parapet Details----------------------------------------------------------------------------------------------308
14.8.2 Shelf Angle/Flashing Details------------------------------------------------------------------------------------310
14.8.3 Sill and Jamb Details---------------------------------------------------------------------------------------------313
14.8.4 Floor Connection Details----------------------------------------------------------------------------------------316
14.8.5 Wall Base Details-------------------------------------------------------------------------------------------------317
14.8.6 Expansion Joint Details------------------------------------------------------------------------------------------321
14.8.7 System Configuration---------------------------------------------------------------------------------------------323
CHAPTER 17 GLOSSARY---------------------------------------------------------------------------------359
CHAPTER 18 REFERENCES----------------------------------------------------------------------------373
CHAPTER 19 INDEX-----------------------------------------------------------------------------------------377
xv
PREFACE
Masonry is perhaps the oldest building material, yet it is the least understood. This book is intended to
assist the designer in understanding the materials and the construction process. It is our desire to fulfill a need
of the designer, that is, to understand masonry materials in simple terms.
This book incorporates the latest information available and is consistent with the design provisions of the
2006 International Building Code, the 2005 Building Code Requirements for Masonry Structures (ACI 530/
ASCE 5/TMS 402) and the 2005 Specification for Masonry Structures (ACI 530.1/ASCE 6/TMS 602). The
authors are presenting the material intended for the benefit of non-engineering disciplines, such as architects
and contractors. There are a number of engineering concepts contained in the publication, but they are important
to understanding the value of the basic concepts of masonry.
There are several sources that this publication incorporates, including the previous editions of the Masonry
Design Manual, Technical Notes from the Brick Industry Association and National Concrete Masonry Association
and a number of other technical publications developed by the Masonry Institute of America and other sources
were used in the develpment of this publication. The compilation of this information is focused to the benefit of the
designer and should be a valuable tool in improving the masonry industry.
This publication is not intended to replace the designer and anyone developing a masonry project should
seek the assistance of a design professional. The Masonry Institute of America welcomes recommendations
for the extension and improvement of the material and any new design techniques that may be incorporated into
future editions.
ACKNOWLEDGEMENTS
We gratefully acknowledge the recommendations and suggestions of the professionals who helped improve
and prepare this publication.
We are particularly appreciative to James E. Amrhein, James J. Kesler, Leonard L. Thompson and John J.
Van Houten who were the contributing authors to the previous edition.
Technical support and comments came from many sources and we are grateful to all. Gregg Borchelt of the
Brick Industry Association provided many useful comments relative to brick masonry. James Feagin and Roger
Utesch continually offer suggestions on practical construction methods.
Countless hours of staff support were provided by Luis Dominguez and Debby Chrysler in the development
and production of this publication. Others that made significant contributions included Larry Carnes, Dan Autovino
and Jim Buckley. We sincerely appreciate their input.
We appreciate the continued support of the Board of Trustees of the Masonry Institute of America, Ron
Bennett, Chairman, Doug Williams, Jim Hensley, Sr., Frank Smith, Ken Tejeda, Rennie Tejeda, Bobby Williams,
Jim Smith, Steve Winegardner and Julie Salazar who have given their full cooperation to see that this publication
has been successful and a benefit for the masonry industry.
xvi MASONRY DESIGN MANUAL
MASONRY INSTITUTE
OF AMERICA
The Masonry Institute of America, founded in 1957 under the name of Masonry Research, is a promotional,
technical research organization established to improve and extend the use of masonry. The Masonry Institute of
America is supported by the California mason contractors through labor management contracts between the
unions and contractors.
The Masonry Institute of America is active in California promoting new ideas and masonry work, improving
national and local building codes, conducting research projects, presenting design, construction and inspection
seminars and publishing technical and non-technical papers, all for the purpose of improving the masonry
industry.
The Masonry Institute of America does not engage in the practice of architectural or engineering design or
construction nor does it sell masonry materials.
INTERNATIONAL CODE
COUNCIL
Since the early 1900s, the United States had been served by three sets of building codes developed by three
separate model code groups: Building Officials and Code Administrators International, Inc. (BOCA), International
Conference of Building Officials (ICBO), and Southern Building Code Congress International, Inc. (SBCCI). These
codes were extremely effective and responsive to regional needs. But, in 1994, recognizing the urgent need for
a single set of codes that would serve national needs, the three groups united to form the International Code
Council (ICC) with the express purpose of creating and developing one master set of comprehensive, coordi-
nated, design and construction codes.
Substantial advantages are inherent to this single set of codes. Code enforcement officials, architects,
engineers, designers, and contractors throughout the United States can now work with a consistent set of
requirements. States and localities that currently write their own codes or amend the early model codes may
choose to adopt the International Codes without technical amendments, which encourages consistent code
enforcement and higher quality construction. Enhanced membership services are an additional benefit. All
issues and concerns of a regulatory nature now have a single forum for discussion, consideration, and resolution.
Whether the concern is disaster mitigation, energy conservation, accessibility, innovative technology, or fire
protection, the ICC offers a means of focusing national and international attention on these concerns.
These codes provide a comprehensive package for adoption and use in the 21st Century.
The ICC also offers unmatched technical, educational, and informational products and services in support
of the International Codes, with more than 300 highly qualified staff members at 16 offices throughout the United
States and Latin America. Products and services readily available to code users include:
Working under its three sponsoring organizations, the American Concrete Institute (ACI), the American
Society of Civil Engineers (ASCE), and The Masonry Society (TMS), the Committee has been charged with
developing and maintaining consensus standards suitable for adoption into model building codes. Since The
Masonry Society has received ANSI accreditation, TMS has become the lead sponsor in the production of the
MSJC.
As ACI moves into its second century of progress through knowledge, it has retained the same basic
mission: develop, share, and disseminate the knowledge and information needed to utilize concrete to its fullest
potential.
To provide essential value to members, their careers, partners and the public, ASCE develops leadership,
advances technology, advocates lifelong learning, and promotes the profession.
INTRODUCTION
INTRODUCTION
Masonry structures have been constructed since
the earliest days of mankind, not only for homes but
also for works of beauty and grandeur. Stone was the
first masonry unit and was used for primitive but
breathtaking structures such as the 4000 year old
Stonehenge ring on England’ s Salisbury Plains.
Additionally, structures such as the stone pyramids Masonry has been used worldwide to construct
of Yucatan and Teotihuacan, Mexico, demonstrate the impressive structures such as St. Basil’
s Cathedral in
skill of ancient masons. Moscow.
The Pyramid of the Sun, built in the 2nd century A.D. The Taj Mahal in Agra, India, demonstrates unique
dominates the landscape of the ancient city of monumental characteristics of stone.
Teotihuacan in Mexico.
In the United States, masonry is used from Maine strength concrete block walls are 12 in. (305 mm) thick
to Hawaii and has been the primary material for building CMU for the bottom three floors and 8 in. (203 mm)
construction from the 18th to the 21st centuries. thick CMU for the upper 10 floors.
The introduction of reinforced masonry allowed wall Another oustanding example of reinforced load
thickness to be decreased dramatically and provided a bearing masonry is the 28 story Excalibur Hotel in Las
rational method to design walls to resist dynamic lateral Vegas, Nevada. This large high-rise complex consists
loads from winds and earthquakes. of four buildings each containing 1008 hotel rooms.
The load bearing walls for the complex required
An excellent example of the benefits of reinforced masonry with a specified compressive strength of
masonry is the 13 story Pasadena Hilton Hotel in 4,000 psi at the base of the wall.
California, completed in 1971. The load bearing, high
MASONRY DESIGN MANUAL
28 Story Excalibur Hotel, Las Vegas, Nevada. Walt Disney Concert Hall, Los Angeles, California.
CHAPTER
1
CLAY BRICK UNITS
The term “ brick”means manufactured units of In addition to machine manufactured brick, brick
either clay or shale, dried and fired. Any of the other can be hand formed. Hand formed bricks are unique
materials that are made into brick units, such as and the compressive strength characteristics are less
concrete, sand lime, and so forth, must use a than for the machine extruded brick, but still
descriptive adjective relating to the brick material, for conforming to the requirements of the ASTM Standard
example, concrete brick. (ASTM C 62, Standard Specification for Building Brick
(Solid Masonry Units Made From Clay or Shale)).
Brick’ s main ingredient is clay. While clay is one Hand formation of brick, however, allows for additional
of the most abundant materials on the earth, the clays array of shapes and characteristics not created
used in brick production must possess certain through machine manufactured brick.
properties and characteristics. There must be
plasticity, which permits units to be shaped or molded 1.1.1 REINFORCED BRICK –AN OVERVIEW
when mixed with water. Furthermore, units must have
sufficient strength to maintain shape after forming. Brick is intrinsically strong in compression but
Also, when subjected to elevated temperatures during weak in tension. Through the centuries, brick has been
the firing process, the clay particles must fuse together the building material of choice since it “ stacked”well
to create a durable unit. and has high compressive strength properties. While
brick masonry is one of the oldest forms of building
Mechanization and automation have been growing construction, it wasn’ t until recent history that the
in the brick plant during the past fifty years. Heavy weakness of brick in tension was overcome by
machinery is used to mine and transform the clay into combining the brick (strong in compression) with a
dense, precise units. The bricks are fired in continuous material that is strong in tension –steel. In other words,
tunnel kilns at carefully controlled temperatures to the brick was reinforced with the steel. Again, in the
produce the best unit that can be made from the clay modern sense, reinforced brick masonry in the United
used. The brick is inspected, sorted and packaged States is a relatively new type of construction, requiring
2 MASONRY DESIGN MANUAL
new design procedures and construction methods. About 70 years ago, the concept of reinforced
These methods have been developed during the past masonry was advanced in California primarily as an
70 years from experimental investigations, through the outgrowth of the need to improve the resistance of
construction of thousands of buildings which have existing brick masonry structures to earthquake forces.
demonstrated the practicability and economy of Since that time, reinforced masonry has not only been
construction and whose performances have confirmed successfully used on the West Coast of the United
the soundness of the principles of design and through States, but also throughout the world.
ongoing research focused at practical ways to reinforce
old brick masonry and limits on the performance ability
of new masonry construction.
Reinforced brick masonry consists of brick
masonry in which steel reinforcement is embedded in
the brick masonry system. The reinforcement is placed
so that the masonry, as a whole, will have greatly
increased resistance to forces which produced tensile,
shearing and compressive stresses. The principles
of reinforced brick masonry design are the same as
those commonly accepted for reinforced concrete and
similar design formulae are used.
Arch brick
Building Brick is a brick unit for building purposes FIGURE 1.5 Types of solid clay brick.
not especially treated for texture or color and also
called Common Brick, and conforms to ASTM C 62.
Thin Brick are clay units specifically designed for
adhered veneer application. Maximum thickness as
Face Brick or Facing Brick are brick made for
defined in ASTM C 1088 is 13/4 in. (44.5 mm), and are
facing purposes, often treated to produce desired
commonly between 1/2 and 1 in. (12.7 and 25.4 mm)
surface texture. They are made of selected clays, or
thick. Thin brick can also be manufactured in special
treated, to produce desired color and conform to ASTM
shapes, such as corner units.
C 216.
31/2 21/2
111/2 111/2
Jumbo Norman
Solid shell Double shell Cored shell
hollow hollow hollow
brick units brick units brick units
Sailor Soldier
FIGURE 1.7
Stack Bond
Typical brick orientation.
American Bond
Running Bond, 1/2 Bond
The durabili ty of brick is indi cated by Absorption should not be confused with Initial Rate
measurements of water absorption, saturation of Absorption (IRA) as explained in Section 1.2.12.
coefficient and compressive strength as described in
ASTM C 62, Section 4.2. Durability can be evaluated
1.2.6 COMPRESSIVE STRENGTH
by a pass-fail grading according to the test method
contained in ASTM C 67, Standard Test Methods for Based on the gross area, extruded brick generally
Sampling and Testing Brick and Structural Clay Tile, yield a higher compressive strength and lower absorp-
Section 8. tion than those using the dry-press or soft-mud
process. Additionally, higher firing temperatures in the
1.2.4 FREEZING AND THAWING kiln usually produce higher compressive strength brick.
If firing temperatures are too high, however, brick will
The criteria listed in Table 1.2 shows that Grade melt in the kiln. Therefore, the default specification
SW brick is limited in the absorption and saturation should be for extruded and kiln-fired brick.
coefficient, which means that there will be less moisture
present within the unit when subjected to the freeze-
thaw cycle. Similarly, Grade MW brick is limited to a
less stringent value for the absorption and saturation
coefficient and there is no limit placed on Grade NW
brick.
1
Table 1.2 Common Brick or Building Brick Durability Physical Requirements
Minim um Com pressive Maximum W ater Absorption Maxim um
Strength (brick flatwise), by 5-h Saturation
2
Gross Area, psi (MPa) Boiling, % Coefficient
Designation Average of 5 Individual Average of 5 Individual Average of 5 Individual
brick brick brick
G rade SW 3000 (20.7) 2500 (17.2) 17.0 20.0 0.78 0.80
Grade MW 2500 (17.2) 2200 (15.2) 22.0 25.0 0.88 0.90
3
G rade NW 1500 (10.3) 1250 (8.6) no lim it no lim it no limit no lim it
1
Based on ASTM C 62, C 216 or C 652.
2
The saturation coefficient, or C/B Ratio, is the ratio of absorption by 24-hour submersion in cold water to that after 5-hour
submersion in boiling water.
3
Does not apply for ASTM C 216 and C 652.
CLAY BRICK UNITS 7
The compressive strength of brick produced in
the United States normally exceeds the compressive
22/3” 21/4” 31/5”
strengths associated with concrete. Compressive
strength of brick can be greater than 20,000 psi (137.9 8” 35/ ”- 31/ ” 8” 8”
4” 8 2 4”
MPa), and most brick exceed compressive strength Standard Modular Standard Engineer Modular
of 5,000 psi (34.5 MPa), therefore, the minimum
compressive strengths of Table 1.2 are rarely a 23/4”- 25/8”
22/3” 31/5”
problem. Higher required strengths, such as for
heavier loads in multi-story construction or other 95/8” 12” 12”
3” 4” 4”
specific requirements for loading or weathering, must
be expressly specified. King Size Norman Engineer Norman
1.2.8 SIZE
Bricks are manufactured in a variety of different
sizes and shapes. Some of the modular brick
terminology listed includes Modular, Engineer Modular, Round Cap Ridge Cap
Roman, Norman and Utility brick.
1.2.9 CORING
1
Table 1.3 Permissible Variations in Dimensions
Specified Dimension, inches (mm) Maximum Permissible Variations from Specified
Dimension, + or -, inches (mm)
3
Up to 3 (76) incl. /32 (2.4)
1
Over 3 to 4 (76 to 102) incl. /8 (3.2)
3
Over 4 to 6 (102 to 152) incl. /16 (4.8)
1
Over 6 to 8 (152 to 203) incl. /4 (6.4)
5
Over 8 to 12 (203 to 305) incl. /16 (7.9)
3
Over 12 to 16 (305 to 406) incl. /8 (9.5)
1
ASTM C 62, Table 3
CLAY BRICK UNITS 9
3. When bricks with an excessively high I.R.A. on the inside of the brick will dry out. By drying out,
are tapped into place, the bond between the the water will migrate to the surface of the brick. This
brick and the mortar may be disturbed. migration has the potential to bring with it soluble salts
and create efflorescence. Precautions must be taken
4. An extremely high I.R.A. will have the tendency to minimize efflorescence and achieve the optimum
to rapidly dry the mortar so that the proper in masonry strength and aesthetics.
water retention for high strength and good
bond may not be achieved.
1.2.13 VISUAL INSPECTION
5. Brick with an extremely low I.R.A. do not draw The building brick delivered to the site shall, by
water from the mortar and the brick tend to visual inspection, conform with the requirements as
float. This can be compensated for by using specified by the purchaser if special requirements have
a mortar with low water retention. been stated in addition to ASTM, or comply with the
sample or samples supplied to the purchaser. For
6. A good bond between the mortar and brick is customary construction, minor flaws, indentations,
preferred to achieve the desired resistance to surface cracks and minor chips resulting from the
water penetration through the masonry customary handling of building brick shall generally
system. not be deemed grounds for rejection in the wall.
Burned clay units shall have an initial rate of Unl ess otherwise agreed upon by the
absorption not exceeding 0.035 ounce per square inch manufacturer or the seller, building bricks, when
(1.6 L/m 2) during a period of one minute. The delivered to the job site, shall contain not less than
International Building Code references MSJC Code 95% whole brick according to ASTM C 62.
for requirements. Article 3.2 C.2 of the 2005 MSJC
Specification requires that the initial absorption rate shall 1.2.14 EFFLORESCENCE
not exceed one gram per minute per square inch.
Requirements are the same as 30 grams per minute Efflorescence is caused by the leaching of soluble
per 30 square inches (194 cm2). Wetting of the brick salts from within the masonry to form a whitish surface
prior to laying achieves a lower I.R.A. which may be deposit. In order to minimize efflorescence, proper
necessary for the stated reasons. planning is necessary. The key is to minimize the
migration of water into the masonry. Attention should
The wetting of the brick is preferred 3 hours to 24 be given to the following:
hours prior to laying, but may be done immediately
before laying if time is a constraint. Figure 1.14 shows 1. Proper design of construction details such as
different water content conditions of the brick unit. providing dampproof course at proper levels
Surface dry is the ideal condition where the center is and at correct locations.
wet and the surface is slightly damp.
2. Prevention of water entering into the body of
Surface dry is the ideal condition for creating the the brickwork. Special attention should be
maximum bond strength. However, the excess water given to properly tooled mortar joints.
1
Table 1.5 Face Brick Durability Physical Requirements
Min. Compressive Strength Maximum Water Absorption Maximum
2
(brick flatwise), psi (MPa) by 5-hour Boiling, % Saturation Coefficient
Designation Average of Individual Average of Individual Average of Individual
5 brick 5 brick 5 brick
Grade SW 3000 (20.7) 2500 (17.2) 17.0 20.0 0.78 0.80
Grade MW 2500 (17.2) 2200 (15.2) 22.0 25.0 0.88 0.90
1
Based on ASTM C 216, Table 1
2
The saturation coefficient on C/B Ratio, is the ratio of absorption by 24-hour submersion in cold water to that after 5-hour
submersion in boiling water.
CLAY BRICK UNITS 11
boiling water for 5 hours. The amount of water absorbed 1.3.8 SIZE
is recorded as a percentage of total weight of the dry
unit. The resultant ratio of the two is the cold water/ Brick manufacturers may name brick rather than
boiling water (C/B) ratio, or the saturation coefficient. list by size. Most manufacturers follow the terminology
and sizes for brick defined for modular brick such as
The C/B ratio is considered a measure of durability Standard Modular, Economy, Norman and Roman (see
from the concept that water, which easily enters the Figure 1.11).
brick, will have room to expand under freezing
conditions. Standard practice in the masonry industry is to
define unit size in the order of width x height x length.
The best practice is to specify brick size in the order
When the weathering index, as shown in Figure
of width x height x length, and then by name. The
1.10, is less than 50, the absorption and saturation
designer should verify that the size and orientation of
coefficients may be waived in accordance with ASTM
the brick is compatible with the project drawings.
C 216.
Manufacturers frequently make special brick to
Absorption should not be confused with Initial Rate satisfy project requirements.
of Absorption (IRA).
1.3.9 CORING
1.3.6 COMPRESSION STRENGTH
Unless specified, the brick may or may not be
Similar to common brick, compressive strength cored at the option of the manufacturer or possibly
of 2,500 psi (17.2 MPa) for Grade MW brick and 3,000 the option of the contractor. Normally, a manufacturer
psi (20.7 MPa) for Grade SW brick is required (Table will provide a majority of the brick with cored holes
1.5). Higher required strengths, such as for heavier which permit a more uniform firing, saves on material,
loads in multi-story construction or other specific and is beneficial in the trasportation process.
requirements for loading or weathering, must be
expressly specified. The net cross sectional area in any plane parallel
to the surface containing the cores shall not be less
1.3.7 COLOR AND TEXTURE than 75% of the gross cross sectional area, and no
core hole may be closer than 3/4 in. (19.1 mm) to any
Color and texture are “ strong points”of face brick, exterior face of the brick.
since both attributes are exposed. Face brick can be
manufactured in a variety of textures ranging from 1.3.10 FROGGING
smooth to combed face. According to ASTM C 216, a
majority of the brick will have one end-texture and color One bearing edge of the face brick may contain a
similar to the face. If the project requires two ends or frog not exceeding 3/8 in. (9.5 mm) deep and the frog
two faces to be of finished texture and color, the may not be closer than 3/4 in. (19.1 mm) to any exterior
requirement must be clearly stated by the specifier. face of the brick. As with building brick, deep frogs
are permitted, with the same restrictions.
Face brick is available in many appealing textures
and finishes while enjoying relative freedom from At one time, nearly all brick in the United States
cracks, warpage or exposed particles. were molded with the signature of the manufacturer
embossed in the frog, but most brick are now
There is a wide range of available colors for face manufactured using the extruded process and frogs
brick. The colors may range from off-white to jet black, are only occasionally seen in new brick.
with intermediate colors of yellow, orange, red, blue,
purple, brown and gray. Some projects require a 1.3.11 TOLERANCES
consistent color, while others specify a ‘ blend’ , or
The dimension tolerances for face brick are
combination of colors.
contained in Table 1.6 and the distortion tolerances
are in Table 1.7. The dimensional tolerances require
Brick samples of at least four units should be
greater precision than that for common or building brick
approved for texture and color prior to the start of the
and type FBX brick require greater precision than FBS
project.
brick.
12 MASONRY DESIGN MANUAL
1
Table 1.7 Face Brick Tolerances on Distortion
Maximum Dimension, in. (mm) Maximum Permissible Distortion, in. (mm)
Type FBX Type FBS
1 3
8 (203) and under /16 (1.6) /32 (2.4)
3 1
Over 8 - 12 (203 - 305) incl. /32 (2.4) /8 (3.2)
1 5
Over 12 - 16 (304 - 406) incl. /8 (3.2) /32 (4.0)
1
ASTM C 216, Table 4
In order to determine dimensional tolerances, a body of the brick. In other words, it may not be merely
sample of ten brick representing the extreme range is a surface color unless specifically agreed upon by the
selected and compared to the allowable variation in purchaser and seller. The standard also states that
Table 1.6, Column A. From the sample of ten brick, the brick shall be free of cracks and other defects that
the average size is determined and the permissible will interfere with the proper setting of the brick or that
dimensional tolerances from the average size is listed will impair the strength or the permanence of the
in Table 1.6, Column B. construction.
1.3.12 INITIAL RATE OF ABSORPTION (I. R. A.) Except for chips, FBX brick shall be free of cracks
and other imperfections when viewed from a distance
The I.R.A. requirements for face brick are the same of 15 ft (4.6 m), and FBS or FBA brick shall not exhibit
as common or building brick. these imperfections when viewed from a distance of
20 ft (6.1 m).
1.3.13 VISUAL INSPECTION This visual guideline applies to the installed
ASTM C 216 states that all brick units shall be materials, and can also be used for workmanship
made of clay, shale or fireclay materials and that any acceptance of the complete brick installation. Table
admixtures or colors used in giving a special color to 1.8 list the ASTM acceptable extent of chipping.
a unit shall be uniformly distributed through the entire
14 MASONRY DESIGN MANUAL
Table 1.8 Maximum Permissible Extent of Chippage from Edges and Corners of Finished Face or
1
Faces onto the Surface
Percentage Chippage in in. (mm) Percentage Chippage in in. (mm)
Type
allowed2 in from allowed2 in from
Edge Corner Edge Corner
1 1 1 3 1 1
/8 - /4 /4 - /8 0 - /8 0 - /4
FBX 5% or less 95 to 100%
(3.2 - 6.4) (6.4 - 9.5) (0 - 3.2) (0 - 6.4)
3 1 5 3 1 1 3
FBS /4 - /16 /8 – /2 0 - /4 0 - /8
10% or less 90 to 100%
(Smooth) (6.4 - 7.9) (9.5 - 12.7) (0 - 6.4) (0 - 9.5)
FBS4 5
/16 - 7/16 1
/2 - 3/4 0 - 5/16 0 - 1/ 2
15% or less 85 to 100%
(Rough) (7.9 - 11.1) (12.7 - 19.1) (0 - 7.9) (0 - 12.7)
FBA to meet the designated sample or as specified by the purchaser, but not more restrictive than Type FBS (rough)
1
ASTM C 216, Table 2
2
Percentage of exposed brick allowed in the wall with chips measured the listed dimensions in from an edge or corner.
3
Smooth texture is the unbroken natural die finish.
4
Rough texture is the finish produced when the face is sanded, combed, scratched, or scarified or the die skin on the face is entirely
broken by mechanical means such as wire-cutting or wire-brushing.
3
Table 1.9 Hollow Brick Section Properties
Nominal width of Minimum solid Minimum cored Minimum end
units, in. (mm) face shell or double face shell or end web
1 2
thickness, in. shell thickness , thickness , in.
(mm) in. (mm) (mm)
3 3
3 & 4 (75 & 100) /4 (19) ---- /4 (19)
1
6 (150) 1 (25) 1 /2 (38) 1 (25)
1 1
8 (200) 1 /4 (32) 1 /2 (38) 1 (25)
3 5 1
10 (250) 1 /8 (35) 1 /8 (41) 1 /8 (30)
1 1
12 (300) 1 /2 (38) 2 (50) 1 /8 (30)
1
Cores greater than 1 in.2 (650 mm2) in cored shells shall be not less than 1/2 in. (13 mm) for any edge. Cores
not greater than 1 in.2 (650 mm2) in shells cored not more than 35% shall be not less than 3/8 in. (10 mm)
from any edge.
2
The thickness of webs shall not be less than 1/2 in. (13 mm) between cells, 3/8 in. (10 mm) between cells and
cores or 1/4 in. (6 mm) between cores.
3
Based on ASTM C 652, Table 2.
16 MASONRY DESIGN MANUAL
1
Table 1.10 Hollow Brick Tolerances on Dimensions
Permissible Variation, max.
Specified Dimensions
Type HBX Type HBS and HBB
1 3
3 (76) and under ± /16 (1.58) ± /32 (2.38)
3 1
Over 3 to 4 (102), incl. ± /32 (2.38) ± /8 (3.18)
1 3
Over 4 to 6 (152), incl. ± /8 (3.18) ± /16 (4.76)
5 1
Over 6 to 8 (204), incl. ± /32 (3.97) ± /4 (6.35)
7 5
Over 8 to 12 (306), incl. ± /32 (5.56) ± /16 (7.94)
9 3
Over 12 to 16 (408), incl. ± /32 (7.14) ± /8 (9.52)
1
ASTM C 652, Table 3
1
Table 1.11 Hollow Brick Tolerances on Distortion, in. (mm)
Permissible Distortion, max.
Dimension, max.
Type HBX Type HBS
1 3
8 (204) and under /16 (1.58) /32 (2.38)
3 1
Over 8 to 12, (306), incl. /32 (2.38) /8 (3.18)
1 5
Over 12 to 16 (408), incl. /8 (3.18) /32 (3.97)
1
ASTM C 652, Table 4
CHAPTER
2
CONCRETE MASONRY UNITS
Concrete masonry units are equally adaptable for for future additions to the structure. Color can also be
interior as well as exterior treatments; for appealing altered or enhanced by aging and erosion, sandblast-
space dividers and for attractive exterior terrace walls ing, or by the action of acid or detergent cleaners. A
and other enclosures. Many times a unit which can be sparkling white color can also be achieved with the use
readily made with the same pattern or treatment on of natural white sand and white cement.
both faces serves handsomely as both exterior and
interior finish wall material with added economic and The size of concrete masonry units is designated
aesthetic advantages. by width by height by length, in that order. The nominal
dimensions are typically 3/8 in. (9.5 mm) larger than the
Concrete masonry units can be installed in a actual unit dimensions, which allows for a 3/8 in. (9.5
multitude of pattern arrangements and combinations to mm) mortar joint while still keeping a standard module.
create an unending diversity of effects. The designer The most common nominal widths of concrete masonry
not only prefers to express ingenuity in development of units are 4 in. (102 mm), 6 in. (152 mm), 8 in. (203
the design, but also can very often obtain helpful mm), 10 in. (254 mm) and 12 in. (305 mm). The
suggestions or useful guidance through consultation common heights are 4 in. (102 mm) and 8 in. (203
with manufacturers’representatives or industry mm), except for concrete brick, which may be typically
professionals. One should not hesitate in availing such 22/3 in. (67.7 mm) high. The nominal length of concrete
expert technical knowledge. brick is commonly 8 in. (203 mm), but can be as long
as 12 in. (305 mm). Nominal block lengths are normally
Projecting or recessing a certain number of units 16 in. (406 mm).
can create a geometric pattern or design. Another
interesting variation consists in using units which are The weight of concrete masonry units varies.
only half the usual course height and occasionally Depending on the aggregates used, concrete masonry
projecting these units slightly beyond the face of the units are normally manufactured using concrete with
wall plane. Ground face units can be utilized to add densities ranging from 85 to 140 pounds per cubic foot
interest in the form of color and texture. (1362 to 2243 kg/m3). The lighter units provide more
fire resistance, have an improved noise reduction
Many of the fluted and ribbed units are designed coefficient and are more economical to place in the
so the vertical flutes or striations will appear in the wall. Heavier units occasionally provide increased
finished wall as unwavering continuous straight lines compressive strength, higher water penetration
for indefinite height, even when laid in regular running resistance and greater thermal storage capabilities.
bond wherein the joints alternate over the center of the Concrete masonry units are referred to as lightweight,
block unit in the courses above and below. The medium weight, or normal weight depending on the unit
continuity contributes to creation of the soaring density (see Table 2.1).
monolithic effect.
With any configuration or texture the designer Table 2.1 CMU Weight Classification
chooses, the overall effect will be influenced and Unit Weight, Classification
3
heightened by the play of lights and shadows, enhanced pcf (kg/m )
by control of colors and textures and by introducing Less than 105 (1680) Lightweight
contrasts. Curved surfaces will produce interesting 105 to 125
Medium weight
(1680 -2000)
shadows caused by broken surfaces. Vertical surfaces
125 and greater Normal weight or
can produce bold rugged effects.
(2000) Heavy weight
One of the many benefits of concrete masonry is
natural appearance. The color of natural sands and
aggregates render an earthy look of the masonry units. 2.2 PROPERTIES
Use of natural colors makes the structure appear to
Concrete Masonry Units can be either hollow or
belong to the environment. Different colors can be pro-
solid load-bearing in accordance with ASTM C 90
duced by using different aggregates or different natural
Standard Specification for Loadbearing Concrete
cements, or color can be changed by pigments or by
Masonry Units or hollow or solid non-loadbearing,
surface treatment. Occasionally, use of a transparent
conforming to ASTM C 129 Standard Specification for
sealer may be warranted. Use of natural materials,
Non-Loadbearing Concrete Masonry Units. Concrete
sands, cements and aggregates is recommended. This
brick should conform to ASTM C 55, Standard
will result in a more natural appearance with lower main-
Specification for Concrete Brick. There are many
tenance costs and can facilitate material duplication
different sizes and textures of concrete masonry units
to fit any application. There are precision units,
CONCRETE MASONRY UNITS 19
slumped, or adobe textured block, split-faced block,
Nominal length - less mortar joint
fluted block, ground faced block and special effect = Actual length
architectural units.
Actual width
support staff and offer valuable assistance to the A A
designer in the conceptual phase of the project.
Consultation with the manufacturers support staff is
invaluable assistance to the designer in the choice of
materials.
The industry standard modular concrete block is FIGURE 2.2 Industry standard modular block.
shown in Figure 2.1. The manufacturing process of the
concrete block causes the bottom of the block to have Table 2.2 Minimum Thickness of Face Shells
1
narrower thickness and sloped interior sides. This also and Webs
allows a larger surface for bedding of mortar as units Minimum Minimum
are laid in the wall. The sloped sides helps the block Nominal Specified Face Shell Web
slide out of its mold after it has cured. Figure 2.2 and Width Width Thickness Thickness
2
(in) (in) (in) (in)
Table 2.2 lists the minimum thickness of the shell and 5 3 3
webs. 4 3 /8 /4 /4
5
6 5 /8 1 1
5 1
Web 8 7 /8 1 /4 1
5 3 1
10 9 /8 1 /8 1 /8
Cell 5 1 1
12 11 /8 1 /2 1 /8
1
This table is to be used in combination with Figure 2.2
2
For solid grouted masonry construction, minimum face
shell thickness shall be not less than 5/8 in. (16 mm).
Face shell
Shapes of block include straight, radius and angled.
End
Web Standard colors are gray, tan and pink. Manufacturers
also have a wide variety of colors available on special
Cell
order.
Ears
2.2.2 METRIC
Many countries use the metric or Systems
Face shell International (SI) method of measurement. The United
States favors a conversion to the ‘ soft metric’ system
Concave end
for concrete block, which is maintaining the current size
of the unit and using metric nomenclature that is not
FIGURE 2.1 Industry standard modular block. rounded to size. A (US) standard nominal size concrete
20 MASONRY DESIGN MANUAL
block 8 in. wide by 4 in. high by 16 in. long is 194 mm For historical references, the widely used 1997
by 92 mm by 397 mm. Adding a typical 9 to 10 mm Uniform Building Code (UBC) Standard 21-4 was similar
mortar joint makes the US units slightly, but intolerably, to ASTM C 90, however Standard 21-4 did contain some
larger than the metric units. intentional differences relating to the concrete masonry
unit requirements. One of the differences is the
Adding a 10 mm mortar joint, the standard 190 x recognition of both Grade N and Grade S by Standard
90 x 390 metric block becomes 200 x 100 x 400 block 21-4. In addition to the Type I unit, which is the required
in metric (millimeter) units. unit for ASTM C 90, Standard 21-4 recognizes the Type
II unit.
In November, 1996, the Cox Bill, also known as the
Savings in Construction Act went into effect in the As a practical matter, there are very few block
United States. This bill gave designers and the industry manufactured that conform only to Type S specifica-
the flexibility to continue design and use of the English tions.
System of units for concrete block masonry. Even
though the dimensional difference of 8 in. (203 mm) Also, UBC Standard 21-4 specifically recognizes
and 200 mm is small, it is too great to be compensated slumped block units as a structural unit. The slump
by a 3/8 in. (9.5 mm) mortar joint. The cost to industry textured block is widely used in the Southwestern
to manufacture and stock two sets of units (English United States to duplicate the traditional adobe
and Metric) would be staggering. Since 1996 the use appearance.
of English Units has continued and will continue for the
foreseeable future. The amount of moisture a concrete unit absorbs
can affect its strength. Table 2.3 lists the strength and
In Chapter 16, there are conversion tables for values absorption requirements for concrete masonry.
of length, speed, area, weight or mass, volume, density,
force, pressure, energy and temperature from English The specified compression strength value that is
measurement to SI (metric) measurement. common for ASTM C 90 conforming units can be used
to verify a design strength (f’ m
) = 1,500 psi (10,342 kPa)
2.2.3 COMPRESSION STRENGTH for solid or partially grouted reinforced masonry walls.
The definition of f’m
is the design value used in masonry.
ASTM C 90, Standard Specification for Load- The actual compressive strength of the masonry system
bearing Concrete Masonry Units, requires that the must not be less than the design value of f’ . This
m
average compressive strength of 3 units, based on the value of 1,500 psi is not the compression strength of
net area of the unit, be at least 1,900 psi (13,100 kPa). the unit, it is the design value of the total masonry
In 1990, ASTM deleted the differentiation between Grade system.
N and Grade S concrete block and required all block
units under ASTM C 90 designation meet the higher, Table 2105.2.2.1.2 of the 2006 International Building
old Grade N, standard. Code (2006 IBC), lists verified compression strengths
Grade N units were defined as acceptable for of the masonry based on the compression strength of
exterior use above or below grade, whereas Grade S the concrete unit and the type of mortar used. The
units were limited to above grade exterior use provided strength of the grout should conform to ASTM C 476
the units are covered with a protective coating or not and the minimum compression strength of the grout
exposed to the weather. must equal or exceed f’ m
but not be less than 2,000 psi
(2006 IBC Section 2105.2.2.1.2).
1
Table 2.3 Strength and Absorption Requirements
Water Absorption, Max. (Avg. of 3 units) With
2 3
Compressive Strength , min. psi Oven-Dry Weight of Concrete. lb./ft
Average Net Area Weight Classification
Lightweight Medium Weight Normal Weight
Avg. of 3 Units Individual Unit
Less than 105 105 to Less than 125 125 or More
1900 1700 18 15 13
1
ASTM C 90, Table 2.
2
Higher compressive strengths may be specified where required by design. Consult with local suppliers to determine availability of
units of higher compressive strength.
CONCRETE MASONRY UNITS 21
For example, when a masonry wall is designed for 2.3.2 SPLIT FACED UNITS
a compression strength of 1,500 psi, the concrete
masonry units need to be 1,900 psi using Type S or M Split-faced units have an irregular surface
mortar. appearance. Two split faced units are manufactured
as one block and separated into two units by splitting
For high-rise load-bearing buildings, high cantilever the block (Figure 2.3). This provides an irregular
retaining walls, tall slender walls with an h/t ratio roughened texture on the face shell.
between 30 and 50, or heavily loaded members, the
strength of the concrete masonry unit may require more
than the basic minimum strength of ASTM C 90. When
high strength units are required, the units should be
specified as follows:
6 x 8 x 16 Standard 6 x 8 x 8 Half
16 x 8 x 6 C-Alternate 12 x 8 x 8 C-Alternate
ACCESSORY BLOCK
155/8”
15 /8”
5
15 /8”
5
75/8”
75/8” 75/8”
155/8” 155/8”
75/8” 75/8”
115/8” 115/8”
2” 1”
11/2” 2” 3”
1”
2.7 COMPONENT UNITS AND cavity between units (where the web of the standard
unit would normally be) and the void is filled with grout
SECTIONS (Figure 2.6). This system of creating walls allows the
designer to vary the width wall without having the block
A component masonry wall is a system of creating manufacturer make special block and permits different
concrete masonry walls by using the face shell pieces colors and textures on opposite faces of the wall.
of the block. The component units are held in place
through cross ties. Reinforcing bars are placed in the
115/8” 23/4”
235/8”
75/8” 235/8” 21/4”
Variable wall thickness
Reinforcing steel 513/16”
75/8”
12”
513/16”
Ties
21/4 x 8 x 12 x 24 21/4 x 8 x 24
Grout Outside Corner Return Standard Inside Face
cavity
21/4 x 8 x 24 21/4 x 8 x 12 x 24
Variable wall thickness Split Face Split Face Outside
Corner Return
The following figure shows some of the paving units Basketweave/Parquet Units and Pattern
available. Check local manufacturer for availability.
Varying the bond or joint pattern of a concrete FIGURE 2.7 Paving bond patterns.
masonry patio or walk can create a wide variety of
interesting and attractive designs.
CONCRETE MASONRY UNITS 33
2.9.1 SPECIFICATIONS
Facing material shall conform to ASTM C 744,
Standard Specification for Prefaced Concrete and
Calcium Silicate Masonry Units, with respect to
imperviousness, resistance to fading (chemical
Venus II Unit and Pattern resistance), opacity and tolerances on dimensions, and
when tested in accordance with ASTM E 84, Standard
Test Method for Surface Burning Characteristics of
Building Materials, shall have a flame spread index and
other fire characteristics in accordance with local
requirements. Units tested for shrinkage as per ASTM
C 426, Standard Test Method for Linear Drying Shrinkage
of Concrete Masonry Units, shall be free of crazing,
cracking and spalling. The facing shall return over ends
and edges of the block, forming a lip at least 1/16 in. (1.6
mm) thick, resulting in a 1/4 in. (6.4 mm) exposed mortar
joint. When tested for abrasion, the facing shall have a
wear factor not in excess of 130, in accordance with
ASTM C 501, Standard Test Method for Relative
Resistance to Wear of Unglazed Ceramic Tile by the
Taber Abraser.
At all times use reasonable and proper care in Double-glazed units, if available, permit construction
handling units to prevent marring or damaging faces, and finish of two-faced walls in a single operation. This
edges and corners. During erection, keep walls free of system should be used only when tight bed depth
excess mortar and, upon completion, clean walls with tolerance or second face alignment is not mandatory.
a masonry cleaning compound recommended by the
manufacturer. Structural glazed units offer many fire safety
advantages. Glazed units provide the same fire rating
2.9.2 MANUFACTURER’
S STANDARDS as concrete block. As with precision concrete block,
fire ratings of 1, 2, 3 and 4 hours can easily be achieved
Concrete units to be glazed shall be top grade units with structural glazed units, depending on wall
conforming to the latest revision of ASTM Specifications thickness and grouting requirements.
for Concrete Masonry Units.
Structural glazed units are often used where sanitary
Tolerances on dimensions shall be: conditions are a concern, such as kitchens and
hospitals. The impervious facing is easily cleaned and
1. Permissible variation in face dimensions from sanitized.
Standard: ______________ 1/16 in. (1.6 mm).
2. Permissible variation in bed depth dimensions As with any manufactured item, a minor variation
from Standard: _________ 1/16 in. (1.6 mm). in shade or color is to be expected. A wide range of
3. Maximum permissible face distortion: colors, including blue, green, yellow and brown are
_____________________ 1/16 in. (1.6 mm). available.
The color of the surface shall conform to an approved Laying of these units is performed in the same
sample consisting of f iv e stretcher units fully manner as for precision structural concrete block units.
representing the range of shade and color.
Stretcher Units
Glazed 1 Side
2 X 8 X 16 4 X 8 X 16 6 X 8 X 16 8 X 8 X 16
Glazed 2 Sides
4 X 8 X 16 6 X 8 X 16 8 X 8 X 16 8 X 8 X 16
2 X 8 X 16 4 X 8 X 16 6 X 8 X 16 8 X 8 X 16
2 X 8 X 16 4 X 8 X 16 2 X 8 X 16 4 X 8 X 16
Jamb
4 X 8 X 16 2 X 8 X 16 4 X 8 X 16
Cap
2 X 8 X 16 4 X 8 X 16 2 X 8 X 16 4 X 8 X 16
3
NATURAL STONE
This manner of heat and pressure forms dense Elastic - naturally cemented fragmental grains but
metamorphic rocks, differing widely from the igneous without interlocking or mosaic relation such as
or sedimentary types. When limestones or dolomites quartzite.
crystallize, they form a metamorphic rock commonly Grano Balstic - a granular mosaic texture in which
called marble. All calcareous (calcium based) rocks, the grains are tightly compacted, the minerals are
as well as some dolomitic and serpentine rocks that dominantly of equidimensional kinds and present
are able to be polished, are commercially called marbles. irregular mutual boundaries such as granite.
