Академический Документы
Профессиональный Документы
Культура Документы
Process
medium
Fuel
Flow sheet symbol
INTRODUCTION part of this section, specific control systems are described for
start-up heaters, process heaters, and reforming and cracking
The discussion that follows covers a wide range of process furnaces (Figure 8.27a). The last part of this section discusses
furnaces, including heaters, cracking furnaces, and reformers. some of the more advanced control strategies that can be
Each type of furnace is described from a mechanical and applied to furnace controls and optimization.
process standpoint, in enough detail to make the recom- In furnaces and heaters, thermal energy is transferred to
mended control strategies understandable. Examples are pre- a process stream or feed in a controlled manner. The typical
sented so that extrapolation can be made to services not furnace, or heater (the terms will be used interchangeably),
specifically discussed in this section. The recommended con- usually takes the form of a metal housing lined with an
trol strategies are broken down into the following categories: insulating refractory. The charge can enter as a liquid, gas,
1) process controls, 2) fuel firing controls, and 3) safety controls. or two-phase mixture and may or may not be transformed
In the first part of the section, general information is to a different state by the energy supplied. In these types of
provided concerning the furnace and fired heater processes, furnaces, the charge can be carried through the furnace or
their sensor and analyzer requirements, and their basic control heater continuously through metal tubes or can be batch-
requirements, including air preheat controls. In the second heated by leaving it stationary after it enters the furnace.
Light
hydrocarbons
Hydrogen
recycle
Fractionator
Separator
Reformate
FIG. 8.27a
Illustration of a multistage reforming process.
1966
The discussion in this section covers the controls of 1) refin- feed flow loss or because of flame impingement; 2) explosion
ery feed heaters and reboilers, 2) pyrolysis furnaces for eth- in the firebox caused by the loss of flame or by improper
ylene production, and 3) steam reformers for hydrogen or ignition or purge procedures; and 3) implosion of the furnace
synthetic gas production. or refractory damage caused by high draft.
As will be seen later, the heat content of the hot flue gases Furnace design and operation must follow OSHA’s code
leaving the furnace can be used to preheat process feed in a of federal regulations: 40CFR1910.119, “Process Safety
feed preheater or can preheat the boiler feedwater and generate Management.” The standard ANSI/ISA-84.01–1996,
process steam. “Application of Safety Instrumemented Systems (SIS) for
Controls for the more common types of process furnaces the Process Industries,” must also be implemented, usually
will first be described from a process standpoint. Next, the by applying independent PLCs for the control of firing
important process variables will be noted and the methods shutdown sequences.
used to measure and control them will be outlined. The var- The required level of reliability must be determined by the
ious types of firing controls applicable to the particular type analysis of the required Safety Integrity Level (SIL), described
of furnace will then be described. Finally, specific safety in the ISA Standard TR84.02-2002. The SIL level is estab-
considerations and instrumentation will be presented. lished using process hazard analysis (PHA), which determines
As will be seen, the common control strategies include if dual- or triple-redundant PLCs must be used. An interna-
a feedback temperature/flow cascade loop, where the furnace tional companion standard that is also applicable in making
outlet temperature adjusts the fuel flow into the fired furnace. this decision is IEC 61508, “Functional Safety–Safety-Related
The firing controls may use feedforward based on the feed Systems.” In addition, local codes and industry practices, usu-
flow rate in order to speed up the control system response to ally set by the insurers of the plant, should also be consulted
changes in feed flow rate. before controls are designed and installed.
Furnaces with long dead times or with highly interacting
control loops tend to be unstable (Figure 8.27a). To overcome The Combustion Process
these problems, the use of mathematical analysis and process
simulation may become a necessity. The control systems To completely burn the combustible portion of any given fuel,
outlined have been empirically developed, and most of them an ideal quantity of oxygen and, therefore, an ideal quantity
are tried and reliable designs. In the more advanced control of air is required. Under real conditions, the inefficiencies in
strategies, which are described in the last part of this section, combustion require that some additional air be provided to
process dynamics are also taken into full consideration. ensure complete combustion. The quantity over and above the
ideal (stoichiometric) amount of air is called the “excess air.”
On a volumetric basis, air contains 0.21 oxygen and 0.79
GENERAL CONSIDERATIONS nitrogen (on a mass basis 0.232 oxygen and 0.768 nitrogen).
For example, in the combustion of methane (CH4), the ideal
The primary functions of furnace control systems are amount of air required per pound is 4/0.232 = 17.24 lb, and
in volumetric units, the volume of air required per cubic foot
of methane is 2/021 = 9.52 ft .
3
1. To ensure that the charge receives the heat energy at
the proper rate. In feed heater furnaces, the main con- The ratio of air supplied per pound of fuel (W1) to the
trolled variable is the exit temperature of the charge. air theoretically required (W) is
2. To maintain efficient combustion of the fuel. Proper (W1/W) = {3.02[N/(CO + CO2)]}/{34.56[C/3 + H − O/8]}
combustion of the fuel requires the regulation of the
8.27(1)
air-fuel ratio, and the control of the atomizing steam
flow rate when fuel oil is burned. Other important
controlled variables are draft and stack emissions of Combustion Efficiency and Excess Air If we call “a” the
NOx and of other pollutants. ideal (minimum) amount of air required for complete com-
bustion and we call “xa” the actual amount of air admitted,
3. To maintain the safety during all phases of furnace
then “x − 1” is the excess coefficient. On a volumetric basis,
operation so as to prevent explosions or fires.
the excess air requirement (E in %) can be calculated by
Standards Applicable to Furnace Controls E = K[21/(21 − %O2) − 1] ⋅ 100 8.27(2)
The ANSI, API, CFR, IEC, ISA, NFPA, and OSHA standards where K = 0.9 for gas, 0.94 for oil, and 0.97 for coal.
that are used to regulate furnace controls are listed at the end Using the stack gas composition analyzer readings for
of this section, before the Bibliography. carbon monoxide (CO), the air supply to the furnace can be
In furnace operations, safety is a very important consid- adjusted to maintain the combustion efficiency at the opti-
eration. In the case of refinery furnaces, the potential sources mum. Figure 8.6ttt in Section 8.6 shows the relationship
of hazards include 1) fire or explosion caused by tube rupture. between measured ppm concentration of CO in the stack
Such rupture can occur because of tube overheating due to gases and furnace efficiency.