Natural patterns within the stone can be highly Table 3.2 list some common stone veneers used in
varied, and provide special features that make building the United States.
stone a unique material. In addition to the pattern, the
texture is varied, ranging from coarse fragments to fine
grains and crystalline structures. Texture also varies
with the hardness of minerals composing the stone.
As with any masonry product, the v arying Where the new stone is to be installed, a review is
characteristics of individual units enhance the beauty required prior to the stone installation to permit
of the finished product. If consistency in the final product adjustments of anchorage or thickness to be
is desired, natural stone may not be the correct material incorporated into the design of the facade area.
selection.
42 MASONRY DESIGN MANUAL
3.9.5 SANDSTONE
Sandstone is a sedimentary rock usually consisting
of quartz cemented with silica, iron oxide or calcium Block
carbonate. Sandstone has a wide range of colors, from
red to yellow to white, depending on the presence of
other minerals. Sandstone is easy to quarry and shape
due to its soft consistency. It is vulnerable to erosion
and deterioration from air pollution. Brownstone is a
variety of sandstone.
Sandstone is quarried primarily in New York, Ohio, FIGURE 3.4 A quarried block and a cut slab.
and Pennsylvania and formed from deposits of sand
(silicon dioxide). Two types of sandstone are
brownstone, typically used in wall construction, and
bluestone, principally for paving and wall copings.
1 2
43
21
1 2
3 4
1 2
FAA Federal Credit Union, Hawthorne, California. Soka University, Aliso Viejo, California.
CHAPTER
4
TERRA COTTA
It then goes in the form of slabs to the kilns, where cladding material on skeletal-framed structures. It
it is brought to a high heat, which burns out the sawdust served as an excellent cladding which architects
and fuses clay particles. appreciated for its fire safety, light weight and low cost,
as well as for its aesthetic appeal.
This process takes about forty-eight hours, and
produces in that period about one hundred and eighty Terra cotta can be molded into any designs or
tons of fireproof lumber. architectural shapes or colors needed. It is frequently
used for special ornamental work and architectural
It is next planed, tongued, grooved, or sawed into detail.
any desirable shapes.”
5
GLASS BLOCK
53/4”
Mortar
37/8”
6
REINFORCING STEEL
Reinforcing steel in masonry has been used 2. The minimum reinforcement protection.
extensively in the West since the 1930’ s, revitalizing
the masonry industry in earthquake prone areas. 3. The proper spacing of longitudinal and
Reinforcing steel extends the characteristics of ductility, transversal reinforcement.
toughness and energy absorption that is necessary in
structures subjected to the dynamic forces of 4. Sufficient anchorage of flexural and shear
earthquakes. reinforcing bars.
Reinforced masonry performs well because the 5. Adequate lapping of the reinforcing bars.
materials; steel, masonry units, grout, and mortar, work
together as a single structural unit. The temperature 6. Sufficient stirrups, metal plates, spirals, and
coefficient for steel, mortar, grout and the masonry units ties in order to provide confinement.
are very similar. This similarity of thermal coefficients
allows the different component materials to act together 7. Adequate grout coverage of the reinforcing steel.
through normal temperature ranges. Disruptive stresses
are not created at the interface between the steel and
the grout which would allow effective force transfer.
6.2 TYPES OF REINFORCEMENT
Structures subjected to severe lateral dynamic 6.2.1 REINFORCING BARS
loads, such as earthquakes, must be capable of
providing the necessary strength or energy absorbing For reinforced masonry construction, deformed bars
capacity and ductility to withstand these forces. range in size from #3 (3/8 in. [9.5 mm] diameter) to a
Reinforcing steel serves to resist the shear and tensile maximum size of #11 (13/8 in. [34.9 mm] diameter) as
forces generated by the dynamic loads. It can also required by 2005 MSJC Code, Section 1.13.2.1. The
provide sufficient ductility to the masonry structure so Strength Design Provisions of 2005 MSJC Code Section
that the structure can sustain load reversals beyond 3.3.3.1 limits the maximum size of reinforcement to a
the capability of plain, unreinforced masonry. #9 bar. This reinforcing steel must conform to ASTM A
615, A 706, A 767, A 775 or A 996 which specify the
In order for the reinforcing steel to provide adequate physical characteristics of the reinforcing steel.
ductility and strength, the reinforcing steel must be
designed and placed properly to provide a continuous ASTM A 615 and A 996 list the requirements for
load path throughout the structure. The designer must reinforcing steel manufactured from billet, rail and axle
pay special attention to reinforcing steel details to steel respectively. ASTM A 707, A 767 and A 775 are
ensure continuity. The following items must be provided: generally not applicable since they cover low alloy, zinc-
coated and epoxy-coated reinforcing steel which are
1. The proper size and amount of reinforcement seldom used in masonry construction.
which complies with the limited minimum and
maximum percentages of reinforcement and
other code requirements.
Table 6.1 Reinforcing Steel Bar Designations, Sizes and Weight (ASTM A 615 Chart)
2
Inch-Pound Bar Nominal Dimensions
Nominal Weight
Size Diameter Cross Sectional Area
1 lb./ft. (kg/m) 2 2
Designation (mm) in. (mm) in (mm )
#3 (10) 0.376 (.560) 0.375 (9.5) 0.11 (71)
#4 (13) 0.668 (.994) 0.500 (12.7) 0.20 (129)
#5 (16) 1.043 (1.552) 0.625 (15.9) 0.31 (199)
#6 (19) 1.502 (2.235) 0.750 (19.1) 0.44 (284)
#7 (22) 2.044 (3.042) 0.875 (22.2) 0.60 (387)
#8 (25) 2.670 (3.973) 1.000 (25.4) 0.79 (510)
#9 (29) 3.400 (5.060) 1.128 (28.7) 1.00 (645)
#10 (32) 4.303 (6.404) 1.270 (32.3) 1.27 (819)
#11 (36) 5.313 (7.907) 1.410 (35.8) 1.56 (1006)
1
Bar numbers are based on the number of eighths of an inch included in the nominal diameter of the bars (bar numbers
approximate the number of millimeters of the nominal diameter of the bar).
2
The nominal dimensions of a deformed bar are equivalent to those of a plain round bar having the same weight (mass) per
foot (meter) as the deformed bar.
REINFORCING STEEL 57
Reinforcing steel may be either Grade 40, with a 1st—Producing Mill (usually an initial)
minimum yield strength of 40,000 psi (276 MPa) or
2nd—Bar Size Number (#3 through #18/#10 thru
Grade 60 minimum with a minimum yield strength of
#55)
60,000 psi (414 MPa). Grade 60 steel is furnished in
all sizes, while Grade 40 steel bars are normally 3rd—Type of steel (Type A for Axle, W for Low Alloy,
available in #3, #4, #5 and #6 sizes. If Grade 40 steel S for Billet, R for Rail.)
is required, special note must be made to ensure
4th—Grade of reinforcement; for Grade 60 steel
delivery. A designer should verify that the grades and
(grade is shown as a marked 60 or One (1) grade mark
sizes of reinforcement are available in the geographic
line (Figure 6.2). The grade mark line is smaller and
area of a given project.
between the two main longitudinal ribs which are on
opposite sides of all U.S. made bars. For grade 75
The identification marks are shown in Figures 6.2
steel, there are two grade mark lines.
and 6.3 and described in descending order:
H
Initial of H H
Initial of H
producing mill producing mill
Grade line (One line only) Grade line (One line only)
H Initial of H Initial of
producing mill producing mill
FIGURE 6.4 Heavily reinforced masonry wall. FIGURE 6.7 Column reinforcement.
FIGURE 6.10 Truss type joint reinforcement. FIGURE 6.13 Truss type joint reinforcement
tying brick veneer face to concrete masonry wall.
FIGURE 6.15 Ladder type joint reinforcement tying two wythes of a brick wall together.
Glass block
Masonry mortar
Joint reinforcement
7
VENEER
“3. Building Trades. a facing of a certain material Yet the veneer still provides both the beauty and
applied to a different one or to a type of construction durability of masonry. Additionally, the veneer also
not ordinarily associated with it, as a facing of brick increases the fire resistance, noise resistance and water
applied to a frame house.” resistance over a non-veneered wall.
“6. to face or cover (an object) with a material that The use of v eneer is by no means a new
is more desirable as a surface material than the basic development. In fact, limestone veneer covered some
material of the object” of the pyramids in Egypt and pieces of it can still be
seen at the top of the Great Pyramid, Cheops.
“8. to give a superficially valuable or pleasing
appearance to.”
“
VENEER - A facing attached to a wall for the
purpose of providing ornamentation, protection or
insulation, but not counted as adding strength to the
wall.”
Sheathing board
Mortar net
Concrete
masonry unit
Flashing
Brick veneer
Flashing
Non-combustible
veneer support
FIGURE 7.5 Typical seismic veneer anchors. FIGURE 7.6 Typical non-seismic ties.
66 MASONRY DESIGN MANUAL
New Zealand, which is an active seismic region, As shown in Figure 7.7, this tie is excellent for
uses a significant amount of masonry veneer. An transferring the lateral loads to the backup system while
effective and popular brick anchor in that region is the allowing for relative movement in the horizontal and
La Palle’ flexible tie connection. vertical directions with the backup system.
8
MORTAR AND GROUT
Table 8.1 Mortar Types-Classes of In accordance with the MSJC Code, Type M or S
Construction mortar must be used for the lateral load resisting system
Mortar Type Construction Suitability in Seismic Design Categories D and E. This
Designation requirement provides additional strength and bond in
M Masonry subjected to high compressive structures located in high seismic risk areas.
loads, severe frost action, or high
lateral loads from earth pressures, 8.1.1.2 SPECIFYING MORTAR
hurricane winds, or earthquakes.
Structures below or against grade such
Field mortar should always be specified by type
as retaining walls.
based on proportion specif ications. Property
S Structures requiring high flexural bond specifications are intended for laboratory prepared
strength and subject to compressive mortar.
and lateral loads.
1
Table 8.4 Compressive Strength of Mortar
Mortar 2" dia. x 4" high 2" (50.8 mm)
Type (50.8 x 102 mm) Cube Specimen
Cylinder psi (MPa)
Lateral Lateral
Specimen psi compression compression
(MPa)
M 2100 (14.5) 2500 (17.2)
S 1500 (10.3) 1800 (12.4)
N 625 (4.3) 750 (5.2)
1 P P
Lesser periods of time for testing may be used provided the
relation between early tested strength and the 28 day strength 2 2
of the mortar is established.
1
Table 8.5 Mortar Proportions for Unit Masonry
Proportion by Volume (cementitious materials)
Portland Mortar Cement Masonry Cement Aggregate Ratio
Hydrated Measured in Damp
Mortar Type Cement or
Lime or Lime Loose Conditions
Blended
M S N M S N Putty
Cement
1
M 1 - - - - - - /4
1 1
Cement- S 1 - - - - - - over /4 to /2
1 1
lime N 1 - - - - - - over /2 to 1 /4
1 1
O 1 - - - - - - over 1 /4 to 2 /2
1
M 1 - - 1 - - - - Not less than 2 /4 and
M - 1 - - - - - - not more than 3 times
1
Mortar S /2 - - 1 - - - - the sum of the separate
cement S - - 1 - - - - - volumes of cementitious
N - - - 1 - - - - materials
O - - - 1 - - - -
M 1 - - - - - 1 -
M - - - - 1 - - -
1
Masonry S /2 - - - - - 1 -
cement S - - - - - 1 - -
N - - - - - - 1 -
O - - - - - - 1 -
1
2006 IBC Table 2103.8(1)
Masonry cements can be proprietary with specific 3. Improves the water retentivity or board life of
ingredients not disclosed, therefore, the MSJC Code the mortar.
imposes the seismic restriction.
8.1.2.3 MORTAR SAND
8.1.2.1.3 MORTAR CEMENTS
For masonry mortar, sand aggregate is required to
Mortar cement is also a Portland cement based conform to ASTM C 144, Standard Specification for
material which meets the requirements of ASTM C 1329, Aggregate for Masonry Mortar.
Standard Specification for Mortar Cement. Mortar
cement may be used for mortar in all Seismic Design Sand used in preparing mortar can be natural or
Categories. manufactured. Manufactured sand is obtained by
crushing stone, gravel or air-cooled blast-furnace slag.
Unlike masonry cement, mortar cement was It is characterized by sharp and angular particles
developed specifically for use in seismic application, producing mortars with workability properties different
therefore, the lateral load-restriction does not apply. than mortars made with natural sand which generally
Manufacturers of this material were deliberate in have round, smooth particles.
developing a cement that would satisfy the requirements
of structural engineers and building officials. Sand gradation is most often specified or defined
by referring to a standard sieve analysis. For mortar,
8.1.2.2 HYDRATED LIME sand is graded within the limits given in Table 8.7.
Hydrated lime is manufactured from calcining Table 8.7 Sand for Masonry Mortar
1
Hydrated lime can be used without delay making it Sand should be free of injurious amounts of
more convenient to use than quicklime. deleterious substances and organic impurities. ASTM
C 144 provides guidelines on determining if an aggregate
Hydrated lime must conform to ASTM C 207, has excessive impurities.
Standard Specification for Hydrated Lime for Masonry
Purposes, and is available in Types S, SA, N and NA. Concrete sand should not be used in mortar since
Types S and N hydrated limes contain no air entraining the maximum grain size is too large. Additionally, the
admixtures. Types NA and SA limes provide more fine particles which are needed in masonry sand have
entrained air in the mortar than allowed by ASTM and often been washed out of concrete sand thus creating
therefore may not be used. Additionally, unhydrated harsh, coarse sand unsuitable for mortar. Mortar sand
oxides are not controlled in Type N or NA limes thus needs at least 5% fines which pass the No. 200 sieve
making only Type S hydrated lime suitable for masonry to aid plasticity, workability and water retention of mortar.
mortar.
72 MASONRY DESIGN MANUAL
Mortar sand, like all mortar ingredients, should be Mixing time of the mortar should be long enough
stored in a level, dry, clean place. Ideally, it should be for a uniform, even color to be obtained and should be
located near the mixer so it can be measured and added the same length of time for every mortar batch.
with minimum handling and can be kept from Additionally the mixing sequence should be the same
contamination by harmful substances. for each batch. MSJC Specification requires that mortar
be mixed between 3 and 5 minutes.
8.1.2.4 WATER
Retempering of colored mortar should be kept to a
Water must be clean and free of deleterious amounts minimum to reduce the variations in color of the mortar.
of acids, alkalies or organic materials. Water containing For best results, colored mortar should not be
soluble salts such as potassium and sodium sulfates retempered.
should be avoided since these salts can contribute to
efflorescence. Finally, the source, manufacturer and amount of
each ingredient should remain the same for all colored
8.1.2.5 ADMIXTURES mortar on a project in an effort to obtain uniform color
throughout. Prepackaged mineral color additives that
can be added to the mix based on full sacks of Portland
There are numerous admixtures which may be
cement will minimize mortar color variation.
added to mortar to affect its properties. One of these,
called a retarding set admixture, delays the set and
stiffening of mortar. The set may be delayed for 36 8.1.3 MIXING
hours or more if desired.
8.1.3.1 MEASUREMENT OF MORTAR MATERIALS
There are also admixtures used to replace lime.
These may be an air entraining chemical or pulverized The method of measuring materials for mortar must
fire clay or bentonite clay to provide workability. Care be such that the specified proportions of the mortar
should be taken with these admixtures since the bond materials are controlled and accurately maintained. A
between the mortar and the masonry units may be reasonable method to control the mortar proportions is
affected. to use full sacks of cement per batch and to use
measuring boxes for the proper amounts of lime and
The use of any admixtures should be accepted by sand. Dry preblended mixes are also available.
the architect or engineer and must also be acceptable
to the building official. 8.1.3.2 JOB SITE MORTAR MIX
8.1.3.5 RETEMPERING
Collar joint
8.2 GROUT
Grout is a mixture of Portland cement, aggregates
and water mixed to fluid consistency so that it will have
a slump of 8 to 11 in. (203 to 279 mm). The MSJC
Specification states that grout slump of 11 in. (279 mm)
e. Squeezed Joint - Provides for a rustic, high is permissible. Grout is placed in the cores or cells of
texture appearance. Satisfactory indoors and hollow masonry units or between the wythes of solid
exterior fences. Not recommended for exterior units to bind the reinforcing steel and the masonry into
building walls, for no weather resistance is created a structural system.
because the mortar is not compressed back into
the joint. Also the top ledge allows for pooling of
the water.
8.2.1.1 FINE GROUT and the top of the grout, with the cone removed, is the
slump. Both types of grout, fine and coarse, must
Fine grout is used where the grout space is small, contain enough water to provide a slump of 8 to 11
narrow or too congested with reinforcing steel. When inches (203 to 279 mm).
fine grout is used, there must be a clearance of 1/4 in.
(6.4 mm) or more between the reinforcing steel and the
masonry unit. 4”
8 “to 11”Slump
1 part Portland cement
12”Cone
21/2 to 3 parts sand
Water for a slump of 8 to 11 in. (203 to 279 mm)
2. Plasticizer Admixtures - Used to obtain the high The required minimum compressive strength of
slump required for grout without the use of excess 2,000 psi (13,800 kPa) is needed in order to achieve
water. By adding a plasticizer to a 4 in. (102 mm) adequate bond between the grout, the reinforcing steel
slump grout mix, an 8 to 11 in. (203 to 279 mm) and the masonry unit. This minimum value is
slump can be achieved. satisfactory for masonry construction in which the
specified design strength, f’
m
, equals 1,500 psi (10,300
3. Cement Replacement Admixtures - Used to kPa), and the masonry unit has a compressive strength
decrease the amount of cement in grout without of 1900 psi (13,100 kPa). The compressive strength of
adversely affecting the compressive and bond the grout in concrete masonry construction should be
strengths of the grout. Types C and F fly ash are 1.25 to 1.33 times the design strength of the masonry
by far the most common cement replacement assemblage, f’ m
.
admixtures. Typically, 15 to 20% of the Portland
cement by weight is replaced with fly ash as long IBC Section 2105.2.2.1.1(3) states that grout used
as the strength characteristics are maintained. in clay masonry conform to the proportion requirements
of ASTM C 476, Table 1, or meet the minimum design
strength requirements (f’ m
), but in no case shall the
4. Accelerator Admixtures - Used in cold weather strength of grout be less than 2,000 psi (13.8 MPa)
construction to reduce the time that the wall must
be protected from freezing. Accelerators decrease If grout tests are required, the following schedule is
the setting time of grout and speed up its strength suggested.
gain. Accelerators also increase the heat of
hydration preventing the grout from freezing under 1. At the start of grouting operations, take one test
most circumstances. per day for the first three days. The tests should
consist of three specimens which are made as
Careful consideration must be given prior to the outlined in Section 8.2.2.5 and in accordance with
use of all admixtures since an admixture may adversely ASTM C 1019, Standard Test Method for Sampling
affect certain grout properties while improving the and Testing Grout.
intended properties. Admixtures containing chloride
salts and antifreeze liquids may not be used despite 2. After the initial three tests, specimens for
the apparent benefits, since chlorides cause corrosion continuing quality control should be taken at least
of the reinforcing steel. Admixtures can significantly once each week. Additionally, specimens should
reduce the compressive and bond strengths of the grout. be taken more frequently for every 25 cubic yards
(19 m3) of grout, or for every 2,500 square feet
Similarly, care should be taken when using two or (232 m2) of wall, whichever comes first.
more admixtures in a grout mix since the combination
of admixtures can produce unexpected results. Under 8.2.2.5 T ESTING GROUT STRENGTH
all circumstances, information regarding laboratory and
field performance of an admixture should be obtained In order to determine the compressive strength of
from the manufacturer prior to use in a grout. The MSJC grout, specimens are made that will represent the cured
Specification contains the same intent, but is somewhat grout in the wall. The specimen is made in a mold
more general, requiring that admixtures must be consisting of masonry units identical to those being
acceptable. used in construction and at the same moisture condition
as those units being laid. The units are arranged to
Admixtures that rely on air entrainment are a code form a space approximately 3 to 4 in. (76.2 to 102 mm)
concern. ASTM C 476 refers to ASTM C 260 for square and twice as high as it is wide (Figures 8.10
conformance of air entraining admixtures, whereas, and 8.11).
historically, the UBC stated that tests must be
conducted for mortar and grout compliance for the To prevent the grout from bonding to the masonry
admixtures. units, the space is lined with permeable paper or a
porous separator which allows any excess water to be
8.2.2.4 GROUT STRENGTH REQUIREMENTS absorbed into the units. A paper towel does an excellent
job.
ASTM 476 requires that the minimum grout
compressive strength shall be 2,000 psi (13,800 kPa) The representative samples of grout are placed in
at 28 days. molds which will remain undisturbed for 48 hours (ASTM
C 1019, Section 6.1). The grout samples are placed in
molds, in two layers, puddled and kept damp and
MORTAR AND GROUT 79
Though lifts may not exceed 5 feet (1.5 m) in height,
Line units with an
a grout pour may consist of several lifts. For example,
absorbent material if the wall is built 20 feet (6.1 m) high, the total grout
Tape pour could be the entire 20 feet (6.1 m). For this
situation, the contractor could place the grout in 4 lifts
of 5 feet (1.5 m) each.
The total height of masonry to be grouted prior to FIGURE 8.12 Ties for two wythe walls.
the erection of additional masonry is called a grout pour.
Grout is placed in increments called lifts. A grout lift is
the height of grout placed in a single continuous
operation.
80 MASONRY DESIGN MANUAL
The maximum horizontal spacing between ties is height must be consolidated by means of a mechanical
36 in. (914 mm) and the maximum vertical spacing is vibrator. The grout must also be reconsolidated after
24 in. (610 mm). Additional ties are provided around the excess water is absorbed by the units to close any
opening larger than 16 in. (406 mm) in either dimension. voids due to the water lost.
The ties are placed within 12 in. (305 mm) of the opening
and have a maximum spacing of 36 in. (914 mm). Horizontal construction joints should be formed
between grout pours by stopping the grout pour 11/2 in.
(38.1 mm) below the top of the masonry. Where bond
beams occur, the joints may be reduced to 1/2 in. (12.7
mm) deep to allow sufficient grout above the horizontal
reinforcing steel.
After lower section is grouted,
Section AA
1”
1”
5’ maximum
Grout in 5’ lifts to top of pour.
Wall tie #9 wire spaced:
Vertically for
Cleanout opening running bond - 16” o.c.
at all vertical
reinforcing bars. Vertically for stack
5’ maximum
bond - 12” o.c.
A A
32” maximum spacing of cleanout
openings for solid grouted walls; 48”
maximum for partially grouted walls. Cleanout opening.
Seal prior to grouting
but after inspection.
FIGURE 8.14 Maximum spacing of cleanout
holes.
Provide vertical Reconsolidate the grout after the ex-
grout dam every cess water has been absorbed into
Two wythe masonry walls must be tied together 30’ maximum the masonry units.
with wire ties or joint reinforcement to prevent blowouts
and bulging.
can be placed m), are constructed by laying masonry units in the grout
in one lift
space for the full height of the wall.
Stop grout pour (not
grout lift) 11/2 below At the bottom of the wall the footing may be covered
top of masonry units
with a layer of loose sand to prevent mortar droppings
5’ max.
Cleanout opening.
Seal prior to grouting
but after inspection
Controlled Placement of Grout with Barriers • no intermediate reinforced bond beams are
placed between the top and the bottom of the
pour height.
FIGURE 8.17 Grout barriers.
8.2.2.7 CONSOLIDATION
CHAPTER
9
BRICK MASONRY
CONSTRUCTION
In chapter one, clay brick, as a material, was 9.1.1 BRICK MASONRY BOND PATTERNS
presented. In this chapter, brick design and construction
will be given in detail. Such topics will include the Bond patterns such as English or Flemish, or
importance of the brick pattern, types of loading, variations of these, may be used to create patterns in
empirical design, environmental design and structural the face of a wall. Pattern refers to the change or varied
design. Detailing issues will also be addressed. As arrangement of brick, texture or color used in the face.
mentioned in the preface of this book, the material is Using the same structural bond, it may be possible to
for the non-engineering disciplines of the building secure several patterns. Also, patterns may be
industry. However, basic knowledge of the issues and produced by the method of handling the mortar joint or
terminology of the engineer is assumed. There are by projecting or recessing certain units from the plane
many books and other publications available that give of the wall, thus creating a distinctive wall texture that
an in-depth discussion of the engineering of brick. A is not solely dependent upon the texture of the individual
significant amount of information in this chapter is brick.
derived from the Brick Industry Association’ s Technical
Notes. The designer is encouraged to use the most Five essential structural bonds are typically used
current information by using the sources available in to create typical patterns: Running Bond, Common or
the Reference Section. American Bond, Flemish Bond, English Bond, and
Stack Bond. With variations of the color and texture of
the brick and of the joint types and color, an unlimited
9.1 AESTHETIC DESIGN number of patterns can be developed through the use
of these bonds.
Brick masonry and shaped stones are possibly the
oldest manufactured building materials. They are also,
Running Bond - The running bond consists of all
when used well, two of the most beautiful and enduring
stretcher units with units overlapping in adjacent courses
building elements. Brick, for example, is a building
and is the simplest of the basic bond patterns. Running
material of bewildering flexibility, and is used to solve
bond is further identified by the length of overlap, such
an infinite number of design problems. When brick is
as half bond or third bond. The running bond is utilized
used with imagination and care, with good design and
extensively in cavity wall construction and veneered
with attention to color and texture, it can create a
walls of brick, and often in facing tile walls where the
structure that is both aesthetically appealing and
bonding may be achieved by extra width stretcher tile.
functional.
Because of the importance of the running bond
The most visual and important characteristics of
pattern to structural integrity, the MSJC Code formally
brick and brickwork are how it will be assembled and
defines a running bond pattern as:
the pattern the layout creates, or the bond pattern. The
bond pattern gives a statement to the architectural
“The placement of masonry units such that the
quality, but it is extremely important to the structural
head joints in successive courses are horizontally
quality.
offset at least one-quarter the unit length.”
84 MASONRY DESIGN MANUAL
FIGURE 9.5 Garden wall bond with units in Stack Bond This is a weak bond, typically used
dovetail fashion. for decorative effect on veneers. All vertical joints are
aligned, and steel joint reinforcement must be installed.
English Bond This pattern is made f rom Since all vertical joints are aligned there is no overlapping
alternating courses of headers and stretchers on each of units. Normally this pattern is bonded to the backing
course. The headers are centered on the stretchers with rigid metal ties, but when 8 in. (203 mm) boundary
and the joints between the stretchers in all the courses units are available, they may be used. In stack bond
are lined up vertically. Snap headers are used in dimensionally accurate masonry units must be used if
courses which are not structural bonding courses. the vertical alignment of the head joints is to be
maintained.
As design requirements change, new sizes may 9.1.2.2 COORDINATION OF MASONRY UNITS
be added and less popular sizes discontinued. Also,
Figure 9.10 shows the way in which the coordination
not all manufacturers produce all the typical sizes.
of different modular masonry units can be achieved.
Therefore, the designer should consult current
manufacturer or regional catalogs for available sizes in
The exterior face brick are shown with 3/8 in. (9.5
any locality before proceeding with a design.
mm) joints and are backed up with units, such as
structural clay tile designed for use with 1/2 in. (12.7
9.1.2.1 DIMENSIONS OF MODULAR UNITS
mm) joints. The inside facing of ceramic glazed units
As illustrated in Figure 9.9, the dimensions of are laid in 1/4 in. (6.4 mm) joints. As indicated in the
modular units are “ nominal”and are equal to the enlargements, the full coordination between units is
specified dimension (i) plus the thickness of the mortar apparent. The thickness of the vertical joints between
joint (j) with which the unit is designed to be laid. The the different types of units is the average of the joint
specified length of a unit, for example, whose nominal thickness used with each unit.
length is 12 in. (305 mm) is 111/2 in. (292 mm) if the
units were designed to be installed with 1/2 in. (12.7
mm) mortar joints, or 115/8 in. (295 mm) for 3/8 in. (9.5 12”
mm) mortar joints. /4” 1/8”
1
/8”
/4”1/4”
3
/8”
/2”
/4”
1
1
/8”
1
Thickness = T
1
Nominal Wall
Thickness = t
Actual Wall
Cavity 1
/2 j
/16”
3 1
/4”
7
/16”
/4”1/4”
/16”
w
/2”
/8”
/16”
3
1
/2 j
1
Plan
3
3
1
1 1 1
j i /2 j /2 j w /2 j
Cavity
H h
3
/16”wall ties
j Wall Sections
L 16”o.c. vertically
W
36”o.c. horizontally
Elevation Section
Lower case letters indicate actual dimensions. 9.1.2.3 INITIAL DESIGN CONSIDERATIONS
A 4 in. (102 mm) modular grid should be established
FIGURE 9.9 Modular unit dimensions. as a reference system for the three dimensional
elements of plan and structure, but no part of the plan
Face brick are normally laid with either 3/8 in. (9.5 should be forced to fall on the grid, nor should any
mm) or 1/2 in. (12.7 mm) thick mortar joints, however dimension be forced into multiples of 4 in. (102 mm).
some products, such as ceramic glazed brick or Economics can be realized in construction costs
structural clay facing tile, are designed for 1/4 in. (6.4 through the use of modular dimensions, thus minimizing
mm) thick mortar joints. field cutting brick units.
The standard dimensions of a single unit may vary 9.1.2.4 GRID LOCATIONS OF MASONRY WALLS
from the specified dimensions by no more than the
permissible tolerances for variation in dimensions Figure 9.11 shows grid locations of mortar joints in
included in the applicable ASTM Standard. walls constructed with various modular units when the
walls are centered between grid lines.
Traditionally, brick masonry was made of natural Textural flexibility is given by mortar joints.
earth colored brick and either white or gray mortar. Although, only the concave, V-shaped, and weathered
Revisions to the manufacturing process and suitable joints are recommended for exterior use due to moisture
pigments now provide an almost limitless color pallet concerns, it is surprising how the use of these joints
from which a designer may choose. will modify the appearance of a wall. Since moisture
penetration is not a consideration in interior masonry,
Variation of colors can be accomplished by more dramatic joint profiles, such as raked or extruded
changing the color of the units or mortar. To create joints, can be used to create interesting textures and
different effects, mortar color can be used to contrast shadows. The size of the joint, of course, provides
or blend with the brick . Greater contrast between mortar many additional possibilities.
and brick enhances the separation of the units, creating
a more ornate surface which appears to contain more The combination of brick and mortar creates many
texture. As the viewing distance increases color variation textures, which is further expanded with imaginative
changes. Small patterns are lost and larger ones bond patterns and by projecting and recessing brick
dominate as the area is viewed from farther away. units. Brick masonry is renowned for the textural effects
created with corbels, racking and dentils. When
Varying hues of the same color may be thoughtful attention to texture is given, the facade of
accomplished due to the materials and manufacturing the building can easily be altered from ultra-modern to
methods for brick. The bricks, when laid, create a rustic.
variegated pattern of color which cannot be achieved
with any other building material. Brick which appear
to have little variation in color can be used when a
uniform color is desired.
BRICK MASONRY CONSTRUCTION 89
9.1.6 SCALE For larger projects, rational design typically result in a
material cost savings over empirical design .
The most important architectural aspect of a building
is the scale. The dimension of the building naturally A rational or engineering design of structures
has the greatest influence on scale, but architectural considers the presence of loads, the interaction of
features and materials are important factors. Features elements and the amount of material present to resist
such as long slender colonnades, for example, make those loads. Basic assumptions concerning perfor-
even the most modest size building appear large. mance of materials are made. A significant amount of
masonry is designed based on the following three
The scale of a building is perceived, but controllable. principles:
Based on comparative affirmation it is a judgment of
size by the observer. Studies show that two identical 1. Normalize force (stress) and normalized
objects have a different perception under different deflection (strain) are directly related to each
lighting conditions. The object with brighter lighting will other by a proportion (Hooke’ s Law),
appear larger. Also, given two equal length lines, one
horizontal and one vertical, the vertical line appears 2. Cross-sections which are straight and form a
longer. Furthermore, highly ornate areas reduce scale, plane, before loading, remain straight and form
whereas plain areas increase scale. Comparative a plane after loading (no warping), and
objects must be present to give scale since size is
relative. 3. Masonry (bri ck, m ortar, grout, and
reinf orcement) works t ogether as one
Brick is the human-scale building element by homogeneous system.
tradition. Perhaps this is one of the reasons brick
masonry is so popular, as it gives a human scale to 9.2.1 LOADS
structures. The combination of darker colors and
horizontal lines reduces the scale of a building. To Imposed loads govern the sizes of structural
create flat, stretching ranch homes, Frank Lloyd Wright members. Building codes and standards traditionally
made extensive use of long, thin brick. The comparison prescribe the value and combinations of loads.
of the relatively small size of individual units to the large Structures and members must be designed to resist
building elements can give the elements an exaggerated the most unfavorable effect of load placement and
large scale. Architects can make use of smaller brick combination. Vertical loads are either dead loads or
units and mortar joints that can be used to mislead the live loads; common horizontal loads are wind,
viewer. The use of oversized units modify the learned hydrostatic and seismic loads.
comparison of scale and makes the element appear
smaller. 9.2.1.1 DEAD LOADS
Dead loads are long term stationary forces which
9.2 DESIGN LOADS include the self-weight of the structure and the weight
of permanent equipment and machinery, such as; walls,
All structures must be designed to support their roofs, stairways, partitions and fixed HVAC or service
own weight along with any superimposed forces, such equipment. Dead loads are computed from known
as the dead loads from other materials, live loads, wind material weights and their respective sizes. Additionally,
pressures, seismic forces and earth pressures. These the 1997 Uniform Building Code Section 1606.2 required
vertical and lateral loads may be of short duration such a uniformly distributed dead load of 20 psf (0.96 kN/m2)
as those from wind or earthquake, or they may be of where wall partitions are to be used. However, the 2006
longer duration such as the dead loads of machinery International Building Code, Section 1607.5, now
and equipment. Proper design must consider all classifies this 15 psf wall partition loading as a live
possible applied forces along with the interaction of these load. This double classification is brought on by the
forces on the structure. nature of the wall partition load. If the partitions are
present, they are usually in place for a long time and
Empirical or rational methods can be used in the the partitions are positively attached to the structure,
design of brick masonry structures. The successful thus becoming a part of the dead load mass for seismic
performance of previously constructed buildings are forces and long term creep (deflections). However, if
determined by empirical methods and are often used the partitions are not present, then the dead load is not
on smaller projects. Based on engineering principles, present to help hold the building down during wind and
rational methods are developed from the analysis of seismic events (i.e. resist over-turning) and the partition
test results, interaction of members and load distribution. loading should be considered as live loading. The caveat
90 MASONRY DESIGN MANUAL
in the code should not be followed blindly and a designer 9.2.1.5 HYDROSTATIC LOADS
should be given leeway to exercise judgment. In either
case, dead load vs. live load, both require uniformly Loads due to confined liquids or soils in contact
distributed dead load of 15 pounds per square foot (0.74 with the member are hydrostatic loads. The most
kN/m2) when partitions are used and the minimum common example of a hydrostatic load imposed on
specified live load is less than 80 psf. ASCE 7-05 also masonry would be liquid saturated soil behind a retaining
requires a minimum design dead load of 15 pounds per wall.
square foot (0.74 kN/m2) for framed partitions using 2 x
4 wood studs, plastered two sides. 9.2.1.6 MATERIAL PROPERTY LOADS
Due to changes in temperature and moisture
9.2.1.2 LIVE LOADS
content construction materials expand and contract.
Live loads are short duration forces which are Stresses are developed in the material if these
variable in magnitude and location. Examples of live movements are restrained. Differential (very small)
load items include people, furniture, rain and snow. movement between adjacent materials causes stress.
The behavior of each material and the interaction of
The 2006 IBC, Chapter 16, addresses these live materials must be examined to consider these
loadings. Table 1607.1 of the IBC is a comprehensive additional stresses.
live load list based on the use and occupancy of the
structure.
9.3 LOAD DISTRIBUTION
9.2.1.3 WIND LOADS Wind loads and external lateral forces on a wall
Wind loads exert a pressure and a suction on the are horizontal loads which transmit the forces to
exposed building surfaces and are particularly important horizontal and vertical supports. Vertical loads exert a
in high-rise construction. Factors such as height of force that is transmitted through the floors, columns,
the structure, gust factors, exposure, wind speeds and beams or walls and ultimately into the ground.
importance designation of the structure are included in
the design for wind loads. Wind forces overturning of Due to non-uniform loading, the effect of torsion or
the structure must also be considered. twisting of the structure must be taken into account.
All loads are transmitted through the foundation and
9.2.1.4 SEISMIC (EARTHQUAKE) LOADS into the ground in one way or another.
Load
9.4.1 COMPRESSIVE STRESS
Tension
Masonry is the assemblage of masonry units,
mortar and grout. The strength of a completed masonry
wall is based on all three of these working together.
Compression
Quality materials used in the construction process Flashing is a thin impervious membrane, installed
will improve water penetration resistance in brick at specific locations in a masonry wall system. Water
masonry. When water passes through a brick wall, it that penetrates the exterior wythe gravitates to the base
also passes through voids and separations or cracks of the wall panel and flashing collects the water and
between the brick units and the mortar. Under normal directs the moisture to the exterior through weep holes.
conditions and exposures, large amounts of water do Flashing is essential in providing water drainage in
not pass directly through the brick and mortar. Highly barrier wall systems.
absorbent clay masonry units will absorb water but do
not contribute to the flow of water through the wall. 2005 MSJC Code, Chapter 6, requires flashing and
all construction documents should specify the type of
The extent of bond between the brick and the mortar flashing and show its exact location. In brick masonry
is a key item in resistance to rain penetration in properly walls various types of flashing materials may be used.
built brick masonry. Extent of bond is defined as the Typically, flashing materials are formed from sheet
area of contact between the interface of the brick and metals, bituminous membranes or plastics. Flashing
the mortar surfaces. On the other hand, bond strength directly affects how a masonry wall performs and the
is a measure of the adhesion between the masonry selection is largely determined by cost and suitability.
unit and mortar. High bond strength between brick and To avoid leaking in the brick masonry walls, superior
mortar may not necessarily result in an extent of bond quality materials should be selected since replacement
that would provide high resistance to rain penetration. in the event of failure will be expensive.
Higher extent of bond results in increased water
penetration resistance of brick masonry. Extent of bond Many types of materials are available for flashing,
between the clay masonry unit and mortar selected however, not all materials are recommended. The
can be increased by: following is a list of flashing materials with various
recommendations.
1. Using Portland cement-lime mortar.
Copper is an excellent flashing material,
2. The cement content of the mortar should be in durable and available in special, pre-formed shapes.
the range of 1:1/4 to 1:1, cement-lime. Typical copper flashing is made from 10 to 20 oz.
sheet copper.
3. Mix ing m ortar f or compatibil ity with
workmanship. This means using maximum Plastic flashings are durable, resilient
amounts of water and retempering as materials, which are highly resistant to corrosion.
necessary. The ability to retemper is based on Performance records of the material should be
many f actors including the ambient air evaluated and where possible, test data to ensure
temperature.
satisfactory performance because the chemical
compositions of plastics vary widely. Typical
4. Applying pressure when laying brick units.
thickness of plastic flashing is 20 mil. to 60 mil.
5. The Initial Rate of Absorption (IRA) of the clay Stainless steel is an excellent flashing
masonry unit when laid should be less than material. It is impervious to moisture and resists
30g/min/30 in.2. For high absorption units, this chemicals well. The minimum thickness should
may be obtained by prewetting the units. be at least 0.01 in. (0.25 mm).
Effectiveness of bond between the mortar and clay Combination flashings, such as metal foil,
masonry unit may be reduced by: glass fiber reinforcement, copper and plastic, were
developed to utilize different materials to produce a
1. Increasing the mortar air content beyond 12%. moderately priced flashing with good properties.
For the various flashings available, manufacturers’
2. Low (< 60%) water retentively of the mortar. literature should be consulted.
3. Smooth (die skin) texture of the bed surface. Asp halt-impregnated felt is not
recommended as a material to be used for flashing
4. Using brick with heavily sanded bed surfaces. in masonry construction. During installation, it can
be easily damaged and in many cases, turns brittle
and can degrade with time.
BRICK MASONRY CONSTRUCTION 95
Aluminum should not be used as a flashing Flashing at tops of walls limits the amount of
material in brick masonry construction. The caustic moisture entering the wall. Flashing at the base of a
alkalis present in mortar will attack aluminum. wall diverts moisture to the outside of the wall. To divert
the water to the exterior, continuous flashing must be
Lead is susceptible to corrosion in mortar. Lead
placed above grade at the base of walls. Base flashing
should not be used as a flashing material in brick
prevents water from rising up into the wall system due
masonry.
to capillary action. When the designer has determined
the elevation for placing base flashing in the wall
The location of flashing is as important as the
according to plans, care should be taken so flashing is
material. Moisture that enters a wall gradually travels
not installed below grade.
downward. Proper design requires flashing at shelf
angles, heads of openings, window sills, spandrels,
Flashing should be placed under all sills and turned
wall bases, projections, tops of walls, recesses, and
up at the ends to form dams. Special flashing
roofs. The locations noted above are either tops,
considerations may be required for soffits and deep
bottoms or horizontal interruptions of walls.
reveals.
Wall ties
Flashing
Sealant
Weep holes
Metal anchor
15° min.
Flashing turned up Concrete or
beyond end of sill stone sill
1 in. (25 mm) min.
Flashing
Weep holes
Wall ties
Flashing
Sealant
Weep holes
Wood or
15° min.
steel frame
Weep holes
1 in. (25 mm) min.
Flashing
Flashing
Flashing should be installed at the top of all
openings. The flashing should be placed directly on
Weep holes top of the lintels and turned up at the ends to form
dams.
Coping
1 in. min.
W aterproof
sheathing Ties Elastic
Grout sealant
Steel stud
Flashing
back-up
Flashing
Flashing
Rigid
Steel angle insulation 2 in. min. air
Weep holes space
Sealant
Weep holes @
24”o.c. Flashing and counterflashing
Shims Roofing
Sealant Sheathing
Face of Purlin anchor
beam or Sealant
slab back-up
Clear for
vertical
movement or Joist hanger
provide
Ledger with anchor bolts as required
compressible
for vertical and horizontal forces
material
Bond beam or chord reinforced
as required for lateral loads
FIGURE 9.22 Shelf angle anchored to beam
or slab. FIGURE 9.24 Masonry cap flashing detail.