The optimum percentage of excess oxygen is some per- Although, in theory, any of these equations should pro-
centage greater than what is theoretically needed for com- duce the same results, experience has shown that the input-
plete combustion. This margin is usually between 2 and 4% loss method [Equations 8.27(5) and 8.27(8)] produce the
for most furnaces. For continuous emission monitoring sys- most reliable results, because the other methods are more
tem (CEMS) purposes, the pollutant concentrations are cal- sensitive to errors in process measurements.
culated with a reference basis of 3% O2 on a dry basis. Many furnaces burn gas preferentially and oil only as a
The amount of carbon monoxide in the stack gases can standby. Emission compliance for NOx is easier if gas fuel
be measured to determine the optimum set point for excess is being burned. However, some of the control systems
O2 control. Elevated CO levels indicate that some of the fuel described in this section are suited for combination firing
is unburned, which results in the waste of heat and the danger (i.e., firing both gas and oil simultaneously).
of potential explosion at high CO levels. In some installations,
instead of continuously monitoring CO, only a one-time mea- Combustion Air Preheat With regard to furnaces, the over-
surement is made to establish the crossover between the pres-
all efficiency is the ratio of the amount of heat absorbed by
ence of excess oxygen and excess unburned fuel.
the process to the amount of heat liberated by the fuel. One
Combustion efficiency is usually defined in terms of heat of the major heat losses in a furnace is the heat lost up the
input and output. In the case of furnaces, an energy balance
stack in the form of hot flue gases. Therefore, much attention
around the unit must account for the total heat input and the
has been devoted to reducing the flue gas exit temperature
total useful heat output. The difference is the total heat loss,
as much as practical (to approximately 300°F, or 150°C).
as illustrated in Figure 8.6kkk in Section 8.6.
A common method of reducing this waste is to add a
combustion air preheater to the furnace. This device is a heat
H I = HO + H L 8.27(3) exchanger that transfers some of the heat from the hot flue
gases to the cold combustion air, before it enters the burners
where (Figure 8.6ll in Section 8.6). Thus, the heat energy re-enters
HI = heat input rate the furnace and is available for transfer to the process stream.
HO = heat output rate In addition to the combustion air preheater, it is usually
HL = heat loss rate necessary to add a forced draft fan to push the combustion
air through the preheater (exchanger) instead of relying on
Furnace efficiency can be defined by one of the following natural draft. The instrumentation necessary to control this
three equations: equipment is relatively simple. Figure 8.27b shows a typical
combustion air preheat system.
Input-output method: In this control system, the forced draft fan is driven by
a steam turbine drive, equipped with a variable-speed gover-
EFF = 100 •( HO /H I ) 8.27(4) nor. A pressure controller (PIC-1) maintains the discharge
pressure (and consequently the airflow) by manipulating the
Input-loss method: fan speed. A low-pressure alarm (PAL-1) is included to alert
the operator of possible fan malfunction.
EFF = 100 •(1 − H L /H I ) 8.27(5) A trip interlock (FY-1) is provided to trip the forced draft
fan to minimum speed in the event of failure of the induced
Output-loss method: draft fans. This precaution is necessary to prevent positive
pressure in the hot combustion chamber, which could cause
EFF = 100 •[1/(1 + H L /H I )] 8.27(6) the hot gas or flames to blow out through the burner openings
and other leaks in the furnace.
Now, if these equations are expressed in terms of Temperature indicators TI-1, TI-2, TI-3, and TI-4 are pro-
Q = heat absorbed by fluid vided on both streams in and out of the combustion air pre-
W = fuel rate heater to monitor the operation. Pressure measurements PI-1
I = heating value of fuel and PI-2 are also included to allow the checking for excessive
L = total heat loss pressure drop across the unit.
Stack Combustion
air
PI TI preheater TI
1 1 2
Combustion
air to
burners
Forced
draft fan
Drive steam
T PI
2
PAL
FY 1
Fails to 1
min. speed
I PIC
1
FIG. 8.27b
Combustion air preheat controls.
Fuel Gas Controls Figure 8.27c shows a typical fuel gas off valve. This is no longer permissible, and separate, dedi-
header, which can be branching off to several furnaces after cated shut-off valves are required. Figure 8.27c illustrates a
the knockout pot. The relief valve shown should be piped to typical fuel gas regulating station with the safety shut-off
a relief header. For larger furnaces, the pressure control would valves left out and only their location being shown in the
be by a continuously throttling controller, rather than by a broken pipe line.
regulator. Figure 8.27d shows the safety shutdown valving usually
The primary function of the furnace’s safety system is to used in the gas feed to a furnace. The top configuration is
shut down the fuel supply if unsafe conditions evolve. In earlier installed in the main gas line and consists of three on/off,
furnace designs, the fuel control valve also served as the shut- tight shut-off, usually rotary ball valves. The dual shut-off
Set @
PSV 75 PSIG S/D
Permissive
PSL PAL TIC PALH
Set @ Set @
PCV 45 PSIG PT PCV 12 PSIG
PI PI
TCV
PT FE PT
Supply K.O. FC
105 PSIG LSH LC Fuel supply gas
POT
Set @ Shut-off
PCV 2− WC PI valves PI
LAH
Pilot gas
FIG. 8.27c
Fuel gas regulation station showing both the main gas supply line (top) and the pilot gas line (bottom). The locations of the safety shut-off
valves are also shown in the broken pipe, but their actual configuration is separately illustrated in Figure 8.27d.
ZSCO
ZSCO S FO S ZSCO
From PCV
FC Main gas FC
Block and bleed valves
ZSCO S
From PCV
FC
Pilot gas
ZSCO—limit switch closed/open
FIG. 8.27d
Safety shut-off valve configuration for the main gas (top) and the pilot gas (bottom) lines. Dual shut-off valves and a vent valve are used
for the main, single shut-off valve for the pilot line.
valves are fail closed (FC), while the vent valve between • Define the process outputs (conditions) and the actions
them is fail open (FO). Therefore, when the shutdown inter- required in response to them
locks are actuated, the two FC valves close, while the FO • Considerations for manual shutdown
vent valve opens and vents the gas between the two FC • Reset functions
valves, plus any leakage that might occur, to a safe location. • Actions on loss of power; UPS requirements
The ZSCO (closed-open limit switches) provided on all three • Response time requirements for the SIS to bring the
valves confirm to the controlling PLC that the interlock process to a safe state
requirements have been performed. • Operator interface criteria, including alarms and alarm
The pilot gas line is usually provided with only a single responses
shut-off valve with limit switch. • Diagnostics; on-line and off-line testing
• Minimize nuisance trips while maintaining safety
Safety Instrumented Systems SIS (formerly known as
emergency shutdown system, or ESD) systems in general are
discussed in detail in Sections 5.8 and 6.10. When designing a As the final control elements in any SIS system are valves
furnace control system, the designer should evaluate the follow- and dampers, their requirements should be defined by giving
ing functional SIS requirements and clearly define the following: consideration to the following:
• Define the safe state of the furnace (e.g., fuel shut-off, • Opening/closing speed
forced draft dampers open, and so on) • Leakage
• Define the process variables, their normal operating • Fire resistance–body and actuator
range, and their limits • Failure position
• Performance after staying in the same position for long Procedures for on-line testing must also be established.
periods Manual bypass switches should be available for each input
• Use separate shut-off and control valves that can initiate a shutdown so that the device can be tested
• Selection and correct sizing of solenoid valves and pro- periodically. If a bypass is open, that condition should also
tecting them against plugging with bug screens be indicated locally and alarmed in the central control room.
• Installing the solenoids between the valve positioner In connection with testing of ESD systems, the ISA standard
and the valve actuator (S91.1-1995) should be followed, which lists the “Require-
• Providing all shut-off valves with open-closed position ments for Functional Testing.”
detecting limit switches, which are wired to the SIS
Purge Controls After a shutdown, the pilots must not be
The reliability of PLC-based SIS systems is increased by turned on and the furnace must not be reignited until all
implementing them in redundant or triple-redundant (voting combustible gases are purged out. The purge cycle is initiated
system) configurations, as far as their processors and power by the operator, who must not start the cycle timer in the
supplies are concerned. Important measurement and status safety PLC system until after the purge time has elapsed. At
input signals also are configured into 2 out of 3 voting sys-
that point, the PLC unblocks the shut-off valves. A pilot flame
tems, to avoid nuisance shutdowns caused by the failure of
detector is usually also part of the purge logic, and if no flame
a single device or instrument. The shutdown output signals
is detected after a few seconds, the purge will shut down and
should also be redundant, and these redundant signals should
the cycle has to be restarted.
originate on different I/O cards in the DCS or PLC systems.
Large, PLC-controlled furnaces that are provided with
The SIS safety and shutdown system is usually located
emission abatement and monitoring systems are also pro-
on a PLC that is separate from the control equipment that
vided with their own local control panel (Figure 8.27e),
directs the normal operation of the furnace. Such safety sys-
which is integrated into the total DCS- or PLC-based control
tems usually include a flame scanner. It is important to keep
system. Flow and draft indicators, alarms and shutdown
the air flowing through the firebox during a shutdown. In
bypass/test switches, and purge cycle controls are also often
case of tube rupture, this may generate a lot of smoke, but it
will protect the system from explosions that are caused by provided on these local panels. The purge-related pilot lights
fuel-rich mixtures. Shutdowns are usually triggered by the are usually designated as “purge on,” “purge failed,” or purge
following conditions: complete.” After the purge is complete, the pilot burners can
be ignited, and later the main gas control valve can also be
• Low gas pressure: flame may go out and the resump- opened.
tion of gas flow can cause explosion
• High gas pressure: may blow flame away from burner Pollution Abatement
• Loss of flame, which can be detected by flame scanners
• High draft: may buckle furnace Furnace emissions must meet federal (EPA) and local air
• Low to zero draft: may push flames out quality requirements. The applicable standards and guidelines
• Low feed flow: will cause tube overheating, coking, include:
and eventual tube rupture
• Safety system failure: if PLC watchdog timer times • ANSI/API 536, “NOx Control for Fired Equipment in
out, this triggers hardwired fuel valve closure. Refineries”
• 40CFR Part 60, “New Source Performance Standard”
The emergency shutdown system software package (section for oil refineries)
within the PLC logic (also called the “problem solver”) will • 40CFR Part 61, “National Emissions Standards for
cause the following actions as applicable: Hazardous Pollutants”
• Fuel gas shutdown, with manual reset Larger furnaces must be fitted with CEMS, which will
• Pilot gas shutdown (not all furnaces) be discussed in the next paragraph after NOx controllers.
• Opening of stack and fan dampers Gas- and oil-fired furnaces, operating at over 2800°F in
• Ammonia injection shutdown–NH3 valve, blowers (if their hot zones, typically produce about 100 ppm NOx in their
the process includes them) stack gas. EPA standards require that this concentration be
reduced to 5 ppm or even 2.5 ppm. This can be achieved by
On furnaces with two induced air fans, dampers may be several means:
programmed to close if the fan is not running. The feed is
usually shut down later manually when tubes have cooled off. • Use of cool-burning burners, with optimal air/fuel mix-
Guidelines for training can be found in OSHA Regulation ing nozzle design
1910.119, which defines the requirements for safety systems- • Use of flue gas recirculation, where part of the flue
related training. gas is returned into the firebox to cool the flame
LP–7
FIG. 8.27e
Local burner panel with status-indicating running lights and manual pushbuttons for purging and testing a typical furnace.
• Installation of catalytic converters between furnace and SCR Controls The controls of the SCR process are shown
stack in Figure 8.27f. Here, from a storage tank, liquid ammonia
• A combination of all above is metered by a positive displacement pump or by Coriolis
flowmeter to the ammonia vaporizer, which is heated by the
Installing new burners and providing recirculation, by dilution air. From the vaporizer, an array of small pipes takes
means of fans, can reduce NOx to around 25 ppm. This still the ammonia vapors to the distribution grid for injection at
leaves the need for costly catalytic converters, which use different elevations into the firebox.
vaporized ammonia to convert NOx (mostly N2O3), according Each pipe section in the distribution grid is provided with
to Equation 8.27(10) as: a balancing throttling valve, which serves to evenly distribute
the vapors. The control valves in the major branches are
N2O3 + 2NH3 = 2N2 + 3H2O 8.27(10)
controlled by the ammonia flow controller (FIC-1), which
To accomplish this conversion, because of the resistance also controls the positive displacement ammonia pump. This
of the selective catalytic reduction (SCR) catalyst bed, forced controller measures the ammonia flow and in addition
draft fans with control dampers are required. They must be receives a feedback signal from a chemiluminescent NOx
installed on elevated platforms, making the installation analyzer transmitter and a feedforward signal, FT-1, the fuel
expensive. gas flow transmitter, which detects the firing rate (gas flow)
In the SCR process, by using a suitable catalyst, the NOx of the furnace or boiler.
reaction can be carried out at 300–400°C, a temperature FIC-1 also receives a trimming signal from the oxygen
normally available in a flue gas system. Figure 8.27f shows analyzer transmitter. It was found that increasing the amount
a schematic diagram of the SCR process. In this process at of excess oxygen initially tends to increase the formation of
least 1% O2 must be present in the flue gas, which is normally NOx, but further increases tend to decrease it due to flame
the case in boiler and furnace applications. cooling. The injection of ammonia is stopped by TSHL-1
Using a movable injection lance is another effective (high-low temperature switch) when the converter tempera-
means of reducing NOx, CO, and volatile organic carbon ture drops under 600°F, to prevent catalyst damage.