Projections and recesses provide a surface to Roof penetrations must be designed and installed
collect water. They should be sloped away from the with great care to avoid moisture penetration. Flashing
wall to drain and have flashing as close to the sloped design depends upon the type of roofing used.
surface as possible. Counterflashing should extend through the outside
wythe and overlap the roof flashing a minimum of 4 in.
(102 mm).
BRICK MASONRY CONSTRUCTION 97
Metal cap
All flashing should extend beyond the face of the
wall to form a drip. To ensure that any collected water
completely exits the wall system, flashing must extend
Roof membrane
through the wall. Flashing, which ends behind the
Roofing exterior face of the wall may allow water to re-enter the
Sheathing wall around and under the flashing.
Joist anchor to wall a positive
connection
Flashing around corners should be continuous. The
pieces of flashing, to achieve this continuity, may need
to be cut, lapped 6 in. (152 mm) and sealed to conform
to the shape of the structure. Flashing should be sealed
Joist hanger
when it is necessary to cut, puncture or interrupt the
Ledger with anchor bolts as required flashing.
for vertical and horizontal forces
Bond beam or chord reinforced as A layer of gravel a few inches deep or material
required for lateral loads
specifically designed to catch mortar droppings on top
of flashing in the cavity will aid in preventing mortar
FIGURE 9.25 Metal coping detail. droppings from falling directly upon the flashing and
clogging the weep holes. Rounded gravel about 3/8 in.
There are other considerations regarding installation (9.5 mm) in size will avoid blocking the weep holes and
of flashing which the designer must address in addition puncturing the flashing. A bed of mortar conforming to
to specific location information. the curve of the flashing should be placed under the
flashing for extra support of the gravel bed.
Typically, flashing is not available in one long,
continuous sheet. Therefore, pieces should be lapped
at least 6 in. (152 mm) and the laps sealed with mastic
or an adhesive compatible with the flashing material.
FIGURE 9.26 End dam detail. Flashing influences the force necessary to cause
sliding of masonry on its support. For masonry on
In order to direct moisture to the building exterior, concrete, the static friction coefficient is approximately
flashing must be higher on the inside of the wall than 0.59 for in-plane loads and 0.86 for out-of-plane loads.
the outside. The inside edge should be fixed to the When plastic flashing is used, these values are reduced
backing or embedded in a reglet in concrete or the by approximately 15%. Paper-backed copper flashing
mortar joint of the interior masonry wythe. The change lowers the coefficient of static friction to 0.43 in-plane
in height of the flashing should be at least 8 in. (203 and out-of-plane to 0.45. Masonry on steel gives a
mm).
98 MASONRY DESIGN MANUAL
static friction coefficient of 0.58 in-plane and out-of-plane moisture which may lead to spalling of the brick through
loads. Plastic flashing increases this coefficient by successive freeze-thaw cycles or surface efflorescence.
approximately 18% while paper-backed copper flashing When moisture tries to move through the coating,
reduces this coefficient by approximately 27%. clouding or whitening of the coating may occur. The
water vapor permeance of the coating must be close to
9.6.6 WEEP HOLES that of the brickwork for proper performance.
Weep holes must be provided immediately above There is no recognized standard set of tests to
the flashing in order to properly drain water collected evaluate coating suitability for exterior brick masonry.
on the flashing. Weep holes can be formed by open ASTM E 514, Standard Test Method for Water
head joints, a removable rope or rod, a wick or drainage Penetration and Leakage Through Masonry, can be
tube. The least dimension of weep holes should be 1/4 used to compare the effectiveness of a water repellent
in. (6.4 mm), although 2005 MSJC Code permits weep coating by testing uncoated and coated walls.
holes as small as 3/16 in. (4.8 mm). Weep holes should
be spaced no further apart than 24 in. (610 mm) on Clear water repellents will not eliminate water
center horizontally even though 2005 MSJC Code allows penetration in all cases and other factors must be
weep holes to be spaced up to 33 in. (838 mm) apart. considered, such as:
The maximum spacing should be reduced to 16 in. (406
mm) where a wick material is used as the weep hole. 1. The majority of cracks or incompletely filled
joints cannot be closed by coatings.
9.6.7 VENTS
Two benefits provided by air vents in the exterior 2. Coatings will not completely stop staining and
wythe of a drainage wall are: air flow across the backside efflorescence or may cover efflorescence
of the brick wythe which aids in the evaporation of sufficiently to prevent its removal.
moisture and the equalized pressure in the cavity which
reduces water sucked into the cavity. 3. On areas already coated, successiv e
applications of water repellent coatings may
W hen the exterior wythe is coated with an not be possible.
impermeable surface such as glazed brick, air vents
are essential. A careful and thorough inspection should be made
of the areas involved prior to considering any application
The vents should be placed at the top and bottom to masonry walls. This inspection should determine
of cavities. Vents spacing should not exceed 24 in. the condition and suitability of caps and copings,
(610 mm) on center horizontally. At the base of the flashing, weep holes, caulking or sealant joints, mortar
cavity, non-wicked weep holes may serve as vents. joint conditions and general execution of details.
Frequently this type of examination will identify the
source of the problem and prevent further consideration
9.6.8 COATINGS of water repellent coatings and their associated risks.
Clear exterior masonry wall coatings, which reduce
the amount of water entering the wall, fall into several 9.6.9 EFFLORESCENCE
broad material groups: silicones, silanes, siloxanes,
gum waxes, acrylics, resins, rosins, paraffins, oils, Efflorescence is a white, powdery deposit of water-
polymers and various combinations. Typically, these soluble salts left on the surface of masonry as the water
materials are available in two types of solutions: water- evaporates. The principal issue of efflorescence is the
based solutions and solv ent-based solutions. objectionable appearance on the brick surface. Even
Environmental considerations severely limit the use of though an efflorescence problem is complex, it is not
solvent-based solutions. difficult to remove and usually is not harmful to the brick
masonry.
Coatings resist water differently and they are often
grouped together. The broadest groups of coatings are Efflorescence occurs when water-soluble salts in
those which form a protective skin and those which solution are present somewhere in the wall and are
change the angle of contact of water from suction to brought to the surface of the masonry and deposited
repellency. Generally, the second group, made up of there by evaporation. The salt solution may migrate to
penetrating materials such as silanes and siloxanes, the surface of the wall between the mortar and units,
gives better performance with fewer problems than film through the mortar, or the masonry units.
forming coatings. The film forming coatings may trap
BRICK MASONRY CONSTRUCTION 99
There are certain conditions which must exist in stone, precast concrete, or other similar material.
order for efflorescence to occur. These materials may contribute to efflorescence
on the face of adjacent brickwork.
• Soluble salts must be present within or in contact Brick - Soluble salts may exist within the brick
with the masonry assembly. due to the composition of the raw materials and
the high temperatures associated with the brick
• There also must be a source of water in contact manufacturing process. If sulfates are present in
with the salts for a sufficient length of time to permit the raw materials, additives, such as barium
the salts to dissolve. carbonate, are used to immobilize and render the
sulfates insoluble.
• There must be migration of salt solutions to the
surface in an environment which allows evaporation. The potential for brick units to effloresce may be
assessed by the efflorescence test described in
The salt crystals can form within the bodies of the ASTM C 67, Standard Test Methods for Sampling
units under certain circumstances. The pressure may and Testing Brick and Structural Clay Tile. ASTM
cause cracking and distress to the masonry when this Standards C 216, C 652, C 902 and C 1088 require
occurs. These conditions can occur when high vapor that the ASTM C 67 rating for efflorescence be ‘
not
resistant coatings are used. effloresced’
.
The most common salts found in efflorescence are Hydrated Lime - Lime does not generally
sulf ate and carbonate compounds of sodium, contribute to efflorescence. However, a cleaning
potassium, calcium, magnesium and aluminum. solution containing hydrochloric acid can react with
Common sources of soluble salts include mortar, rain- lime to produce soluble calcium chloride which can
water, ground water, concrete masonry, concrete, brick migrate to the surface.
or other sources, or from chemical reactions of these
materials. It is often erroneously assumed to be the Sand - Sands with soluble alkali sulfates will cause
fault of the brick since efflorescence appears on the efflorescence unless the sulfates are removed. This
face of the brick. A detailed description of some of the contamination may include: sea water, soil runoff,
most common sources of the salts is given below. plant life and decomposed organic compounds.
Sands commonly available and used in mortar
Backing - Masonry materials used as backing or should be cleaned and washed.
inner wythes of masonry walls may contain large
quantities of soluble salts. If sufficient water is There are other outside sources of soluble salts
present to dissolve the salts and pathways are that may contribute to efflorescence in addition to the
provided for the solution to reach the exterior surface masonry materials. Various types of sources are
these units may contribute to efflorescence on the admixtures, calcium chloride used as an accelerator,
face of the wall. Condensation within the inner ground water and fertilizers. Chemically reacting with
wythe is a common source of water. masonry ingredients, cleaning materials or acid rain
may cause efflorescence.
Trim - Building trim, such as caps, coping, sills,
lintels, or keystones can be natural stone, cast
100 MASONRY DESIGN MANUAL
If masonry could be constructed to contain no This deflection may result in movement of the supporting
water-soluble salts, or if no water penetrated the member. This movement can cause additional stresses
masonry, efflorescence could not occur. The practical to develop in the masonry that the supporting member
approach to the elimination of efflorescence is to reduce is carrying. In order to limit the movement of the
all contributing factors. supporting member, footings, beams and lintels
supporting brick masonry should be limited to a
9.6.10 MOVEMENT maximum deflection of span length divided by 600 or
0.3 in. (7.6 mm), whichever is less. Rotation of the
Every material used in the construction of a building support must also be considered.
is in a constant state of motion. Building materials
expand and contract due to the changes in temperature. Improper detailing of brick masonry can cause a
Several materials move with changes in moisture non-bearing wall to become a bearing wall (carry vertical
content. All materials change dimension due to stress; load), possibly causing cracking or collapse. When
some materials tend to flow when subjected to brick masonry is built tight to the underside of a beam
sustained loads. Building elements are subject to load- or floor, the brick masonry will not allow the beam or
induced def lections. T hese mov em ents are floor above to deflect. Since the beam or floor cannot
theoretically reversible for unrestrained conditions. It deflect, it transfers load directly to the brick masonry.
is necessary to consider the effects of potential Thus the brick masonry now has a beam or a floor
differential movements of the various materials, since bearing on top of it. Detailing of an opening of deflection
different materials are used in today’
s building structures. gap between the underside of a beam or floor and the
top of non-bearing brick masonry can be critical.
9.6.10.1 T HERMAL MOVEMENT
Thermal movements of clay masonry units and other 9.6.10.5 DIFFERENTIAL MOVEMENT
building materials can be estimated from the thermal Historically, brick buildings were constructed using
coefficient of expansion determined by laboratory tests. thick, massive walls in the structure. These massive
The 2005 MSJC Code lists the thermal expansion walls, under heavy loading, could resist differential
coefficient, kt, for clay masonry as 4 x 10-6 in./in./ºF movement with little distress. Many buildings
(7.2 x 10-6 mm/mm/ºC).
Joint free of all material Stop longitudinal
9.6.10.2 MOISTURE MOVEMENT except for backer rod wire at all brick
and sealant expansion joints
Many building materials, metal excluded, expand
with increases in moisture absorption and contract with
moisture dissipation. These movements are reversible
for several building materials, with others they are not. Brick expansion joint Exterior face of
Due to moisture absorption, fired clay masonry products 4”brick veneer
expand slowly and this expansion is not reversible by
drying at atmospheric temperatures. The 2005 MSJC Expansion Joint
Code lists the moisture expansion coefficient, ke, of
clay masonry as 3 x 10-4 in./in. (3 x 10-4 mm/mm).
Alternate position of
flashing with weep holes
9.6.10.3 CREEP shifted upward one brick
9.6.10.4 DEFLECTION
The U-value is calculated by taking the reciprocal sound insulator although it is not a good sound barrier.
of the sum of the thermal resistance of each of the Common face brick reflect about 95% of incidental
assemblage’ s materials. The U-value analysis model sound.
assumes a steady state of heat flow and therefore is
not accurate in predicting actual energy loss. Since
actual climatic conditions are dynamic, the model must
9.8.1 DECIBELS
be modified to produce more accurate results.
The decibel (dB) is a logarithmic unit used to
describe the ratio of the signal level. The decibel is the
9.7.3 THERMAL MASS smallest change in sound energy the human ear can
Thermal mass is demonstrated by the use of adobe perceive. Based on a logarithmic scale, the
brick masonry in hot desert regions. Adobe brick measurement of sound by decibels develops a ratio
masonry has a low R-value and therefore would not be between two sounds. A 1 dB increase corresponds to
a candidate for use in the hot desert because it does an increase of 26% in sound intensity. Thus, 2 dB is
not insulate well. While this is true, the adobe brick 26% greater in intensity than 1 dB and 40 dB is 26%
has high thermal mass. This means it takes a lot of greater than 39 dB.
energy to change the temperature of the adobe masonry
from one side (sunny and hot outside) to the other (shady The reduction of sound or noise through a wall
and cool inside). During the evening, the hot brick gives assemblage is measured as a decrease in decibels.
heat back to the cool night air. The next morning the Judged by a typical human, a 6 dB reduction is
sun has to start all over again in trying to change the equivalent to a 30 to 50% noise reduction. High pitched
temperature of the adobe brick from one side to the sounds are associated with high frequencies and low
other. frequencies with low pitched sounds. In the air, high
frequency sounds attenuate, or die out, much faster
The high mass of brick has a slower thermal than low frequency sounds.
response when compared to lightweight materials such
as vinyl or wood siding. The difference in thermal 9.8.2 TRANSMISSION LOSS
response will have a significant effect on the wall’ s
performance under changing conditions. Massive The energy loss as sound travels from one side of
materials will perform better than the U-value model a partition to another is known as transmission loss. A
predictions. Lightweight materials will come closer to partition does not have the same transmission loss for
the U-value model prediction. The ASHRAE’ s Handbook all frequencies of sound. When the transmission loss
of Fundamentals explains the modifications to the heat for all frequencies is known, a partition’s performance
loss and heat gain equations for dynamic performance can be fully described. To easily compare partitions, a
of walls. The ability of massive materials to absorb single number rating system is necessary. A simple
and hold heat and the time necessary to transfer heat average of transmission losses at different frequencies
are reflected in these modifications. The amount of is not a good indicator of a partition’
s performance as a
heat held is directly proportional to the weight of the sound barrier. A high transmission loss at one frequency
material. will cancel a low transmission loss at another frequency
with a simple average. The result is a partition with a
good average transmission loss but which does not
9.8 ACOUSTICS perform acceptably at certain sound frequencies.
Wall ties provide a connection between the masonry Metal ties should be corrosion resistant and must
wythe and the backing and transfer loads perpendicular be made of steel. Corrosion resistant ties may be
to the wall surface from the masonry wythe to the stainless steel or hot-dipped galvanized.
backing. A tie system must:
The combination of mortar and grout with metal
be securely embedded in the masonry bed ties in a collar joint bond two wythes of masonry
joints of wythes and attached to the backing, developing composite action. Collar joints filled with
grout have higher allowable shear stresses than collar
have sufficient stiffness to transfer loads,
joints filled with mortar. The collar joint must be
have a limited amount of mechanical play, completely filled in order to achieve assumed structural
be corrosion-resistant and strengths. Grout or mortar filled collar joints must be
accompanied by metal ties.
be easily installed.
9.9.1.3 BARRIER AND DRAINAGE WALLS
All metal ties fall into one of five categories, even
though there are many different types of metal ties: A barrier wall system requires a full collar joint
directly behind the exterior masonry wythe. Moisture
corrugated metal ties, tries to migrate toward the interior wythes when a wind-
unit wire ties (rectangular ties), driven rain penetrates a barrier wall’ s exterior wythe of
brick masonry. The joint is intended to act as a barrier
adjustable unit wire ties, and inhibit inward movement when this migrating water
standard joint reinforcement, and reaches the filled collar joint. Figure 9.35 shows how
water ideally flows back out of the wall system. The
adjustable joint reinforcement.
key item to be an effective barrier is that the collar joint
must be completely filled with grout or mortar. Flashing
Adjustable ties are used to allow in-plane differential and weep holes are recommended but not required in
movement and to adjust for unaligned coursing. Joint a barrier wall system. Detailed and constructed barrier
reinforcement is a combination of reinforcement to wall systems, when properly designed, are rated good
restrict in-plane stress and a tie to transmit load. with respect to water penetration resistance.
Drips or kinks in metal ties, which were originally Single-wythe masonry walls can be considered a
intended to impede moisture flow across the tie in special case. The masonry wythe, in single-wythe walls,
drainage walls, are not recommended. Drips do not is usually much thicker than a nominal 4 in. (102 mm)
inhibit moisture migration, but significantly reduce the thick exterior brick wythe, and, as a result, the added
stiffness of the ties and the ability to transfer load. thickness helps to prevent water from penetrating to
the interior of the wall system. Drainage wall systems
are more effective in preventing water penetration than
single-wythe walls or multi-wythe barrier wall systems,
but with careful detailing and quality construction
practices, single and multi-wythe walls can perform well.
Solid or hollow units are used in the design of single-
wythe brick masonry construction.
Corrugated Tie Rectangular Tie Adjustable Tie To prevent water from entering the structure, a
drainage wall system relies on an air space behind the
exterior wythe, along with flashing and weep holes. The
drainage wall assumes that water from a wind-driven
rain may penetrate the exterior wythe of brick. When it
does, the moisture migrates inward to the cavity or air
space. Then it gravitates or flows down the back face
of the outer brick wythe, is collected on the flashing,
and is directed out of the wall system through the weep
holes. Properly detailed and constructed drainage wall
Adjustable Joint Joint Reinforcement systems are rated excellent with respect to water
Reinforcement penetration resistance.
Grout
Drainage Wall
Reinforcing
steel
Barrier Wall
F IGURE 9.36 Reinforced grouted brick
masonry.
FIGURE 9.35 Barrier and drainage walls.
One concern in homes is air leakage through the 9.9.1.5.1 MATERIALS FOR SINGLE-WYTHE BEARING
building envelope. In brick homes there will be some WALLS
leakage through weep holes and at the top of the The selection of masonry materials for a single-
brickwork even though the brick wall provides an effective wythe brick bearing wall system should consider
air barrier. To prevent air leakage, building paper or structural, energy and other performance requirements,
sheet membrane materials are commonly installed over as well as aesthetic appeal.
exterior sheathing materials in wood frame construction
but these materials are not appropriate for direct Solid or hollow brick in single wythe bearing wall
application on brick bearing walls. Alternate approaches structures may be used. Since the bricks will be
to further limit air leakage are the use of either foil- exposed on the exterior face, solid units should meet
faced rigid board insulation or so-called “ air-tight the requirements of ASTM C 216 Standard Specification
drywall” . These approaches rely on the air penetration for Facing Brick. Hollow units should meet the
resistance of the paper or other films on the insulation requirements of ASTM C 652 Standard Specification
or gypsum board. The joints between the sheets of for Hollow Brick. Structural and model building code
insulation or gypsum board must be sealed or taped to requirements, aesthetics, availability and cost will
achieve an impenetrable air barrier. Additionally, joints determine the minimum unit compressive strength, type
between different materials and joints around door and and sizes of units used.
window frames should also be sealed.
110 MASONRY DESIGN MANUAL
There are many brick sizes manufactured today. Also, the maximum bar size should not exceed
Solid units are commonly manufactured in nominal the nominal thickness of the wall in inches to ensure
widths of 3, 4, and 6 in. (76, 102 and 152 mm). Hollow proper development of the reinforcement. For example,
units, which are less than 75% solid, are manufactured a maximum reinforcing bar size of No. 8 (M #19) is
in nominal widths of 4, 5, 6 and 8 in. (102, 127, 152, recommended for nominal 8 in. (203 mm) walls.
and 203 mm). Nominal 5 and 6 in. (127 and 152 mm)
wide hollow brick are the most common units used to Steel reinforcing bars must conform to ASTM
construct reinforced brick bearing wall homes. Standard A 615, A 706, A 767, A 775 or A 996 depending
upon the type of bar used. Joint reinforcement, if used,
In reinforced brick bearing walls, hollow brick are should comply with ASTM A 951 and be hot-dipped
common because they hav e cells which can galvanized or made from stainless steel to reduce the
accommodate vertical reinforcement and grout. The possibility of corrosion.
applicable building code dictates the minimum size of
cells in hollow units intended to be reinforced. Larger A load-bearing brick wall often contains vertical steel
vertical bars, horizontal reinforcing bars and coarse grout reinforcement uniformly spaced along the length of the
require larger cell sizes. wall and horizontal reinforcement in bond beams.
Vertical reinforcement may also be necessary around
In the design and construction of reinforced load- openings and at building corners. Figure 9.37 shows
bearing masonry walls, uniform spacing of vertical one example of incorporating vertical reinforcing bars
reinforcement is important. The cell sizes and unit in a wall built with solid units.
length should be coordinated to provide cells which align
vertically for ease of grouting and uniform spacing of
reinforcing bars. The majority of hollow brick designed
Horizontal joint
to accommodate reinforcing bars have masonry unit reinforcement
lengths equal to twice the masonry unit width so that
cells align vertically when the masonry is laid in half
running bond.
Furring with
insulation
Flashing
FIGURE 9.39 Reinforced hollow brick.
Weep holes
24 in. (610
Bond beams, which are horizontal reinforced mm) o.c.
grouted elements, are used to anchor bolts for attaching Floor joist
ledgers and plates and span wall openings. Bond
beams are formed by using special U shaped units or Intermediate
by removing part of the cross web of hollow brick. blocking
W aterproofing
Necessary anchor bolts and reinforcement are placed, below grade
and the bond beam is grouted solid. The depth of the
bond beam required will depend on the design loads for
the structure, the material properties of the masonry Foundation
and the amount of reinforcement used. wall
Bond
beams as
required
F IGURE 9.42 Basement/ craw l space Floor joists
Ledger joist
Interior Finish
Hat channel
Foundation wall
Waterproofing Rigid insulation Brick bearing
below grade wall
Vertical reinforce-
ment in grouted
cell
F IGURE 9.43 Basement/ craw l space
foundation bond beam support. FIGURE 9.45 Roof connection.
BRICK MASONRY CONSTRUCTION 113
lateral forces and uplift forces on the roof. Using
anchor bolts embedded in a bond beam or masonry
below, a wood plate is attached to the top of the wall.
A reinforced concrete bond beam or a reinforced and Insulation Brick wall
grouted brick bond beam may be used, as depicted in
Figure 9.45. Flashing
Interior finish
Insulation
Interior finish
Flashing
Wood plate
Furring anchor Brick bearing
wall Brick wall
Horizontal reinforcement
Furring with Anchor bolt
insulation Sealant
with steel plate
Interior finish grouted into Jamb (Plan View)
core
Double hung
FIGURE 9.46 Roof connection. wood window
following masonry work. During the masonry Typically, one wythe of the wall is built up not more
construction, fasteners necessary for attachment of the than 16 in. (406 mm) ahead of the other wythe in order
cabinets, insulation and interior finishes may be to accommodate wall ties. Spacing of ties is not to
incorporated. The interior frame walls may be built at exceed 36 in. (914 mm) on center horizontally and 24
the same time with the exterior load-bearing brick walls in. (610 mm) on center vertically. The 2005 MSJC
once the floors have been constructed,. Specification requires at least one tie for every 41/2
square feet (0.42 m2) of wall area when W2.8 (MW
Brick bearing walls should reach sufficient strength 18) wire is used and at least one tie every 22/3 square
before any temporary or permanent loads are applied. feet (0.25 m2) of wall area when W1.7 (MW 11) wire is
Curing conditions will affect the rate of strength gain used. Joint reinforcement may also be used to tie the
of load-bearing masonry. The masonry walls, if two masonry wythes together.
sufficient moisture is maintained, should cure a
minimum of three days before supporting floor or roof
loads. The required curing periods of the reinforced
brick masonry beams are at least seven days. Poor
curing condi tions, such as exposure to cold
temperatures, may require longer curing times. The
floors and roof may be attached once the brick bearing
walls are cured. As soon as the masonry is complete,
the windows, doors, plumbing, electrical and heating
systems, insulation and interior finishes can be
installed.
1
/ 2” 2” 2”
4” 6” 3” 3” 3” 3” 3” 3”
1 2 3 4 5
4” Brick Wall 6” Brick Wall 61/2” Brick Wall 8” Brick Cavity Wall 8” Reinforced
Metal - Tied Brick Wall
8” 4” 2” 4” 4” 2” 4” 4” 2” 6” 4” 4” 4”
6 7 8 9 10
8” Brick Wall 10” Brick 10” Reinforced 12” Brick 12” Reinforced
Cavity Wall Brick Wall Cavity Wall Brick Wall
9.9.1.8 REINFORCED HOLLOW MASONRY WALLS Method No. 3 (2006 IBC Section 2105.3) provides
for removing specimens, or prisms, from the constructed
In the United States, hollow brick were first
wall and testing in accordance with ASTM C 1314.
developed and marketed in the Southeast under a
Obviously, this method would be used only when
regional specification of “Jumbo Brick” . These units
compressive masonry strengths have not been
have been used in thousands of buildings since the
satisfactorily determined by Method 1 or Method 2.
1920’ s. Hollow units of this type were more nearly
brick than tile, consequently, the special specification
There is also a method recognized by the California
and wide use of hollow brick occurred. These units
Division of the State Architect which acknowledges
were made and marketed under several different
compressive test results from core samples taken from
names, for example, Dubrick, Speedbrick, Jumbo
masonry. This is especially useful when marginal
Brick, and others. They were typically 8 in. (203 mm)
results are obtained from recognized methods and
nominal in thickness and had face sizes ranging from
further limited testing for verification of compressive
nominal 21/4 by 12 in. (57.2 by 305 mm) to nominal 4
strength of masonry is desirable.
by 12 in. (102 by 305 mm).
A detailed knowledge of the material properties is
Four types of hollow brick are described by ASTM
essential when any new material is offered to the
Standard C 652. The classification by types is related
construction industry. Initial evaluation, such as with
to the appearance characteristics of the units. The
International Code Council’ s Evaluation Services, will
proper type is selected by the specifier depending on
provide the designer and Building Official verification
the project and the intended use.
that the new material complies with the intent of the
building code.
Reinforced hollow brick masonry may be designed
using the requirements of the MSJC Code. This
Hollow bricks are normally laid with only face shell
standard contains provisions for both double wythe
bedding and unreinforced hollow brick walls may show
grouted reinforced masonry and for reinforced grouted
a reduced masonry strength bearing capacity due to
hollow cell masonry. In addition, there are provisions
the reduction of the amount of bedding mortar.
for partially reinforced masonry. Reinforced masonry
is required to contain a minimum area of reinforcement, Fully bedded mortar (applied on all cross webs and
based on the cross-sectional area of the wall, with not face shells) may increase the strength bearing capacity
more than two thirds of the steel in the principal in non-grouted brick walls. This allows webs to
direction. contribute in resisting the axial, shear and bending
loads.
Masonry strength for reinforced hollow brick
masonry constructed in accordance with the IBC is Typically, if the structural capacity and proper
determined by one of three methods: material properties are provided, hollow brick can be
used where solid brick are used. Hollow bricks are
Method No. 1 (2006 IBC Section 2105.2.2.2) produced with the same outside dimensions as solid
provides a means of testing compressive prisms built brick and show no visual evidence on the face of
of similar materials, under the same conditions and in containing cores in excess of that found in solid brick.
stack bond pattern. Test prisms are constructed and
tested in accordance with ASTM C 1314 Standard Test An economic alternative to double wythe solid
Method for Compressive Strength of Masonry Prisms. construction or solid brick veneer construction is the 4
Masonry prism strength of hollow brick masonry is in. (102 mm) hollow brick.
normally determined at 28 days after prism construction
by dividing the test load by the net area of the Due to its use with reinforced brick masonry as
assemblage. wel l as the adv antages of reduced costs in
manufacturing, transportation, and installation, hollow
Method No. 2 (2006 IBC Section 2105.2.2.1.1) bricks are widely available. They can be used under
provides a means of assuming an ultimate compressive the masonry provisions in the model building codes
strengt h of masonry, based on the net area and masonry design standards.
compressive strength of hollow units and the type of
mortar used for construction. 9.9.1.9 CAVITY WALLS
A cavity wall is two wythes of masonry separated
by a space varying from 2 in. (50.8 mm) to 41/2 in. (114
mm). The space between the wythes of brick may
contain insulation for thermal efficiency.
BRICK MASONRY CONSTRUCTION 119
Parapet details and movement joints are critical
2”minimum air space in any masonry system and this is particularly true with
Insulation cavity walls.
Counter flashing
There is evidence that the British rekindled the
Base flashing
cavity wall as historic plans in the early 1800’
s show 2
wythes of brickwork connected by brick headers. This
is a type of unreinforced cavity wall that is still
constructed. There is more evidence (circa 1821) with
published information on the benefit of cavity wall Dovetail anchor
construction as a means to keep moisture migration slot and 1/4”
flexible dovetail
from entering a building. In the second half of the 19th anchor @ 16”
century, there is evidence of the British using wrought o.c. horizontally
iron for brick ties.
Flashing Flashing
Brick Horizontal joint
Weatherproof membrane reinforcement
Joint reinforcement
Plan View
Brick
Flashing Continuous
1”minimum air space bond beam or
precast
Polyisosyanurated rigid board insulation
concrete lintel
Concrete block
Concrete block
Brick
Concrete
block
Concrete plank
Flashing
Bearing plate and membrane
mortar bed as required all ends and
Continuous bond beam joints lapped
(2) and sealed
differential material properties between clay and The given illustration shows a concrete masonry
concrete and elect to isolate the brick into panels. Shelf infill system, which is tied into the concrete frame. This
angle rotation and deflection must also be considered. is accomplished with a dovetail tie system into the
concrete. There are other methods to achieve this
The design illustrated in Figure 9.65 shows the anchorage, but the anchors should be flexible enough
concrete floor supported by one wythe of the cavity to accommodate the inevitable movement, yet rigid
wall, thereby reducing thermal bridging. Modular layout enough to support the concrete masonry wall.
has also been considered allowing for full units Perimeter connections may also follow this rule, or the
immediately below the concrete slab. designer may prefer to decrease the spacing between
ties, since the spacings listed in the MSJC Code are
maximum dimensions.
Concrete Horizontal joint Properly designed hollow unit masonry walls may
block reinforcement at 16” also serve as the veneer backup system. The backup
o.c. vertically system must meet deflection criteria and be able to
support and transmit any imposed lateral loads from
Concrete
slab
the veneer.
Dovetail slot
Drywall
Brick
Flexible anchors
set into dovetail
slots
1”minimum air space
Concrete frame
Sealant
Flashing
Weep hole
When the actual cause is the expansion or curling
24”o.c. of the concrete slabs bearing on the walls, thermal
strains or other movements are frequently cited for
Sealant
cracking in masonry walls. The curling of the concrete
Required shelf angle slab has been known to pick up the brick wall below.
In detailing the structure, this behavior of concrete is
often overlooked by the designer. A typical detail that
FIGURE 9.69 Balcony section. will relieve this condition is shown in Figure 9.71. In
this design, the bond is broken between the concrete
9.9.1.12 CAVITY WALL CONNECTIONS slab and the brick wall by building paper. With respect
to the wall, this allows the slab to have some freedom
A typical foundation detail is shown in Figure 9.70. of movement. Further, it permits the longitudinal
The bond, in this case, is broken between the base of thermal and moisture movements to occur without
the cavity wall and the top of the concrete beam by distress. The slab is thickened into a beam over the
flashing. In the foundation the transfer of movement interior wythe to help stiffen the slab and reduced
to the wall is reduced. Bond breaks also permit curling. Provisions must be made for insulation under
differential thermal and moisture movements without certain climatic conditions.
distress to either the brick wall or the concrete
foundation. Furthermore, by placing reinforcing bars Once again, this detail may not be seismically
and filling the cavity with grout, a bond beam or tie compatible due to lateral restraint requirements. Lateral
beam can be formed at the bottom of the wall. This restraint can be provided by clips or channels at the
will attach the inner and outer wythes of masonry top of the masonry wall.
126 MASONRY DESIGN MANUAL
Metal ties
Solid bridging
at anchor
Lateral
support metal
anchors @ 8’o.c.
maximum
3
/16”wall ties at first Joists anchors at
course below joists every 4th joist
/4”anchor
1
Wood plate
Compressible
filler
Plan Section
Dovetail
slot
/16”diameter
3
metal ties
2”typical cavity
Plan Section
Wood plate
1
/4”anchor
Brick header course
metal ties
1
/4”anchor
2”typical cavity
Compressible material
1
/4”anchor
Brick and concrete
block cavity wall
Steel angle metal
tie holder
1
/4”metal tie
Plan Section
Dovetail
slot
Brick cavity wall
1
/4”anchor /16”wall tie
3
/4”anchor rod
1
Rod offset
Plan Section
3
/16”metal wire tie
/4”anchor rod
1
welded to column
/4”anchor
1
Plan Section
FIGURE 9.80 Concrete column and cavity wall
corner.
FIGURE 9.78 Wall anchorage to steel columns.
BRICK MASONRY CONSTRUCTION 129
Stock sizes of window and door frames should be
used in cavity walls. In cavity walls, solid masonry
jambs at windows and doors should be avoided. For Flashing
steel windows, the jambs must be partially solid to Weep holes
accept most standard jamb anchors. Wood or steel Reinforced
casings must be used to adapt non-modular steel brick lintel
casement windows to modular cavity walls. Cavity wall
ties spaced at 3 ft (914 mm) or less should be placed
around all openings not more than 12 in. (305 mm) Caulking
from the opening. Head
Reinforced
CMU lintel
Steel angle lintels
Weep holes
Flashing Jamb
Caulking
Caulking
Head Caulking
Wall ties
Flashing
Sill
Jamb
Flashing Caulking FIGURE 9.82 Metal casement window.
Caulking
Flashing
Caulking
Sill Head
Exterior pressure
Interior pressure
moisture penetration resistance for exterior brick walls.
Cavity pressure
This idea is to introduce air into the cavity of common
drainage type walls to provide pressure equalization Vent area
so that the cavity works in resisting wind-driven
moisture penetration.
To prevent the passage of water and air without the exterior cladding is the driving force causing air to
limiting differential movement, sealing of movement enter the cavity. This pressure difference decreases
joints is required. The principal resistance to the as the air enters the cavity. The flow rate is proportional
passage of water through joints in exterior elements to the pressure difference and when the air flows into
is the sealant. A backing material and/or filler is needed the cavity, the flow decreases.
for all movement joints.
As shown in Figure 9.86, the wind pressure flowing
In a brick veneer or a cavity wall system, the rain around a building creates a distribution of positive and
screen wall equlized pressure will be subject to axial negative pressures over the building exterior cladding.
and lateral loads. For the rain screen wall to perform The lateral flow of air in the cavity will occur if the cavity
as intended, imposed loads must be taken into account of the rain screen wall is continuous, horizontally or
in the design of these new wall systems. Moisture vertically. The pressure equalization will not occur if air
leakage, thermal and air retarder performance must is permitted to flow laterally in the cavity. Moisture
also be considered in other environmental loads. The penetration into the wall assembly might not be reduced
pressure equalized rain screen principle may be when this occurs.
affected by several parameters. These parameters,
which are often interrelated, include: The cavity must be compartmented to prevent lateral
airflow. The size of the compartments should
• Rate of applied wind load, be based on the pressure differences across the exterior
• Magnitude of applied wind load, cladding. The greatest pressure differences are
experienced at the corners and tops of buildings,
• Cavity volume,
consequently, the compartments located in these areas
• Stiffness of the interior wall and the exterior should be small. The compartments can be larger where
cladding, pressure differences are small, such as near the center
• Compartmentation of the cavity wall and of the exterior cladding.
• Leakage areas of the air retarder and the
exterior cladding. Recommendations by designers are that these
compartments should be no more than 4 ft (1.2 m)
In theory, no wind load should be imposed on the parallel to tops and corners of the facade for a 20 ft
exterior cladding, which is an advantage of the pressure (6.1 m) wide perimeter zone as shown in Figure 9.87.
equalized rain screen wall, however, wind is dynamic
and variable so that the pressures applied to the wall There must be a series of openings to connect each
are constantly changing. The perfect rain screen wall cavity space to the exterior of the wall system to provide
would pressure equalize immediately. A pressure pressure equalization in the rain screen wall. The
difference occurs across the exterior cladding due to a openings should be placed at the top and bottom of
time lag between the imposed wind load and the each compartment. To avoid airflow loops in the cavity,
pressure equalization in the cavity. all openings at the top and bottom should be placed at
the same height.
In buildings, pressure differences from two main
sources have been encountered. The first is frequently No specific guidelines exist for the required amount
known as a stack effect which is created by temperature of openings for each compartment. The area of openings
differences between the exterior and the interior of the depends on the airtightness of other components of
building. The wind forces that are imposed on the the cavity, such as the air retarder system and the cavity
building envelope is the second. The pressure closures. The recommendation, if completely sealed
differences across a wall system at the top and sides compartment closures are used, is a 10:1 ratio for
may be a combination of both and is not the same for cladding air leakage to air retarder leakage.
all parts of the building envelope.
The cavity closures will not form an airtight seal of
The movement of air into the cavity causes pressure the individual compartments. Therefore, the required
in the cavity to increase and match the external pressure opening area should be larger. A proportion of 25 to 40
applied when positive pressure is applied to the exterior times more air flow volume through the openings in the
cladding. Depending on the volume of the cavity is the exterior brick wythe than air leakage through the interior
volume of air required to achieve pressure equalization. wall is recommended by some studies. Consequently,
When the cavity volume increases, the vent openings the less the area of openings in the exterior cladding
in the exterior brick wythe must be increased in order required for pressure equalization of the cavity, the
to permit more rapid pressure equalization. The tighter the compartment. Testing of a mock-up wall
pressure equalization. The pressure difference across compartment may be required to obtain the airtightness
BRICK MASONRY CONSTRUCTION 133
Positive pressure on windward face
Opening
Exterior brick wythe
Cavity (Partially pressurized)
Interior wall
Compartments every 10
ft. to 20 ft. from center of
facade in both directions
Jack - An arch having horizontal or nearly horizontal Keystone - Wedge-shaped unit at the center or summit
upper and lower surfaces. of an arch or vault, binding the structure actually or
symbolically.
Major - An arch with spans greater than six feet.
Typical forms are Tudor arch, Semicircular arch, Label Course - A ring of projecting brickwork that forms
Gothic arch, or Parabolic arch. the extrados of the arch.
Minor - Arch with maximum span of six feet. Typical Rise - The distance at the middle of an arch between
f orms are Jack arch, Segmental arch, or the spring line and intrados or soffit.
Multicentered arch.
Multicentered - An arch whose curve consists of Skewback - The incline surface on which the arch joins
several arcs of circles which are normally tangent the supporting wall.
at their intersections.
Skewback Angle - The angle made by the skewback
Relieving - An arch built over a lintel, flat arch, or from horizontal.
smaller arch to divert loads, thus relieving the lower
member from excessive loading. Soffit - The exposed lower surface of any overhead
component of a building such as a lintel, vault, cornice,
Segmental - An arch whose intrados is circular but or an arch or entablature.
less than a half circle.
Span - The horizontal clear dimension between
Semicircular - An arch whose intrados is a half abutments.
circle.
Spandrel - A flat vertical face in an arcade bounded by
Slanted - A flat arch which is constructed with a the adjacent curves of two arches and the horizontal
key stone whose sides are sloped at the same tangent of their crowns.
angle as the skewback and uniform width brick and
mortar joints. Springing - The upper and inner edge of the line of
skewback on an abutment.
Triangular - An arch formed by two straight inclined
sides. Springer - The first voussoir from a skewback.
Tudor - A pointed, four-centered arch of medium Spring Line - A horizontal line which intersects the
rise-to-span ratio whose four centers are all beneath springing.
the extrados of the arch.
Voussoir - One masonry unit of an arch.
Venetian - An arch formed by a combination of Jack
arch at the ends and Semicircular arch at the
middle.
BRICK MASONRY CONSTRUCTION 137
Venetian Tudor
Triangular Gothic
4 in.
Flashing min.
Building paper overlapping flashing
End dam
Tray flashing
Mini
mum
1 Step flashing
/3 sp
an
FIGURE 9.94 Flashing a Jack arch.
Building paper
& exterior
sheathing
Wall tie
Inside face
of wall Jack Arch Semicircular
Skewback Arch Skewback
Weep hole
Tray flashing Keystone
at arch crown
Wall tie
Keystone
Metal tie @ 24 in. Regular mortar joint thickness
(600 mm) max. Cant brick
along arch ring or
as required
Segmental
Brick masonry Arch Skewback
FIGURE 9.98 Structural arch soffit. The abutment at the springing should be cut or be
a special cant-shaped brick. This allows vertical
Arches on either wall face should be bonded to alignment with the brick beneath, producing more
the brick masonry forming the soffit. A bonding pattern accurate alignment of the arch.
or metal ties should be used to tie the brick masonry
forming the soffit together structurally and to tie the The intersection of the arches may occur at the
arches on either wall face to the soffit. If metal ties skewback when two arches are adjacent, such as with
are used to bond the masonry, corrosion resistant box a two-bay garage or building arcades. A vertical line
or metal wire ties should be placed along the arch span between arches should be avoided. A special shape
at a maximum spacing of 24 in. (610 mm) on center. brick can mesh the two arches properly.
Compacted soil
FIGURE 9.105 Rigid base paving assembly. A brick paving assembly must support vertical traffic
loads (live load) plus its own weight (dead load). The
A semi-rigid base would typically consist of brick paving must resist abrasion from traffic. Vehicular
continuous asphalt. On this type of base only traffic may impart horizontal thrust to the paving
mortarless brick paving should be used and may be assembly from braking, acceleration and turning action
used for pedestrians areas such as malls or medium of wheels. Resistance is provided by the inter-locking
to heavy vehicular traffic. bond pattern of the pav ing assembly. Three
classifications of traffic are light, medium and heavy.
A flexible base consists of compacted earth
covered with gravel and sand, or a mixture of sand Light traffic - Residential pedestrian traffic, such
and cement (Figure 9.106). Brick pavers for flexible as on patios, walkways, porches, gazebos and
base should be at least 25/8 in. (67 mm) thick to reach pool areas.
a good interlock if used in heavy vehicular traffic. This
thickness is ideal for any chamfers or rounded edges, Medium traffic - Commercial pedestrian traffic,
which should not exceed 3/16 in. (4.8 mm) in depth or such as on city walkways, entranceways, shopping
width. Some brick pavers are made with spacers or malls and light residential vehicular traffic, such
lugs. The lugs are typically 1/8 in. (3 mm) providing an as residential driveways and parking lots.
even gap for the jointing sand. During compaction of
the pavers the lugs keep the paver edges from touching Heavy traffic - Commercial vehicular traffic, such
each other reducing the chippage of the pavers. When as on streets and commercial parking lots.
the pavers are subjected to heavy vehicular traffic, lugs
are necessary. 9.9.3.2 SITE
The site may range from a small residential patio
There are a number of issues that must be to a major urban renewal project. Successful
addressed in brick paving design, including: installations will depend upon proper subgrade design
and preparation. Remove all vegetation and organic
• site materials from the area to be paved. Areas containing
• traffic poor sub-base material should be removed and refilled
• drainage with suitable material which is properly compacted.