(VOC), while improving thermal efficiency by optimizing the
combustion process in boilers. The injection lance can be The NOx Controller Figure 8.27g describes the ammonia
used with or without low NOx burners. controller (FIC-1 in Figure 8.27f) that is used as a cascade
These lances reduce NOx emissions by 60–90% by inject- slave of AIC-1 to control the NOx in a crude oil distillation
ing air, ammonia, or urea through retractable lances in the heater furnace, which has a maximum gas firing rate of 8.5
upper furnace. This creates turbulence and better mixing in MMSCFD. The figure also shows the various feedforward
the gas flow in addition to lowering the stoichiometric ratio and trimming adjustments of the total control algorithm.
of O2. The lances are automatically retracted from the boiler Feedforward is applied from the fuel gas flow transmitter
on a regular basis and cleaned to remove the accumulated (FT-1), which is the main determining factor in arriving at the
layers of soot and other depositions. Their costs are about set point of FIC-1. Oxygen content, detected by the transmitter
75% less than those of SCRs. AIT-2, serves to trim the fuel gas flow signal. Therefore,
Feedback from
chemiluminescent
NOx controller AIC–I Two I.D.
Feed forward from fans
fuel gas flow From O2 transmitter M
PCV SV SCR
18% FT
Liquid S
NH3
Variable FC
Coriolis Furnace
stroke, positive meter
displacement
pump
Vaporizer
Heater
Flue gas or
dilution air
blower
FIG. 8.27f
Control system for an SCR-type NOx reduction system for the injection of ammonia.
changes in the output signals of FT-1 and AIT-2 will instan- The cascade master of the feedback portion of this control
taneously change the set point of the ammonia flow controller, system is the NOx controller, AIC-1. This loop is slow; its
FIC-1. The basis for this relationship is that the NOx produc- dead time can be 10 min, because the time lags from the NH3
tion is proportional to both fuel flow and to excess oxygen, injection points to the stack and then through the sample line
because the free nitrogen radicals—at over 2800°F—will seek to the NOx analyzer all add up before a measurement is
out the extra oxygen and will combine with it. obtained.
O2 −0.5
0–10% − Manual
AIT ⋅
2
ratio
Bias ⋅ Σ ⋅ FIC
0–8.5 SP 1
MMSCFD
FT ⋅
1
Fuel gas
flow Bias
0–120 lbm/hr
FT
1
MMSCFD - million standard
cubic foot per day NH3 to From
SCR system NH3 tank
FIG. 8.27g
The configuration of the control algorithm of the ammonia controller (FIC-1 in Figure 8.27f) used to control the NOx emissions of a furnace.
For the control algorithm shown in Figure 8.27g all mea- Described here is a typical CEMS system used on a
surement and control signals are scaled, so that the measurement refinery furnace with selective catalytic reduction-based NOx
output ranges of each transmitter or controller are converted to abatement controls.
a 0–1 scale. For example, the output of the NOx analyzer The CEMS can utilize a zirconium oxide-based stack
controller (AIC-1) is also 0–1, and when it is 50% (a value oxygen analyzer for firing controls and a chemiluminescent
of + 0.5), by subtracting −0.5, its influence on the set point NOx analyzer.
of FIC-1 is eliminated. On the other hand, when the feedfor- The CEMS provides NOx readings (corrected to 3% O2)
ward portion of this algorithm cannot correct for the changes and an O2 signal for the ammonia injection controller
in the SCR process, the feedback controller (AIC-1) will start (Figure 8.27g). The data collected by the CEMS is also used
moving its output away from 0.5 and will start correcting the by the local air quality agency and by the plant monitoring
FIC-1 set point. system (PMS), using Equation 8.27(2). The O2-corrected NOx
Such an algorithm can be implemented either by a single- emission (E) is calculated on the basis of the actual measured
loop programmable controller or by the DCS system. concentration O2 concentration (C).
For a particular set of conditions, the following calcula- If sampling-based analyzers are used (and not directly
tions can serve as an example of the operation of this control inserted probe-type analyzers), the components of CEMS
scheme: systems can include:
At an average NOx concentration of 110 ppm, the total
unabated NOx flow rate in the stack has been calculated to be • Stack sample probe, located usually 2/3 up the stack
26.7 lbm/hr. The conversion of 1 mole of NOx (Mw = 47) (Figure 8.27h)
requires about 1 mole of NH3 (Mw = 17). Thus, the rate at which • Heated sample line with thermostat
pure ammonia should be added is 17/46 ⋅ 26.7 = 9.87 lbm/hr • Sample conditioning cabinet with sample pump
NH3. Ammonia is received in 19% solution; consequently, • O2 and NOx analyzers
this solution should be injected at a rate of 9.87/0.19 = • Microprocessor with auto-calibration controller and
52 lbm/hr. solenoid valves
It was found that excess oxygen also contributes to NOx • Rack of calibration gas bottles
formation and that up to 4% more NOx is formed for each
additional percentage of excess O2 over the concentration of Sampling The stack sample probe is a stainless steel tube
2%. Because of draft limitations, the furnace in this example that extends into the stack and has a HastelloyC, 0.5-µ-size
operates at a 5% excess oxygen level (3% over the 2% mini- filter, a test and sample gas connection, and an electric heater
mum). Therefore, 3 ⋅ 4% = 12% added NH3 is required, which with RTD. The sample line is heated to 300°F to keep mois-
comes to 1.12(52) = 58.2 lbm/hr. ture from condensing. An alternative method is to use a
To measure the ammonia flow rate, a Coriolis meter with dilution extractive sample probe (Figure 8.27i). This method
a range of 0–120 lbm/hr can be used, so that the 58.2 lbm/hr of sampling has the advantage of not requiring a heated
rate would approximately correspond to 50% of range. sample line or a chiller/dryer.