• brick material
• bond pattern 9.9.3.3 DRAINAGE
• other materials
• subgrade Surface and subsurface drainage are significant.
Exterior brick paving should be sloped at least 1/8 to 1/4
in. per foot (10 to 20 mm per meter). Large exterior
paved areas for malls and vehicular parking lots require
BRICK MASONRY CONSTRUCTION 147
a greater slope. All paving should be sloped away 9.9.3.5 INSTALLATION
from buildings, retaining walls and other elements
There are three basic methods for installing brick
capable of collecting surface water.
paving with mortar joints.
Mortar joints are less durable than the brick units
The first method is by the conventional use of
and standing water should be avoided. The long
troweled mortar. For durability, type S or M mortars
dimension of the mortar joints should parallel runoff.
are recommended for use in brick paving, with type M
Mortarless pav ing requires bot h surf ace and
used in locations subject to freezing. Brick pavers are
subsurface drainage. A significant moisture problem
buttered with mortar and pushed into a leveling bed of
is upward capillary action rather than the downward
mortar. The joints between the units should be
drainage, particularly in areas with high water tables.
completely filled to maximize moisture penetration
A capillary break should be used, such as a layer of
resistance. The width of the mortar joints is typically
gravel, to prevent this upward flow of moisture. 3
/8 to 1/2 in. (9.5 to 12.7 mm). Joints should then be
Regions with relatively impervious soils, capable of
tooled with a concave jointer when mortar becomes
surface water retention, may require subsurface
thumbprint hard.
drainage systems.
Turf
Sand should not be placed directly over gravel.
Sand will sift into the voids of the larger granular
material when drainage occurs. An impervious Paver Top soil
membrane, such as geotextile fabric, can separate the
1”sand
two materials.
Pave edge
Compacted
9.9.3.4 EDGING aggregate base
Spike
A method of containment must be provided around
Compacted subgrade
the entire perimeter of the paved area to prevent
horizontal movement of mortarless brick paving units
and the base over which they are installed. This may
be a brick soldier curb set in concrete or mortar, or a
special edging manufactured specifically for the
FIGURE 9.108 Paver restraint system.
purpose of brick paving. Landscaping timbers or
railroads ties may serve as an edging material. An The second method involves placing each brick unit
existing concrete curb, building or retaining wall may on a mortar leveling bed with a 3/8 to 1/2 in. (9.5 to 12.7
also be used. mm) open space between the units. The space is filled
by pouring a fluid mixture of 1 part Portland cement
and 3 parts of sand between the units. This is easily
4 in. compacted accomplished by placing mortar using a grout bag.
gravel base When grout is poured into the joints, the units must be
2 layers of 15 lb. protected to facilitate cleaning since grout will smear
Expansion joint
building felt the units, or immediately cleaned using sponges and
1
/2 in. to 1 in. Weep holes ample clean water. The joints should also be tooled to
sand bed @ 16 in. o.c. a concave finish.
Gravel
Flexible brick
perimeter The third method uses a dry mixture of 1 part
paving
drainage
Portland cement and three parts sand. Brick pavers
are installed on a damp cement and sand cushion with
open joints between the units. The dry grout mixture
is swept between the paving units. After sweeping
excess material from the paving surface, the paving is
Compacted earth sprayed with a fine mist of water until the joints are
saturated. The pavement should be maintained in a
Soldier course
edging embedded
damp condition for a period of two to three days. Mortar
in concrete footing joints should be tooled.
9.9.3.6 STUCTURAL BRICK FLOORS Bri ck pav ers, like all materials, change
dimensionally with changes in temperature. A slip
Brick may also be used in self-spanning floor plane between pavers and a waterproofing membrane
systems by using some form of reinforcement. The may be placed to avoid disruption to the membrane.
system may stand alone, that is, use brick, mortar, For example, it may consist of a porous gravel cushion,
grout and reinforcement, or work in harmony with other asphalt impregnated protection board or other material
elements, such as concrete or wood systems. capable of withstanding both horizontal abrasive
movement and vertical traffic loading.
9.9.3.6.1 SUSPENDED DIAPHRAGM BASES
9.9.3.6.4 BRICK PAVING DESIGN ASSEMBLIES
Certain special design factors must be used to
minimize the risk of deterioration and to assure long The following illustrations show how brick paving
term performance on a roof deck or suspended plaza. can be adapted to suspended diaphragm bases of
A roof deck plaza application must be structurally various types. These support bases may consist of
sound, aesthetically appealing, durable and economical reinforced brick masonry slabs, reinforced concrete
to install. slabs, steel decking, and wood framing.
The thermal aspects of roof terraces are similar FIGURE 9.109 Brick drain.
to those of normal roofs. The position of roof insulation
is important relative to the temperature variation of 9.9.3.6.5 STRUCTURAL CONSIDERATIONS
each element in a paved roof assembly. Insulation
may be placed directly over a membrane. The structural design of the suspended base should
follow normal design procedures. As with any solid
Roof deck insulation should be a non-rotting, masonry, the dead weight of brick pavers should be
moisture resistant, closed-cell type of material capable considered when combined with other materials and
of retaining thermal resistance in the presence of water. design conditions, such as live loads, vibration and
Traffic loading may be supported on insulation impact from traffic. The dead weight of mortared or
materials in a deck assembly provided the insulation mortarless brick pavers may be taken at approximately
material is structurally adequate. 10 psf per inch of thickness for structural design
purposes. Brick pavers are available in various
thickness so their total weight will vary. The most
popular pavers are 15/8 in. (41.3 mm) to 21/4 in. (57.2
mm) thick, weighting approximately 16 to 22 psf (766
to 1054 N/m2), respectively.
BRICK MASONRY CONSTRUCTION 149
Diaphragm action becomes important in order to designed to support a 50 psf (2.4 kN/m2) live load,
maintain the integrity of mortar joints for mortared spanning about 6 ft (1.8 m). Turning a unit on edge to
paving. The span for mortared paving should be limited increase the slab’s thickness, the design load capacity
to a deflection of l/600 for mortared paving and l/360 can be doubled (100 psf [4.8 kN/m2]) and the span
for flexible paving. increased to over 7 ft (2.1 m) using the same size hollow
brick and the same mortar.
9.9.3.6.6 REINFORCED CONSTRUCTION
9.9.3.6.7 BRICK ON SHEET STEEL FORMS
Reinforced brick paving can be used to span an
open space or over a fill which has the potential of uneven A corrugated sheet steel as a base is utilized as a
settlement. Reinforcement in the masonry can eliminate variation of reinforced brick construction. Reinforcement
the necessity for a separate reinforced concrete slab of masonry can provide an economical solution to the
or other rigid base. problem of constructing brick floors over open spans
while the steel serves as a form. Steel is placed near
Various types of reinforced brick masonry slabs, the top of the pavement in grouted mortar joints for
as shown in Figure 9.110, can support a wide range of continuous spans. Brick are placed on a bed of mortar
live load conditions. and vertical joints are filled with mortar or grout.
/4”clear
3
41/2”
#2 @ each joint
51/2”
1
/4”clear
Top of mortar bed
Section A-A
d = 2.75”
31/2”
A
12”
#3 @ each cell
#4 gage transverse A
wires @ 41/2”o.c.
d = 5.5”
71/2”
2 x _ solid bridging
Structural slab Wood joists
All level drains and waterproofing membranes should No curing time for flexible brick pavement is re-
be installed in strict accordance with the manufacturers’ quired. Spread damp sand in thin layers and permit
instructions and specifications for suspended decks the sand to dry before sweeping sand into the joints.
where control of surface drainage is required. Sand must be clean and free of clay to avoid surface
“scumming”of the finished paving.
9.9.3.6.10 INSULATION
Usually brick floors and pavements are abrasion
Figure 9.112 depicts insulation required to support resistant and hard wearing, therefore, coatings to
a specific design live load. The insulation must also be maintain surface appearance are not normally
capable of withstanding the temperatures transferred required. Coatings and waxes may be desirable on
through the protection board from the application of hot interior brick floors to enhance the appearance and
bitumen. make the surfaces easier to clean.
High-bond and latex modified Portland cement Certain coatings on exterior brick pavement are
mortars may vary among manufacturers, therefore, not recommended, as they may cause an extremely
the instructions for installation should be carefully slippery surface when wet during cleaning or in a
followed. Mortar joints should be properly tooled when rainfall. Other coatings, such as non-slippery water
the mortar is thumb print hard. repellent sealants, may be beneficial for exterior
applications. For interior brick there are a few aspects
9.9.3.6.12 CLEANING to be considered before applying any type of coating.
When cleaning high-bond mortared pavement, A common historic practice of applying a sealer
cleaning should be done as soon as possible after the on brick paving prior to waxing has been satisfactory,
mortar joints have been allowed to cure. A surface however, sealer and wax must be checked for
applied bond breaker may be applied to the brick prior compatibility prior to final application.
to mortar application to assist in the cleaning process.
Sealers typically have two purposes:
Steam cleaning is eff ective in melting any
protective paraffin coating and lifting excess mortar. 1. To lock loose sand in the cracks, and
Drains should be protected from clogging during the 2. To provide a protective finish.
cleaning process. A visual inspection after cleaning
may reveal problem areas that require scraping or light
brushing with a stiff bristle brush. Do not use wire
brushes when cleaning masonry.
152 MASONRY DESIGN MANUAL
When a sealer is used, it should be tested on a to the masonry and may be a source of efflorescence.
small area and evaluated before full application. A Use clean sand on the affected area to render icy
compatible wax should be selected, preferably a water surfaces passable.
emulsion type which is recommended for brick floors.
Where a metal snow plow blade is used to remove
The floor surface should be dry before a coating snow, the blade should be rubber tipped or mounted
is applied. To determine the most economical and on small rollers and the blade edge should be adjusted
effective means for maintaining a brick floor, each to a clearance height suitable to the pavement surface.
maintenance situation, whether it be with a sealer and Needless chipping of the edges of the brick should be
wax or a synthetic sealer-finish material (spry-buffing avoided regardless of the method used.
process), must be judged on its own merit.
9.9.4 LANDSCAPING
Removing snow on large or small areas of brick
pavement should not present any particular problem. In landscape architecture brick plays an ever-
To preserve the character of the brick there are growing role. Since it is made of natural earth materials
precautionary measures that can be taken. Avoid the and available in a multitude of colors that are
use of chemicals and “ rock”salt that aid in melting harmonious with nature, brick is an ideal landscape
ice. Using these materials will introduce soluble salts material. The designer is not limited in creativity when
using bond patterns of brick in an imaginative way.
Figure 9.117 illustrates a few basic patterns.
9.9.4.5 FOUNTAINS
Often, designers avoid the use of brick in
combination with water for fear of deterioration of the
masonry. There are, however, many examples of
successful brick projects with water including waterfalls
FIGURE 9.119 Planter boxes. and fountains.
9.9.6 MASONRY HEATERS gases circulate through a maze of brick units before
being sent up the chimney. The heated mass is an
For centuries, throughout Europe and in nearly every efficient heat sink that absorbs the heat energy, evenly
region of the world, masonry heaters have been used distributes it throughout its mass by means of the
to heat rooms. Masonry heaters differ from an open flowing combustion gases through the winding flues that
face fireplace. There are many different styles, usually absorbs much of the heat energy before the combustion
named for the country of origin, such as Russian, gases are released to the chimney.
Finnish and German.
9.9.7 PARAPETS
13
9 4
12
5
7
6
1
extension of the brick buildings on which they appear. • into a transmitted path through the barrier
Used in conjunction with fine architectural detail the • over a reflected path away from the residential
art becomes part of the building, and the building or commercial area
becomes part of the art to make a project stand out.
Sound can be reduced to tolerable levels by
The design is the first step in creating a brick changing different parameters, such as height and
sculpture. The design process starts with an idea, or mass of the wall. Brick aids in the reduction of the
several ideas, then the architect and sculptor work noise since it is a massive material.
together to create a final design. Each idea is studied,
and after a process of elimination, one is chosen and
developed into a working design. The sculptor then
carves the design into the unfired clay brick. The brick
is coded for reassembly at the jobsite after the carving
is completed. The method of firing used in the carved
brick is the same used in the other brick. The brick
shrinks an amount approximately equal to one mortar
joint during the firing. The reassembly of the units
with mortar joints without distortion of the design is
allowed by this shrinkage.
9.10 CLEANING
There are two prominent methods of cleaning both
new and old masonry. One is using an abrasive
blasting technique commonly called sandblasting. This
method is popular for Europeans who prefer to
maintain a historic look on their buildings. They are
very sophisticated with equipment and workmanship,
and perform an excellent job cleaning masonry.
FIGURE 9.133 Brick sculpture. The American method prefers using cleaning
agents as a basis for cleaning masonry. Historic
9.9.11 SOUND BARRIER WALLS masonry, which is far younger than European historic
masonry, can be returned to the pristine, new look
Public awareness of noise pollution mandated
using specialized masonry cleaning solutions.
some modification of highway boundaries. Sound
Technology continues to advance the cleaning agents
barrier walls are part of the solution with brick sound
offering different products for the various colors and
barrier walls contributing a share Providing an
textures of brick masonry.
aesthetically pleasing appearance, brick sound barrier
walls reduce noise. The use of brick in this application
The final appearance of new masonry is highly
provides a human scale not found in other materials.
dependent on how clean the brick is maintained during
construction and the efficiency by which the brick is
When strategically located between the traffic
cleaned after construction. Ideally, the mason will clean
noise and the adjacent residential or commercial
the brick as the work progresses, but there is always
properties, sound barrier walls effectively distribute
some mortar debris left on the brickwork that should
noise:
be cleaned.
• into different paths
• into a diffracted path over the top of the barrier
BRICK MASONRY CONSTRUCTION 159
Although not practical on many commercial When the brick construction is complete, the
projects, a simple washing with a garden hose and a project may require a general cleaning. When this is
fiber brush shortly after the end of the workday is a necessary, the brick should be cleaned as soon as
highly effective method of keeping the completed brick practical, but not less than seven days, after the
clean. Typically, the bricklayer will make an effort to brickwork is finished. The method of cleaning and the
clean major mortar stains and droppings as the work cleaning agents should be the least required to
progresses. Taller brick walls will accumulate mortar minimize the potential of irreversible texture and color
droppings as the work progresses and these are impact on the brick. When possible, water alone is
cleaned at the end of the project. Water blasting will the preferred cleaning method.
normally remove these minor droppings in an effective
manner. Bef ore cleani ng the brickwork, t he brick
manufacturer should be consulted for recommendations
The contractor may be able to construct the scaffold on materials and methods effective in cleaning the brick.
far enough away from the wall to mitigate the mortar Such consultation will help in refining the general
droppings that attach to the wall. Scaffold plank should methods and recommendations given in Table 9.3.
be kept reasonably clean to minimize the mortar debris
that will potentially come in contact with the wall. The cleaning agents should never dry on the brick
Protection at the base of the wall will also keep the masonry surface. This is an issue that is particularly
mud and mortar spatter to a minimum and attention important in hot weather. Hot weather cleaning may
must be given to the rainy season, where rain splatters require additional personnel to keep water on the wall
will spray the debris on the base of walls if unprotected. during the cleaning process, or coordination of cleaning
in small or shady areas.
When the brick are laid, a diligent mason will use
the trowel to capture protruding mortar and finish the Cleaning should be done when the temperature
joints in the appropriate manner. After the joints are is at least 50°F (10°C). This assures that the cleaning
tooled, excess mortar can be cut away with a trowel agents will be effective in the cleaning process. Always
or brushed away with a non-metallic brush. Using a test the cleaning process on a small, inconspicuous
sponge with clean water on a very dense brick may be panel before the overall cleaning process.
an effective cleaning method.
The cleaning procedure should consider the Additionally, reinforced masonry performs well
following: because the materials; steel, masonry, grout, and
mortar, work together as a single structural unit. The
Coordinate the schedule for cleaning. Cleaning temperature coefficients for steel, mortar, grout and
should always be performed when the masonry units are similar allowing the different
protection requirements are minimal. Wait at component materials to act together through normal
least seven days for the mortar to sufficiently temperature ranges. Thus, disruptive stresses are not
cure and clean within one month of the generated by temperature changes which would destroy
completed brickwork. After one month mortar the bond and force transfer between the reinforcing steel
and the grout.
BRICK MASONRY CONSTRUCTION 161
Additionally, reinforced masonry materials work
together as a unit because the reinforcing steel is
locked into the masonry system. This mechanism is
developed through the grout.
Vertical reinforcement
Metal ties
The design and construction of any building with
seismic exposure must take into consideration Brick wall
connections to adjacent structural systems. If
connections hold together and make the structure Foundation
dowels
perform as a total system the structure will not only
surv iv e but also f unct ion, ev en after major
earthquakes. Wire mesh or reinforcement
6” 5 /2”
1
Slab on grade
Details of reinforcing bar size and spacing is
Finish
dependent on engineering requirements. All grade
connections must be satisfactory to transmit the forces
12”
due to the lateral and vertical loads. The elements
must be sufficiently tied together to act as a unit. 2 - #5
continuous
typ.
3”clear
Following are typical reinforced grouted brick
masonry wall details: 12”
Typical dimensions
Vertical reinforcement
Metal ties
Brick wall
Foundation
Vertical reinforcement
dowels Metal ties
Wire mesh or reinforcement
Slab on grade Brick wall
6”
Finish
grade Foundation
dowels Wire mesh or
reinforcement
Slab on grade
6”
Finish
24”
grade
12”
2 - #5’
s
continuous
24”
typ.
3”clear
12”
12”
24” 2 - #5’
s
continuous
Typical dimensions typ.
3”clear
6” 12” 6”
Vertical
Metal ties reinforcement
Brick wall
Foundation dowels
Wire mesh or
reinforcement
Slab on grade
16”
2 - #5
continuous typ.
3”clear
16”
Typical dimensions
FIGURE 9.140 Continuous footing, interior wall slab on grade (Rectangular shape).
1 - #4 nosing bar
12”
1”
71/2”
Wire mesh or
reinforcement
4”
Brick wall
Finished grade
12”
2 - #5’
s
continuous typ.
3”clear
16” Typical dimensions
2 x 4 @ 16”o.c. 2 x 4 @ 16”o.c.
16d @ 4”o.c. 2 x 4 plate 16d @ 4”o.c. 2 x 4 plate
Concrete slab Lightweight concrete Concrete slab Lightweight concrete
on grade on grade
5
/8”plywood
5
/8”plywood
2 x 12
floor joist
2 x 12
blocking @
48 “o.c.
Barrier membrane
6 x 65/16”@ 48” Barrier membrane
o.c. w/13/4” Anchor bolt
6 x 65/16”@ 48” Anchor bolt
diameter bolt
o.c. w/13/4”
each leg
Vertical reinforcement diameter bolt
each leg Vertical reinforcement
Typical dimensions
Typical dimensions
FIGURE 9.143 Masonry wall and wood floor
connection at grade (Joist perpendicular). FIGURE 9.144 Masonry wall and wood floor
connection at grade (Joist parallel).
164 MASONRY DESIGN MANUAL
- 6”
1’
Vertical Vertical #5 dowels x 30”
reinforcement long @ 48”o.c. Isolate steel
reinforcement
stagger weld column from grout
bars to column
Brick 1’
- 8”
pilaster
Typical dimensions
Brick wall 5
/8”diam. anchor
bolts @ 48”stagger
#3 ties @ 16”o.c.
Vertical
reinforcement
C w8 x steel column
Vertical reinforcement 16”square brick column
Typical dimensions
Brick wall #5’s @ 24”o.c.
x 6’- 0”typ.
2 sets of #3 ties @ 16”o.c.
Vertical
6 vertical bars 16”square brick column reinforcement C
Typical dimensions
FIGURE 9.145 Brick masonry pilaster and F IGURE 9.146 Brick masonry wall and
columns (Plan sections). concrete column steel (Plan sections).
BRICK MASONRY CONSTRUCTION 165
Metal ties Metal ties
2 x _ blocking
2 x _ @ 16”o.c. 2 x _ @ 16”o.c. @ 48”o.c.
4 x _ ledger w/ 3/4”
anchor bolts @ 48”o.c.
Anchor bolt
Joist hanger Brick wall
Metal ties
Vertical reinforcement
Metal strap Angle 6 x 6 x 5/16”
@ 48”o.c. w/ 3/4”
Anchor bolt
diam. bolt each leg
Vertical
2 x _ blocking
reinforcement
@ 48”o.c.
Metal ties Brick wall
2 x _ @ 16”o.c.
Anchor bolt
4 x _ ledger w/ 3/4”bolts @ 48”o.c.
Brick wall
F IGURE 9.151 Exterior wal l, rafters
perpendicular to wall, roof overhang clip angle
rafters to wall.
FIGURE 9.148 Exterior wall, joists parallel to
wall 4 x _ ledger, metal tie straps, no lightweight
concrete. 2x_@ 2 x _ blocking
16”o.c.
Metal ties
Vertical reinforcement
Metal strap Angle 6 x 6 x 5/16”@
48”o.c. w/ 3/4”
diam. bolt
Anchor bolt
each leg
Vertical reinforcement
2x_@ Joist hanger
16”o.c. 4 x _ ledger w/ 3/4”
anchor bolts @ 48”o.c. Metal ties Brick wall
Brick wall
2 x _ continuous
blocking
2 x _ blocking 2 x _ @ 16”o.c.
2 x _ @ 16”o.c. 2 x _ blocking
Angle 6 x 6 x 5/16”
Anchor bolt
@ 48”o.c. w/ 3/4”
diam. bolt each leg Brick wall
Vertical
reinforcement
Light metal steel
Metal ties #5 dowels joist
Brick wall
@ 24”o.c.
24” 36” Plate embedded
in masonry
FIGURE 9.155 Interior wall, rafters parallel FIGURE 9.158 Exterior wall, metal decking
to wall. parallel to wall.
BRICK MASONRY CONSTRUCTION 167
Brick wall
Brick wall
Plate embedded
in masonry
#5 dowels
#5 dowels @ 24”o.c.
@ 24”o.c. 24” 36”
24” 36”
Brick wall
Brick wall
Plate embedded
#5 dowels in masonry
#5 dowels @ 24”o.c.
@ 24”o.c. 24” 36”
24” 36” Plate embedded
in masonry
Metal ties
/2”diam. @ 24”o.c.
1
Vertical
Metal ties Metal decking reinforcement Metal decking
Lightweight concrete Lightweight
Vertical Brick wall
concrete
reinforcement
Brick wall
#5 dowels
#5 dowels @ 24”o.c. L 31/2”x 31/2”x 3/8”
@ 24”o.c. 24” 36” w/ 3/4”anchor
24” 36” Plate embedded in
bolts @ 32”o.c.
masonry
FIGURE 9.161 Exterior wall, metal decking FIGURE 9.164 Interior wall, metal decking
perpendicular to wall. parallel to wall.
168 MASONRY DESIGN MANUAL
Metal ties
1
/2”diam. @ 24”o.c. Concrete slab
Vertical
reinforcement Metal decking
Lightweight
Brick wall
concrete
#5 vertical
Concrete slab
Bond beam reinforcement
Vertical reinforcement
#3 vertical
1”metal strap
Bond beam reinforcement
Brick wall
Brick wall
F IGURE 9.170 Brick wall, bon d beam FIGURE 9.171 Brick wall, intersection.
intersection.
170 MASONRY DESIGN MANUAL
10
CONCRETE BLOCK
ceilings is a favorite approach of many architects. Left building dimensions and the cell layout must be able
exposed, concrete masonry is easily integrated into a to accommodate required structural members.
total living environment. Further, cell aligment must be coordinated for the
required continuity of structural members.
Concrete masonry is easily insulated and has a
high thermal mass. As a relatively heavy material, like There are many design solutions for the installation
stone, it slowly absorbs and releases heating or cooling of concrete block masonry. This chapter presents a
energy. Concrete masonry can provide additional limited number of generic design approaches
heating or cooling hours in which the HVAC system considered to be the most typical. Using this infomation
does not need to be utilized. Concrete masonry’ s as a foundation, the designer is encouraged to develop
inherent thermal mass makes it the ideal choice for details using the basic concepts of dimensioning,
creating a more energy-efficient building. detailing, and interfacing with other materials. If these
few general approaches are used, the designer can
be further assured that the mason can efficiently
10.2 LAYOUT AND ASSEMBLY implement the installation and any design can be
constructed with efficiency.
10.2.1 MODULAR CONSIDERATIONS
A significant cost in masonry construction is labor. 10.2.2 MODULAR DIMENSIONS
One way of reducing the amount of labor is using Table 10.1 shows the number of block units
dimensions that are based on the length of a concrete required for certain lengths and heights. For absolute
block (a module). This is known as modular precision, the number of stated block units will always
dimensioning. Modular dimensioning allows for whole measure 3/8 in. (9.5 mm) less than the given in the
units to be placed. This eliminates the labor and time table. This dimension can be adjusted by the mason
of field cutting and custom fitting any concrete blocks during construction, particularly in long or high walls.
to fit non-modular dimensions.
Figure 10.1 shows how the actual height
In addition to the assurance of economy, the quality dimension of the concrete masonry unit and the height
in concrete masonry construction is obtained when of the mortar joint combined to form a modular
modular consideration is given to details and layout. dimension.
The wall surface and unit module must match the
155/8”
/8”
3
155/8”
33/8”for 4”block
75/8””for 8”block
/8”
3
16'-0" 12 48 24
16'-4" - 49 -
1
16'-8" 12 /2 50 25
17'-0" - 51 -
17'-4" 13 52 26
17'-8" - 53 -
1 8”total unit height
18'-0" 13 /2 54 27
3
18'-4" - 55 -
18'-8" 14 56 28 75/8”block
19'-0" - 57 -
19'-4" 141/2 58 29 3
/8”
19'-8" - 59 -
20'-0" 15 60 30 FIGURE 10.2 Example of vertical modular
20'-8" 151/2 62 31 height.
174 MASONRY DESIGN MANUAL
FIGURE 10.4 Elevation of a running bond CMU wall with opening dimensions.
*
16’- 0”
8”concrete block
8”concrete block
Dowel
Concrete slab
Dowel from foundation
allows for short distance Waterproof
threading the CMU over membrane
reinforcement
Fill
12”(typ.)
1’- 0”
8”(typ.)
Continuous Continuous
reinforcement reinforcement
3”clear
1’- 8”
4” 10” 4”
FIGURE 10.7 Exterior wall with slab floor. FIGURE 10.8 Exterior wall with slab floor.
176 MASONRY DESIGN MANUAL
8”concrete block
8”concrete block
Continuous horizontal
reinforcement
Vertical
Continuous horizontal
reinforcement
reinforcement
Dowel
Vertical reinforcement
Dowel
1’- 0”
16”(typ.)
Continuous Continuous
reinforcement reinforcement
3”clear
1’
- 8”(typ.) 1’- 8”(typ.)
FIGURE 10.9 Exterior wall on slab floor. FIGURE 10.11 Exterior wall with raised slab
floor.
8”concrete block
Continuous
horizontal Dowel
reinforcement
Dowel
4”
6”min.
(typ.)
18”min.
(typ.)
1’- 0”min.
(typ.)
Continuous
12”min.
(typ.)
reinforcement
8”
(typ.)
Continuous
3”min.
reinforcement
3”min.
18”(typ.) 1’- 8”(typ.)
FIGURE 10.10 Exterior wall with raised floor. FIGURE 10.12 Interior wall with slab floor.
CONCRETE BLOCK 177
Continuous
horizontal Vertical reinforcement
reinforcement Waterproof
membrane (typ.)
4”concrete
4”
slab (typ.)
Wood plates
18”min.
with bolts
(typ.)
12”
4”
12”masonry
foundation wall
grouted solid
4”
Compacted
8”(typ.)
gravel or 16”
stone fill Typical dimensions
18”(typ.)
8”
Foundation
together.
reinforcement dowel
9”min. (typ.)
12”- 1 story
15”- 2 story
min. (typ)
Bond beam
Vertical steel
Parapet wall
Combined
lintel and
bond beam
Horizontal
steel in
lintel
Beam
Vertical steel units
each side of
Vertical opening Sash units
steel
Sill units
Horiz. bond
beam Tie
16”x 16”pilaster
Ledger
10.6.1 TIMBER CONNECTIONS Tension straps
connected
One of the most important issues to avoid in timber directly from wood
beam to CMU wall
framing to masonry walls is cross-grain bending on
the timber ledger. Cross-grain bending has such little
strength that the National Design Specification (NDS)
for timber design does not give stress values. Cross-
grain bending creates tension forces perpendicular to
the fibers of the timber member, in which timber is
extremely weak (Figure 10.18).
Wood or masonry
Diaphragm nailing
Ledger
F
Hanger
Force diaphragm pulls the
top of the ledger away
F
Tension straps
A moment (equal and opposite
connected directly
forces applied at a distance
from wood beam
apart) creates cross grain
to CMU wall
bending
2 x 14 @
16”o.c. (typ.)
8”concrete block Joist hanger
Pre-manufactured girder
and hanger
Horizontal reinforcement
8”concrete block
FIGURE 10.24 Wood beam to CMU wall with
drag strut (2 sides).
FIGURE 10.21 Pre-manufactured wood girder
to CMU wall.
Vertical reinforcement Perimeter nailing
Vertical reinforcement
Ledger
Perimeter Tension strap connected from wood Strap @ 48”o.c.
nailing /8”plywood
5
beam directly to CMU wall alt. each side
5
/8”plywood
Perimeter nailing
Perimeter nailing
Tension tie
Vertical /8”plywood
5
reinforcement Strap @ 48”o.c. (typ.)
Vertical
Horizontal reinforcement /2”plywood
1
reinforcement
8”concrete
block wall
8”concrete Horizontal
block reinforcement
2 x 14 @ 2 x roof
16”o.c. (typ.) rafters (typ.)
Joist hanger
Joist hanger
FIGURE 10.23 Wood beam to CMU wall with FIGURE 10.26 Wood rafter to CMU parapet wall
drag strut. (rafter perpendicular to wall).
CONCRETE BLOCK 181
Perimeter nailing
8”concrete
block wall Steel beam
Vertical reinforcement
Vertical reinforcement
#5 @ 16”o.c.
footing dowel /2”dia. @ 24”o.c. (typ.)
1
Horizontal
(typ.) reinforcement
Metal decking
Slab reinforcement
Concrete slab
18”
#5 dowels
12”
@ 24”o.c.
(typ.)
3”CLR.
16” 8”concrete
block wall
Typical dimensions Steel beam
Horizontal Horizontal
reinforcement reinforcement
8”concrete 8”concrete
block Metal decking block Metal decking
wall wall
Slab reinforcement Slab reinforcement
#5 dowels
@ 16”o.c.
#5 dowels
(typ.)
@ 24”o.c.
(typ.)
Vertical reinforcement
Vertical reinforcement
Horizontal
reinforcement Horizontal
reinforcement
8”concrte
block Metal decking 8”concrete
wall block Metal decking
Slab reinforcement wall
Slab reinforcement
Concrete slab
Concrete slab
#5 dowels
@ 16”o.c.
#5 dowels
(typ.)
@ 24”o.c.
(typ.)
Vertical reinforcement
1
/2”dia. @ 24”o.c.
(typ.)
Horizontal #5 dowels
@ 16”o.c. Metal decking
reinforcement
(typ.) Slab
reinforcement
8”concrete Concrete
block Metal decking slab
wall
Slab reinforcement
Concrete slab
#5 dowels
@ 24”o.c.
(typ.)
Bar joist
Horizontal
Plate embedded reinforcement
in masonry
Vertical
reinforcement 12”Concrete
block wall
1
/2”dia. @ 24”o.c. 10.7 CORNER PATTERNS
(typ.)
#5 dowels
@ 16”o.c. Metal decking While maintaining the modular dimensions and
(typ.) Slab patterns on a straight wall can be accomplished with
reinforcement relative ease, some issues can arise when transitioning
Concrete around corners. An 8 in. (203 mm) wide unit turns a
slab
corner with ease since the 8 in. (302 mm) width is half
the unit length of 16 in. (406 mm). This simple
configuration is shown in Figure 10.42. Other wall
widths are a more difficult challenge in turning a corner,
but with the correct unit and placement, this challenge
can be overcome (Figures 10.37 through 10.41, 10.43,
and 10.44). This section provides some examples of
Bar joist how the modular dimensions can be maintained at the
Horizontal corner details.
reinforcement
Vertical
reinforcement 12”Concrete
block wall
Mo
du Mo
le 6” du
of le
8” of
8”
4” 4 ”
4” +
le
du 4” 16” le
16” Mo du 6”
8” o
16” 8 ”M
16”
16” 8”
16”
16” 4” 14”
6”
16” 6”
4”
16”
16”
8” 16”
16” 16”
8”
4” 16” Mo 14”
Mo du
du 4” le
le +4
of
8” ” - 2”
le
d ule odu
M
Mo 8”
8”
FIGURE 10.37 4" (102 mm) wall to 4" (102 FIGURE 10.39 6" (152 mm) wall to 6" (152
mm) wall. mm) wall.
4”
16” 6”
16”
4” 12”
16”
4” 6” 16”
16”
16”
8”
8” 6”
16” 16”
12”
8”
16”
16”
8”
Mo
du
le
of
6” Mo 8”
du l e
le d u
of 16” o
8”
8 ”M 8”
16” 16”
8”
8”
16” 16”
16”
8”
16”
14”
8”
8”
8”
16”
16” 8”
16”
16” 16”
16” Mo 16”
16” du 8”
6” le
” of
+6 8”
8”
ule of
Mod ule
8” d
Mo
FIGURE 10.41 6" (152 mm) wall to 8" (203 FIGURE 10.43 8" (203 mm) wall to 12" (304
mm) wall. mm) wall.
Mo Mo
du du
le le
of of
8” 8”
o f
ul e le
16” od 8” du
”M 8” Mo + 4”
8
16” 16” 8”
8” 8”
16” 16”
16” 16”
8” 8”
8”
16”
16”
16”
16” 16”
16” 16”
Mo 8”
du 16” 8”
le Mo
of du
8” 8” le
e of of
l 8” 8”
du of
Mo le
du
Mo
FIGURE 10.42 8" (203 mm) wall to 8" (203 FIGURE 10.44 12" (304 mm) wall to 12" (304
mm) wall. mm) wall.
186 MASONRY DESIGN MANUAL
16
”c
en
ter
s
FIGURE 10.45 Arrangement of steel and open 8” x 8” x 16” Four No. 6 and two No. 5
end units - 16" (406 mm) and 24" (610 mm) spacing. bars detailed
FIGURE 10.47 28" x 16" (711 x 406 mm) stan-
dard pilaster in 12" (305 mm) wall.
CONCRETE BLOCK 187
16”pilaster
alternate unit 12”x 8”x 16”
Four No. 5
bars detailed
Four No. 5
bars detailed
)
mm
( 6 10
4” 2”(51”mm)
2
11/2”(38 mm)
Metal strap
Shear wall
Flange Metal straps at
4’- 0”(1.22 m)
o.c. vertical
Grouted
cells
As = 0.1 in2/ft
(211 mm2/m)
FIGURE 10.53 Exploded isometric view of FIGURE 10.55 Metal strap anchorage and grout
reinforcing steel for intersecting walls. reinforcement bonding at wall intersection.
CONCRETE BLOCK 189
Vertical steel
Continuous horizontal
Bar in grout space reinforcement
Bond beam
units
2’- 0”lap
Lintel
reinf.
Lintel units
FIGURE 10.56 Typical wall connections - Plan
of joint reinforcement showing intersection and
alternate lapping.
FIGURE 10.58 Lintel and bond beam detail.
Caulking
Gasket
Stop horiz.
bars each
side of joint
except at Backer rod
chord bars
1
/2”typ.
/8”typ.
3 Backer rod 1
/2”maximum control
joint width
Notes: 1
/2”maximum
1. Table values are based on the use of horizontal control joint width
reinforcement having an equivalent area of not less
than 0.025 in./ft. (52.9 mm/m) of height to keep
For Ratings Up to and Including 4 Hours
unplanned cracks closed.
2. Criteria applies to all concrete masonry units.
3. This criteria is based on experience over a wide FIGURE 10.61 Typical fire rated CMU wall
geographical area. Control joints spacing should control joints.
be adjusted up or down where local experience
justifies but no farther than 25 ft. (7.62 m)
1
NCMA TEK Note 10-2B
192 MASONRY DESIGN MANUAL
Door
Note: For control joints in head section over openings install divi-
sion strips in 8”sections with alternating key each side of
joint.
Stop
Sealant
FIGURE 10.62 CMU wall control joint with 11/2”rough buck
reinforcement passing through the joint. Shim space
3
/4”frame
11/2”rough buck
Shim space
3
/4”frame
FIGURE 10.63 Exterior door jamb - Butt FIGURE 10.66 Interior door jamb (6" CMU) -
method. No plaster.
CONCRETE BLOCK 193
Plaster
Door
Door
Plaster
Door
Door
Masonry opening
Door opening
Door
Plaster
Masonry opening
FIGURE 10.69 Interior door jamb (6" CMU) -
Metal frame wrap
No plaster.
around type
Plaster
Door
Door
11/2”frame
Tee anchor (or wire anchor) in mortar
joint. Frame installed before block work
Sealant
Shim space
FIGURE 10.73 Metal frame with tee anchor in
mortar joint.
FIGURE 10.70 Interior door jamb (6" CMU) -
Plaster one side.
194 MASONRY DESIGN MANUAL
Caulking
Masonry
opening
Shim space
FIGURE 10.76 Window jamb.
Door opening 1 /2”frame
1
Door
Caulking
Rough header
Masonry
opening
Shim space
Door /4”frame
3
opening
Stop
Door
Caulking
g
Heat Gain
3 am 6 am 9 am Noon 3 pm 6 pm 9 pm
Time
FIGURE 10.80 Masonry vs wood stud thermal lag time. (NCMA TEK Note 6-3).
196 MASONRY DESIGN MANUAL
Window
opening
Reinforced grout
filled cell at 48”
o.c. maximum
Cleanouts,
when required
Continuous bars
in foundation
8”
Concrete slab
12”
8”
2” Waterproof membrane
4” 18”
10” um
Compacted free draining blanket of inim ions
4” ”m en
s
clean gravel or crushed stone 12
l dim
a
pic
12 18” Ty
Ty ”m
p ica ini
mu
ld m
im
en
sio Splices in reinforcement to
ns
be staggered and lapped
per code
Anchor bolts
Door
opening
Continuous
grout filled
bond beam
Cleanouts,
when
required
Reinforcing bars
continuous in
8” foundation
Concrete slab
12”
8”
2” Waterproof membrane
4” 18”
10” um
inim ons
4” Compacted free draining blanket of ”m si
clean gravel or crushed stone 12 en
l dim
a
pic
12 18” Ty
Ty ”m
p ica inim
ld um
im
en Splices in all reinforcement shall be
sio
ns staggered and lapped per code
Wood Wood
frame frame
roof roof
W indow W indow
Waterproof membrane
18”minimum
Fill 10”
12”
4” 4”
Reinforced as Reinforced as
8”min. required required 8”min.
18” 18”
12”minimum 12”minimum
Typical dimensions Typical dimensions
Floor joists
Floor joists
#4 cont.
”min.
18”min.
18”minimum
6’
12”min.
blocks below
floor line
Grout fill all cells Grade
12”minimum
Solid blocking
12”min.
w/bolts
”min.
8”min.
6’
#4 cont.
#4 cont.
12”
Typical dimensions
12” minimum
Typical dimensions
minimum
FIGURE 10.84 Typical CMU foundation wall FIGURE 10.86 Typical CMU foundation wall
perpendicular to floor joists. perpendicular to joists.
Solid blocking -
2”x 6”foundation grade bolts as required
redwood or treated sill for horizontal
loads
Blocking Plywood
”min.
Floor joists
18”minimum
6’
#4 cont.
Grade
Floor Joist
joists
18”min.
12”min.
#4 cont.
”min.
6’
#4 cont.
12” Typical dimensions
minimum
12”
minimum Typical dimensions
FIGURE 10.85 Typical CMU foundation wall FIGURE 10.87 Typical intermediate CMU wall
parallel to floor joists. parallel to joists.
200 MASONRY DESIGN MANUAL
#4 cont.
”min.
6’
#4 cont. min.
12”minimum
Typical dimensions
reinforcement as
required by design
Dowel Dowel
10”min.
18”minimum
18”minimum
Grade
12”min.
Typical dimensions
12”minimum
Typical dimensions
12”minimum
FIGURE 10.89 Typical exterior wall - Slab floor. FIGURE 10.90 Typical interior wall - Bearing
partition, slab floor.
CONCRETE BLOCK 201
10.15.6 ROOF CONNECTION DETAILS FOR RESIDENTIAL CONSTRUCTION
Nails to blocking
Horizontal
reinforcement
FIGURE 10.91 Typical joist parallel to wall. FIGURE 10.93 Wood tie beam.
Saw block to
Cripples
match roof pitch
for gable
Brace 2”x 6”
2 x _ ledger
Horizontal reinforcement
Vertical reinforcement
Vertical reinforcement
8”concrete block
8”concrete block
FIGURE 10.92 Typical masonry gable. FIGURE 10.94 Typical wood frame gable.
202 MASONRY DESIGN MANUAL
The walls are designed for lateral pressure of not 10. Block fence to be placed at center of “
I”type
less than 10 pounds per square foot (479 Pa) in foundation and at either edge of “ L”type
accordance with the minimum requirements stated in foundation.
ASCE 7-05, Section 6.4.2.1.1.
6’- 0”max.
Designs are the common types used, grade beam, Joint reinforcement
and spread footing. Footings should be level. Use or 1-#4 horizontal at
step footings for uneven terrain with each step a height midheight
24”lap length
to fit the masonry module, typically 4 in. (102 mm) or 8
#4 vertical dowels
in. (203 mm). @ 48”o.c. in
foundation
10.16.2 GENERAL NOTES Finished grade
2”min.
Designs are not to be used for retaining walls and 1 - #4 horizontal
1’- 0”
are based on the following criteria: in foundation
3”CLR.