The “manual ratio” correction factor applied to the set In the standard sampling system, a sample conditioning
point of FIC-1 is available for the operator to correct for such cabinet is provided, where the sample is quickly chilled to
differences as the calculated 58.2 lbm/hr and the 50% range knock out water without washing out the gases of interest.
of the flow meter. These components are usually followed by a gas dryer, then
a bypass rotameter, which is used to control the sample gas
Continuous Emission Monitoring Systems In order to com- flow rate to the NOx analyzer.
ply with the requirements of the federal agencies (see “Stan- A solenoid manifold is also provided, so that auto-calibration
dards and Guidelines” at the end of this section) and with can be performed every 24 hours, by injecting zero and span
local air quality district requirements, microprocessor-based, gases. Sample system alarms are also provided to signal such
self-calibrating CEMS analyzers are used. The CEMS micro- conditions as high sample gas moisture content, low sample
processor calculates the pollutant concentrations reduced to line temperature, and high condensate level.
3% O2 (as a measure of gas dilution) and provides rolling
averages, peaks, their duration, and other records as required NOx Analyzer In the chemiluminescent NOx analyzer, the
by the local agency. The CEMS is usually wired directly to reaction that takes place is described by Equation 8.27(11):
the agency’s computer. Emissions are referenced to the firing
NO + O3 . NO2 + light @ 0.6–3µ 8.27(11)
rate (gas flow) to provide the total mass of pollutants emitted.
For gas-fired heaters, the pollutant that is continuously The intensity of light emission is proportional to the NO
monitored is only NOx. In case of fuel oil-fired boilers and concentration in the sample. The chemiluminescence ana-
furnaces, SO2 is also monitored. Other pollutants, such as lyzer is usually provided with a catalytic converter to reduce
CO, CO2, and particles (opacity) are only checked periodi- the NOx to the NO form and then uses its ozone generator
cally by portable instruments. EPA 40CFR60 provides spe- to measure NOx in the range of 0–50 ppm NOx. The main
cific criteria for CEMS. components of this analyzer are shown in Figure 8.27j.
(Outside)
2 in min
8 in max unless gate valve
(Inside)
installed
3 in I.D. (minimum) industrial flange
capped when not in use
Sampling ports Install gate valve if stack
A. 2 ports, 90° apart with diameter contains dangerous gases
less than 10 ft + port length or gases over 200°F under
4 ports, 90° apart with diameter positive pressure
over 10 ft + port length Strength requirements
Guardrail
50 lb side load
At least two stack diameters 50 lb radial tension load
above stack exit 200 lb vertical shear load
750 ft-lb moment
At least one stack diameter
48
At least eight stack diameters in plus 3 ft from stack circumference
below last obstruction Clearance
Work area clearance 36 in
zone
Work platform
C. No obstructions
within 3 ft horizontal
radius on platform
beneath ports
FIG. 8.27h
The location of a stack sampling probe.
Analyzers for Furnace Control tifies it. The cost of the analyzer and its upkeep must be bal-
anced against the energy savings and increased safety. If the
In addition to the analyzers discussed above, in connection firing load or the type of fuel to the furnace often changes, the
with pollution abatement-related furnace analyzers, are the oxygen analyzer is a necessity from a safety standpoint alone.
analyzers that are used in controlling the furnace’s operation. The O2 sensor can be a solid-state heated zirconium oxide
These include oxygen analyzers, combustibles detectors, and probe that can be placed directly in the stack (Figure 8.27k).
fuel heating value (calorific) analyzers. An instrument air purge connection is recommended for peri-
odic blowing. At temperatures of over 600°F, these probes
Oxygen and Excess Air Analyzers An oxygen analyzer is produce an open circuit voltage that is related to the partial
commonly used on furnaces to measure the oxygen content pressure of oxygen in accordance with the Nernst Equation
of the flue gas. From this information, the amount of excess shown in Equation 8.27(12):
air being delivered to the furnace can be computed. Keeping
the excess air at a minimum results in conservation of heat, RT O 2partial pressure in reference gas
E= ln 8.27(12)
because the sensible heat content of the excess air is dis- nF O 2partial pressure in sample gas
charged into the atmosphere and is an outright heat loss.
The efficiency of combustion can be maximized by throt- where
tling the air of the furnace to maintain the oxygen content of E = the open-circuit voltage developed
flue gas at a desirable value. The analyzer is also tied to a low- R = the universal gas constant
oxygen alarm, which warns the operator if hazardous furnace T = the temperature
atmospheres are developing. n = the number of electrons transferred per molecule of
The decision whether to install an oxygen analyzer is based oxygen
on economic considerations, and energy efficiency usually jus- F = Faraday’s constant
CO2 analyzer
Probe Cal/backflush
Cal backflush in
Cal of
probe valve Backflush NO2 analyzer
Cal gas in
air in
Zero air
regulator
FIG. 8.27i
The components of a dilution-extractive sampling system.
Paramagnetic oxygen analyzers are less frequently used. The concentration of one combustible gas component,
They can be installed on the sides of fireboxes, to check for carbon monoxide, is sometimes used as a constraint variable
potentially explosive fuel-rich pockets. The sample gas is drawn in a “low select” configuration, in connection with the
to these analyzers by an air aspirator provided with a water seal. excess oxygen controller as described in connection with
Figure 8.6bbbb in Section 8.6. The CO analyzer can be of
Combustible Analyzers Combustible analyzers measure the the infrared type and can be installed to look “across the
amount of unburned fuel in the furnace flue gas (CH4, CO); stack.”
they are mostly used as portable instruments during emissions
certification. For an in-depth discussion of combustible ana-
lyzers refer to Section 8.16 in Chapter 8 of the first volume of Combustion gases
this handbook. Probe
Calibration
gas Oxygen Duct
Flowmeter
Solenoid Ozonator
valve
High-voltage
Catalytic power supply
NO2 NO
convertera Reactor Photo tube
Instrument Amplifier
Optical air supply output 4–20 MADC
Sample
air filter Reference
Optical air set
Vacuum window
Time pump Temperature
Read-out
programmer controller/amplifier
a
Converter can be omitted if only NO is measured FIG. 8.27k
FIG. 8.27j High-temperature, electrochemical, zirconium oxide-based oxygen
Chemiluminescence nitric oxide analyzer. analyzer probe.