1. Concrete for footing to be f’ = 2,500 psi (13.9 1’- 6” Alternate bend
c
MPa) minimum at 28 days or optional 1 part
Portland cement, 21/2 parts sand and 31/2 parts FIGURE 10.95 6 in. concrete masonry block
gravel with a maximum 71/2 gallons of water wall fence with “
I”type foundation.
per sack of cement.
2. Concrete block units shall conform to ASTM
C 90. #4 vertical
reinforcement
3. Reinforcing Steel to be deformed and conform
@48”o.c. 1-#4 horizontal at top
to ASTM A 615, grade 40 or grade 60.
Minimum lap length shall be 24 in. (610 mm).
Joint reinforcement
6’- 0”max.
#4 vertical
6 in. (152 mm).
dowels @ 48”
5. Center vertical reinforcement in the concrete o.c. in
block cell. foundation
Finished grade
6. Concrete block units shall be laid in running
2”min.
bond. 2 - #4 horiz.
in foundation 1’- 0”
7. Concrete block cells to have vertical continuity
of the cells. All cells containing reinforcement 3”CLR.
shall be solidly grouted (vertical and horizontal 2’- 0”
reinforcement).
FIGURE 10.96 6 in. concrete masonry block
wall fence with “
L”type foundation.
CONCRETE BLOCK 203
11. When inspection is required, first inspection The designs given for continuous footing walls
to be after trenches are ready for concrete typically satisfy the design criteria for Exposure C.
foundation and all required steel is tied in
place. The second inspection shall be when
the vertical and horizontal steel is in place,
10.17 RETAINING WALLS
but not grouted.
The popular use of masonry in retaining walls is a
12. Foundat ion m ust be pl aced agai nst
result of the ease of construction combined with the
undisturbed soil with no appreciable slope
inherent visual beauty. With proper engineering and
of side walls on all types of foundations.
reinforcing steel, masonry retaining walls also provide
13. Height of fences shall comply with all high structural integrity.
provisions of the local building code.
Retaining walls are built to restrain a mass of earth
10.16.3 CONTINUOUS FOOTING WALLS or other material. They have the capacity to resist
overturning and sliding forces. Because overturning
Continuous footing designs are based on the and sliding can lead to catastrophic failure, the code
applicable Exposure Category as defined in IBC requires a 1.5 safety factor (2006 IBC Section 1806.1).
Section 1609.4. Sliding is resisted by the friction between the footing
and the soil, plus the pressure of any earth in front of
IBC Section 1609.4 the wall. A key at the bottom of the footing can provide
1609.4 Exposure category. For each wind direction additional resistance to sliding. In the 2006 IBC, Table
considered, an exposure category that adequately 1804.2 lists allowable values for lateral bearing
reflects the characteristics of ground surface pressure and the coefficient of friction, based on the
irregularities shall be determined for the site at which type of soil. Overturning is resisted by the weight
the building or structure is to be constructed. (vertical loading) of the wall, footing, and soil resting on
Account shall be taken of variations in ground the footing.
surface roughness that arise from natural topography
and vegetation as well as from constructed features. The soil pressure is usually highest under the toe
(front bottom edge of footing) and should not exceed
1609.4.3 Exposure categories. An exposure the bearing capacity of the soil which it rests upon.
category shall be determined in accordance with the
following: The wall must also be strong enough to prevent
failure at any point in its height due to the force of the
Exposure B. Exposure B shall apply where the retained material, which is resisted by the reinforcing
ground surface roughness condition, as defined steel in the masonry wall.
by Surface Roughness B, prevails in the upwind
direction for a distance of at least 2,600 feet (792 In order to reduce lateral pressure loads on a
m) or 20 times the height of the building, whichever retaining wall, drainage for water behind the wall should
is greater. be provided. This drainage prevents excessive
hydrostatic pressure from developing. Two common
Exception: For buildings whose mean roof height methods of drainage to relieve hydrostatic pressure
is less than or equal to 30 feet (9144 mm), the are shown in the figures below. In Figure 10.97 gravel
upwind distance is permitted to be reduced to is used to direct water into a plastic tube, with
1,500 feet (457 m). perforations on top, that will channel the water out and
away from the wall. In Figure 10.98, a pre-manufactured
Exposure C. Exposure C shall apply for all cases and proprietary geo-filter mesh is used to direct the
where Exposures B or D do not apply. water down to a gravel channel. Water is then directed
through the base of the wall by weep holes or weep
Exposure D. Exposure D shall apply where the joints.
ground surface roughness, as defined by Surface
Roughness D, prevails in the upwind direction for If drainage is not provided, hydrostatic pressure
a distance of at least 5,000 feet (1524 m) or 20 must be considered. The hydrostatic pressure could
times the height of the building, whichever is double or triple the soil pressure.
greater. Exposure D shall extend inland from the
shoreline for a distance of 600 feet (183 m) or 20
times the height of the building, whichever is
greater.
204 MASONRY DESIGN MANUAL
FIGURE 10.97 Cantilever retaining wall with The stability of a gravity retaining wall depends on
gravel and perforated pipe drainage. the weight of the wall and the weight of soil bearing on
the footing. As the height of the retaining wall
increases, or the amount of retained soil increases,
and the base thickness must also increase. Uplift
pressure at the back of the wall (the heel) is avoided by
Proprietary designing the gravity retaining wall thick enough at the
geo-filter mesh base so that the resultant of all forces (overturning force
and vertical loads) falls within the middle one-third of
the base. The eccentricity of the resultant force is equal
Gravel channel
to or less than one-sixth of the base width. When the
with weep holes in
vertical joints only eccentricity (e) is equal to one-sixth the base width
exactly, the maximum footing pressure on the soil at
the front edge of the base (toe) will be twice the average
pressure on the soil.
Compression buttress
Depends on weight or brace
for stability
Cross-Section
10.17.3 CANTILEVER RETAINING WALLS Adjacent slabs are often tied into the foundation
(Figure 10.103(b)) reducing the need for a large
The most common type of retaining wall is the foundation. These slabs help resist sliding forces and
cantilever retaining wall (Figures 10.102 and 10.103). contribute to reducing soil bearing pressure and
The tension stresses which develop in the wall are overturning forces.
resisted by reinforcing steel placed in the wall and off
center toward the soil side (tension face) of the wall.
The base resists sliding, overturning and rotating due
Property line
to the lateral loading and must also be large enough
to assure that the bearing capacity of the soil is
adequate.
Stem
Heel Toe
Property line
Tension face Compression
face
Heel Foundation
Toe
Adjacent slab
Cantilever retaining walls can be designed with a (b) Retaining wall adjacent to property line with foundation
minimum length of heel or toe, which is useful in limited tied into floor slab to increase the sliding resistance.
space areas such as near property lines and existing
utility lines (Figure 10.103). These walls require special * Provide at least a 2" (50.4 mm) footing extension to allow for
attention to assure they can resist the lateral earth construction tolerances.
forces and overturning moment through their own weight
and strength. When there is no footing heel on a property
FIGURE 10.103 Property line type retaining
wall, there will be no resisting soil mass and thus the
walls.
wall foundation may be large and heavy.
Retaining walls must be designed to safely resist Cantilever retaining wall footings must be placed
overturning and sliding due to the forces imposed by on firm, undisturbed soil. In areas exposed to freezing
the retained backfill. The factor of safety against temperatures the base of the footing should be placed
overturning should ideally be at least 2.0 and the factor below the frost line.
of safety against sliding not less than 1.5. In addition,
the bearing pressure under the footing or bottom of the Backfilling against retaining walls should be
retaining wall should not exceed the allowable soil delayed for at least 7 days after placement of grout.
bearing pressure, or should provide a factor of safety of During backfilling, heavy equipment should not
at least three over the ultimate bearing capacity. approach closer to the top of the wall than a distance
equal to the height of the wall.
CONCRETE BLOCK 207
Care should also be taken to avoid exerting large To give an indication of the material and size of a
impact forces on the wall, such as dumping a large retaining wall, Figure 10.104 provides two typical types
mass of earth against the wall. Ideally, backfill should of cantilever retaining walls - Heel Dominate and Toe
be placed in 12 to 24 in. (305 to 610 mm) increments, Dominate. The heel dominate retaining wall has the
with each lift being compacted by hand equipment. majority of the foundation extending into the retained
earth. The toe dominate retaining wall has the majority
Prov isi ons m ust be made to prev ent the of the foundation extending into the non-retained side
accumulation of water behind the face of the wall and of the wall.
to reduce the possible effects of frost action. In most
cases, weep holes spaced 4 to 8 ft (1.2 to 2.4 m) apart The design tables for the cantilever retaining walls
along the base of the wall are sufficient. are for retained soil with no slope (level soil at the top
of the retaining wall). Design lateral pressures are for
Where heavy prolonged rains are anticipated, a 30 psf per foot of depth and for 45 psf per foot of depth.
continuous longitudinal drain along the back of the wall
may be used in lieu of weep holes. The design criteria for the tables is based on the
following material assumptions:
Climate, soil conditions, and type of construction
determine the need for waterproofing the back face of Masonry design strength, f’
m
= 1,500 psi
retaining walls. Waterproofing is recommended in Concrete masonry units, ASTM C 90
areas subject to severe frost action; in areas of heavy Grout strength, 3,000 psi
rainfalls; and when the backfill material is relatively Footing concrete strength, 3,000 psi
impermeable. The top of masonry retaining walls Reinforcement, Grade 60
should be capped or otherwise protected to prevent
water entry into hollow cores.
Horizontal reinforcement
2”clear
CMU Vertical reinforcement
Continuous #4
Vertical Drainage system reinforcement (typ.) H
reinforcement typically gravel and Top reinforcement
H
perforated pipe
12” (typ.)
Top
reinforcement Bottom
12” (typ.) reinforcement 3”
clr. D
Lateral 10” 6'-8" #5 @ 8" #5 @ 16" 4'-0" 1'-0" #6 @ 24" 5'-0" 1'-0" #6 @ 24"
Pressure 10” 6'-0" #4 @ 8" #4 @ 16" 3'-6" 1'-0" #5 @ 24" 4'-6" 1'-0" #6 @ 32"
45 psf 8” 5'-4" #5 @ 16" #4 @ 32" 3'-0" 1'-0" #5 @ 32" 3'-9" 1'-0" #6 @ 32"
8” 4'-8" #4 @ 16" #4 @ 32" 2-6" 1'-0" #4 @ 32" 3'-0" 1'-0" #5 @ 32"
8” 4'-0" #4 @ 32" #4 @ 32" 2'-0" 1'-0" #4 @ 32" 2'-3" 1'-0" #4 @ 32"
10” 8'-0" #5 @ 8" #5 @ 16" 4'-6" 1'-0" #5 @ 16" 4'-0" 1'-0" #6 @ 24"
10” 7'-4" #4 @ 8" #5 @ 16" 4'-0" 1'-0" #6 @ 24" 3'-6" 1'-0" #6 @ 32"
Lateral 10” 6'-8" #5 @ 16" #4 @ 16" 3'-6" 1'-0" #5 @ 24" 3'-3" 1'-0" #5 @ 32"
Pressure 10” 6'-0" #5 @ 16" #5 @ 32" 3'-0" 1'-0" #5 @ 32" 3'-0" 1'-0" #5 @ 32"
30 psf 8” 5'-4" #4 @ 16" #4 @ 32" 2'-6" 1'-0" #4 @ 32" 2'-6" 1'-0" #5 @ 32"
8” 4'-8" #4 @ 32" #4 @ 32" 2'-3" 1'-0" #4 @ 32" 2'-0" 1'-0" #4 @ 32"
8” 4'-0" #4 @ 32" #4 @ 32" 2'-0" 1'-0" #4 @ 32" 1'-6" 1'-0" #4 @ 32"
1
Allowable values: Bearing = 3000 psf, Lateral Bearing = 200 psf with an increase of 100% per foot of depth, Coefficient of Friction = 0.35
Lateral 12” 6'-8" #5 @ 8" #5 @ 16" 4'-6" 1'-6" #6 @ 24" 5'-6" 1'-3" #6 @ 24"
Pressure 12” 6'-0" #4 @ 8" #4 @ 16" 4'-0" 1'-0" #6 @ 32" 5'-0" 1'-0" #6 @ 32"
45 psf 12” 5'-4" #5 @ 16" #4 @ 32" 3'-6" 1'-0" #5 @ 32" 4'-6" 1'-0" #5 @ 32"
12” 4'-8" #4 @ 16" #4 @ 32" 3’
-0" 1'-0" #5 @ 32" 3'-9" 1'-0" #4 @ 32"
12” 4'-0" #4 @ 32" #4 @ 32" 2'-6" 1'-0" #4 @ 32" 3'-0" 1'-0" #4 @ 32"
10” 8'-0" #5 @ 8" #5 @ 16" 4'-9" 1'-0" #6 @ 16" 4'-9" 1'-0" #6 @ 16"
10” 7'-4" #4 @ 8" #5 @ 16" 4'-3" 1'-0" #5 @ 16" 4'-3" 1'-0" #5 @ 16"
Lateral 10” 6'-8" #5 @ 16" #4 @ 16" 3'-9" 1'-0" #6 @ 24" 4'-0" 1'-0" #6 @ 24"
Pressure 10” 6'-0" #5 @ 16" #5 @ 32" 3'-3" 1'-0" #6 @ 32" 3'-6" 1'-0" #6 @ 32"
30 psf 8” 5'-4" #4 @ 16" #4 @ 32" 3'-0" 1'-0" #5 @ 24" 3'-0" 1'-0" #5 @ 24"
8” 4'-8" #4 @ 32" #4 @ 32" 2'-6" 1'-0" #4 @ 24" 2'-6" 1'-0" #4 @ 24"
8” 4'-0" #4 @ 32" #4 @ 32" 2'-3" 1'-0" #4 @ 32" 2'-3" 1'-0" #4 @ 32"
1
Allowable values: Bearing = 3000 psf. Lateral Bearing = 200 psf with an increase of 100% per foot of depth. Coefficient of Friction = 0.35
2
Rankine value of 0.36 applied to the 100 psf vertical surcharge
CONCRETE BLOCK 209
10.17.4 SUPPORTED WALLS Load
Compression face
supported top and bottom (Figure 10.105). Each wall
type must be designed and reinforced accordingly.
Note that the location of reinforcement may be on the Load
opposite face of a cantilevered retaining wall for
Tension face
maximum efficiency. Continuity of the connections at
the top and the bottom must be developed by proper
reinforcement in order to provide the required degree
of fixity.
The segmental retaining walls offer many design the toe of the structure for stability. Shear capacity is
advantages, which include aesthetics, design flexibility, an important component to assure that the units act
economics, ease of installation, performance and together as a coherent mass, since the system consists
durability. of individual units dry stacked upon each other.
The design of segmental retaining walls can be Shear capacity provides a means of transferring
conventional (gravity), soil-reinforced or geosynthetic. lateral forces from each course to the adjacent course.
Due to the concrete unit size, shape, batter, and other This is provided by the frictional resistance between
conditions, the structural capacity of the segmental segmental reinforced wall units in the form of keys or
retaining wall system will v ary. Manuf acturer leading/training lips.
recommendations should be followed for design
information. When using multiple depth walls, taller segmental
retaining walls can be achieved. These walls increase
10.17.5.1 CONVENTIONAL OR GRAVITY the weight of the wall system and provide a steady
base and greater resistance to soil pressures.
Conventional or gravity segmental retaining walls
can be constructed with either single or multiple depths The conventional or gravity retaining wall is usually
of units (Figure 10.108). The conventional segmental battered so that the wall steps back into the hillside.
retaining wall structure must have enough mass to The force of gravity on the heavy units resists lateral
prevent both sliding at the base and overturning about soil pressure to form a functional retaining wall.
s
Exc avation boundarie
Total height of wall
Wall
(b) Multiple Depth and Battered Segmental Wall embedment depth
Building walls below grade are known as Windows and window wells of a variety of shapes
foundation walls. These walls may serve as support and sizes can easily be accommodated with the
for above grade walls or other structural members, modular nature of concrete masonry, providing
such as enclosure walls around excavated areas or basements with warm, natural lighting. Glass block
as both supporting and enclosure walls. units can be incorporated into the walls in lieu of
traditional glass windows for additional security and
Concrete masonry is excellent for basement and privacy.
foundation wall construction due to economy, durability,
strength, noise insulation, termite resistance and fire 10.18.5 ENERGY EFFICIENCY
resistance. These attributes justify the widespread use
of concrete block masonry for foundation walls and The consistent temperatures in basements are due
basements. to the thermal mass of concrete masonry, consequently
providing a more comfortable area. Large windows wells
Basements are typically built with standard gray and walk-out basement doors may also contribute to
block which can be unfinished or used as a base for heat by allowing solar energy into basements.
other finish treatments such as plaster, paint or
wallboard on furring strips. Attractive finishes to the 10.18.6 FIRE RESISTANCE
interior walls of a basement can be achieved with
architectural units. Concrete masonry successfully resists the passage
of flames, smoke and heat. Building codes give high
10.18.1 MAINTENANCE AND LOW COST fire ratings to concrete masonry walls, making efficient
One of the advantages of concrete masonry fire walls for hotels, apartments and other structures.
construction is the high quality and performance which These concrete masonry attributes are excellent for
makes the concrete masonry units competitive with basements to safeguard against the spread of electrical
other construction materials. In cases where the and mechanical fires.
212 MASONRY DESIGN MANUAL
#5’
s @ 48”o.c.
10.18.9 BASEMENT DESIGN horizontal
Crawl space walls and curtain walls frequently fall Typical Dimensions
and Detailing
into this large stem wall definition. The basement, crawl
space, and stem walls are laterally supported at the FIGURE 10.110 Typical basement wall.
top by a first floor diaphragm.
Vertical
reinforcement
10.18.10 WATER PENETRATION RESISTANCE
Basement walls must resist water penetration in
order to prevent water damage to adjoining storage
Stem wall and habitable spaces. To mitigate below grade water
problems, three techniques are commonly and
collectively employed:
#5’s @ 48”o.c.
vertical 1. A surface drainage system to collect and direct
water away from the foundation is installed.
Footing
2. Dampproofing or waterproofing systems are
applied to the masonry walls.
3. Drainage is provided to direct surface and roof
FIGURE 10.112 Stem wall. water away from the basement.
Gutters and downspouts will collect water from the Backfilling is one of the most critical operations in
roof of the building and deposit it away from the basement construction. Proper backfilling will prevent
foundation. When necessary, water from downspouts or minimize wall cracking during the construction
should be directed onto splash blocks or carried away process. Walls designed to be supported at the top
using plastic tubing. With the use of roof overhangs, may crack or even fail if not properly braced until the
balconies, and porches the soil that surrounds the lateral supports at the top of the walls are provided.
foundation may be protected from the direct exposure
of rain. To prevent infiltration of surface water, planting One bracing scheme which has been used for
of shrubbery or the placement of a thin layer of residential basement walls is shown in Figure 10.116.
impermeable soil over the backfill immediately adjacent Considerably more bracing may be required for high
to the foundation wall will further help. walls or large backfill pressures.
”
-0
8’
”
-0
8’
2 x 10
plank
2x4
cleat 2 x 10
brace
2 x 4 strut
brace
Two 2 x 6 stakes
driven into firm soil
at least 12”
FIGURE 10.116 Typical bracing scheme for concrete masonry basement walls.
CHAPTER
11
REINFORCING STEEL
Compression
Lateral Force
Lateral Force
Compression
Tension Tension to the left. While the masonry on the left side of the
wall is being squeezed in compression, the reinforcing
Reinforcing steel on the right side of the wall, closest to the earth,
Reinforcing
steel
steel is being pulled into tension.
Grout
Grout
In Figure 11.4, note how the reinforcement is
placed closer to the tension side than the compression
Concrete masonry Brick side. This location is advantageous in a retaining wall
application since the load is always causing tension
on the right and compression on the left.
FIGURE 11.2 Forces transmitted through
masonry and grout to steel.
“
d”distance
Tension side
Compression side
squeezing together in the center, placing the masonry
into compression. The bottom of the beam, however,
is pulling apart in the center, putting it in tension. When
the limited tension capacity of the masonry is
exceeded, masonry cracks and the steel reinforcement
resists the tension force. This combination of steel
reinforcement and masonry extends the application and
use of masonry for structures.
d/2
d
Shear
cracks
Maximum Ground Motion for the Continental U.S. –0.2 sec Spectral Acceleration
(5% critical damping), Site Class B (2006 IBC Figure 1613.5(1))
Maximum Ground Motion for the Continental U.S. –1.0 sec Spectral Acceleration
(5% critical damping), Site Class B (2006 IBC Figure 1613.5(2))
If SDC A walls are part of the lateral force-resisting The required area of 0.20 in.2 (129 mm2), equates
system (shear walls), walls may be designed to one #4 bar, which is 0.20 in.2 (129 mm2) in cross-
empirically in accordance with 2005 MSJC Code sectional area.
Section 1.14.2.2. Lateral force-resisting walls in SDC’ s
In addition to the above, columns require ties with
A and B shall have minimum reinforcement of 0.20
a minimum of two ties within the top 5 in. (127 mm) of
in.2 (129 mm2) in cross-sectional area and shall be
the column.
provided at corners, within 16 in. (406 mm) of openings
0.20 in2 reinforcement area min.
2
0.20 in reinforcement at top of wall & at roof and floor
area, (minimum each levels
0.20 in2 reinforcement way at spacing shown)
Top of roof area (minimum around Top of
openings) parapet
24”minimum
but not less
than 40 bar
diameters
0.20 in2 reinforcement 24”minimum but 0.20 in2 reinforcement 0.20 in2 reinforcement area min. at
area (minimum around not less than 40 area, (minimum each top of wall & at roof and floor levels
openings) bar diameters way at spacing shown)
Top of parapet
Top of
roof
4’-0”maximum spacing 4’
-0”maximum spacing of 0.20 in2 reinforcement
of vertical reinforcement horizontal reinforcement area min. at base of wall
or in top footing
levels.
required
also be provided.
fully grouted using open-end units or hollow units with
full head joints. When using solid units for stack bond Vertical reinforcement
masonry, the head joints must be fully mortared. in grouted cells spaced
Additionally, the maximum spacing of reinforcement 4’- 0”o.c. max.
for stack bond masonry is 24 in. (610 mm) on center. #4 bar at base of
wall or at the top
SDC E, contains additional requirements for stack of footing.
bond masonry. Stack bond masonry should be
constructed with open end units so that the void in the Dowel to match
vertical reinforcement.
head joint is eliminated. Bond beam units are ideal to
facilitate the flow of grout and spacing of reinforcement
should not exceed 16 in. (406 mm) for horizontal and
24 in. (610 mm) for vertical using 1/2 in. (12.7 mm) FIGURE 11.15 Typical block wall section.
reinforcement for the lateral force resisting system.
No. 3 vertical bars at 8 in. (203 mm) on center The California Department of Transportation
would make masonry construction difficult and normally designs freeway sound barrier walls using
expensive. Using #5 vertical bars at 24 in. (610 mm) the double steel configuration. The result was an
on center is more economical. absolute minimal amount of failure of these tall
cantilev er walls during the 1994 Northri dge
Size and spacing of steel for an 8 in. (203 mm) Earthquake.
wide concrete masonry wall using minimum reinforcing
t
steel coefficient is given in Table 11.3 below.
Specified
d distance spacing Tolerance + 2”
FIGURE 11.18 Tolerances for steel placement. FIGURE 11.19 Maximum slope for bending
dowel into position (ACI 318, Section 7.8.1.1).
REINFORCING STEEL 225
When footing dowels are not properly aligned, the
dowels may be bent to a maximum 6:1 slope as shown
in Figure 11.19. Vertical reinforcement can transmit
forces to the dowels even when the two bars are not
in direct contact.
Style:
New dowels can be installed into the foundation if 6-1V-1H Style: 8-1V-1H
dowels are not supplied or if they are improperly
located. Dowels can be installed by several methods
including drilling over-sized holes and securing the
dowels with grout or epoxy. Installing expansion
anchors, cinch anchors, anchor shields, or some other
positive connection may also be used to anchor dowels
into the foundation.
11.8.5 CLEARANCES
11.8.5.1 CLEARANCE BETWEEN REINFORCEMENT AND
MASONRY UNITS
The effectiveness of reinforcing steel depends on
the amount of grout surrounding the reinforcement.
Code requirements are contained in 2005 MSJC
Horizontal
reinforcing steel
Specification, Article 3.4 B. Reinforcing steel must have
Grout
space a minimum of 1/4 in. (6.4 mm) of grout between the
steel and the masonry when fine grout is used. When
PLAN SECTION coarse (pea gravel) grout is used, the clearance between
the steel and the masonry units must be at least 1/2 in.
Typical double curtain positioner (12.7 mm). This assures proper bond so that stresses
are transferred between the steel and the masonry.
FIGURE 11.20 Reinforcement positioners for
brick masonry.
226 MASONRY DESIGN MANUAL
1
/4”min. for fine grout
1
/2”min. for course grout
Spliced 1”or db min.
bars
1”or db min.
/4”min. for fine grout
1
1
/4”min. for fine grout
1
/2”min. for course grout
1”or db
min. 1”or db
min.
11.9 ANCHORAGE OF
REINFORCING STEEL IN
11/2” MASONRY
recommended
In order to develop reinforcing steel in masonry,
sufficient embedment must be provided. This can be
accomplished by using a bar of sufficient length, or
when sufficient length is not possible, hooks may be
used. The term “ develop” means providing holding power
by the masonry. For example, if the reinforcement has
a tension (pulling out of the masonry) of 1000 lbs. and
2”for bars larger 11/2”interior the reinforcement is only embedded 1/4 in. (6.4 mm) into
than #5, 11/2”for
#5 bars and
the masonry, failure would occur with less than 1000
smaller when lbs. of force. The tension force was not developed in
exposed to earth the masonry.
or weather
The development length is based on the allowable Table 11.6 Standard Hook and Bend
bond stress, the bar diameter, and the sum to be
developed in the steel bar. db = bar diameter D = 5db for #3 through #7, Grade 40
D = Finished inside D = 6db for # 3 through #8, Grade 50/60
bend diameter D = 8db for #9 through #11, Grade 50/60
2005 MSJC Code Section 2.1.10.2 requires
embedment length as: Dimensions of Dimensions of
Standard 180 Standard 90
ld = 0.0015dbFs for bars in tension Hooks Hooks
Bar
The minimum embedment for reinforcement is 12 Grade J (in) D (in) A (in) D (in)
Size
in. (305 mm) and 6 in. (152 mm) for wire. #3 40
5
2 /8
7
1 /8
1
5 /2
7
1 /8
1 1 1 1
#4 40 3 /2 2 /2 7 /4 2 /2
11.9.1.2 HOOKS 3 1 1
#5 40 4 /8 3 /8 9 3 /8
The term “hook”or “ standard hook”used for tie #6 40
1
5 /4
3
3 /4
3
10 /4
3
3 /4
anchorage in SDC’ s D and E means a minimum turn 1 3 1 3
#7 40 6 /8 4 /8 12 /2 4 /8
of 135 degrees or 180 degrees. 1 1
#3 50/60 3 2 /4 6 2 /4
A hook has the benefit of developing stress within #4 50/60 4 3 8 3
3 3
a very short distance. #5 50/60 5 3 /4 10 3 /4
1 1
#6 50/60 6 4 /2 12 4 /2
According to 2005 MSJC Code Section 1.13.5, a 1 1
#7 50/60 7 5 /4 14 5 /4
‘
standard hook’is defined as one of the following:
#8 50/60 8 6 16 6
3 1 1
1. A 180-degree turn plus extension of at least 4 #9 50/60 11 /4 9 /2 19 9 /2
1 3 3
bar diameters but not less than 21/2 in. (63.5 #10 50/60 13 /4 10 /4 22 10 /4
mm) at free end of bar #11 50/60
3
14 /4
1
11 /2 24 12
J D 180°
.
D1
max
d
4 db or 21/2”min.
45 °
13
5
°
Strength design provisions are somewhat more Anchor bolts can be divided into two categories:
complex for determining reinforcement lap splices. 1. Embedded anchor bolts which are placed and
The following formula applies: grouted during construction, and
2. Drilled-in anchors which are placed after
0.13d b 2 f y construction of the masonry.
l de
K f 'm
230 MASONRY DESIGN MANUAL
Anchor bolts are subjected to shear and tension 11.10.2 TIES AT ANCHOR BOLTS IN COLUMNS
forces resulting from loads, such as gravity loads,
earthquakes, wind forces, differential movements and Section 1.14.5.3.1 of the 2005 MSJC Code
dynamic vibrations. The magnitudes of these loads requires confinement of anchor bolts at the top of
can vary significantly. columns for SDC C and above. Anchor bolts are
placed within at least 2 No. 4 lateral ties, with the ties
The Uniform Building Code required that bent bar located within the top 5 in. (127 mm) of the column.
anchor bolt must have a hook with a 90-degree bend
and an inside diameter of three bolt diameters, plus an
extension of 11/2 bolt diameters at the free end. Minimum cover 11/2 in.
for #5 and smaller
bars, 2” for bars larger
The effective embedment length, lb, for plate or than #5
headed anchor bolts is the length of embedment
measured perpendicular from the surface of the
masonry to the bearing surface of the plate or head of
5”
the anchorage, and lb for bent bar anchors is the length
of embedment measured perpendicular from the
surface of the masonry to the bearing surface of the
Ties must surround
bent end minus one anchor bolt diameter. The 2005 anchor bolts, and
MSJC requires a minimum embedment of 2 in. (50.8 column bars
mm) or 4 bolt diameters, whichever is greater.
Column
ties
***
db
**
***
db
** Min. extension
= 1.5 db 11.11 COLUMNS
Plate anchor bolt
lb * 11.11.1 GENERAL
Nominal 8”CMU
Column Ties
75/8”square actual
24”
Column ties 4-#3 bars
12-#10 bars
6 ”
All longitudinal bars for columns shall be enclosed max.
by lateral ties. Lateral support is provided to the Tie anchorage
6d min.
longitu-dinal bars by the corner of a complete tie Column reinforcement
having a 90° or 135° turn plus an extension of 6 bar Max. area = .04 bt
Min. area = .0025 bt
diameters. The corner bars shall have such support Min. size #3
provided by a complete tie enclosing the longitudinal Max. size #11(ASD)
bars. Alternate longitudinal bars shall have such Max. size #9 (SD)
lateral support provided by ties and no bar shall be
farther than 6 inches from such laterally supported
bar as shown in Figure 11.36. FIGURE 11.36 Reinforcing tie details.
232 MASONRY DESIGN MANUAL
Alternate courses
Alternate courses
Tie spacing
Alternate courses
Maximum tie spacing for SDC D and above is 8 FIGURE 11.42 Non-projecting wall brick
in. (203 mm) and the ties must be at least 3/8 in. (9.5 columns with ties in mortar joint.
mm) in diameter. Additionally, the ties must be
embedded in grout. Ties in grout space
Tie spacing
Stagger ties
Wall ties
Wall ties
11.11.5 PROJECTING WALL COLUMNS OR column capacity, columns called pilasters are often built
PILASTERS projecting from the face of the wall.
Heavily loaded girders which frame into a wall may Projecting pilasters also serve to stiffen the wall if
require substantial base plates in the column. In order adequately supported at the top and bottom. The wall
to provide a convenient girder seat and adequate between pilasters can then be designed to span
horizontally allowing very high walls to be built using
only nominal masonry thickness.
Vertical reinforcement
Lateral ties
FIGURE 11.45 Construction of reinforced concrete masonry pilaster with continuous bond beams.
12
NATURAL STONE
Sedimentary rocks (sandstone, limestone, and Both rubble and ashlar masonry may be laid as
travertine), coursed stone masonry which has continuous
horizontal joint lines or as uncoursed or random which
Metamorphic rocks (marble and slate). does not.
236 MASONRY DESIGN MANUAL
Uncoursed Fieldstone
Two-Height Pattern
3/4
”
R
Shim
Stainless steel Corner Cove
expansion bolt
Corrosion
resistant angle
Stone veneer
Corner Block
Stone veneer
Steel stud
structural support
Two way cramp
strap anchor
Building designs can be affected by the distinctive Granite, although capable of absorbing moisture,
physical characteristics of every stone. The most is significantly less porous than other building stones.
common types of building stones are granite, marble, Granite is cut with a slurry of water and abrasive
limestone, travertine and sandstone. material. The moisture absorbed during fabrication
gives the granite a different color than in its dry state
12.3.1 GRANITE and occasionally, granite is shipped before it is
completely dried. Granite will return to its true color
Granite is an igneous rock and is made up of after drying. Once dry, rain and humidity will not
sev eral diff erent minerals such as f eldspars, normally penetrate the stone.
amphiboles, biotites and other mineral combinations,
each having a different hardness. However, granite 12.3.1.2 BUILDING APPLICATIONS
owes its hardness and density to the fact that it has
been solidified deep within the earth under extreme The requirements for each construction project are
pressure. For this reason, the chemical composition different and unique. To create stone pieces exactly
of granite is comparable to lava. The crust of the earth sized for the project, architects and engineers must
has changed with seismic activity, forcing veins of work closely with design craftsmen and stone setters.
granite to the surface. Glaciers scraped off layers of
dirt, sand and rock to expose granite formations. Modern quarrying and fabrication techniques
applied by stone producers have given architects a
wide variety of alternatives to consider when designing
with granite.
NATURAL STONE 241
Exterior The imagination of landscape architects to make
exterior settings, such as planters, benches, terraces
Enhancing the appearance with beautiful and and fountains, inviting and useful as well as beautiful
durable granite cladding is one of the best ways to is unlimited. Each building structure should be created
showcase a building. Designers may choose from a by designers that work directly with stone experts.
wide range of granite cladding systems. The Elaborate elements contain idividual pieces numbered
application of a granite cladding system with striking in the manufacturing process enabling correct field
exteriors is a distinctive process to each building. assembly. Landscape structures may be built with
Depending on the project and application, specific concrete or masonry backup and use granite as a
anchoring systems may be recommended by granite veneer.
producers.
12.3.1.3 MAINTENANCE
Interior
Acid rain and modern air pollution combined with
Granite, for interior design, can be shaped to the freeze/thaw cycles are eroding and staining marbles,
designer’ s requirements. The use of granite in lobbies, limestones and sandstones. The natural beauty of
fountains, executive offices and stylish bathrooms is structures can be damaged by these forces and the
unlimited. The architect or designer can have pieces structural integrity compromized. Granite is known to
of granite virtually any size or shape fabricated be the hardest and most moisture-resistant of all
particularly for the required building. Lobbies and building stones and most resistant to these destructive
atriums are open spaces where granite is used forces. Even granite, however, if subjected to staining
extremely well. Also, the use of granite makes unique agents, can lose luster due to dirt and other normal
fountains, benches and pilasters. Granite desks and forces in high-traffic areas.
coffee tables make executive offices and boardrooms
distinctive and elegant. Stylish bathrooms are created The high density of natural granite resists absorption
with beautiful, maintenance-f ree granite walls, of staining materials and in many situations granite
counters and vanities. surfaces are best left untreated with impregnating or
sealing agents. A mild solution of soap and water is
Landscaping enough to clean dirt from the granite surface. When
thermal-finished granite is expected to be in regular
Granite is popular in exterior landscape design due contact with stai ning agent s, an appropri ate
to its durability and beauty. Courtyards and gardens impregnator should be used to enhance stain
can be enhanced with granite paving, benches resistance. The surface texture or color of the granite
fountains and planters. should not be altered by the impregnators. As usual,
when applying an impregnator, a sample area of the
granite should be tested to assure that there will be no
detrimental affect to the color or texture.
12.3.1.4 DETAILS
Anchor
Dowels Stone Stone
Anchor
Stone coping
(sloped for drain)
Dowel
Concrete or masonry
Anchor
Stone Stone
Grout Anchor
Anchor
joint Stone Stone
Grout
joint Grout joint
Mortar bed Level surface
Stone
Mortar bed
Anchor
Steel truss
Anchor
Anchor
Clip angle
Stone Face of
granite
Concrete
Concrete Anchor
Strap anchor
Clip angle
Steel truss
Clip angle
Anchor
Shim
Anchor
Leveling bolt
Face of Face of
granite Support granite
structure
Dowel
Anchor bolt
Clip angle
Clip angle
Bond
breaker
Anchor
bolt
Face of
granite
Face of
Self taping
granite
metal screws
Precast
concrete
Masonry or
concrete
Kerf
Granite soffit
Continuous kerf
FIGURE 12.17 Granite faced precast.
12.3.2.1 APPLICATION
Anchor bolt
Marble has been successfully applied as an exterior
Granite soffit
veneer on various types of buildings. The wide variety
of colors, textures, patterns, and sizes provides a cost-
effective way for the designer to achieve a unique
FIGURE 12.18 Granite faced soffit. character to the structure.
•the rift and cleavage of the crystals, Marble is a very brittle material and cannot
withstand large deflections. Any deflections in a marble
•the interlocking of the crystals, and system must be minor or the deflections must occur
at the joints. In addition marble can be heavy
•the nature of any cementing materials present (dependent on thickness) which could induce higher
seismic forces. Seismic considerations require
Thermal Expansion engineering based on specific factors for each project
such as panel weight, wind load, back-up material,
The thermal expansion of marble is an important structural flexure and seismic conditions.
consideration since its coefficient varies from one
variety to another. This consderation is due to the 12.3.2.3 INTERIOR VENEER
marble use with different materials when forming large
units that are firmly attached. The quarries can provide With interior veneer applications, the aesthetic factor
information for thermal characteristics of any specific is significantly important, therefore, colored and veined
marble. marbles are usually used since they present many
decorative features.
Fire Resistance
In the architectural application of stone veneer,
Marbles, as any stone, are fire resistant. Heat there are many features that can be achieved
travels through marbles quite rapidly due to thermal depending on the type of material. One features is
conductivity. The fire resistance of marble can be the pattern of panel placement.
improved with the use of insulating material.
Veneer Patterns
Abrasion Resistance
Marble will lend i tself t o speci f ic pat tern
Marbles are recommended for floors and stairs, arrangements, such as side slip pattern and end slip
particularly when the Ha (abrasion hardness valve) is 10 pattern. The natural folds and veins found in marble
or more, due to wearing quality when exposed to create a distinctive marking trend throughout the stone
pedestrian traffic. The method for determining Ha is block that is necessary for a pattern.
contained in ASTM C 241, Standard Test Method for
Abrasion Resistance of Stone Subjected to Foot Traffic. Formal patterns require selectivity, which usually
increases the installed cost of the marble or stone
Translucency veneer.
Twp Way “
L”Strap
“
U”Cramp Strap “
Z”Cramp Strap Twisted Strap
Cramp Strap with Dowel
“
L”Bar or Eye Rod and Bar Strap (with
“
U”Bar “
Z”Bar Hooked Bolt Dowel Dowel)
Wire Tieback Wire Lewis Key Ring Lead Cinch Sleeve Type Expansion
(with Dowel) Tieback (Plug Anchor) Anchor bolt Anchor Bolt
Plain
Threaded
There are a wide variety of colored grouting Modern construction practice uses backing rods
materials offered by many suppliers. Testing should placed between the marble veneer units with a caulking
be done to determine the acceptability between the sealant applied into the joint from the face side of the
colored joint filler and the stone before proceeding, since veneer (see Figures 12.24, 12.25 and 12.26).
some marbles are more porous than others. The
pigments contained in the colored grout should not stain
the stone.
Compressed Joint
Sealant
Caulked waterproof joints are applied over joints To avoid possible smears in critical areas, tape can
that have backing rods inserted. The backing rods be used along the joint edges.
can be porous, called open cell, or the backing rod
can be non-porous, called closed cell, and are typically Gaskets, when used as joint fillers, are usually
made of polyetilene or polysteryne rope. extruded or pre-formed for joint; slight pressure will
compress the gasket for efficient water protection.
Caulking
Before applying the caulking sealant, all kerfs or
The best sealing is obtained with special caulking holes on the surface of the marble to which the sealant
materials called sealants. These are typically highly will be applied must be filled with a high-quality non-
plastic compounds, usually silicon or (poly)urethene. staining compatible sealant.
A good sealant should sati sf y t he f ollowing
requirements: The caulking or sealant application of marble stone
veneer is one of the final steps in cladding construction.
1. It must provide resistance, through time, to The sealant compound must be compatible with all
atm ospheric agents wi thout marked other units to perform correctly. Proper caulking of
alterations of physical and chemical qualities; the joints prevents moisture penetration and avoids
the development of high stress from any movement
2. It must give constant adherence to the of the marble veneer.
materials to which it is applied;
NATURAL STONE 251
Mortar and Sealant Joints Moisture flows through the natural faults and voids
in the stone at different rates, blocked off in some
Preventing the formation of stains on exterior areas, flowing readily through others, evaporating as it
veneered stone will assist in maintaining the aesthetic reaches the face of the stone. The problem can be
appeal of marble veneer. Cement used in mortar should aggravated by kerfs in the edge of the stone.
not contain noxious components, such as blast furnace
cements or a high alkaline portland cement. Also, the Lining kerfs with epoxy or polyurethane or applying
aggregate should be carefully washed and free of clay, a hydrophobic sealer or the use of a material that can
iron and salt. prevent water being transmitted from the kerf edge to
the face of the stone is effective in eliminating the damp
The compressive strength of the mortar used for appearance problem.
joint sealing must be less than the compressive
strength of the marble. This ensures that the mortar The visual effect of lining and sealing material on
will fail first, thus allowing time to correct and repair the behavior of the entire veneer should be evaluated
the cause of the failure before the marble can be prior to its use.
damaged. See Figure 12.27 for typical portland
cement mortar joints. Flashing
Masonry or concrete
Concave Flush backup
(Tooled)
Reglet
V - joint Raked
(Tooled) (Tooled)
Flashing
Caulked joint
FIGURE 12.27 Typical portland cement
mortared joints.
FIGURE 12.28 Continuous waterproof flashing
(typical detail for concrete or masonry backup).
Epoxy Fill
Since the advent of thinner building stone, water Commonly used flashing materials are waterproof,
may penetrate stone veneer more rapidly than normally rubberized fabric, polyethylene or soft neoprene sheets
expected. Areas with dark, damp appearance of or soft, thin gauge stainless steel or copper flashings.
moisture may occur on the face of thin stone. The
darker area is the result of moisture in the stone. Flashing should be placed over all openings, lintels
and continuous support angles with 1/4 in. (6.4 mm) weep
holes spaced every 24 in. (610 mm) along the flashing,
even though the 2005 MSJC Code allows for 3/16 in. (4.8
mm) diameter weep holes spaced at 33 in. (838 mm) on
center.
252 MASONRY DESIGN MANUAL
Masonry or concrete
Cement
spot
Anchor Details
FIGURE 12.30 Mitred joint corner.
Careful detailing of the anchoring system is
important. By considering different stone slabs and
Cement spot
how they are going to perform as a unit, the designer
can create an appealing and durable structure.
Face of veneer Masonry or
When developing anchor details, code requirements concrete
must be met. A common type of anchor system is U - cramp #8
known as “ wire tied”. In this system, the marble veneer wire anchor Cement spot
is attached to a structural support system through a
/4”to 3/8”
1
combination of wire ties and portland cement spots.
The wire ties resist the tension loads and the portland Face of veneer
cement spots transfer compression loads. All anchor Caulk
ties must be made of non-ferrous or stainless steel
corrosion-resistant metal. Aluminum wire is not Masonry or concrete
acceptable. All wire anchors must be embedded in
portland cement spots. Gypsum casting plaster can
be used for interior installation only. Face of veneer
Cement spot
U - cramp #8
wire anchor
Face of veneer
Cement spot
Steel stud
Face of stone
Shim Masonry or
concrete
Anchor bolt
In addition to the wire tied system, slab marble
stone veneer can be anchored in a variety of methods.
Dowel L-
Stone veneer can be mechanically installed to backup strap
masonry or concrete with cement mortar or casting
plaster around the anchors, as shown in Figures 12.33
and 12.34.
Cement spot
FIGURE 12.35 L-strap anchor clip with dowel.
Masonry or
concrete
Masonry or
concrete
Cement spot
Wood studs
Shim
Face of stone
#9 gauge
copper wire
Screw at each
stud
Screw at each
stud
Steel studs
Face of stone
Self tapping
metal screw
Self tapping
metal screw
Wire
reinforced
lathing
Wire reinforced lathing
Steel studs
Face of stone
Anchored stone veneer on steel studs with
wire reinforced lathing system using metal
strap and dowel anchor and grout spot
Concrete screw
Concrete
screw
Masonry or
concrete Wire
backup reinforced
lathing
2”to 21/2”
Head support
Marble veneer
#8 non-ferrous
wire
Face of
Attaching clip Steel strut marble slab
Blindside with
gooseneck anchor
Attaching clip
Metal dowel
Attaching clip
Steel strut
Marble veneer
Soffit
Quirk corner
Soffit furring
Horizontal Base Support channels 18”o.c.
Soffit
3
/16”diam. FIGURE 12.42 Bar strap with dowel soffit
hole
anchor.
Soffit panel
fastened to
Marble liner concrete insert
epoxied and
dowelled to
marbled slab
FIGURE 12.40 Disk soffit anchor.
Marble
liner
Shelf angle
Masonry
U - cramp strap or
type anchor concrete
U - cramp #8
wire anchor
1
/4”minimum
FIGURE 12.41 Eye rod and dowel soffit anchor. FIGURE 12.45 U-cramp strap and marble liner
soffit anchor.
NATURAL STONE 257
Marble liner
Masonry or
concrete
Shelf angle Gypsum wallboard
(interior only)
Gypsum plaster
FIGURE 12.46 L-bar or hooked bolt soffit spot (interior only)
anchor. or cement mortar
Blind edge
anchor
Caulked
joint
Steel
tube Marble face
Continuous
aluminum Not serrated using
screw attached @
FIGURE 12.53 Extruded aluminum offset
extrusion anchor.
each stud
Steel
channel
Alternate stud
Face of
stone
Extruded
Special serrated aluminum
locking washer head
support
Neoprene shim
Resilient
bearing
Steel plate, welded tape
(or bolted) to steel
Marble face
tube
Resilient
bearing
tape
Caulked joint
Base
support
FIGURE 12.52 Extruded aluminum anchor with FIGURE 12.54 Continuous extruded aluminum
anchors in continuous slots cut in the stone.
bearing point.
NATURAL STONE 259
Relieving angle (attached to Depth of concrete varies according to required strength
structure, frame, or studs by bolting
or welding) 8-gage stainless steel
wire
Resilient bearing
tape (both sides)
Concrete
11/2”- 2”typical
Impervious
Extruded plastic or
aluminum membrane
intermediate
anchor
Varies
Non-continuous
slot
Masonry or
Face of
concrete
stone
Anchor bolt
Relieving angle
Base support
Frequent mopping of floors and sponge washing First, wet marble surfaces with hot, clean water. A
of countertops is beneficial for keeping the polished mild household cleanser may be lightly sprinkled over
appearance in marble. Exercise caution when using the wet stone. Then, mop and rinse the marble surfaces
a scrubbing machine to avoid scratching the marble thoroughly with clean hot water using a scrubbing
surface. Normal cleaning products and acids are not motion and dry with mop or cloth.
recommended for marble.
In many cases, special interior floor marble areas
Typically, prev ention sav es time spent on should be protected where a polished finish is not
treatments and remedies, particularly since damage practical. Sealers, in this case, should be applied after
to marble is irreversible. the floor marble has been cleaned to reduce
maintenance. Also, sealers prevent staining around
Honed Interior Marble toilets and in food preparation areas such as
countertops.
Honed marble has a satin surface with relatively
little light reflection. Maintenance of honed interior For application the manufacturer’ s directions
marble follows the guidance for polished interior should be followed and sealers should only be applied
marble. to clean interior floor marble.
Cramp
Concrete slab Mortar bed
Flashing
Drip
Full Mortar Bed Bonded
Full mortar
Bricks or Drip
Concrete slab bed
plastic pods
Vapor barrier
Flashing
Corner Spots
Shim
Bolt to steel
Bolt to steel framing, beams, clip framing,
angles, concrete inserts, etc. concrete inserts
or to face of
concrete
1
/4”min. /4”min.
1
Shim
Spacer
/4”min.
1
Joint sealant
/4”min.
1
backer rod
Sealant and
1
/4”min.
backer rod
Insert
Shim
Rod welded to clip angle
1
/4”x 3/4”bar welded
to clip angle (typ.)
Insert
Shim
Joint min. 1/4” Joint min. 1/4”
Concrete
L - strap dovetail anchor
dovetail
slot
L - strap dovetail in
vertical joint
Cement spot
1
/4”min.
Drip
L - strap dovetail in
Insert vertical joint
1
/4”x 3/4”bar welded
Insert
to clip angle Clip angle across
vertical joint
Joint min. 1/4”
Shim
Shim
L-strap dovetail anchor
Cement spot
Drip
Cement spot
Cement spot
Cement spot
Cement spot
Cement spot
Cement spot
Cement spot
Shim
Insert
Dovetail L - strap
Clip angle
Shim
Insert
Shim
Expansion shield
Cement spot
Cement spot
1
/2”
Masonry or Bent strap anchored to
concrete marble veneer with
expansion shield and
1
/2” bolt
Drip
/4”
3
Marble veneer
Butt Joint
/4”
3
L - strap anchored to
Masonry or marble veneer with
concrete expansion shield and
bolt
Standard Reglet
U cramp strap anchor
Note: Stagger anchors
11/2” to clear each other
Marble veneer
Quirk Joint
/2”
1
/4”min.
1
/4”min.
1
3
/16”min.
Quirk Joint
Quirk Joint
FIGURE 12.66 Veneer details.
268 MASONRY DESIGN MANUAL
Cement spot
Cement spot
Masonry or concrete
Masonry or concrete
Masonry or concrete
Masonry or concrete
Metal feature strip
Drywall partition
Epoxy to base
Wire anchor
Solid grout
/4”min.
intersection of
panels
1
Mortar setting bed over concrete
Sealant
Full Mortar Bed Method
Backer rod
Marble treads
Marble treads
Dowel
Anchor clip
Adhesive Adhesive
Mortar bed
Structurally
Reinforcement Sub slab
sound wood
Membrane subfloor
Setting Methods
Based on granular texture and other natural Concrete walls, floors or finish grade (soil) can be
characteristics, limestone is classified in two colors sources of akali. The moisture may be excess water
and four grades. Specification of limestone should in mortar, rainwater, or moisture from soil. This moisture
identify the required color and grade as well as the picks up water-soluble free alkali from various sources
surface finish to be applied to the stone. as it migrates to an evaporation surface at the stone’ s
face above grade. The stain that appears at the surface
Color of the stone is related to the moisture moving through
the stone and dissolves small pieces of organic matter.
Buff color ranges from a light cream shade to a When this material moves to the face of the stone,
brown tinted buff. moisture evaporates and the alkali and organic matter
left at the surface of the stone appears in the form of
Gray color ranges from a light silver gray to shades stain.
of blue tinted gray.
Efflorescence
Grade
Efflorescence is the white, powdery scum that can
Limestone is formed by nature, thus, the limestone appear on the stone’ s surface after construction and
classifications are based on the degree of fineness depending on the type of salts can also be brown green
grain particles and other natural characteristics. or yellow. Stain and efflorescent are similar in many
ways even though the components are different.
Limestone is a natural stone that contains several Typically, efflorescence producing salts found in
noticeable calcite streaks or spots, fossils or shell masonry are sulfates of sodium, calcium, magnesium,
formations, pit holes, reedy formations, open texture iron and potassium.
streaks, honeycomb formations, iron spots, travertine-
like formations and grain formation changes.
272 MASONRY DESIGN MANUAL
Efflorescence is more soluble in water than stain, Appropriate tooling compacts the mortar against
therefore it is easier to remove. the sides of the stone and will improve the bond
between the mortar and the stone units.
Efflorescence problems can occur when water
penetrates the lower part of the material surface. 12.3.3.5 COLD WEATHER PROTECTION
Efflorescence can cause stresses on walls, which can
cause flaking or exfoliation. Protection of limestone during construction is
necessary if the outside temperature is 40º F or below.
Dampproofing treatments such as bituminous or In limestone, admixtures or anti-freezes should never
cementitious coatings can act as a moisture barrier be used to lower the freezing point of mortar. Cold
against groundwater and control or prev ent weather provisions for masonry construction are
efflorescence. Proper materials and details along with contained in Article 1.8 of the 2005 MSJC Specification.
quality construction also help to prevent eflorescence.
Limestone may be covered with felt paper,
12.3.3.3 ANCHORS tarpaulin, or polyethylene. Units may be protected in
a tent-like environment, which would allow auxiliary
Anchors are embedded in the limestone with heating. When using salamanders, care should be
mortar, sealant or other non-expansive, stable material taken to prevent smoke under the covering.
and should be stainless steel, or other non-corrosive
metal. Masonry veneer, by definition, is a non- Limestone should not be place on a snow or ice-
structural element. In addition to anchors, which give covered bed. Under this conditions bond cannot be
lateral support to the limestone veneer, supports developed between the mortar bed and the frozen
provide the bearing surface for the dead weight of the supporting surfaces.
stone. All supports f or l imestone shoul d be
manufactured from type A36 steel, 304 or 316 stainless 12.3.3.6 SEALANT SYSTEMS
steel or other corrosion resistant metal.
Sealants provide a moisture protective barrier
12.3.3.4 MORTAR AND POINTING similar to mortar systems. There are two types of
sealant systems, one-part and two-part. The common
Mortar consists of cementitious material and well one-part systems are the moisture-cure and air-cure
graded sand with sufficient fines. Mortar should be systems. Two-part systems use a catalyst or chemical
tested on limestone prior to construction to assure that to cure. The setting of mortar can be considered similar
it will not bleed into the stone, particularly when using to curing, but in the construction process, sealants
colored mortars. Mortar is used for many purposes must be handled differently since they are not intended
such as: to support weight.
•Bonding the units together Sealants are normally supported by a backer rod.
•Setting material A backer rod is placed in the joint to a predetermined
•Leveling the units depth. The sealant should not adhere to the backer
•Providing shear and compressive strength rod, but to the parallel surfaces only. Omitting the backer
•Sealing irrugularities of the stone rod from the system may contribute to premature failure.
Prior to the application of the joint sealant, the
A typical mortar mix of 1 part portland cement, 1 manufacturer may recommend a primer which must be
part hydrated lime, 6 parts sand aggregate, or a applied to the interior surfaces of the joint to assure
preblended mix, will provide adequate compressive adhesion.
strength (ability to support vertical loads), bond strength
(ability to resist eccentric or lateral loads), and durability 12.3.3.7 EXPANSION JOINTS
(weather resistance).
Expansion joints are used to accommodate
Mortar used in pointing should be a soft, not strong, increases in length in long runs of walls and consist of
mix. Any movement of the building can place a premolded filler and sealant compound. The
excessive stress on the edges of the stone and cause premolded filler should be adequately compressible to
chipping or spalling at the joints if a high compressive allow for structural and thermal differential movement
strength mortar is used. Add only enough water to flexible enough to return to the original shape. Caulking
make the mix workable. or compressible sealant should be completely elastic
and should be tooled to ensure maximum adhesion to
the contact surfaces.
NATURAL STONE 273
Typical examples of expansion joints:
Waterstop
Bondbreaker tape
Mortar
Sealant bead
3
/8”typ.
1
/2”typ.
1
/4”typ. 12.3.3.8 CLEANING
12.3.3.9 DETAILS
Flashing cap
Rod anchor
Twisted strap
anchor FIGURE 12.75 Floor span.
Adapter
channel
welded to
steel
1”min./2”
recommended
Grout anchor
in CMU
Stainless steel
split anchor
Bond beam
Adjustable
FIGURE 12.76 Steel or concrete frame anchor. FIGURE 12.77 Anchors at horizontal joints.
276 MASONRY DESIGN MANUAL
Dovetail
anchor
Grout CMU
Adjustable
insert
Weld
plate
Flashing cap
Epoxied joint
Stainless steel
dowel
Wood cant
Masonry back-up
Epoxied joint
Soffit Drip
Compressible
Liner block or joint material
cleat
Setting bed
End adapter
welded to beam Sealant and
foam rod
Flashing
Adjustable
disc type
anchors for
lateral stability
of both panels
Inserts cast
into concrete
Shelf angle
Flashing
Flashing
Stone lintel
Anchor
Anchor
Stone jamb bolt Limestone architrave
Caulk
Limestone facing
Jamb
Setting bed
Head
12.4 SUMMARY
12.4.1 STONE ANCHORAGE
5. The anchorage capacity should be verified by There are many sealers available and some do not
multiple tests of the actual anchorage. The have the ability to resist water penetration. These
anchorage fastener connection to the backup coatings lie on the surface of the stone and provide
should be duplicated in the anchor test only shine or varnish to the stone’
s surface.
apparatus. Revised anchor design if the
anchorage tests do not provide the capacities The process of removing stains from natural stone
needed. is complicated and warrents professional guidance.
Evidence frequently shows that when stone Marble floors may be resurfaced to bring back the
anchorage fails, rupture occurs where anchors are original shine. The process involves specialized
attached to brittle stone, not where the anchors are machinery and technical expertise. This type of
connected to the backup. Alternative or backup procedure can be expensive so a reputable refinisher
designs should always be re-evaluated as outlined for the project is advisable.
above for adequacy. Proper performance of the
stone’s supporting substrate is essential. Both the 12.4.3 MAINTENANCE
backup and base design should be rechecked for
adequacy to assure long-term system performance. One misperception is that natural stone is
maintenance free and resist the effects of time, however,
12.4.2 SEALING any contractor or building manager will disagree. The
maintainability of these natural products is one of the
Stone surfaces require careful maintenance to major elements that affect the practicality of bringing
protect them from stains and environmental pollutants. polished stone back into residential and commercial
Most stone requires little maintenance, which is simple buildings.
and economical.
Successful use of natural building stone in any
Stone floors should be cleaned with warm water residential or commercial projects is a result of correct
and a liquid soap that will not leave a residue. Cleaners mai ntenance procedures. The cont ractors,
containing acids or abrasive chemicals sould never manufacturers and distributors must educate the end-
be used on stone. Avoid spilling sugary or carbonated user for proper care, cleaning and maintenance of the
drinks as these may etch the surface of the stone and stone. Long lasting beauty and appearance of natural
remove the shine. The use of waxes on stone should stone will guarantee continued demand.
be avoided since waxes attract airborne dirt.
The best way to understand guidelines in stone
New stone floors, counters or cladding require the care is to look at each natural stone and determine
use of a quality penetrating sealer immediately after what is needed and what should be avoided.
installation. There are a wide variety of sealers
available, and a specialty stone cleaner should be 1. Natural stone is very susceptible to chemicals.
used. Regular maintenance can be easier if a Major threats are acids, salts, and alkalis.
professional initially seals the stone surface.
2. Natural stone needs a stone care system or
Granite’ s natural high density resists absorption of conditioning. The use of ordinary cleaners may
staining materials and requires little or no sealing. A be harmful to the stone. These products dry
specialty penetrating sealer may be used to increase out the stone and pull the life out of the stone.
stain resistance and will prevent absorption of liquids
and oils, which can darken the surface of the stone. 3. Natural stone needs regular cleaning. Damp
mopping will be enough to keep it looking good
Marble should be sealed since it is vulnerable to and to prevent dirt and soil from clogging pores.
staining. A quality penetrating sealer will prevent water
rings left by glasses placed on the marble surface. 4. Natural stone requires protection against water
penetration. Moisture is the main factor
Limestone is more resistant to staining due to its contributing to the decay of masonry. Moisture
unusual characteristics. However, when limestone is contains soluble salts from polluted rain water
exposed to air over a period of time will weather and or chemically treated tap water, melted ice,
become harder on the surface. A penetrating sealer is and adjacent masonry materials. The stone’ s
recommended to prevent staining. natural components react to moisture and
efflorescence.
NATURAL STONE 281
5. Natural stone should be stain-proofed. Even The stone will wear if left unprotected. Even
dense granite has a capillary structure, and an entrance mat helps in the protection of stone
can therefore stain. There are no stain removers floors.
that can successfully penetrate the fine pores
of the stone and stain, therefore, it is nearly 8. Natural stone surfaces must be slip-resistant.
impossible to completely remove deeply ADA regulations require a degree of slip
penetrated stains. In order not to permanently resistance which cannot be achieved with any
harm the stone, only very mild, non-acidic stain smooth natural stone.
removers should be applied.
9. Chemical cleaners may dam age the
6. Natural stone must breathe. Thus, sealers environment and personal safety. Users must
and maintenance products should not block be aware of possible property damage.
the pores of stone. Chemical cleaners such as acids and alkalines
can cause serious injury and health hazards.
7. In order to preserve the natural polish of stone, Carefully analyze Material Safety Data Sheets
natural stone surfaces must be protected and reject chemicals which endanger the
against foot abrasion and other wear and tear. environment.
282 MASONRY DESIGN MANUAL
Leeds Castle.
Westminster Abbey.
Windsor Castle.
13
GLASS BLOCK
70
60
40
30
20
10
0
0 50 100 150 200 250 300
Panel size is limited by the 2006 IBC based on Glass block panels must be reinforced with at least
wind pressure and absolute maximum dimensions and two 9 gauge W 1.7 (MW 11) in the horizontal bed joints
areas. Figure 13.1 provides limitation on panel size at intervals not exceeding 16 in. (406 mm). When joint
based on given wind pressure. reinforcement is lapped, the splices are to be at least 6
in. (152 mm).
When the design wind pressure does not exceed
20 psf (958 N/m2), glass block panels may be designed 13.1.7 INSTALLATION
using the criteria of Table 13.1 providing none of the
maximum values is exceeded Glass block panels give an attractive, air-tight,
light-transmitting panel that is completely finished on
Table 13.1 Maximum Glass Block Panel Size both sides. In one operation, preassembled panels
Unit Type can be set into openings. There is nothing to
Standard Thin Thin deteriorate and the glass blocks require little care.
Units Hollow Solid
Units Units
Exterior Walls
Area 144 85 100
sq. ft. sq. ft. sq. ft. 2
Height 20 ft. 10 ft. 10 ft.
Width 25 ft. 15 ft. 15 ft. 10 9
Interior Walls
Area 250 150 100 7 2
sq. ft. sq. ft. sq. ft.
Height 20 ft. 20 ft. 20 ft.
Width 25 ft. 25 ft. 25 ft. 8 6
11 5
Glass block panels must be laterally supported
against out-of-plane displacement. This can be 4
accomplished by providing panel anchors at the sides
3
and top of the glass block panels spaced not more
than 16 in. (406 mm) apart. Lateral support can also 1
be provided by using channel type restraints with the
glass block inset into the channels by at least 1 in.
(25.4 mm). Expansion joints of at least 3/8 in. (9.5 mm)
are also required at the ends and top of glass block
panels.
FIGURE 13.2 Glass block installation.
GLASS BLOCK 285
The standard installation of a glass block window
is shown in Figure 13.2.
13.2 TYPICAL GLASS BLOCK
DETAILS
1 Sill area, to be covered by mortar, shall first be covered
with heavy coat of asphalt emulsion.
13.2.1 HEAD DETAILS
2 Adhere expansion strips to jambs and head with asphalt
emulsion. Expansion strips must extend to sill.
3 When emulsion on the sill is dry, place full mortar bed.
Do not furrow the mortar.
Exterior
Interior
Finish
Finish
4 Set lower course of glass block units. All mortar joints
are full joints without furrows. Do not tap glass block
units into place with tools.
CMU lintel block
5 Install panel reinforcement in horizontal joints as follows:
a) Place 1/2 depth of mortar bed joint on top of glass
block. Expansion strip
Deflection
b) Press panel reinforcement into place.
c) Cover the panel reinforcement with the other 1/2 of
space
the mortar bed and trowel smooth. Do not furrow.
d) Panel reinforcement is to be continuous. Lap panel
reinforcement a minimum of 6", as required. Panel Anchor screw
reinforcement shall not bridge expansion joints.
Steel 2 x 2 x 14 (typ.)
6 Place full mortar bed on joints not requiring panel
1 inch min.
reinforcement. Do not furrow. Sealant and backer
rod
7 Repeat at each course.
Glass block unit
8 Strike joints smoothly while mortar is still plastic. Rake
out spaces to be caulked. Remove excess mortar from
the face of glass block and wipe dry. Tool joints smooth
and concave before mortar sets.
FIGURE 13.4 Cross-section of glass block head
9 AFTER the final mortar has SET, pack backer rod tightly joint at CMU wall.
between glass block and jambs & head. Leave room for
caulking.
10 Caulk panels per manufacturer.
11 Clean the glass block using sponge and clean water. Steel stud
Change water often. Do not use a wire brush. Buff with
cheesecloth.
Sheathing
Weather-resistant
membrane
Flashing
Panel anchor Tube steel
Steel lintel
Weep holes
Mortar Expansion
strip
Horizontal
reinforcement Steel channel
Mortar
Exterior Finish 1 inch min.
Asphalt emulsion
Sealant and backer rod Interior finish
Glass block Precast conc.
sill
Sill anchor
Metal flashing
Horizontal reinforcement Steel tube
Steel 2 x 2 x 14 (typ.)
Anchor screw
Steel stud framing
CMU
Interior Finish
FIGURE 13.9 Sill - Glass block in steel stud
FIGURE 13.6 Jamb - Glass block in CMU wall. wall with brick veneer.
Metal stud
Glass block
Gypsum board
Mortar Solid blocking
Asphalt emulsion
Sealant
Glass block
37/8”
53/4”
Panel anchor
Horizontal reinforcement
1
/4”
Expansion strip
Horizontal reinforcement
Expansion
strip
Panel anchor
Expansion
Horizontal
strip
Sealant reinforcing
Mortar
Glass
45° block
block
Glass
Glass block
block
PLAN VIEW
73/4”
Mortar
Expansion
strip
37/8”
Panel anchor
Expansion
strip
1
/4”exp. bolts
two per anchor
Glass block
Glass Horizontal reinforcement
block Sealant
Bullnose finish
Glass
block PLAN VIEW
6”min. lap
14
VENEER
functional. Moisture must have a clear path to drain A rigid system deflects little. Since the backup
through the weep holes, which must be open for system deflects very little and the veneer is attached
passage of moisture to the exterior of the veneer. to the backup system, then veneer will have limited
deflection. The limited deflection of the veneer
The corners, which can be particularly susceptible reduces the possibility of water intrusion through
to seismic damage, can perform well if the designer flexural cracks in the veneer.
understands wall movements relative to each other.
Traditionally, structural masonry backup systems
The anchored attachment system must have the have been constructed with Concrete Masonry Units.
flexibility of allowing vertical and horizontal movement
relative to the backup system and at the same time be Clay brick, or hollow clay brick, can also be used
capable of transferring the lateral wind and seismic to support veneer. This is seldom considered due to
loads to the backup system for ultimate ground the increased cost. Instead, two wythes of brick with
distribution. one wythe being the veneer brick facing have been
used.
W hen properly designed and constructed, a
masonry veneer system will survive natural elements, Anchored veneer can easily be attached to structural
such as wind and earthquakes, with minimal or no masonry with a variety of wall ties or joint reinforcement.
damage. A prime advantage of this type of system is the ease in
which insulation can be placed in the cavity between
Masonry veneer systems can be constructed from the wythes of masonry. Moreover, when properly flashed
a variety of materials in a number of different ways. and drained with weepholes, the system can prevent
The designer can select systems and materials to water intrusion into the building.
achieve a desired look or texture.
Prior to placing the anchored veneer the structural
This chapter presents the constructability of the masonry backup must be waterproofed. Frequently,
most important materials and systems that are used this is done by painting the backup with bituminous tar
in masonry veneer. Manufacturers of each product or by covering with 30 pound (13.6 kg) felt. This added
should be consulted for more detailed information on measure helps mitigate the moisture penetration
specif ic products and installation procedures through the masonry.
associated with their products.
Exterior sheathing
Brick
Thin brick veneer veneer
units Weep
holes
Thin set mortar
Building paper
with 6 in. (150
Weep screed mm) minimum lap
at base
Flashing
1. The brick veneer/steel stud wall system should FIGURE 14.5 Steel stud backup system.
be detailed as a panel wall, or fully supported
at each story height by the structural frame 3. Use at least 18 gauge (1.2 mm) metal studs
through shelf angles. to allow for adequate screw thread grip.
However, the deflection criteria may require a
2. Limit the deflection of the steel studs to h/600
minimum of 16 gauge (1.5 mm) metal stud,
of the height of the stud backup when
except for lightly loaded and dry areas, such
considered alone as a full lateral design load.
as building interiors where 18 gauge (1.2 mm)
This ensures that the studs will be sufficiently
studs may be adequate.
stiff so that the veneer will be adequately
supported with only minor cracking from 4. Steel studs should be galvanized coated to
bending. conform to ASTM A 525, Grade G-90.
VENEER 293
5. Rigid sheathing should be securely fastened a simply supported beam where the maximum deflection
to both sides of studs. The sheathing must and moment would occur at the midspan.
be properly detailed and attached.
Shelf angles can also be supported by bolting
6. Horizontal bracing at mid-height for added
directly to the structural backup. This is particularly
stiffness is recommended.
advantageous since the angle size can be minimized
by installing bolts at a relatively close spacing, such
The design of the steel stud system should meet
as the stud spacing. This also reduces the overall
the requirements of either the IBC or the Metal Lath/
deflection of the angle so that only the deflection of
Steel Framing Association design criteria.
the projecting angle leg may be critical. Shelf angles
at floor levels must be supported in this manner so
14.3 SHELF ANGLES that the load from the angle is not transferred to the
veneer below.
The horizontal leg of the angle must extend to
support at least two-thirds of the veneer thickness. Avoid attaching heavily loaded shelf angles to steel
Angles must also support the veneer without excessive studs since the substantial bending moment created
deflection or rotation. Provide a more substantial angle by the large load and eccentricity could overstress the
or a built-up structural steel member if deflections relatively flexible studs. Any loads imposed upon the
exceed l/600 to l/720. studs must be considered in the design of the stud.
The deflection of the angle should be limited to When installing shelf angles, a clear space of at
the lesser of l/600 or 0.3 in. (7.5 mm) and the rotation least 1/2 in. (12.7 mm) must be left at the ends of each
of the edge of the shelf angle should not exceed 1/16 in. angle. This allows the steel angle to expand without
(1.6 mm). damaging the surrounding masonry.
Shelf angles over openings may be supported by Similarly, space should be provided between the
bearing on adjoining masonry, subject to building code ends of steel shelf angles at floor lines so each angle
provisions. In this case, the shelf angle would act as can expand and contract independently.
Steel stud
Building paper,
weatherproof
membrane
Concrete floor
Seismically required
Structural steel framing
horizontal joint
reinforcement
Exterior sheathing
Anchor ties
Recommended 2” (50.8 mm)
air space
Weep holes
Flashing
Continuous
metal flashing
Caulking Recommended 2”
minimum air space
Backer rod
Foundation
Flashing must be continuous along the length of
the veneer with sufficient lap joints to prevent moisture Flashing
from migrating under the flashing. Where flashing
terminates at the end of shelf angles, end dams must FIGURE 14.8 Adhesive flashing system.
be constructed to direct the flow of moisture outward.
L2
L1
Expansion
joints
Any successful veneer system design will consider Discontinuities - When the veneer encounters any
expansion and contraction in the veneer system. discontinuity, a vertical expansion joint should be
provided. Examples are changes in height, thickness,
The need for vertical expansion joints depends on and presence of any large openings, dissimilar
the climate area in which the structure is located, materials or abutment to other building elements.
temperature change, type of structural frame and the
materials involved in construction. Spacing - W it h all v ariables taken i nto
consideration, maximum spacing of the vertical
Additional attention should be given to vertical expansion joints should be calculated. The spacing
expansion joints in the following areas: of the vertical expansion joints of clay masonry should
never exceed 30 ft (9.1 m), and a 20 ft (6.1 m)
Corners –In order to avoid buckling as depicted in maximum spacing is recommended.
Figure 14.10 some type of vertical expansion joint
should be placed in close proximity of the corner.
14.7 SYSTEM DETAIL
A vertical expansion joint can be placed at the
corner of the veneer and this may be accomplished
REQUIREMENTS
by following a continuous seam up through a series of
attached vertical and horizontal joints. Normally, this This section describes masonry veneer systems
method is cost prohibitive. in detail along with specific requirements contained in
the 2006 IBC and the 2005 MSJC Code. Sections
Alternately, the vertical expansion joint can be and details are provided which show the minimum code
placed within ten feet of the corner. The distance from requirements along with recommendations based on
the corner on the adjacent wall would be the maximum design principles and standard construction methods.
calculated space between joints, less the distance on
the adjacent wall (Figure 14.10).
296 MASONRY DESIGN MANUAL
Minimum thicknesses for various types of wall Typically, any veneer attached to a wood stud
coverings are contained in IBC Table 1405.2. The system or a cold-formed steel framing system is limited
given thicknesses are based on weather protection for to 30 feet (9.1 m) abov e the noncombustible
the material and application. Note that the requirement foundation. This height limitation is increased to 38
for adhered masonry veneer is only 0.25 in. (6.4 mm), feet (11.6 m) for a gable condition.
whereas the anchored masonry veneer must have a
minimum thickness of 2.625 in. (53.3 mm). This is The restriction on wood framing can be attributed
based on the concept that adhered veneer is applied to to fire safety. In the event of a fire, the veneer could
a system that already considers water management, collapse if the wood stud frame backup disintegrates
such as a plaster substrate. Anchored veneer, on the and a fall of a system in excess of 30 feet (9.1 m)
other hand is the first line of defense for moisture could be catastrophic. There are also considerations
penetration. The units must also be adequately thick of differential movement, that is, a wood frame backup
for the mason to place the units with stability. shrinks over a long period of time, whereas, a brick
cladding will expand over a long period of time.
veneer) supported by
Dead load (weight of
shelf angles
Adhered veneer may be designed and installed 2. Adhering to Concrete Block Masonry or
without limitation to height and length; however, Concrete with surface preparation.
consideration must be given for brick expansion and 3. Adhering to a wood or metal stud system with
building contraction. The code language states that surface preparation.
the consideration is to control restrained differential
movement between the veneer and backing. 4. Placing into forms and cast integrally with
concrete.
In order to satisfy this requirement, adhered 5. Adhering to prefabricated panels, on the job site,
masonry veneer may be applied with vertical and or any other selected location.
horizontal expansion joints between sections. The
vertical distance between horizontal expansion joints
would likely be between floors, or approximately 10 ft. Thin brick varies in size, color and texture,
(3 m). The horizontal distance between vertical joints depending on the manufacturer. Common face
should be compatible with the building design and dimensions are approximately 21/2 in. (64 mm) by 75/8
ideally not exceed 15 to 20 ft. (4.6 to 6.1 m). in. (194 mm) with a thickness of about 7/16 in. (11 mm).
The thickness may be as much as 7/8 in. (22 mm),
There is also a unit size limitation imposed by 2005 which is preferred when a raked mortar joint is desired.
MSJC Code Section 6.3.2.1 which states that the
thickness of adhered units are not to exceed 25/8 in.
(66.7 mm). The section further requires that the
VENEER 299
Longer units of 111/2 in. (292 mm) are available and
extra consideration should be given to units of greater
thickness. Long thin brick veneer units may warp in
the firing process, which can cause difficulty for the
installer and dissatisfaction for the end user.
12”(305 mm)
)
Maximum weight of 15
20”(508 mm)*
Adhesive
Caulking for
expansion
36
Proper joint allows the concrete backing structure to move, while ”(
0
the caulking compresses. No stresses are transferred to the ma- Sin .9 m
* Maximum dimension in gl
sonry veneer. e d ) ma
this configuration. Maxi- ime xim
ns u
mum dimensions and ion m
maximum area (720
FIGURE 14.15 Adhered veneer with provision square inches (0.46 m2)).
for expansion.
Adhered veneer units shall not exceed 25/8 in. (66.7 mm) in speci-
fied thickness, 36 in. (914 mm) in any face dimension, nor more
that 5 ft2 (0.46 m2) in total face area, and shall not weigh more than
15 lb/ft2 (73 kg/m2).
a backing of cold-
story
Non-combustible, non-
30’(9.1 m)
Maximum height
corrosive lintels over all for veneer
openings where veneer is supported by
not self spanning. Lintel foundation
deflections limited to l/600
FIGURE 14.19 Veneer system over 30 feet (9 m) in height with a backing of cold-formed steel
framing.
302 MASONRY DESIGN MANUAL
30’(9.1 m)
Wood frame backup
Anchored brick
veneer system
Veneer supported by Waterproof sheathing
non-combustible base
Height limit from foundation Brick veneer units may be made of clay or
Height at plate, Height at gable, concrete. Clay brick is by far the most popular masonry
ft (m) ft, (m) material for veneer applications.
30 (9.14) 38 (11.58)
Seismic required
No.9 gauge (3.76 Corrosion resistant
Metal stud back-up system mm) wire or equiva- anchors at least 0.3-
lent. Maximum stud inc hes (0.8 mm
spacing at 16”(406 thick by 7/8 inches
mm) o.c . Butt (22 mm) wide
Installation fill splices in wire per-
Weatherproof mitted, but 4”(102
sheathing mm) lap rec om-
mended
Required 1”(25.4 mm) In high Seismic Design
Ma
minimum air space 16 x. st Categories the tie must
”( ud have lip to engage the
40 sp
6 m ac horizontal joint
m) ing
o.c reinforcement
.
Foundation
2. With stud backing, a 2-inch by 2-inch (51 by 51 The two methods contained in 2006 IBC Section
mm) 0.0625-inch (1.59 mm) corrosion-resistant 1405.6 are known as “ wired tied”anchored veneer
wire mesh with two layers of waterproofed paper systems. Figures 14.25 and 14.26 demonstrate the
backing in accordance with Section 1403.3 shall systems.
be applied directly to wood studs spaced a
maximum of 16 inches (406 mm) o.c. On studs, Figure 14.28 shows the periphery dowels which
the mesh shall be attached with 2-inch-long (51 may be required by the Code. These anchors are to be
mm) corrosion-resistant steel wire furring nails at connected to the backing by wire or ties.
4 inches (102 mm) o.c. providing a minimum
1.125-inch (29 mm) penetration into each stud and As with any anchored veneer system, ties must
with 8d common nails at 8 inches (203 mm) o.c. be capable of resisting tension and compression
into top and bottom plates or with equivalent wire forces. Since there is no mortar spot bedding
ties. There shall be not less than a 0.1055-inch requirement, the tie must resist the force, or the system
(2.68 mm) corrosion-resistant wire, or approved can be designed to place spot bedded mortar to
equal, looped through the mesh for every 2 square accommodate compressive forces.
feet (0.2 m2) of stone veneer. This tie shall be a
loop having legs not less than 15 inches (381 mm)
in length, so bent that it will lie in the stone veneer
mortar joint. The last 2 inches (51 mm) of each
wire leg shall have a right-angle bend. One-inch
(25 mm) minimum thickness of cement grout shall
be placed between the backing and the stone
veneer.
306 MASONRY DESIGN MANUAL
FIGURE 14.26 “Wired tied”anchored veneer system, wood stud backup with wire mesh and
waterproof paper.
d
24
ma ”(61 d + 0.63”max.
xim 0 m
um m)
/4”to 1”
24”(610 mm)
3
maximum 1
/3 t
FIGURE 14.28 Anchored veneer doweling for 2 inch (51 mm) stone.
14.7.3.2 BLOCK VENEER, CONCRETE UNITS Quite often, however, the application of block
veneer may be impractical. Alternatively, a wider
structural block may be used to achieve both a desired
Block veneer can be processed with quality control
surf ace appearance and a structural element
standards that allow color and texture variations are
potentially yielding a substantial cost savings.
similar to clay brick. Since the manufacturing process
does not require the high firing temperatures associated
Block veneer may not be as readily available as
with clay products, block veneer is cost competitive.
clay brick veneer units, especially in the smaller, more
traditional, clay brick sizes.
Block veneer can also be made into a variety of
textures, such as smooth, slumped or adobe faced,
As with any product, communication between the
split faced and fluted.
design team and the developer is the key in selecting
the most appropriate product to satisfy the end user,
while maintaining an efficient cost approach.
308 MASONRY DESIGN MANUAL
Horizontal and
Continuous metal coping
vertical reinforcement
Sealant
Sealant
Counter flashing
Metal tie
Steel stud
Insulation
Self-tapping corrosion-
resistant metal screw
Interior finish Weatherproof sheathing
Roofing
Gravel-stop fascia
Dovetail anchor
Sealant
Adjustable anchor
Roofing
Metal tie
8d nail
1”(25.4 mm) minimum air space
Interior finish
Joint reinforcement
@ 16”(406 mm) o.c.
Vertical reinforcement
1”(25.4 mm) minimum air space
Reglet
Flashing
Compressible material
below shelf angle
Lip brick
1”(25.4 mm)
Caulking minimum air
space
Reglet
Flashing
8”(203 mm) max.
Compressible
material Elastic joint sealant
Weep holes
Caulking
Compressible material
Weatherproof sheathing
Tie
Brick veneer
1”(25.4 mm) minimum air space
Building paper
Flashing
Steel angle
Weep holes
Sealant
Adjustable anchor
Alternate position of flashing
with weep holes shifted
upward one brick
Backer rod
Face of beam
or slab
Clear for vertical
movement or provide
compressible material
Vertical reinforcement
Flashing
Single or double 8”(203
mm) CMU bond beam lintel
Weep holes
Steel angle
Metal studs
Building paper
PLAN VIEW
8d nail
Weatherproof sheathing
Metal ties
Brick veneer
Brick sill
Horizontal joint reinforcement
Caulking or sealant as seismically required
PLAN VIEW
Insulation
Building paper
Interior finish
Flashing
Sealant
Building paper
Double hung
wood window
Caulking or sealant
Insulation
Flashing
1”(25.4 mm) minimum air space
Brick veneer
Brick sill
Channel
Weep holes @
24”(610 mm) o.c.
Self-tapping corrosion-
resistant metal screw
Flashing
Metal ties
1”(25.4 mm) minimum air space
Weatherproof sheathing
Interior finish
Insulation
1”(25.4 mm) minimum air space
Weatherproof sheathing
Brick veneer
8d nail
Metal tie
Wood studs
Building paper
Flashing
Finish grade
Anchor bolt
Waterproof membrane
Weatherproof sheathing
Building paper
Insulation Brick veneer
8d nail
Interior finish
Flashing
Finish grade
Anchor bolt
Waterproof
Solid grouted collar joint membrane
Building paper
Insulation
Weatherproof sheathing
Vapor barrier
Wall ties
Bond
Concrete floor break
slab
Vapor barrier
Fill cavity w/mortar or grout up
to underside of flashing
4”to 6”(102 mm to 152
mm) capillary water barrier
Waterproof
membrane Building paper
Reinforced concrete
foundation wall and footing
Flashing
FIGURE 14.47 Base of wall detail, concrete footing, steel stud backup.
318 MASONRY DESIGN MANUAL
W eatherproof membrane
Expansion
joint material
Weep holes
Grade
Grout fill
Vapor barrier
Concrete foundation
W eatherproof membrane
Expansion Flashing
joint material
Grout fill
Waterproof membrane
Vapor barrier
Concrete footing
Alternate bars
FIGURE 14.49 Base of wall detail, concrete footing CMU below grade, CMU backup.
320 MASONRY DESIGN MANUAL
W eatherproof membrane
Weatherproof sheathing
1”(25.4 mm) minimum air space
Insulation
Flashing
Interior finish
Finish grade
FIGURE 14.50 Base of wall detail, concrete footing, steel stud backup.
Insulation
Brick veneer
Weatherproof sheathing
Steel stud
Weep holes
Flashing
FIGURE 14.51 Base of wall detail, concrete footing/slab, steel stud backup.
VENEER 321
14.8.6 EXPANSION JOINT DETAILS
Sealant
Backer rod
1
/2 W or
/2”typ.
1
Exterior face W
of veneer Sealant
1”(25.4 mm)
minimum air space
Backer rod
1
/2 W or
W Sealant
1
/2”typ.
FIGURE 14.55 Vertical expansion joint detail with CMU backup/brick veneer.
VENEER 323
14.8.7 SYSTEM CONFIGURATION
Friction-fit
metal coping
Sealant
Sealant
Horizontal
reinforcement
Metal tie
Dovetail anchor
Vertical
reinforcement
Steel stud
Brick veneer
Insulation
Flashing
Interior finish
Sealant
Sealant
Weep holes
Steel stud
Brick sill
Self-tapping corrosion-
resistant metal screws
Adjustable wire tie
Roofing
Dovetail anchor
Sealant
Adjustable anchor
Flashing
Interior finish Weep holes (above windows)
Head
Steel angle
Sealant
Sealant
Brick sill
Steel stud
Weatherproof sheathing
W eatherproof membrane
Insulation
Weep holes
Flashing
15
SPECIAL TOPICS
This chapter provides information on topics that The term “ shelter”is defined as something that
significantly impact the performance and show the covers or provides protection from the elements. A
benefits of masonry. This is significant since regulatory leaky building is, by definition, not shelter.
issues are more stringent for fire protection, noise
control and energy efficiency. A thorough understanding of the performance of
masonry and the issues relating to moisture
15.2 MOISTURE RESISTANCE penetration will help in designing masonry buildings
that successfully resist moisture penetration.