⋅ Multiplier
Auto-manual FY FY
AIY Heat flow rate
station 1 1D 1B
(BTU/hr)
Square root
FY extractor FT
1C 1B
Varying
⋅ Multiplier BTU To
FY gas burners
1B supply
AIE
Divider FFIC 1
1
AT FY FY Set point Calorimeter
High speed 1 1A 1A
calorimeter I/P AT
FY 1
Flow Temp. Press. 1C
AIE FT TT PT FT
1 1 1 1 BTU 1A
make-up AIC
From fuel or 1
gas supply diluent
gas Symbol Description
supply
FIG. 8.27l FT − 1A, FT − 1B Flow transmitter
Heat flow rate detection loop. FY − 1A, FY − 1B Square root extractor
FFIC − 1 Flow ratio controller
FY − 1C I/P transducer
NH3 Analyzers Wet chemical NH3 analyzers are used to AIE − 1, AT − 1 Calorimeter
detect the ammonia slip when selective catalytic reduction is AIC − 1 Heating value controller
applied for emission control. Excess ammonia in the flue gas FIG. 8.27m
is referred to as “ammonia slip” and must be avoided. NH3 is Control system to automatically maintain the heating value of mixed
difficult to sample because it is very easily dissolved in water. gas streams.
Experimental laser detectors, beaming across the stack, have
been used as ammonia analyzers with some success. products. The BTU measurement so obtained can be used in
a feedforward manner, to compensate for the varying BTU
Fuel Gas Heating Value When the refinery waste gas and content of the fuel values.
utility gas are combined, the mixture resulting from their vary- Figure 8.27n illustrates a fuel gas blending controller.
ing heating values will also have a varying heating value. BTU The formula it uses to arrive at the total heating value of the
analyzers are used to measure the heat flow rate (Figure 8.27l) blended stream is
provided by the fuel being fed to the furnace (see Section 2.4 HT = (F1H1 + F2H2)/ FT 8.27(13)
in Chapter 2 in Volume 1 of this handbook).
where:
In order to stabilize furnace firing, the heating value of
the fuel should be kept constant. This can be achieved by HT and FT are the total BTU content and total flow of
the mixed fuel
blending refinery gas with natural gas, propane, or some other
H1 and F1 are the flow and the BTU content of fuel 1
supplemental fuel having a high and constant heating value.
If the heating value of the total stream drops, more of the H2 and F2 are the flow and the BTU content of fuel 2
supplemental fuel is blended in.
Furnace Instrumentation
This BTU instrument (calorimeter) can also serve as a
safety device by actuating an alarm when the heating value of While the control hardware and software are constantly
the fuel drops to the point where it cannot support combustion. changing, today’s furnaces in larger plants such as refineries
Both the blending of the fuels and the emergency shut- are usually controlled by DCS systems, with independent
down controls can be automated (Figure 8.27m). In this con- PLCs used for safety shutdown. In case of some furnaces,
trol configuration, if the BTU analyzer detects a drop in the PLCs with human-machine interfaces (HMIs) are also used
heating value, the fuel supply is shut down. in place of DCS systems, as are graphic software-supported
If the heating value of the two gases that are blended are PC displays located in the control room and in management
known, but their ratio varies, the resulting variation in the offices. Smaller furnaces can be controlled by single-loop
total heating value can be compensated for by a gas blending analog or digital PID controllers.
system on the main fuel gas header. Both the DCS systems or the microprocessor-based unit
Relatively inexpensive BTU analyzers are available for controllers provide adaptive gain, auto-tuning, feedforward, and
“sweet” gases. They operate by burning a sample stream of the capability of decoupling the interacting loops. Historical
fuel and measure the oxygen concentration of the combustion trends and temperature profiles can be graphically displayed,
PLC control
TT FT PT
Primary
gas
train BTU
FT QT
Optional double
block & vent assembly Blended gas
TT FT PT stream
Diluent/
Enrichment
Gas train
FIG. 8.27n
Pressure- and temperature-compensated fuel gas blending control system used when the BTUs of the blended streams are known, but their
ratio varies. This typical controller also handles the safety shutdown interlocks.
and alarm conditions and status summaries can be shown on is important to make sure that the positioner is faster than
graphic displays with event printouts. Nuisance alarms can be the controller that sets it. Newer E/P positioners also provide
eliminated by the use of smart alarm logic, and diagnostic information on valve diagnostics such as packing problems.
messages can be generated for operating and maintenance Firing shutdown valves should always be separate from
information. All of these capabilities contribute to reducing the fuel control valves and be of the tight shut-off type with fire-
frequency of furnace shutdowns and increase its safety. resistant design. Usually, ball valves with steel seat rings are
used for shut-off services. One should also consider the use
Transmitters and Valves Mostly 4–20 mA analog transmit- of fireproof insulation of the valve actuators and of the air
ters are used with the digital HART protocol superimposed tanks on air-fail switch valves.
over the analog signals to the DCS. In order to save on wiring
costs, newer installations use Fieldbus networks, but their Flame Scanners Only some refinery furnaces are provided
reliability for critical systems is still under evaluation. with flame scanners. Ultraviolet, visible, and infrared designs
Most field devices and their wiring need to be intrinsi- can be considered. Ultraviolet flame detectors measure the
cally safe or explosionproof, approved for Class 1 Div. 2 Gr. flicker of a flame in the UV band and are not blinded by the
B, C, D. Intrinsically safe units are provided with current- hot refractory (Figure 8.27o). Infrared sensors are able to
limiting barriers. Most transmitters and I/P or E/P converters
are provided with NEMA4X/7 explosionproof enclosures. Ultra Visible Infrared
For analyzers, purged enclosures are also used with proper violet
% of maximum flame sensor response
Radiation
safeguards (see ISA Standard S12.4). intensity of
Field instrumentation should not be located close to oil flame Radiation
Ultra-violet
Lead-sulfide Infrared intensity of
potential fire sources, such as on furnace walls. Their wiring detector
photocell detector refractory
should be routed from furnaces to junction boxes or from response
response response
Radiation Intensity
at 3000°F
DCS I/O cabinets that are at a safe distance from potential
100
fire sources, so that in case of a furnace fire, only the wiring 10 Radiation
to the junction boxes will need to be replaced. 1
intensity of
refractory at
1000°F
Final control elements, such as control valves or dampers, 0.1 Radiation intensity
should be selected so their gain variation will compensate 0.01 of gas flame
for the variations in the process gain, with the goal being a 0.001
constant loop gain over the range of the valve openings.
Equal-percentage (gain increasing with load) valve charac- 2000 4000 8000 14,000
teristics should be used when the process gain drops as the Wave length, Angstroms (10−10 meter)
load rises, in order to keep the loop gain at around 0.5. FIG. 8.27o
Control valves should be provided with positioners, in Applicable ranges of selected flame sensors and the range of hot
order to overcome packing friction-caused hysteresis, but it refractors effect.