The term “ waterproof”usually means complete Moisture resistance involves many detail parts of
resistance to water penetration. Masonry, by its nature, a building. Examples include walls above grade, walls
is porous and complete resistance cannot occur unless below grade, roof and floor building elements.
the masonry is coated with an impermeable membrane,
such as bituminous coating. Coating masonry with a Providing moisture resistant walls requires that a
substance defeats the purpose of using masonry. The number of items must be considered before the
coating can change the color and texture of masonry. application of any coating takes place.
Masonry walls may be coated in non-visual locations,
326 MASONRY DESIGN MANUAL
Sealant
Dovetail metal
anchor Caulking
15° min.
Concrete or Flashing turned Metal counter flashing installed in
stone sill up beyond end of mortar joint. See detail
Sealant
15° min.
Wood or steel See Figure
frame 15.5
Weep holes
1 in. (25 mm) min.
Flashing
Airspace
1”Min.
Caulking
Wall ties
Metal counter flashing
installed in bed joint.
Flashing
6”min.
Weep holes
Interior Side
Exterior Side
Steel angles
Caulking
Wall ties
Flashing
Flashing
Cant strip
Roofing material
Weep holes
Steel angles
Permeability is the rate at which a liquid will pass Resin type is often the most direct way to identify
through a porous surface at constant pressure. This types of water repellent treatments. Few in the
is an important concept for masonry materials when construction industry have sufficient training and
dealing with clear water-repellent sealers. Several education in resin chemistry to do more than recognize
factors may cause excessive permeability such as low terms and possibly relate them to a family of types of
cement content, gap gradation of aggregate or materials such as petrochemical organic and silica
insufficient fine aggregates and dry mix design. based materials.
Proper selection may be the first concern when Siliconate. A water based form of silicone,
reviewing and discussing proper clear water repellent siliconates are very alkaline and most siliconates
treatments for masonry. Discussions relating to presently available do not reflect the active siliconate
whether they are monomeric or polymeric resins and solids content which in most cases is only 50% of the
whether they are suspended or dissolved in solvents total weight of the solids. The remaining weight of
can become exasperating. solids is either sodium or potassium hydroxide, which
is why they are so alkaline.
Relating the characteristics to the resin types can
be helpful. Acrylics, stearates, and some silicone water Silicates. Alkali silicates are water-based alkaline
repellent treatments typically form a film on the surface solutions which harden and densify cementitious
of the masonry system. They can also be used to materials.
produce a higher sheen or ’gloss’ appearance. They
can also be used to darken or intensify colors and Silanes. Typically penetrating types sealers,
aggregates within the masonry units. silanes are technically alkyltrialkoxysilanes which is
defined as ‘a monomeric organosilicon compound with
Silanes and siloxanes are typically penetrating- an unhydrolyzaple siliconcarbon bond’. The silanes
type water repellent treatments which react with silicate form a water repellent treatment by chemically bonding
minerals in the concrete masonry units and mortar. with the siliceous minerals in the concrete masonry
The natural alkalinity of cementitious products typically system. Other terms for silane are alkylalkoxy silane
acts as the catalyst for the reaction, along with the and alkytrialkoxy silane. Common carriers include
moisture in the materials. Some silanes and siloxanes alcohol and mineral spirits, but some forms are used
include catalysts in the treatment to promote or extend with water as the solvent.
the reaction.
Siloxanes. Another form of penetrating sealer,
A general description of common language is siloxanes are variations of the alkylalkoxysiloxanes
helpful. Variations in chemistry and combinations of which are oligomerous. They chemically bond to
materials cause generalizations to be only moderately silicate materials in concrete masonry. Variations
useful in identification and selection. The following include polysiloxane, oligomeric siloxane, modified
information may prove helpful in identifying families of polysiloxane, organosiloxane, oligomeric
materials and providing information on the basic resin organosiloxane, and combinations of various siloxanes
types. and silanes.
Acrylics. Acrylic resins are polymers and Blends. As noted in several of the resin type
copolymers. They form a film on the surface. descriptions, different types of resins are often
Variations in chemistry of acrylics allow various forms combined to improve the characteristics of the final
from solids, to elastomerics, to liquids. They are clear, water report treatment.
and can be used with a wide variety of solvents,
including water. Acrylic emulsions are typically water- 15.2.5 SURFACE TREATMENTS
based; acrylic solutions are typically solvent-based.
In addition to providing clear surface treatments
Stearates. Stearate residents are based on stearic on the masonry wall other options for providing surface
acids that form a ‘soap’ in the masonry pores. Originally treatments are available. The disadvantage of using
used as film formers, later chemistries of the stearates these materials is the requirements of periodic
have been marketed as penetrating treatments and as maintenance. For example, when a coating is chapped
integral water repellent treatments. Common terms or damaged it must be repaired to maintain aesthetic
include aluminum stearates and modified aluminum quality.
stearates. The solvents are typically mineral spirits.
Listed below are a number of different treatments
Silicones. Silicones are polymerized resins which that may be applied to masonry walls.
are referred to as organopoly-siloxanes. Variations in
the size and shape of the silicone polymer resin can Paints. Specialty paints are available for masonry.
vary whether the mineral is a film forming or penetration Paint provides color uniformity which may be
type water repellent treatment. There are silicone aesthetically pleasing when new. Once applied,
emulsions but most use mineral spirits or other organic removal of paint may be difficult if return to the natural
solvents. surface of masonry is desired. Types of paint that can
be used for masonry walls include latex paints,
elastomeric paints, and alkyd paints. Each has
favorable characteristics for the designer to consider.
SPECIAL TOPICS 331
Types of paint that are not recommended for can generally be secure that the same product can be
masonry applications are epoxy paints, rubber paints expected to perform as well in similar conditions.
and oil-based paints. These products form an Changes in technology and in regulations, particulary
impervious surface and do not allow the masonry walls limitations on volatile organic compounds (VOC), can
to breathe. Moisture trapped in a wall can be cause manufacturers to change formulations. Variations
problematic. in conditions can also cause previous experience to be
less applicable. In such cases it is appropriate to
Block fillers are used to fill small voids and surface research potential options. There are some important
irregularities. Block fillers are recommended when questions which should be considered during the
porous concrete masonry is to be painted. Block fillers research.
are extremely advantageous in minimizing moisture
penetration. The project, manufacturer’ s literature and local
manufacturer representatives are key sources of
15.2.6 INTEGRAL WATER REPELLENTS research information regarding the appropriate
application of products. Manufactures are the first to
As an alternate to surface applied water repellent realize the danger in reputation where products prove
coatings the designer may wish to consider specifying unsuitable for specific known applications.
integral water repellent additives to the concrete block
and mortar. Addition of this product does not change The following list of questions should provide a
the color or texture of the concrete block or mortar. uniform approach to research which can be used for
comparison of various products.
When using integral water repellents there is no
need to include the product in the masonry grout since, 1. What are the manufacturers recommend
under ideal conditions, moisture should not reach the applications?
grout. Diff erent resins hav e different appropriate
applications. The natural porosity of concrete
The designer must also be aware that the masonry masonry may be inappropriate for some forms of
units will not absorb moisture as traditional masonry water repellent treatments. Manufacturers will
walls do. This is significant for grouted masonry since typically note whether or not concrete masonry is
there is excess water in grout which traditionally an appropriate substrate.
dissipates into the masonry units. The use of integral
water repellents cause hydrostatic pressure in the grout 2. Is the product intended to be a surface or
which forces water into the masonry unit and mortar. penetrating sealer?
Occasionally the water will bleed to the exterior of the The products are clearly formulated as either a
wall through a path of least resistance. surface film or penetrating type, although some
might be classified as a little of both. Where not
Product manufacturers should be consulted on the clearly identified, the product is probably a surface
compatibility issues relating to integral water repellents sealer.
and grouted masonry.
3. How many coats recommended?
15.2.7 CONSIDERATION IN SELECTION Differences in formulations make it important to
understand the manufactures recommendations
Concrete masonry construction is hydrophilic by regarding application, particulary the appropriate
nature; without some form of protection, water moves number of coats and the coverage rate in square
through the natural porosity of the masonry units and feet per gallon. Timing between coats is also
mortar. The water can then find ways into the structure important to the application of the system. Some
and potentially damage interior finishes and materials. materials require a sufficient time for the masonry
Additionally, in areas where freeze-thaw conditions exist, to absorb the initial coat prior to reapplication.
water in the masonry system can expand and damage
the system. 4. Can the treatment be reapplied?
Some forms of water repellent treatments create
There is no specific correct approach to the a water barrier which subsequent coats of the
selection of appropriate clear water repellent same material may not be able to penetrate.
treatments for concrete masonry. Experience is Information regarding application of additional
typically the easiest means of finding an appropriate coats should be determined prior to the selection
material. Those who have successfully utilized products of the material.
332 MASONRY DESIGN MANUAL
5. Can the treatment be coated? Such limitations may only be a concern in heavily
Whether or not the treatment is compatible with populated areas. In other cases, such as
other treatments and coatings might also prove California, the limitations may extend to the
important in the long-term. A new building owner manufacturing of the product as well as sale and
might want a new color and want the masonry to use.
be painted. Repeated vandalism might require
addition of anti-graffiti coatings. The treatment might 10. What are the long-term expectations?
not prove successful for some unknown reason. Since water repellent treatments are going through
Knowing whether or not the water repellent a period of constant change, both in chemistry and
treatment can be retreated, painted, or coated can in limitations on VOC, information on what happens
be useful in making early decisions. over time is only assumption and speculation.
Where treatments have existed without change, it
6. What are the effects of weather during and might be appropriate to ask for the location of
immediately after application? some of the older applications along with
The manufacturer may have advice on what to do recommendations of owners, architects, and
if it rains during or right after the application. contractors who have used the products in the
Recommendations usually list conditions required past.
prior to application, such as requiring a clean, dry
substrate. Typically there are limitations on Warranties can be beneficial in comparing the
weather conditions including minimum and relative quality of one manufacture to another. Quite
maximum temperatures. often a warranty is simply used as a sales tool and is
only as good as the company behind a warranty. A
7. Are there any potential adverse effects such reputable company will stand behind their product
as chemical reaction with adjacent materials? regardless of warranties.
Water repellent treatments on concrete masonry
will be in contact with the same materials in contact 15.2.8 INTERIOR MOISTURE CONTROL
with the concrete masonry; joint sealers (silicones,
polyurethanes, polysulfides, acrylics); windows Interior moisture control would not be complete
and doors (aluminum, wood, steel, bronze) metal without some information on water protection. If there
flashings (copper, galvanized steel, stainless steel, were ever an issue that cannot be code “ quantified”, it
aluminum) and other siding materials (concrete, would be interior moisture control. Water develops on
brick, metals, wood, plastics, stucco). the surface where the temperature is at the condensation
point and is dependent on the micro-climates of an area.
Other material such as glass and landscaping may The buildup of condensation can be mitigated by placing
not be immediately adjacent, but could also be a vapor barrier on the proper side of a wall. Thus, if
affected by water repellent treatments due to wind, regionalized micro-climate varies the code could require
overspray, and run-off. Paint on any adjacent the vapor barrier on the wrong side of the wall. In some
surface and nearby materials could also be areas it may be best not to have a vapor barrier at all.
affected.
Interior moisture in the form of condensation can
8. Are there any special limitations on damage the building components and create occupant
application? discomfort. To confirm code requirements, a vapor
Limitation should include materials that should not analysis is highly recommended. A vapor analysis
be coated. Maximum porosity and minimum should be performed to determine the potential for
permeability requirements might be important. condensation so that appropriate placement and choice
Temperature limitations and moisture content at of insulation and air and vapor barriers can be made.
time of application might be critical to the water
repellent treatment. Types of aggregate in concrete 15.2.9 OTHER CRITICAL ELEMENTS
masonry may also have some bearing on success.
A significant portion of this chapter has focused
9. Are there any known local limitations on use? on surface treatments relating to moisture penetration
Federal, state and local limitations on volatile in masonry walls. Moisture can also migrate into the
organic compounds (VOC) might limit the wall from a variety of other sources including tops of
availability of some otherwise excellent water walls, perimeters of windows and doors, through
repellent treatments in certain areas. expansion and control joints and through other wall
penetrations.
SPECIAL TOPICS 333
15.2.9.1 WALL CAPS 15.2.9.2 MOVEMENT JOINTS
One area for moisture penetration in masonry walls Movement joints are provided in masonry structures
is at the top of the wall. Moisture can enter the top of and properly accommodate moisture and temperature
a wall and will gravitate down any imperfections in the fluctuation. Shrinkage and temperature hairline cracks
system until it exits, usually on the face of the wall. can develop allowing water passage into masonry. As
When the tops of masonry walls are properly designed a general rule, control joints should be placed in
and constructed moisture migration in these areas can concrete masonry every 25 feet but not more than 11/2
be minimized or totally eliminated. times the wall height. In clay brick masonry, expansion
joints should be placed at intervals not exceeding 30
In descending order of performance, the following feet for walls without openings. Ideally, expansion joints
top of wall finishes are the most widely recognized in and clay brick masonry should be spaced closer to 20
design and construction of masonry walls. foot intervals. Additionally, leakage can occur at
movement joints through cracked, unbonded or
1. Sheet metal caps — Sheet-metal caps are by far misapplied caulks and sealants. In order to keep the
the preferred method of finishing the tops of control and expansion joints functional, proper and
masonry walls. A properly designed and installed routine maintenance is required.
sheet m etal cap system wil l prov ide an
impermeable and durable finish. Most designers
are reluctant to specify sheet-metal caps since
proper design and installation require the sheet
metal cap to project vertically down the wall for a
few inches.
3. Masonry copings — Copings using masonry units FIGURE 15.7 Elevation of masonry wall with
are not recommended. The masonry units are not
control or shrinkage joint and abutting into another
impermeable to moisture and there are a number
wall.
of mortar joints along the top of the wall. Use of
this system may be acceptable if through wall
flashing is installed immediately below the cap units. Sealant
1
/2 W or
Through wall flashing is problematic in seismic W /2”typ.
1
Backer rod
Epoxy or non-
shrink grout
/2”
1
Slope cap
/2”
1
Drip edge
Flashing
Caulking
Backer rod Sealant
Section 1-1
FIGURE 15.6 Typical drip edge on precast FIGURE 15.8 Plan view of masonry wall control
concrete wall cap. joint.
334 MASONRY DESIGN MANUAL
Sealant 1
15.2.9.4 WINDOWS AND DOORS
W /2 W or
/2”typ.
1
Backer rod One often overlooked critical element is the
interface between masonry and sills or jambs of
windows and doors. Historically, masonry walls were
thicker and more forgiving on the issue of moisture
penetration, but with thinner masonry walls, careful
Sealant
3
/8” attention must be given to detailing these interfaces.
/2”
Flashing is the primary barrier with sealants (caulk)
1
closing the open crack of the interface. Sealants alone
should never be relied upon for the moisture barrier at
Backer rod the interface.
/2”
Mortar
Sloped flashing
Sill
Sealant
FIGURE 15.11 Flashing at window sill/jamb,
wood studs/brick veneer.
The special inspector should periodically observe If the inside face of the masonry wall shows traces
application of the water repellent treatment and verify of moisture, additional coats of the water repellent
compliance with information included on the check list. treatment are required and the test must be repeated.
Where variations from the contract documents are
observed, they will typically be noted and given to the RILEM Test No. 11.4, RILEM Tube Test. Another
owner and contractor. field test used was developed by the International
Union of Testing and Research Laboratories for
15.2.11 TESTING Materials and Structures (RILEM). A vertical plastic
or glass tube with graduated markings is adhered to a
Tests allow comparison of products and systems. masonry wall with putt y (see Fi gure 15.13).
Several tests are available relating to clear water Permeability is measured based on the change of
repellent treatments for masonry. Some relate to water level in the tube caused by the absorption of the
individual components in masonry construction, such water into the masonry system.
as ASTM C 140 Standard Test Methods for Sampling
and Testing Concrete Masonry Units and Related Units. Although the RILEM test provides an inexpensive
Others are intended to test complete masonry systems, method for determining water penetration into the
such as ASTM E 514 Standard Test Method for Water concrete masonry system, the results must be based
Penetration and Leakage Through Masonry and the Navy with caution. The test is based on a measurement
Hose Stream Test. Still others, like the RILEM tube from only a small area where the tube is located.
test and the CTL Accelerated Field Test provide
information on small segments of the construction.
.
336 MASONRY DESIGN MANUAL
10 ft
Garden hose
Putty 2400
-1200
this level, the water pressure on the wall is 0.14 psi which
Temperature, °C
-600
translates into a dynamic wind speed of 88.5 mph.
3. At predetermined time intervals such as 1, 2, 5, and 10
minutes measure the depth the water level has dropped. 800 -400
-0
15.3 FIRE RESISTANCE 0
0 2 4 6 8
Time, h
Masonry walls should be both structurally sound
and fire resistant. Masonry walls excel in resisting the
passage of heat or flames and can also be used to FIGURE 15.14 The ASTM E 119 standard time/
effectively contain most fires. temperature curve.
SPECIAL TOPICS 337
15.3.1 FIRE RATINGS thickness is the actual thickness of the unit or wall.
However, for hollow clay or concrete units, the wall is
Table 15.1 shows fire resistance from 2006 IBC considered as either ungrouted or solid grouted (partial
Table 720.1(2), Rated Fire-Resistance Periods for grouted walls are considered as ungrouted).
Various Walls and Partitions. This table provides a
classification of masonry walls based on the required As an alternative to 2006 IBC Table 720.1(2) fire-
wall thickness for a specified fire rating time. resistive construction may be approved by the building
official based on evidence submitted showing that the
The specified wall thickness for masonry shown in construction meets the required f ire-resistiv e
2006 IBC Table 720.1(2) is the equivalent solid classification.
thickness. For solid clay units, the equivalent solid
TABLE 15.1 Rated Fire-Resistance Periods for Various Walls and Partitions1, p
MINMUM FINISHED
b
THICKNESS FACE-TO-FACE
ITEM (inches)
MATERIAL NUMBER CONSTRUCTION 4 hour 3 hour 2 hour 1 hour
c
1-1.1 Solid brick of clay or shale 6 4.9 3.8 2.7
1-1.2 Hollow brick, not filled 5.0 4.3 3.4 2.3
Hollow brick unit wall, grout or filled with perlite
1-1.3 6.6 5.5 4.4 3.0
vermiculite or expanded shale aggregate.
1. Brick of clay 4”nominal thick units at least 75 percent solid backed
3
or shale with a hat-shaped metal furring channel /4" thick
formed from 0.021”sheet metal attached to the brick d
1-2.1 1 - - 5 -
wall on 24”centers with approved fasteners, and /2"
Type X gypsum wallboard attached to the metal furring
strips with 1”-long Type S screws spaced 8”on center.
2. Combination 2-1.1 4”solid brick and 4”tile (at least 40 percent solid) - 8 - -
of clay brick
and load-
bearing 2-1.2 4”solid brick and 8”tile (at least 40 percent solid) 12 - - -
hollow clay
tile
f, g
3-1.1 Expanded slag or pumice. 4.7 4.0 3.2 2.1
3. Concrete f, g
3-1.2 Expanded clay, shale or slate. 5.1 4.4 3.6 2.6
masonry f
units 3-1.3 Limestone, cinders or air-cooled slag. 5.9 5.0 4.0 2.7
f, g
3-1.4 Calcareous or siliceous gravel. 6.2 5.3 4.2 2.8
For SI: 1 inch = 25.4 mm, 1 square inch = 645.2 mm2, 1 cubic foot = 0.0283 m3.
15.3.2 FIRE RATINGS OF BRICK VENEER Masonry will not burn. Brick and concrete block
WALLS masonry serve as a barrier to fire like no other
material.
Tables in the IBC show that brick and block Masonry will not fuel the fire and can often prevent
masonry are significantly resistant to fire. The use of the spread of fire to adjacent properties.
masonry shows a responsible approach in the During and after fire, masonry homes will retain
balanced occupancy vs. risk design. One other structural integrity.
significant advantage is that masonry provides passive
Masonry will not produce toxic gas or smoke.
fire protection, that is, masonry will always resist fire,
where as active systems rely on other means of Masonry reduces fire loss.
effectiveness. For example, if there is no water Masonry works full time without electricity, water
pressure, fire sprinklers will not work. supply or maintenance.
Fire ratings may be cumulative. An ungrouted 8 in. 15.3.4 FIRE SAFETY FACTS
(203 mm) pumice concrete block (face shell thickness
11/4 in. (31.8 mm) each) will provide a fire rating of 1 Below are safety tips to assist in limiting the
hour. When a 4 in. (102 mm) solid clay brick is added dangers of a potential fire.
as a veneer another 2 hours of fire rating is achieved for
a total 3 hour fire rating. 1. Fire Retardant Roofing Materials - Fire retardant
roofing materials prevent fires from starting as a
15.3.3 FIRE SAFETY ENVIRONMENTS result of fire rain of flammable embers. Also, these
materials reduce the contribution to fire storms
Fire is one of the most devastating forces which that spread rapidly to other structures and areas.
plagues California homeowners as evidenced by the
wildfires of 1993 in Laguna Beach, Malibu and Altadena Use more than the minimum retardancy in several
that claimed four lives and over 1,000 structures. But hazardous areas. Instead of the slow burning
fires of this type along the wildland/urban interface composition, or the so-called fire retardant roof
zones are not unusual in California. In 1961, 537 coverings, use clay or concrete roofing materials.
structures were destroyed in the Bel-Air fire. In 1970, The fire retardancy of other coverings is only a
a series of wildfires over a two week period destroyed relative degree of slower burning. In the event
722 structures throughout the state and claimed 14 the supports are flammable, the heavier clay and
lives. More recently, there were the 1990 Painted concrete roof coverings will also reduce flying
Caves fire in Santa Barbara County that claimed 641 embers.
structures and the 1991 Oakland Hills fire that
destroyed 3,400 dwellings and killed 25 people. 2. Vents - To prevent passage of embers, place non-
flammable mesh over openings such as roof vents
Most building codes permit residential construction and chimney openings.
to be built solely of combustible materials with few 3. Eave Hazards: Eliminate projecting eaves or cover
exceptions. When residential buildings are built with the underside with fire-resistive material such as
combustible materials, they just add fuel to the fire. properly installed plaster.
The American dream is to own a home, unfortunately,
critical land shortages have caused suburban areas 4. Fire-Resistive Walls: Fire-resistive walls are
to be constructed on dense hillsides. The next logical fundamental, especially those facing possible fire
step is to take the necessary precautions to ensure a approach areas such as vegetation slopes. The
safe family environment. fire-resistive walls may be code-rated fire
endurance masonry walls of one hour or more.
A fire-safe environment can be easily constructed This fire-resistant construction is not only excellent
using non-combustible materials. Masonry is a for new masonry surfaces of desired patterns and
material available for increasing the survival rate in a textures, but also covers, enhances and protects
fire. Reports from previous wildland fire area coverage old flammable surfaces such as wood siding.
found that masonry construction often resisted
rampaging fire, while combustible construction, such When structures are close together, this method
as wood, went up in smoke. Masonry foundations, is important where there is a high risk of the fire
chimneys and walls withstood the fires, standing as jumping from one structure to another.
monuments to the barren landscape of ashes and
rubble which were once thriving communities. What
lessons we can learn from this?
SPECIAL TOPICS 339
2
1 2
13 10 10
10 10 3
6 6
4
5
10 10 10
6 6
7
8 8
9 11 9
10
12
12
1. Roof 8. Plants
2. Vents 9. Garden walls and Curbs
3. Eaves 10. Sprinklers
4. Walls 11. Stand-By Power
5. Overhangs 12. Water Storage
6. Windows 13. Housekeeping
7. 30’ clear
5. Overhangs: Fire-resistive materials should be fuel load and hence stop the up rushing
used to enclose the undersides of balconies and conflagration. These walls are also barriers in lieu
decks at slopes. of sandbags for diverting mud flows after the fire.
6. Dual Pane Fire Windows, Glass Doors and 10. Sprinklers: The use of sprinklers systems for all
Shutters: Windows of this type offer added fire sides of structure will help moisten grass and
protection and shutters may be permanent for vegetation which could provide fuel for the fire.
quick closure or may be stored for quick placement Also for protection of vacant structures, sprinklers
in case of impeding fire. Draperies and curtains would have special potential benefits.
should also be of a fire retardant material.
11. Stand-by Power: Install a generator (diesel or
7. 30' Clearance: The structure should be free of gasoline-driven) to drive a water pump for use of
flammable vegetation or weeds for 30 feet (9.1 swimming pool water or other water sources. In
m). This can be accomplished by the installation the event of a power failure, the generator may
of sand bedded masonry paving which is then also be a stand-by source for lights, stove,
economical, easily installed and adjusted to any refrigerator/freezer and security.
surface or change as desired. Beautiful and
12. Water Storage: Tank storage may be installed
colorful patterns and surfaces may be achieved
which may be connected to provide fire water
for enhancement of aesthetics or use.
storage or as a reserve for those times when water
8. Plants: Fire-resistant plants such as rosemary, service may be interrupted. Of course, there
African daisy or periwinkle should be used in fire should be adequate hoses and outlets available
hazardous areas. for usage. Water from swimming pools can be
used if a small pump and connection is available.
9. Garden Walls & Curbs: The use of masonry walls
and curbs at the tops of slopes will provide several 13. Housekeeping: Flammable bushes, tree
benefits, such as a flame barrier to resist the trimmings, brush and close proximity untrimmed
furnace-like blast of a fire roaring up a slope or to trees are hazardous invitations for disaster and
assure safe back-firing down the slope to remove should be properly trimmed and cleared away.
340 MASONRY DESIGN MANUAL
width
For Ratings Up to and Including 2 Hours
Caulking
Ceramic fiber
blanket
Backer rod
Wythe (R1)
width
For Ratings Up to and Including 4 Hours
FIGURE 15.16 Fire resistance of multi-wythe
masonry wall. Bond breaker Sealant and backer
W hisper
Quiet Conversation
Soft Radio, TV
Private Office
Acoustics is important to the functioning of Selection of the correct materials ensures that
environment from auditoriums, concert halls and movie noise transmission from one room to another is kept
theaters to the residential environment. The need to to reasonable levels. Noise has more of an influence
control noise in other environments, such as open to the occupant’
s comfort than heating or cooling levels.
offices and churches has also been extensively Any structure should hold regular noise to acceptable
recognized. levels. When noise cannot be eliminated or reduced,
the buil ding must f unction to prev ent sound
A quiet environment will increase productivity in transmission. Sound absorption reduces the level of
an office and will aid in recovery when in a hospital. sound generated in a room while sound transmission
Hotel and motel travelers prefer the privacy of peaceful prevention reduces the amount of sound that is carried
accommodations. Noisy voices and loud background from one area to another.
music will have a negative effect on business in
restaurants and other public places of business. 15.4.1 MASONRY SOUND TRANSMISSION
Banks, stores and government institutions recognize CLASS (STC)
the advantage of conducting business in reduced noise
surroundings. Masonry is particularly well suited to the
requirements of noise control in multi-family structures.
Designers have the responsibility to plan a Concrete block or brick wall assemblies provide a
functional and safe environment. In order to function density of material with the noise reduction values
for the specified purpose, interior space requires needed to minimize annoyance and comply with
acoustic attention. The high level of noise in residential recognized and required standards. Sound
applications can be attributed to extensive use of glass transmission ratings are achieved with masonry
and other reflective surfaces, along with the increased construction for the reduction of noise from freeways,
number of electronic devices, such as larger television rapid transit and freight rail systems, aircraft operations
sets, more sophisticated radios and hand-held and industrial activity. Sound rated masonry wall
electronic devices, and the design of smaller rooms systems tested by application of standardized
with lower ceilings. Architects, developers and laboratory procedures are available to the design
contractors know that a successful result of noise professional for combating these exterior noise
control is due to acoustics. sources, as well as undesirable sounds which may be
experienced between units in multi-family housing.
342 MASONRY DESIGN MANUAL
60
50
40
20 30 40 50 60 70 80 Sound
Wall weight - pounds per sq. ft. level meter,
interior noise
measurement
FIGURE 15.18 STC vs. wall weight.
The distinction between isolation and insulation FIGURE 15.19 Isolation; difference between
as they relate to Standards can be described as follows: the exterior and interior noise level measurements.
15.4.5 SOUND ABSORPTION AND NOISE TABLE 15.5 Noise Reduction Coefficients (NRC)
REDUCTION of Selected Materials
MATERIAL NRC
15.4.7 IMPACT NOISE CONTROL Traffic noise largely depends on three factors:
Wall height
The combination of masonry units, mortar and grout
with steel reinforcing bars provides a wall with structural
integrity. The engineered design determines location
and spacing of the reinforcement. The wall may be
supported on a foundation below grade or on deflection
barriers. The design forces of wind pressure and
earthquake force can be resisted by this structural
system. Vertical reinforcement
Typical dimensions
b
Actual wall width FIGURE 15.23 Concrete masonry block noise
Cement mortar cap or barrier wall (double mat steel).
other as desired
Wall
91 dBA
Sound waves
Vertical reinforcement
75 dBA
Dowels
#3 bars 12”o.c.
3”clr.
Typical dimensions
FIGURE 15.22 Concrete masonry block noise FIGURE 15.24 Sound transmission.
barrier wall.
SPECIAL TOPICS 347
Masonry noise barrier walls reflect sound waves
away from the receiver back toward the noise source.
A potential problem can be created when sound waves
reflected off a barrier could be redirected to another
area. Two of the most important properties of the
masonry construction material are the ability to absorb
waves and the surface texture.
Wall
Trucks/cars
Sound waves
FIGURE 15.27 Masonry freeway sound wall.
The design of roof overhang can shield a major Calculate the recommended southern overhang for
glass area from the heat of the summer sun and also a location at 32latitude and provide for a 6' - 8" sliding
allow the lower winter sun to help warm the structure glass door height.
since the suns angle changes from season to season,
lower on the horizon in the winter and higher in the
6' - 8" (Glass Door Height)
summer. A properly designed roof overhang can aid Overhang (OH)
in the effective use of the sun’
s heat as illustrated in 5.2 ( F at 32o latitude)
Figure 15.30.
6.6
OH 1.3 1' - 4"
5.2
Winter sun
6' - 8"
OH 2' - 9"
2.4
Window/Sil l Height
Overhang (OH)
F
W indow
W indow
height
2’- 9”
height
North Latitude F
28 8.4
Summer sun Winter sun
32 5.2
36 3.8
40 3.0 FIGURE 15.31 Effect of overhang on summer
44 2.4 and winter sun.
48 2.0
52 1.7 A porch cover, trellis or awning are ways of overhang
56 1.4 protection that serve the same function as the extension
of the roof structure. In architectural design there is a
great deal of flexibility that will provide the same function.
Mechanical devices provide alternate methods of
shading from summer heat and exposing the window
areas to winter sun. These movable devices require
that the occupant should be aware of the need for shade
or heat at different times of the year. Some shading
options are shown in Figures 15.32 - 15.34.
SPECIAL TOPICS 351
Passive solar heating can be incorporated easily
into plans with very little increase in costs and almost
no change in construction methods or personnel. A
passive solar buildings, is attractive at a time when
energy costs continue to rise.
FIGURE 15.32 Drop shade. To obtain heating and cooling benefits from the
free energy available in the natural environment,
passive solar systems depend on the smart design
and organization of the spaces in a building and the
careful selection of building materials. Passive solar
designs depend on two basic material properties:
South-facing Insulated
double glazing north wall
The convective loop system is ideally constructed 15.5.10 MASONRY AND THE SUN
on the south elevation of the structure, or can be a
separate structure placed in front of and below the In passive solar heating systems the texture of
first floor. The heat flow is by natural means in any surface makes masonry a logical partner with the sun.
design. In this system and in the typical active hot air One of the advantages of masonry is the permanent
systems, no fans or pumps are required. color will not fade or degrade in direct sunlight or high
heat. Also, masonry requires no painting and little or
15.5.9.5 T HERMAL STORAGE ROOF no maintenance. The character and beauty of living
spaces is enhanced by the exposed brick or block on
Typically, masonry or water is the storage mass in the interior of a structure in addition to serving the
a thermal storage roof system located on the roof of a passive solar purpose.
structure. The roof decking, metal or concrete,
supports this mass and also serves as the ceiling for For example, masonry contains a combination of
the space below. This storage roof provides the physical qualities for top performance in passive solar
efficient and even transfer of heat from the mass systems. These attributes are:
above. The thermal storage roofs can provide effective
heating and cooling, and are appropriate passive Conductivity
systems for desert climates due to the location and Absorptivity
operation of the storage component. Specific heat
Emissivity
Thermal storage roofs do not require a collector Mass
component. The storage component is exposed to
the sky and heated by direct radiation from the sun. The attributes of mass cannot be exaggerated.
This heat is stored and slowly transferred through the Masonry walls or floors are an efficient storage
ceiling deck to the living spaces below as illustrated in medium, absorbing and holding heat. Also, it is a
Figure 15.40. moderator of temperature preventing overheating and
keeping a comfortable environment as heat is released
into living spaces. The reason lies in the nature of
masonry: it absorbs the sun’s heat slowly and releases
it slowly. Masonry mass is at the heart of passive solar
efficiency.
16
UNIT CONVERSIONS
ENGLISH/METRIC CONVERSION
Unit Exact Conversion Approximate Conversion
Length
1
1 mile 1.609344 kilometers 1.6 km or 1 /2 km
1 yard 0.9144 meter 0.9 m or 1 meter
1
1 foot 0.3048 meter 0.3 m or /3 meter
1
1 inch 25.40 millimeters 25 mm or /40 meter
Area
2
1 acre 4,046.856 square meters 4000 m
1 2 2
1 square foot 0.0929 square meters /10 m or 1000 cm
2 2
1 square inch 645.2 square millimeters 6 cm or 650 mm
Volume
3 3
1 cubic yard 0.7646 cubic meter or /4 m or
764.56 liters 750 liters
1 3
1 cubic foot 0.0283 cubic meter or /35 m or
28.217 liters 30 liters
3 3
1 cubic inch 16.387 cubic centimeters 16 cm or 16,000 mm
3
1 gallon 3,785.4 cubic centimeters or 4,000 cm or
3.785 liters 4 liters
3
1 quart 946.35 cubic centimeters or 1,000 cm or
0.94635 liter 1 liter
Speed
1
1 mile per hour 1.609344 kilometers per hour 1.6 km/h or 1 /2 km/h
1
1 foot per second 0.3048 meter per second 0.3 m/s or /3 m/s
Weight or Mass
1 ounce 28.35 grams 30 grams
1
1 pound 0.45359 kilogram or 453 grams /2 kg or 500 g
1 kip 453.59 kilograms 500 kg or 0.5 Mg
1 Ton (short) * 907.18 kilograms 1 Mg
Density
3
1 pounds/cubic foot 16.018 kilograms/cubic meter 16 kg/m
3
1 pounds/gallon 119.83 kilograms/cubic meter 120 kg/m
* A short Ton is a unit of weight equal to 2,000 pounds (0.907 metric ton or 907.18 kilograms), as compared to a Long Ton which is a unit of
weight equal to 2,240 pounds (1.016 metric tons or 1,016.05 kilograms).
356 MASONRY DESIGN MANUAL
METRIC/ENGLISH CONVERSION
Unit Exact Conversion Approximate Conversion
Length
5
1 kilometer 0.6214 mile /8 mile or 0.6 mile
3
1 meter 3.2808 feet or 39 /8 inches 3 ft. 3 in. or 3 ft.+
3
1 centimeter 0.3937 inch 0.4 inch or /8 inch
1
1 millimeter 0.0394 inch /32 inch
Area
1 2
1 square kilometer 0.3861 square mile or 247.1 acres /3 mi or 250 acres
1 2 2
1 square meter 1.196 square yds or 10.764 sq.ft. /2 yd or 10 ft
1 2
1 square centimeter 0.155 square inch /6 in
Volume
3
35.315 cubic feet or 35 ft or
1 cubic meter
264.17 gallons 265 gallons
0.0353 cubic feet or
1 liter 3 1 3
0.2642 gallon or 61.024 in /4 gallon or 1 quart or 60 in
1 3
1 cubic centimeter 0.061 cubic inch /16 in
Speed
5
1 kilometer per hour 0.6214 mile per hour /8 mph or 0.6 mph
1 meter per second 3.2808 feet per second 3 ft/s or 1 yd/s
Weight or Mass
1
1 gram 0.03527 ounce /30 ounce
1
1 kilogram 2.205 pounds 2 /4 pounds or 2 pounds
1
1 megagram 2.205 kips or 2,205 pounds 2 /4 kips or 2,000 pounds
1 gigagram 1,102 Tons or 2,205,000 lbs 1,000 Tons or 2 million lbs
Density
1 3
1 gram/cubic centimeter 8.345 lbs/gal or 62.428 lbs/cu ft 8 /2 lbs/gal or 62 lbs/ft
1 1 3
1 kg/cubic meter 0.0081345 lbs/gal or 0.062428 lbs/cu ft /8 oz/gal or /16 lbs/ft
Force
1
1 newton 0.2248 pound force /4 pound force
1 kilo newton 224.8 pound force 225 pound force
Pressure
1 pascal 0.000145 pounds/square inch
1
1 kilo pascal 0.145 pounds/square inch /7 psi
1 mega pascal 145 pounds/square inch 150 psi
Moment
3
1 newton meter 0.737 foot pound force /4 ft lb
3
1 kilo newton meter 0.737 foot kip force /4 ft kip
1
1 newton meter/meter 0.225 foot pound force/foot /4 ft lb/ft
Energy
1000 joules 0.94845 BTU 1 BTU
Temperature
ºCelcius [(1.8 x ºC)+32] ºFahrenheit
17
GLOSSARY
American Bond –A form of bonding two wythes of Apron Wall –That part of a wall that is below a window
masonry wall together with a header course sill.
occurring at every sixth course. The remaining
courses are stretcher courses.
360 MASONRY DESIGN MANUAL
Arch Brick –A wedge shaped brick for special use in Belt Course –See Sill Course.
arches.
Bevel - Once side of a solid body that is sloped with
respect to another side.
B
Backup - That part of a masonry wall behind the
exterior facing.
Bed –The horizontal surfaces (mortar) on which the Breaking Joints –Any arrangement of masonry units
masonry units of the wall lie in courses. which prevents a continuous vertical joint line.
Bed Joint –The horizontal mortar joint upon which Brick –A solid masonry unit of clay or shale, usually
the masonry units are placed. formed into a rectangular prism while plastic and
burned or fired in a kiln.
C
C/B ratio –The ratio of the weight of water absorbed
by a masonry unit during immersion in cold water
to weight absorbed during immersion in boiling
water. An indication of the probable resistance of Channel Block –A CMU with the web portions
brick to freezing and thawing. Also called saturation depressed less than 11/4 in. (6.4 mm) to produce
coefficient. See ASTM C 67. a continuous horizontal channel in which horizontal
reinforcement may be laid.
Camber –A slight arching or upward curve of a beam
or a soffit.
Camber
Cap –Masonry units laid on top of a finished wall or Chase –A continuous recess built into a wall to receive
pier. pipes, ducts, etc.
Cavity Wall –A wall built of two or more wythes of Checkerboard Bond - See Stacked Bond.
masonry units arranged to provide a continuous
air space within the wall. The wythes of wall are Chimney –A shaft built to carry off smoke.
tied together.
Chimney Breast –The projection of the interior or
Cell –A hollow space within a concrete masonry unit exterior face of a wall caused by fireplaces or flues.
formed by the face shells and the webs having a
gross cross-sectional area greater than 11/2 square Chimney Lining -–Fire brick, fire clay, terra cotta or
inches (968 mm2). refractory cement, made to cover the walls of a
chimney to protect the masonry from the effects
of heat.
Cell
Chimney Throat –That part of a chimney directly
above the fireplace where the walls are brought
close together.
Cleanout –Opening in the first course, of a masonry Concrete Block –See Concrete Masonry Unit.
brick wall one or concrete block wall, where the
openings are used to clean out mortar protrusions Concrete Brick –A solid concrete masonry unit made
and droppings. from portland cement and suitable aggregates with
or without additional materials.
D
Damp Course –A course or layer of impervious
material which prevents capillary action of moisture
entering from the ground or a lower course. Also
known as damp check.
Extrados –The exterior curve in an arch or vault. Flare Header –A brick burned on one end to a darker
color than the face.
Fascia –The flat outside horizontal member of a Flemish Bond –A masonry wall having a bond course,
cornice. in every course, consisting of alternating headers
and stretchers. The masonry is so laid that the
Fat Mortar –Mortar containing a high percentage of header lands in the middle of the stretchers above
cementitous components. It is a sticky mortar that and below.
adheres to a trowel.
Floor Brick –Smooth dense brick, highly resistant to
Field –The expanse of area of wall between defining abrasion, used as finished floor surface.
element (i.e. openings, corners, etc.). Typically
composed of a majority of stretcher units. Fretwork –Any ornamental openwork or work in relief.
Fire Box - The interior of fireplace or furnace, serving Frog –A recess in the bearing surface of a brick, not
as the combustion space. exceeding 3/ 8 in. (9.5 mm) in depth, and often
contains the stam ped name of the brick
Fire Brick - Brick made of refractory ceramic material manufacturer.
which will resist cracking when exposed to high
temperatures.
Head joint
Hacking –Laying masonry units so that the bottom ICC –International Code Council.
edge is set back from the plane surface of the
wall. Impervious –The quality of resisting moisture
penetration.
Hard-Burned –Clay masonry products that have been
fired at high temperatures to near vitrification, In Situ –A Latin phrase meaning –in the original or
generally producing low-absorption and high natural place. It is used in construction to
compression strength. reference what was actually built in the field.
Harsh Mortar –A mortar that is difficult to spread. It Initial Rate of Absorption –The amount of water a
is not workable. dry brick will absorb in one minute. The initial rate
of absorption is not to be confused with absorption.
There is no consistent relationship between the
initial rate of absorption and absorption.
366 MASONRY DESIGN MANUAL
Intrados –The under surface or interior curve of an Lean Mortar –Mortar containing a low percentage of
arch. cementitious components.
Jack Arch –An arch that is horizontal or nearly Lightweight CMU –Concrete masonry units that
horizontal. May also be called a flat arch or a consist of lightweight aggregate. Unit weight is
straight arch. The term is also used for any roughly less than 105 pcf.
built arch.
Lime –
Jack Bond –See Stacked Bond. Lime Putty –Hydrated lime in plastic form ready
for addition to mortar.
Jamb –The side of an opening, such as a doorway or
a window. Hydrated Lime –A dry powder obtained by
treating quick lime with water enough to satisfy
Joint Reinforcement –Steel wire, bar or prefabricated its chemical affinity for water under conditions
reinforcement which is placed in mortar bed joints. of its hydration. The term may be modified by
the use of the prefix high calcium, magnesium,
pressure, etc., depending on the exact
chemical cont ent and m ethod of
manufacturing. Hydraulic hydrated lime is a
different material and is not generally used in
masonry construction.
Kerf - A cut made with a saw where the cut does not
go through the masonry unit. A kerf cut can
facilitate the break line of a unit.
L Line pin
Racking – A method entailing stepping back Reveal –That portion of a jamb or recess which is
successive courses of masonry. visible from the face of a wall.
Salient –A prominent feature. Solid Brick - A brick with interior voids creating bearing
surfacing that are at least 75% of the gross cross-
Sailor –an orientation of brick, such that the long and sectional area. No part of any void can be closer
wide face is exposed and laid upright. than ¾”to an exterior edge. It is noted that the
term solid brick does not necessarily mean 100%
Saturation Coefficient –See C/B ratio. solid.
Scutch –A mason’ s cutting tool used for dressing and Spall –A small thin fragment removed from the face
trimming brick to a desired shape. It resembles a of a masonry unit by a blow or by action of the
small pick and is sometimes call a “ scotch” . elements (freeze/thaw).
Slurry –A thin watery mixture of neat cement, or Splay –An inclined surface, as the slope of bevel at
cement and sand. the sides of a door or window; also to make a
beveled surface or to spread out.
Slurry Coat –A brushed application of slurry, generally
applied to the back of adhered veneer units and Split –See Soap.
the support backing.
Stacked Bond –A bonding pattern where no unit
Smoke Chamber – The space in a f ireplace overlaps either the unit above or below by more
immediately above the throat where the smoke than 25% of the length of the unit. Also known as
gathers before passing into the flue and narrowed a plumb joint bond, straight stack, jack bond, or
by the corbeling to the size of the flue lining. checkerboard bond.
Standard Modular Brick –Standard nomenclature Thin Brick - A brick specifically designed for adhered
for a nominal brick size of 4"(width) x 22/3"(height) veneer application. Common thickness are 1/2" to
x 8"(length). 1", with typical maximum thickness of 13/4” .
Stiff Brick –A brick produced by extruding stiff but Tie –Any unit of material which connects masonry to
plastic clay through a die. This is the most masonry or other materials.
common way of mass production of bricks.
Tooling –Compressing and shaping the face of a
Straight Stack –See Stacked Bond. mortar joint with a special tool other than a trowel.
Also known as jointing.
Stretcher –An orientation of brick, such that the long
and thin face is exposed and laid flat.. Toother –A brick projecting from the end of a wall
against which another wall will be built.
String Course –See Belt Course.
Existing New
U
Utility Brick –A standard nomenclature for a brick
size of 4"(width) x 4"(height) x 12"(length).
W
Weep Holes –Openings placed in mortar joints of
facing material at the level of flashing, to permit
the escape of moisture that has built up behind
the wall. Also openings in retaining walls to allow
the escape of water that has built up behind the
retaining wall.
2003/2006 International Building Code, published by ASTM A 706/A 706M-06a Standard Specification for
International Code Council, 5203 Leesburg Pike, Suite Low-Alloy Steel Deformed and Plain Bars for Concrete
600, Falls Church, VA, 22041-3401, www.iccsafe.org. Reinforcement.
2002/2005 Masonry Standard Joint Committee Code, ASTM A 707/A 707M-02 Standard Specification for
Specification and Commentaries, published by ACI Forged Carbon and Alloy Steel Flanges for Low-
Internationl, SEI - Structural Engineering Institute of Temperature Service.
the American Society of Civil Engineers, TMS - The
Masonry Society. ASTM A 767/A 767M-05 Standard Specification for
Zinc-Coated (Galvanized) Steel Bars for Concrete
American Architectural Manufacturers Association Reinforcement.
(AAMA) - Filed Test Specification 501.2 for Water
Leakage. ASTM A 775/A 775M-06 Standard Specification for
Epoxy-Coated Steel Reinforcing Bars.
Angelus Block Co., Inc., 11374 Tuxford St., Sun Valley,
CA 91352-2678, www.angelusblock.com. ASTM A 951 Standard Specification for Masonry Joint
Reinforcement.
Architectural Drafting and Design, Alan Jefferis and
David A. Madsen, Delmar Publishers Inc. ASTM A 996/A 996M-06a Standard Specification for
Rail-Steel and Axle-Steel Deformed Bars for Concrete
Architectural Graphic Standards, Tenth Edition, Reinforcement.
Ramsey/Sleeper, John Wiley & Sons, Inc.
ASTM C 55 Standard Specification for Concrete Brick.
ASHRAE Handbook of Fundamentals.
ASTM C 62 Standard Specification for Building Brick
ASTM A 82/A 82M-02 Standard Specification for Steel (Solid Masonry Units Made from Clay or Shale).
Wire, Plain, for Concrete Reinforcement.
ASTM C 67 Standard Test Methods for Sampling and
ASTM A 167 Standard Specification for Stainless and Testing Brick and Structural Clay Tile.
Heat-Resisting Chromium-Nickel Steel Plate, Sheet
and Strip. ASTM C 90 Standard Specification for Loadbearing
Concrete Masonry Units.
ASTM A 615/A 615M-06a Standard Specification for
Deformed and Plain Carbon-Steel Bars for Concrete ASTM C 91 Standard Specification for Masonry
Reinforcement. Cement.
ASTM A 653/A 653M-06 Standard Specification for ASTM C 126 Standard Specification for Ceramic
Steel Sheet, Zinc-Coated (Galvanized) or Zinc-Iron Glazed Structural Clay Facing Tile, Facing Brick, and
Alloy-Coated (Galvannealed) by the Hot-Dip Process. Solid Masonry Units.
374 MASONRY DESIGN MANUAL
ASTM C 129-05 Standard Specification for ASTM C 780 Standard Test Method for Preconstruction
Nonloadbearing Concrete Masonry Units. and Construction Evaluation of Mortars for Plain and
Reinforced Unit Masonry.
ASTM C 140 Standard Test Methods for Sampling and
Testing Concrete Masonry Units and Related Units. ASTM C 880 Standard Test Method for Flexural
Strength of Dimension Stone.
ASTM C 144 Standard Specification for Aggregate for
Masonry Mortar. ASTM C 902 Standard Specification for Pedestrian and
Light Traffic Paving Brick.
ASTM C 150 Standard Specification for Portland
Cement. ASTM C 1019 Standard Test Method for Sampling and
Testing Grout.
ASTM C 170 Standard Test Method for Compressive
Strength of Dimension Stone. ASTM C 1088 Standard Specification for Thin Veneer
Brick Units Made from Clay or Shale.
ASTM C 207 Standard Specification for Hydrated Lime
for Masonry Purposes. ASTM C 1142 Standard Specification for Extended Life
Mortar for Unit Masonry.
ASTM C 216 Standard Specification for Facing Brick
(Solid Masonry Units Made from Clay or Shale). ASTM C 1314 Standard Test Method for Compressive
Strength of Masonry Prisms.
ASTM C 270 Standard Specification for Mortar for Unit
Masonry. ASTM C 1329 Standard Specification for Mortar
Cement.
ASTM C 404 Standard Specification for Aggregates
for Masonry Grout. ASTM E 84 Standard Test Method for Surface Burning
Characteristics of Building Materials.
ASTM C 426 Standard Test Method for Linear Drying
Shrinkage of Concrete Masonry Units. ASTM E 119 Standard Test Methods for Fire Tests of
Building Construction and Materials.
ASTM C 476 Standard Specification for Grout for
Masonry. ASTM E 492 Standard Test Method for Laboratory
Measurement of Impact Sound Transmission Through
ASTM C 501 Standard Test Method for Relative Floor-Ceiling Assemblies Using the Tapping Machine.
Resistance to Wear of Unglazed Ceramic Tile by the
Taber Abraser. ASTM E 514 Standard Test Method for Water
Penetration and Leakage Through Masonry.
ASTM C 503 Standard Specification for Marble
Dimension Stone (Exterior). Astra-Glaze • Glazed Masonry Units • Trenwyth
Industries • One Connelly Road • P.O. Box 438 •
ASTM C 568 Standard Specification for Limestone Emigsville, PA 17318, www.trenwyth.com/
Dimension Stone. astra_glaze.asp.
ASTM C 615 Standard Specification for Granite BIA Technical Notes 3A, Brick Masonry Material
Dimension Stone. Properties, www.bia.org.
ASTM C 616 Standard Specification for Quartz-Based BIA Technical Notes 3B, Brick Masonry Section
Dimension Stone. Properties, www.bia.org.
ASTM C 629 Standard Specification for Slate BIA Technical Notes 7, Water Penetration Resistance-
Dimension Stone. Design and Detailing, www.bia.org.
ASTM C 652 Standard Specification for Hollow Brick BIA Technical Notes 7B, Water Penetration Resistance
(Hollow Masonry Units Made from Clay or Shale). - Construction and Workmanship, www.bia.org.
ASTM C 744 Standard Specification for Prefaced BIA Technical Notes 9B, Manufacturing, Classification
Concrete and Calcium Silicate Masonry Units. and Selection of Brick, Selection, www.bia.org.
REFERENCES 375
BIA Technical Notes 10A, Modular Brick Masonry, CMACN, Concrete Masonry Association of California
www.bia.org. and Nevada, 6060 Sunrise Vista Drive, Suite 1990,
Citrus Heights, CA 95610, www.cmacn.org.
BIA Technical Notes 10B, Brick Sizes and Related
Information, www.bia.org. Concrete Reinforcing Steel Institute, CRSI, 933 N.
Plum Grove Road, Schaumburg, IL 60173-4758,
BIA Technical Notes 14B, Brick Floors and Pavements, www.crsi.org.
www.bia.org.
Cold Spring Granite Company, 202 South Third
BIA Technical Notes 18A, Design and Detailing of Avenue, Cold Spring, MN 56320-2593,
Movement Joints, www.bia.org. www.coldspringgranite.com.
BIA Technical Notes 21A, Brick Masonry Cavity Walls Design Guide for Anchored Brick Veneer Over Steel
Selection of Materials, www.bia.org. Studs, Western States Clay Products Association,
www.wscpa.us.
BIA Technical Notes 21B, Brick Masonry Cavity Walls
Detailing, www.bia.org. Design Manual for: Concrete Masonry Basements,
prepared by NCMA, published by CMACN.
BIA Technical Notes 26, Single Wythe Bearing Walls,
www.bia.org. Dur-O-Wal, 625 Crane St., Aurora, IL 60505, www.dur-
o-wal.com.
BIA Technical Notes 27, Brick Masonry Rain Screen
Walls, www.bia.org. Efflorescence: Cause and Control, Michael W.
Merrigan, P.E., Masonry Institute of America.
BIA Technical Notes 28, Anchored Brick Veneer, Wood
Frame Construction, www.bia.org. Endicott Clay Products Company, P.O. Box 17,
Fairbury, NE 68352, www.endicott.com.
BIA Technical Notes 28B, Brick Veneer/Steel Stud
Walls, www.bia.org. FEMA, Taking Shelter from the Storm Building a Safe
Room Inside your House (Pub. FEMA 320, March,
BIA Technical Notes 30, Bonds and Patterns in 2004), www.fema.gov/mit/saferoom.
Brickwork, www.bia.org.
FEMA, Design and Construction Guidance for
BIA Technical Notes 31, Brick Masonry Arches, Community Shelters (Pub. FEMA 361, July, 2000),
www.bia.org. www.fema.gov/fima/fema361.shtm.
BIA Technical Notes 36, Brick Masonry Details, Sills Fire Endurance Ratings of Clay Brick Masonry,
and Soffits, www.bia.org. Western States Clay Products Association,
www.wscpa.us.
BIA Technical Notes 43, Passive Solar Heating with
Brick Masonry, www.bia.org. Fire Safety Update, Brick Institute of California.
Brick Industry Association, BIA, 1850 Centennial Park Flexible Vehicular Brick Paving, Brick Industry
Drive, Suite 301, Reston, VA 20191-1542, www.bia.org. Association, www.bia.org.
Build with the Sun Live with the Sun, Brick Industry Fundamentals of Building Construction Materials and
Association, BIA, 11490 Commerce Park Drive, Methods, by Edward Allen, John Wiley & Sons.
Reston, VA 20191, www.bia.org.
Gladding McBean Co., 601 7th Street, Lincoln, CA
Building Stone Institute, 551 Tollgate Road, Suite C, 95648-1828, www.gladdingmcbean.com.
Elgin, IL 60123, www.buildingstoneinstitute.org.
ICC Legacy Report, Fire Endurance of Clay Brick
Can Efflorescence be Controlled?, Jeffrey L. Elder, Veneer, report by Walter L. Dickey, www.icc-es.org/
P.E., Western States Clay Products Association. reports/pdf_files/icbo-es/5058.pdf.
Concrete Masonry Design Manual, CMACN, Concrete Indiana Limestone Institute of America, Inc., 400 Stone
Masonry Association of California and Nevada, 6060 City Bank Bldg., Bedford, Indiana 47421,
Sunrise Vista Drive, Suite 1990, Citrus Heights, CA www.iliai.com.
95610, www.cmacn.org.
376 MASONRY DESIGN MANUAL
Masonry Advisory Council, 1480 Renaissance Drive, Principles of Brick Masonry, Brick Industry Association,
Suite 302, Park Ridge, IL 60068, www.MacOnline.org. BIA, 1850 Centennial Park Drive, Suite 301, Reston,
VA 20191, www.bia.org.
Masonry Design Manual, Third Edition, Masonry
Institute of America, www.masonryinstitute.org. PROSOCO, 3741 Greenway Circle, Lawrence, KS
66046, www.PROSOCO.com.
Masonry Veneer, 2nd Edition, Masonry Institute of
America, www.masonryinstitute.org. Reinforced Concrete Masonry Construction
Inspector’s Handbook, Fifth Edition, Masonry Institute
Marble Institute of America, 28901 Clemens Road, of America, www.masonryinstitute.org.
Suite 100, Cleveland, Ohio, 44145, www.marble-
institute.com. Reinforced Grouted Brick Masonry, Fourteenth
Edition, Masonry Institute of America,
Marble & Stone Slab Veneer, Second Edition, Masonry www.masonryinstitute.org.
Institute of America, www.masonryinstitute.org.
Reinforced Masonry Engineering Handbook, Fifth
National Building Granite Quarries Association, 1220 Edition Updated, Masonry Institute of America,
L Street, NW, Suite 100-167, Washington, DC 20005, www.masonryinstitute.org.
www.nbgqa.com.
Reinforcing Steel in Masonry, Masonry Institute of
National Concrete Masonry Association, NCMA, 13750 America, www.masonryinstitute.org.
Sunrise Valley Drive, Herndon, VA 20171-4662,
www.ncma.org. Removing Efflorescence, John A. Koski, Masonry
Construction Magazine (1992).
NCMA TEK NOTE 7-1A, Fire Resistance Rating of
Concrete Masonry Assemblies, www.ncma.org. RILEM Tube Test by The Construction Technology
Laboratories, Inc.
NCMA TEK NOTE 8-2A, Removal of Stains from
Concrete Masonry, www.ncma.org. Standard Handbook of Structural Details for Building
Construction, Second Edition, Morton Newman,
NCMA TEK NOTE 8-4, Removal of Graffiti from McGraw-Hill, Inc., 1221 Avenue of the Americas, New
Concrete Masonry, www.ncma.org. York, NY 10020.
NCMA TEK NOTE 10-1A, Crack Control in Concrete Standard Practice for Bracing Masonry Walls Under
Masonry Walls, www.ncma.org. Construction (2001), Council for Masonry Wall Bracing.
NCMA TEK NOTE 18-1A, Compressive Strength Stone Anchorage Design, Dimensional Stone
Evaluation of Concrete Masonry, www.ncma.org. Magazine, 1992.
NCMA TEK NOTE 18-3B, Concrete Masonry Stone Maintenance & Care, Dimensional Stone
Inspection www.ncma.org. Magazine, 1991.
NCMA TEK NOTE 18-5A, Masonry Mortar Testing, The Proudfoot Company, Inc., Architectural Acoustics,
www.ncma.org. 588 Pepper Street, PO Box 276, Monroe, CT 06468-
2672, www.soundblox.com.
NCMA TEK NOTE 19-4, Flashing Strategies for
Concrete Masonry Walls, www.ncma.org. W.R. Grace & Co. - Conn., Grace Masonry Products,
62 Whittemore Avenue, Cambridge, MA 02140-1692,
NCMA TEK NOTE 19-5A, Flashing Details for www.na.graceconstruction.com.
Concrete Masonry Walls, www.ncma.org.
19
INDEX
Anchors--------------------------------------------------------------------65, 272
A Angle Brick--------------------------------------------------------------------2
Appearance-------------------------------------------------------------------6
Arch Brick----------------------------------------------------------------------3
Absorption and Saturation--------------------------------------------6, 10 Arch Types and Terminology------------------------------------------135
Abutments-------------------------------------------------------------------143 Architectural Feature Units----------------------------------------------30
Accessory Block------------------------------------------------------------27 Architectural Units---------------------------------------------------------21
Acoustics-------------------------------------------------------------------104 Cap Units----------------------------------------------------------------22
Decibels--------------------------------------------------------------104 Screen Block-----------------------------------------------------------22
Sound Transmission Class--------------------------------------104 Slumped Unit-----------------------------------------------------------21
Transmission Loss-------------------------------------------------104 Split Face Units---------------------------------------------------------21
Active Solar Heating---------------------------------------------------------351 Veneer Units----------------------------------------------------------21
Adhered Veneer-----------------------------------------------------------298 Areas of Refuge----------------------------------------------------------212
Adhered Veneer Installation-------------------------------------------299 Asphalt-Impregnated Felt------------------------------------------------94
Admixtures-------------------------------------------------------------------72 ASTM Stone Specifications----------------------------------------------38
Aesthetic Design----------------------------------------------------------83 Attached Sunspace------------------------------------------------------353
Brick Masonry Bond Patterns------------------------------------83 Attachment of Components---------------------------------------------105
Common or American Bond--------------------------------84
English Bond---------------------------------------------------85
English Cross or Dutch Bond------------------------------85
Flemish Bond--------------------------------------------------84
Running Bond--------------------------------------------------83 B
Stack Bond--------------------------------------------------85
Wall Texture----------------------------------------------------85
Brick Masonry Dimensioning-------------------------------------87 Backing-----------------------------------------------------------------------99
Color--------------------------------------------------------------------88 Barrier and Drainage Walls------------------------------------------------106
Modular Brick Masonry---------------------------------------------85 Basement Design------------------------------------------------------------212
Coordination of Masonry Units----------------------------86 Beaded Joint----------------------------------------------------------------75
Dimensions of Modular Units------------------------------86 Beam with Vertical Load------------------------------------------------216
Grid Locations of Masonry Walls-------------------------86 Bearing Wall Types-------------------------------------------------------116
Initial Design Considerations------------------------------86 Block Veneer, Concrete Units-----------------------------------------307
Scale--------------------------------------------------------------------89 Bond and Anchorage------------------------------------------------------93
Texture------------------------------------------------------------------88 Brick-----------------------------------------------------------------1, 99, 144
Aggregates for Grout------------------------------------------------------77 Mortar and Grout------------------------------------------------------5
Allowable Stresses---------------------------------------------------------92 Orientation of Brick---------------------------------------------------3
Aluminum--------------------------------------------------------------------95 Patterns of Brick-------------------------------------------------------4
Anchor Bolt--------------------------------------------------------------------229 Reinforced Brick - An Overview-----------------------------------1
General------------------------------------------------------------------229 Shapes of Brick--------------------------------------------------------2
Ties at Anchor Bolts-------------------------------------------------230 Angle Brick-------------------------------------------------------2
Anchorage of Reinforcing Steel in Masonry-----------------------227 Arch Brick---------------------------------------------------------3
Development Length----------------------------------------------227 Building Brick----------------------------------------------------3
Development Length of Straight Reinforcement----227 Face Brick or Facing Brick-----------------------------------3
Hooks-----------------------------------------------------------228 Fire Brick----------------------------------------------------------3
Lap Splices for Reinforcing Steel------------------------------229 Hollow Brick------------------------------------------------------3
Special Provisions for Higher Seismic Risk-----------------229 Paving Brick------------------------------------------------------3
Anchored Veneer-------------------------------------------------------------301 Solid Brick--------------------------------------------------------3
Thin Brick---------------------------------------------------------3
378 MASONRY DESIGN MANUAL
F 51, 55, 161, 171, 202, 215, 229, 231, 235, 283, 289, 325
General Notes-----------------------------------------------------------------202
General Requirements--------------------------------------------------296
Glass Block---------------------------------------------------------------51, 283
Face Brick Durability Physical Requirements-----------------------10 General------------------------------------------------------------------283
Face Brick or Facing Brick------------------------------------------------3 Code Requirements-------------------------------------------283
INDEX 381
Design-------------------------------------------------------------283 Hollow Spaces-----------------------------------------------------------------15
Energy Conservation------------------------------------------283 Hollow Brick Section Properties------------------------------------------15
Environmental--------------------------------------------------283 Hollow Brick Tolerances on Dimensions-----------------------------16
Installation----------------------------------------------------284 Hollow Brick Tolerances on Distortion--------------------------------16
Maintenance---------------------------------------------------283 Honeycomb Stone--------------------------------------------------------299
Security-----------------------------------------------------------283 Hooks------------------------------------------------------------------------228
Glass Block Applications--------------------------------------------------53 Housekeeping----------------------------------------------------------------339
Glass Block Construction----------------------------------------------297 Horizontal Surfaces------------------------------------------------------334
Glass Block Properties-----------------------------------------------------52 Humidity----------------------------------------------------------------------93
Glazed CMU-----------------------------------------------------------------34 Hybrid Solar Heating------------------------------------------------------352
Glossary--------------------------------------------------------------------359 Hydrated Lime-------------------------------------------------------------71, 99
Grade----------------------------------------------------------------------------10 Hydrostatic Loads----------------------------------------------------------90
Grade of Brick----------------------------------------------------------------5
Grade NW (Negligible Weathering)------------------------------5
Grade MW (Moderate Weathering)------------------------------5
Grade SW (Severe Weathering)----------------------------------5
Grade Recommendations for Face Exposures-----------------5, 10
Grading Requirements-------------------------------------------------------77
I
Granite-----------------------------------------------------------------42, 240
Granite Building Applications------------------------------------------240 Impact Noise Control--------------------------------------------------------345
Granite Details------------------------------------------------------------242 Index----------------------------------------------------------------------------377
Granite Characteristics--------------------------------------------------240 Initial Design Considerations--------------------------------------------86
Granite Maintenance Tips----------------------------------------------242 Initial Rate of Absorption (I.R.A.)--------------------------------------8, 13
Grapevine Joint-------------------------------------------------------------75 Inspections-----------------------------------------------------------------335
Gravity Walls---------------------------------------------------------------204 Installation--------------------------------------------------147, 247, 284, 297
Grid Locations of Masonry Walls---------------------------------------86 Integral Water Repellents----------------------------------------------331
Ground Water---------------------------------------------------------------93 Interior Moisture Control------------------------------------------------332
Grout------------------------------------------------------------------------------75 Interior Veneer-------------------------------------------------------------247
12 Foot Grout Lifts----------------------------------------------------82 Introduction--------------------------------------------------------------------348
Proportions------------------------------------------------------------77 Isolation vs. Insulation--------------------------------------------------342
Aggregates--------------------------------------------------------77 Insulation-----------------------------------------------------------------------151
Consolidation---------------------------------------------------82 Insulation by STC------------------------------------------------------------342
Grout Admixtures---------------------------------------------77
Grout Pour and Lift-------------------------------------------79
Grout Strength Requirements-----------------------------78
High Lift Grouting Procedure-------------------------------80
Low Lift and High Lift Grouting----------------------------79
J
Low Lift Grouting Procedure-------------------------------79
Methods of Grouting Walls---------------------------------79 Job Site Mortar Mix--------------------------------------------------------72
Mixing Grout----------------------------------------------------77 Joint Reinforcement-------------------------------------------------------58
Testing Grout Strength-----------------------------------------78 Joint Reinforcement and Ties-----------------------------------------227
Types of Grout--------------------------------------------------------75
Coarse Grout---------------------------------------------------76
Fine Grout-------------------------------------------------------76
Self-Consolidating Grout---------------------------------------76
Slump---------------------------------------------------------------76
Grout Admixtures-----------------------------------------------------------77
L
Grout Pour and Lift--------------------------------------------------------79
Grout Proportions by Volume-------------------------------------------77 Landscaping---------------------------------------------------------------152
Grout Strength Requirements-------------------------------------------78 Lap Splices for Reinforcing Steel-------------------------------------229
Guide for the Selection of Masonry Mortars------------------------68 Lateral Stability----------------------------------------------------------93, 143
Lateral Support-------------------------------------------------------------92
Layout and Assembly---------------------------------------------------172
Modular Considerations------------------------------------------172
H Modular Dimensions----------------------------------------------172
Lead---------------------------------------------------------------------------95
Limestone-------------------------------------------------------------42, 271
Limestone Details------------------------------------------------------------274
Head Details---------------------------------------------------------------285 Lintel and Bond Beam Connection--------------------------------------189
Heat Transfer--------------------------------------------------------------102 Live Loads-------------------------------------------------------------------90
R-Value---------------------------------------------------------------103 Load Distribution-----------------------------------------------------------90
Thermal Mass-------------------------------------------------------104 Loads--------------------------------------------------------------------------89
U-Value---------------------------------------------------------------103 Location of Expansion Joints------------------------------------------101
Heat Transmission Coefficients of Building Materials-----------103 Location of Reinforcement “ d”Distance----------------------------223
High-Bond Mortared Pavement------------------------------------------149 Low Lift and High Lift Grouting-----------------------------------------79
High Lift Grouting Procedure--------------------------------------------80 Low Lift Grouting Procedure--------------------------------------------79
Height Limit from Foundation---------------------------------------------302
Hollow Brick------------------------------------------------------------------3, 14
Color and Texture------------------------------------------------------16
Hollow Spaces---------------------------------------------------------15
Tolerances--------------------------------------------------------------16
Types-----------------------------------------------------------------------16
382 MASONRY DESIGN MANUAL
Testing-------------------------------------------------------------------335
M Water Repellent Types----------------------------------------------329
What is Waterproof---------------------------------------------------326
Mortar----------------------------------------------------------------67, 144, 151
Maintenance----------------------------------------151, 241, 259, 280, 283 Mixing-------------------------------------------------------------------72
Maintenance and Low Cost--------------------------------------------211 Extended Life Mortar-------------------------------------------73
Maintenance of Granite Surfaces------------------------------------241 Measurements of Mortar Materials-----------------------72
Manufacturer’ s Standards------------------------------------------------34 Job Site Mortar Mix-------------------------------------------72
Marble------------------------------------------------------------------42, 245 Pre-Blended Mortar-------------------------------------------73
Marble Application-----------------------------------------------------------245 Retempering----------------------------------------------------74
Marble Characteristics------------------------------------------------------246 Mortar Materials------------------------------------------------------70
Marble Details-----------------------------------------------------------------260 Admixtures------------------------------------------------------72
Masonry and the Sun-------------------------------------------------------354 Cements---------------------------------------------------------70
Masonry Cavity Bearing Walls--------------------------------------------121 Color--------------------------------------------------------------72
Masonry Cavity Walls with Concrete Frame-------------------------123 Hydrated Lime----------------------------------------------------71
Masonry Cements---------------------------------------------------------71 Masonry Cements--------------------------------------------70
Masonry Heaters---------------------------------------------------------156 Mortar Cements-----------------------------------------------71
Masonry Stresses-------------------------------------------------------------91 Mortar Sand----------------------------------------------------71
Compressive Stress------------------------------------------------91 Portland Cement----------------------------------------------70
Flexural Tension Stresses-----------------------------------------91 Water-------------------------------------------------------------72
Shear Stresses-------------------------------------------------------91 Types of Mortar------------------------------------------------------67
Masonry Sound Transmission Class (STC)---------------------------341 Property Specifications--------------------------------------68
Material Property Loads--------------------------------------------------90 Proportion Specifications-----------------------------------69
Material Selection------------------------------------------------------------144 Selection of Mortar Types-----------------------------------67
Materials-----------------------------------------------------------------------1 Specifying Mortar----------------------------------------------68
Materials for Single-Wythe Bearing Walls----------------------------109 Types of Mortar Joints----------------------------------------------74
Maximum Glass Block Panel Size------------------------------------284 Beaded Joint---------------------------------------------------75
Measurements of Mortar Materials------------------------------------72 Concave Joint--------------------------------------------------74
Methods of Grouting Walls----------------------------------------------79 Flush Joint------------------------------------------------------74
Metric--------------------------------------------------------------------------19 Grapevine Joint------------------------------------------------75
Metric/English Conversion---------------------------------------------357 Raked Joint-----------------------------------------------------75
Metric System Conversion-------------------------------------------------358 Squeezed Joint------------------------------------------------75
Minimum Area of Steel--------------------------------------------------221 Struck Joint-----------------------------------------------------75
Minimum Radius of Uncut Brick----------------------------------------141 “V”Joint---------------------------------------------------------74
Minimum Steel Ratios-------------------------------------------------------223 Weather Joint--------------------------------------------------74
Minimum Diameters of Bend------------------------------------------228 Mortar and Grout---------------------------------------------------5, 67, 99
Minimum Steel Requirements for High Seismic Exposure----222 Mortar Cements------------------------------------------------------------71
Minimum Steel Requirements for Low Seismic Exposure-----221 Mortar Materials------------------------------------------------------------70
Minimum Thickness----------------------------------------------------------92 Mortar Properties------------------------------------------------------------68
Minimum Thickness of Face Shells and Webs---------------------19 Mortar Proportions for Unit Masonry----------------------------------70
Minimum Reinforcement Requirements----------------------------221 Mortar Sand-----------------------------------------------------------------71
Minimum Area of Steel-------------------------------------------221 Mortar Types-Classes of Construction--------------------------------68
Minimum Steel Requirements for High Seismic Mortars and Pointing--------------------------------------------------------272
Exposure--------------------------------------------------222 Movement--------------------------------------------------------------------100
Minimum Steel Requirements for Low Seismic Movement Joints----------------------------------------------------------333
Exposure--------------------------------------------------221
Miscellaneous Interior Details-----------------------------------------286
Mixing-------------------------------------------------------------------------72
Mixing Grout-----------------------------------------------------------------77
Modular Brick Masonry---------------------------------------------------85
Modular Considerations---------------------------------------------------172
N
Modular Dimensions--------------------------------------------------------172
Moisture------------------------------------------------------------------------148 Natural Lighting---------------------------------------------------------------211
Moisture Intrusion--------------------------------------------------------327 Natural Stone-------------------------------------------------------------37, 235
Moisture Migration Control---------------------------------------------326 Navy Hose Stream Test----------------------------------------------------335
Moisture Movement--------------------------------------------------------100 Noise Control-------------------------------------------------------212, 340
Moisture Resistance----------------------------------------------------93, 325 Flanking Path Control---------------------------------------------344
Consideration in Selection------------------------------------------331 Impact Noise Control---------------------------------------------345
Inspections--------------------------------------------------------------335 Insulation by STC----------------------------------------------------342
Interior Moisture Control---------------------------------------------332 Isolation vs. Insulation--------------------------------------------342
Integral Water Repellents-------------------------------------------331 Masonry Sound Transmission Class (STC)--------------------341
Moisture Intrusion-----------------------------------------------------327 Sound Absorption and Noise Reduction-----------------------344
Openings---------------------------------------------------------329 STC Values of Masonry Walls----------------------------------342
Moisture Migration Control------------------------------------------326 Traffic Noise---------------------------------------------------------345
Other Critical Elements----------------------------------------------332 Design Considerations-------------------------------------346
Horizontal Surfaces--------------------------------------------334 Visual Considerations--------------------------------------348
Movement Joints-----------------------------------------------333 Noise Reduction Coefficient (NRC) of Selected Materials-------344
Wall Caps---------------------------------------------------------333 Non-Projecting Wall Columns---------------------------------------------233
Wall Penetrations----------------------------------------------335
Windows and Doors-------------------------------------------334
Surface Treatments---------------------------------------------------330
INDEX 383
Reinforcement Cover----------------------------------------------------227
O Reinforcement Requirements for Typical
Cantilever Retaining Wall-------------------------------------------208
Reinforcement Spacing----------------------------------------------------223
Openings-----------------------------------------------------------------------329 Clearances--------------------------------------------------------------225
Orientation of Brick----------------------------------------------------------3 Clear Spacing Between Reinforcing Bars----------------226
Other Critical Elements----------------------------------------------------332 Clearance Between Reinforcement and
Overhangs---------------------------------------------------------------------339 Masonry Units---------------------------------------------225
Location of Reinforcement “ d”Distance-------------------------223
Placement of Steel---------------------------------------------------224
Reinforcement Cover------------------------------------------------227
Deformed Reinforcement------------------------------------227
P Joint Reinforcement and Ties-------------------------------227
Reinforcing Bar Positioners-----------------------------------------225
Tolerances for Placement of Reinforcement-------------------224
Reinforcing Bar Positioners--------------------------------------------225
Panel Anchor Details----------------------------------------------------287
Reinforcing Bars------------------------------------------------------------56
Parapet Walls--------------------------------------------------------------108
Reinforcing Steel----------------------------------------------------55, 215
Parapets-----------------------------------------------------------------------156
Reinforcing Steel Bar Designation---------------------------------------56
Passive Solar Energy----------------------------------------------------351
Residential Construction Isometric with Diaphragm Roof--------195
Passive Solar Heating----------------------------------------------------351
Residential Construction Isometric without Roof Diaphragm----197
Passive Solar Basics--------------------------------------------------------352
Residential Design-------------------------------------------------------197
Passive Solar Systems-----------------------------------------------------352
Foundation Detail for Residential Construction------------200
Patterns of Brick-------------------------------------------------------------4
Raised Wood Floor Connection for Residential
Paving Brick-------------------------------------------------------------------3
Construction----------------------------------------------------199
Paving Units-----------------------------------------------------------------22
Residential Construction Isometric with
Permissible Variation in Dimensions------------------------------------8
Diaphragm Roof-----------------------------------------------195
Physical Characteristics--------------------------------------------------40
Residential Construction Isometric without
Physical Nature------------------------------------------------------------41
Roof Diaphragm-----------------------------------------------197
Pilaster Details----------------------------------------------------------------186
Residential Wall Section-----------------------------------------198
Pilaster Units----------------------------------------------------------------26
Roof Connection Details for Residential
Placement of Steel-------------------------------------------------------224
Construction----------------------------------------------------201
Planter Boxes--------------------------------------------------------------153
Residential Wall Section---------------------------------------------------198
Plants---------------------------------------------------------------------------339
Resin (Glazed) Coatings-------------------------------------------------33
Plastic-------------------------------------------------------------------------94
Manufacturer’ s Standards------------------------------------------34
Portland Cement-----------------------------------------------------------70
Shapes and Sizes of Glazed CMU-------------------------------34
Pre-Blended Mortar-----------------------------------------------------------73
Specifications---------------------------------------------------------33
Principles----------------------------------------------------------------349, 351
Retaining Walls-----------------------------------------------------------203
Projecting Wall Columns or Pilasters-----------------------------------234
Cantilever Retaining Walls--------------------------------------206
Properties of CMU------------------------------------------------------------18
Counterfort or Buttressed Walls--------------------------------205
Dimension and Modular Sizes-------------------------------------19
Gravity Walls--------------------------------------------------------204
Compression Strength----------------------------------------------20
Segmental Walls---------------------------------------------------209
Metric---------------------------------------------------------------------19
Conventional or Gravity---------------------------------------210
Properties of Stone-----------------------------------------------------------42
Soil-Reinforced or Geosynthetic----------------------------210
Property Specification Requirements---------------------------------73
Supported Walls----------------------------------------------------209
Property Specifications for Mortars------------------------------------68
Retempering-----------------------------------------------------------------74
Proportions of Grout---------------------------------------------------------77
Roof Connection Details for Residential Construction------------201
Proportion Specifications-------------------------------------------------69
RILEM Test No. 11.4, RILEM Tube Test------------------------------335
Providing Flashing and Weep Holes------------------------------------139 Roof Overhang------------------------------------------------------------350
Roof/Parapet Details----------------------------------------------------308
Rubble and Ashlar Stone-----------------------------------------------235
Rubble Stone Masonry Patterns-----------------------------------------237
Q Rumford Fireplace-----------------------------------------------------------154
Running Bond---------------------------------------------------------------83
R-Value-------------------------------------------------------------------------103
Quarrying and Milling Stone---------------------------------------------43
S
R
Sand---------------------------------------------------------------------------99
Rain----------------------------------------------------------------------------93 Sand for Masonry Mortar--------------------------------------------------71
Raised Wood Floor Connection for Residential Construction---199 Sandstone-------------------------------------------------------------43, 279
Raked Joint------------------------------------------------------------------75 Scale--------------------------------------------------------------------------89
References-------------------------------------------------------------------373 Screen Block------------------------------------------------------------------22
Reinforced Brick - An Overview------------------------------------------1 Screen Walls---------------------------------------------------------------153
Reinforced Construction---------------------------------------------------149 Sealant Systems-------------------------------------------------------------272
Reinforced Grouted Brick Masonry------------------------------------160 Sealing--------------------------------------------------------------------------280
Reinforced Hollow Masonry Walls------------------------------------118 Security---------------------------------------------------------------------283
Segmental Retaining Wall Units-----------------------------------------36
384 MASONRY DESIGN MANUAL
U
U-Value----------------------------------------------------------------------103
Unit Conversions---------------------------------------------------------355
386 MASONRY DESIGN MANUAL
MASONRY INDUSTRY ORGANIZATIONS 387
MASONRY INDUSTRY ORGANIZATIONS
The organizations listed below provide information on the material, design and construction
of masonry systems.
Brick SouthEast, Headquarters Expanded Shale, Clay & Slate Inst. Marble Institute of America
8420 University Executive Park Dr. #800 2225 Murray Holladay Rd., Ste. 102 28901 Clemens Road, Suite 100
Charlotte, NC 28262-3381 Salt Lake City, UT 84117-5385 Cleveland, OH 44145-1166
Phone: 704-510-1500 Phone: 801-272-7070 Phone: 440-250-9222
Fax: 704-510-0042 Fax: 801-272-3377 Fax: 440-250-9223
Web site: www.gobrick.com Web site: www.escsi.org Web site: www.marble-institute.com
Brick SouthEast Florida Concrete & Products Assoc. Masonry Contractors Assoc. of America
1810 Overlake Dr., Suite A 3030 Dade Ave. 33 South Roselle Road
Conyers, GA 30013-1787 Orlando, FL 32804-4014 Schaumburg, IL 60193-1638
Phone: 770-760-0728 Phone: 800-342-0080 Phone: 847-301-0001
Fax: 770-760-7810 Fax: 407-895-3733 Fax: 847-301-1110
Web site: www.gobricksoutheast.com Web site: www.fcpa.org Web site: www.masonrycontractors.org
388 MASONRY DESIGN MANUAL
Masonry Advisory Council Masonry Institute of St. Louis Scaffold Industry Association
1480 Renaissance Dr., Suite 302 1429 S. Big Bend Blvd. P.O. Box 20574
Park Ridge, IL 60068-1354 St. Louis, MO 63117-2203 Phoenix, AZ 85036-0574
Phone: 847-297-6704 Phone: 314-645-5888 Phone: 602-257-1144
Fax: 847-297-8373 Fax: 314-645-5898 Fax: 602-257-1166
Web site: www.maconline.org Web site: www.masonrystl.org Web site: www.scaffold.org
Masonry Industry Promotion Group Masonry Institute of Washington Sealant Waterprfng & Restoration Inst.
102 East Boone Ave., Suite 101 10607 NE 38th Place, Building 18, Suite A 14 W. 3rd Street, Suite 200
Spokane, WA 99202-1748 Kirkland, WA 98033 Kansas City, MO 64105
Phone: 509-324-2320 Phone: 425-828-0433 Phone: 816-472-7974
Fax: 509-324-2489 Fax: 425-828-0438 Fax: 816-472-7765
Web site: www.masonrypromotion.com Web site: www.masonryinstitute.com Web site: www.swrionline.org
Masonry Institute of Hawaii National Concrete Masonry Association Texas Masonry Council
1440 Kapiolani Blvd., Suite 800 13750 Sunrise Valley Drive 314 Highland Mall Blvd., Suite 510
Honolulu, HI 96814 Herndon, VA 20171-4662 Austin, TX 78752-3783
Phone: 808-841-6444 Phone: 703-713-1900 Phone: 888-374-9922
Fax: 808-841-6433 Fax: 703-713-1910 Fax: 512-451-9599
Web site: www.masonryhawaii.com Web site: www.ncma.org Web site: www.texasmasonrycouncil.org
Masonry Institute of Michigan Pennsylvania Concrete Masonry Assoc. Weatern States Clay Products Assoc.
12870 Farmington Rd., Suite A P.O. Box 4 22815 Frampton Avenue
Livonia, MI 48150-1603 Lebanon, PA 17042-0004 Torrance, CA 90501-5034
Phone: 734-458-8544 Phone: 717-279-6346 Phone: 310-257-4704
Fax: 734-458-8545 Fax: 717-272-5147 Fax: 310-257-1942
Web site: www.mim-online.org Web site: www.pacma.com Web site: www.wscpa.us
Masonry Publications
is the
T
he Masonry Institute of America, founded in 1957 under the name Masonry
Research, is a promotion, technical and research organization established to
improve and extend the uses of masonry. Also promotes new ideas and
masonry work, building codes, conducts research projects, presents design,
construction and inspection seminars and writes technical and non-technical papers,
all for the purpose of improving the masonry industry.
Phone (310) 257-9000 Toll Free (800) 221-4000 Fax (310) 257-1942
www.masonryinstitute.org
Get the Most Out of Your IBC®
2006 INTERNATIONAL BUILDING CODE®:
CODE AND COMMENTARY
ICC’s Commentary is the tool you need to understand
the application and intent of the requirements in the
2006 International Building Code®. This valuable tool
contains:
• The complete text of the IBC®, including all tables
and figures
• Corresponding commentary after each section
• Suggestions for effective application
• Historical and technical background of the code
• General Comments and Purpose statements for
each chapter
ASTM STANDARDS:
AS REFERENCED IN THE 2006 IBC®
This comprehensive publication contains all ASTM
standards referenced in the 2006 International Building
Code®. That’s 281 standards in one convenient volume!
(1,920 pages)
#9041S06 List $239 ICC Member $191