FURNACE TYPES HV
Cold synthesis 1
gas Hot gas to converter
Start-Up Heaters
Furnace TT
FIT Flame
Start-up heaters are discussed here first because of their sim- 1 1
scanner
plicity. These units are required at the start-up of a process BS TSH TAH
1 1 1
unit, and their use lasts from a few hours to a few weeks. FI TV
1 TIC
1 1
They are usually vertical, cylindrical units with vertical pro-
cess tubes along the inner walls and with a single burner FSL
1 FC
centered in the floor. Draft is normally by natural convection
induced by a stack mounted on the top of the heater. FC
Processes that require start-up heaters include catalytic S
cracking units to heat up fluidized catalyst beds, ammonia FV FY
units to heat up the ammonia converter catalysts, and fixed- 1 1
I
bed gas-drying units to regenerate the dryer beds.
The start-up heater usually heats an intermediate stream, HS PSL (Burner pilots
1 1 Fuel gas not shown)
such as air or natural gas, which in turn heats another fluid
or solid, such as a reactor catalyst. For example, the start-up
FIG. 8.27p
heater for an ammonia unit is used to heat “synthesis gas”
The controls of a start-up heater.
(primarily a mixture of hydrogen and nitrogen), which in turn
is used to heat the catalyst bed in the ammonia converter to
Fired Reboilers
a temperature of 700°F (371°C).
The synthesis gas is recirculated through the catalyst bed, The fired reboiler provides heat to a distillation tower by heating
gradually bringing it up to operating temperature. After nor- the tower bottoms and vaporizing a portion of it. Normally, a
mal operation has begun, the exothermic nature of the ammo- tower reboiler uses steam or another hot fluid as a source of
nia synthesis reaction keeps the bed at a certain temperature, heat, but where heat duties are great or where tower bottom
and the start-up heater can be shut down. temperatures must be high, a fired reboiler can be used. Depend-
ing upon its size, the reboiler may be of the vertical cylindrical
Process and Firing Controls The important variables are type or the larger, conventional horizontal-type furnace.
the flow and temperature of the “synthesis gas.” Figure 8.27p The fired reboiler heats and vaporizes the tower bottoms
shows the necessary controls for the operation of this unit. as this liquid circulates by natural convection through the
The flow of the cold synthesis gas is measured by the flow heater tubes. The coils are generously sized to ensure adequate
transmitter (FIT-1) and is indicated on a flow indicator (FI- circulation of the bottoms liquid. Temperature of the reboiler
1). The desired gas flow is manually adjusted by operating return fluid is generally used as the means of controlling the
the hand valve (HV-1), while observing the local flow indi- heat input to the tower, provided that the bottoms product
cator (FIT-1). The effluent synthesis gas temperature is main- material has a wide boiling-point range. Overheating the pro-
tained by the temperature controller (TIC-1), which uses a cess fluid is a contingency that must be prevented, because
thermocouple to measure the gas temperature and controls the most tower bottoms will coke or polymerize if they are sub-
flow of fuel gas by modulating the control valve TV-1. jected to excessive temperatures for some length of time.
The fuel gas firing rate is set by process temperature
controller (TIC-1). The heater draft (i.e., negative pressure Process and Firing Controls A common control scheme is
in the firebox) is produced by the stack; the operator sets it shown in Figure 8.27q, which depicts the tower bottom along
by observing the draft gauge (PI-1) and by manually adjust- with the fired reboiler. It is usually not practical to measure
ing the position of the stack damper. Once initially set, the the flow of tower bottoms to the reboiler, first, because the
damper is rarely adjusted again, unless the furnace conditions liquid is near equilibrium (near the flash point), and second,
or loads change drastically. because it is usually of a fouling nature, tending to plug most
flow elements.
Safety Controls Start-up heaters are usually controlled by Proper circulation of the fluid is provided in the careful
simple PLCs or relay systems. Most start-up heaters have hydraulic design of the interconnecting piping. An important
flame scanners. Their SIS system requirements have already variable is the reboiler return temperature, which is controlled
been described in a previous paragraph. by TRC-1 throttling the fuel gas control valve. The high-
temperature alarm (TAH-1) is provided to warn the operator The feed heater of a refinery crude unit is representative of this
if the process fluid reaches an excessive temperature. class of furnaces (Figure 8.27r). Crude oil, prior to distillation
The reboiler return temperature is actually an inferred indi- into the various petroleum fractions (gasoline, naphtha, gas oil,
cation of the percentage of vaporization. The sensitivity of TIC- heavy fuel oil, and residual) in the “crude tower,” must be
1 depends upon the boiling-point range of tower bottoms. A heated to around 750°F and partially vaporized. The heating
wide boiling-point range provides adequate sensitivity. How- and vaporization are done in the crude heater furnace, which
ever, a narrow range does not control well. Often, for these consists of a firebox with preheat coils and vaporizing coils.
cases, a differential pressure controller is used in place of the Larger-duty heaters usually have multiple zones encom-
reboiler temperature to infer percentage of vaporization. A dif- passing multiple passes, and they heat the oil inside the coils
ferential pressure controller (DPIC, not shown) offers increased in the convection section of the furnace. This is the portion
sensitivity to firing for narrow-range boiling-point fluids. that does not see the flame but is exposed to the hot flue gases
The firing controls of fired reboilers are relatively simple on their way to the stack. The vaporizing takes place at the
and are similar to those of the start-up heater. The process end of each pass in the radiant section of the furnace (where
Distillation Distillation
tower Exhaust tower
fan Furnace
FIG. 8.27r
The feed heater of a refinery crude unit.
the coils are exposed to the flame and the luminous walls of one of the passes. If such a trend develops, the flow through
the firebox). The partially vaporized effluent then enters the that pass is altered slightly to drive its temperature back
crude tower, where it is flashed and distilled into the desired toward the desired norm.
“cuts.” The outlet temperature controller (TIC-4) of the com-
Other process heaters that fall into this category are refin- bined crude stream sets the firing rate through a cascade fuel
ery vacuum tower preheaters, reformer heaters, hydrocrack- flow or pressure controller (not shown).
ing heaters, FCCU feed heaters, and dewaxing unit furnaces. However, the desired heat input into the feed stream can
The control system presented is also applicable to these types be more difficult to control, because the effluent of the fur-
of process heaters. nace is partially vaporized and the feedstock varies in com-
position depending upon its source. If the feed were only
Process Controls The prime variables of this process that heated and no vaporization took place, the control would
need to be controlled are require only that the effluent temperature be maintained. If
complete vaporization and superheating occurred, this too
1. The flow of the feed flow to the unit
could be handled by straight temperature control.
2. The proper splitting of the total flow into the parallel
In the case of partial vaporization, combined with a variable-
paths through the furnace, in order to prevent over-
feed composition, effluent temperature control alone is not
heating of any one of the streams and to protect against
sufficient for reliable control. The composition and, hence,
its resultant coking
the boiling-point curve of the feed varies with time, and the
3. The correct amount of heat supplied to the process
required control temperature itself also varies. Therefore, addi-
stream
tional information is required, and it is obtained from the dis-
Figure 8.27s shows the typical process controls for this tillation process, which is downstream of the furnace. By
type of furnace. The crude feed rate to the unit is set by the observing the product distribution from the fractionation, a need
flow controller (FIC-4). This flow is split into the parallel for changing the heat input can be determined.
paths of the furnace by adjustment of the manually set control Current practice is to achieve approximate control with a
valve openings by the hand indicating control (HIC) stations temperature controller (TIC-4) whose set point is periodically
(HIC-1 through HIC-3). changed by the operator to account for feed variations. The
The temperature indicators TI-1 through TI-3 (there may operator depends both on experience and on the results in the
be several TIs on each pass) are periodically observed to fractionator (possibly a crude tower optimization strategy) to
determine if unbalanced temperatures are developing in any determine the proper temperature setting.
TI
6
TAH
HIC TI
1 1
I FAL FI FT
HV
1 1 1
1
FIC
4 FO TAH
HIC TI
2 2
FT I FAL FI FT
HV Feed
2 2 2 to crude
2
Crude distillation
feed tower
FO FO TAH TT TI
HIC 4 5
FV TI
1 3 3
I FAL FI FT HV
3 3 3 3 TAH
TIC To firing
4 controls
FO TI
Note 1. Each coil has
Note 1. several tube
skin thermocouples,
hot spots are alarmed.
FIG. 8.27s
The controls of a crude heater-vaporizer, in which the flow distribution between the passes is manually adjusted.
Feed
Feed to crude
distillation tower
TT
1
PSC TIC
1
PIC
S 3 HS Manual
1 1 S/D
PT
1
PSL Start
3 permit
Fuel gas
FC FC (preferential)
SP PAL
Atomizing PIC
steam 2 S 1
PDT PT
2
Fuel oil
PDIC
1 FC FC (make-up fuel)
PSL
2
FIG.8.27t
The firing controls of a crude oil heater-vaporizer, in which fuel gas is the preferred fuel and oil is used as the make-up fuel.
Firing Controls the set point of PIC-1. Either change will increase the fuel
oil demand and, thus, bring the system back into a stable
Figure 8.27t shows the firing controls for the furnace using operating zone.
fuel gas (or fuel oil as standby). The fuel gas headers serve Newer installations use flow instead of pressure control-
many burners spaced equally along the floor of the firebox. lers (as shown in Figure 8.27u) on the fuel oil make-up to
The burners, being essentially fixed-diameter orifices, will better control the heat balances. These controls are designed
pass more or less fuel depending on the header pressure. In to meet a percentage of the total firing duty assigned to the
the past, a pressure controller was often used in place of flow hearth or floor burners to prevent furnace damage that can
control. Because flow through an orifice is a function of the result from uneven firing. The percentage of the total firing
square root of the pressure, nonlinearity is eliminated by the duty that is assigned to the floor burners is a percentage that
use of pressure control. is recommended by the furnace manufacturer to protect met-
Although fuel oil is the make-up fuel (trim medium), it allurgy, reduce maintenance, and extend furnace life.
must be available in sufficient quantity to take the whole load In Figure 8.27u, the effluent temperature controller (TIC-
in the event of a fuel gas interruption. The temperature con- 4 in Figure 8.27s) is the cascade master, and it adjusts the set
troller (TIC-1) varies the set point of the fuel oil header pres- point of FIC-5 to maintain the furnace effluent temperature.
sure controller (PIC-2) to satisfy process load requirements. Cascading the TIC-4 to FIC-5 is beneficial in that the flow
All burners have turndown ratio limitations. This is the controller compensates for the disturbances (e.g., changes in
ratio of minimum to maximum fuel burning capacity, which fuel supply pressure) without allowing them to upset the efflu-
ratio is usually 3:1. Low pressure in the fuel oil header is ent temperature, whereas the TIC-4 provides the correction
indicative of the potential approach of a minimum firing required to correct the process for slower ambient changes.
condition. Consequently, the low-pressure switch (PSL-2 on
PIC-2) is used to warn the unit operator when this situation
arises. The operator then has the option of going out to the Draft Control Furnace draft is normally maintained by free
furnace and manually turning off some of the individual fuel convection in the furnace (i.e., the stack produces a negative
oil burners or to reduce the fuel gas firing rate by lowering pressure in the firebox), and air is drawn in through louvers
described in the equations below: be taken to maintain the excess steam at all times, because
even a few seconds of interruption in the steam flow, while
CH 4 + H 2O = 3H 2 + CO 8.27(14) feed gas continues, can completely ruin the catalyst charge.
(methane) (steam) (hydrogen) (carbon monoxide)
Process Controls The major controlled process variables
General : Cn H ( 2 n + 2) + nH 2O = (2n + 1)H 2 + nCO
are the feed gas flow, the reforming steam flow, and the
8.27(15) temperature and composition of the effluent. As illustrated in
The carbon monoxide is removed by further reaction later Figure 8.27v, the feed gas flow is maintained by means of a
in the process. The reaction is endothermic (absorbs heat) and pressure-compensated flow controller (FIC-1). Pressure com-
takes place at pressures of approximately 450 PSIG (3.10 MPa) pensation of flow corrects the measurement for fluctuations
and at temperatures of around 1500°F (815°C). in feed gas pressure. The steam rate is maintained by means
The reaction takes place as the feed gas and steam pass of FFC-2, and the ratio of steam to feed gas flow is contin-
through tubes filled with a nickel catalyst, which is heated in ually monitored.
the radiant section of the reformer furnace. Steam must be The ratio controller FFC-2 measures the ratio by dividing
provided in excess of the reaction requirements to prevent the the gas flow signal from FT-1 with the steam flow signal from
side reaction of coke formation on the catalyst. The coking FT-2. If this ratio falls below the limit of approximately 3:1,
of the catalyst deactivates it, requiring expensive replacement. a low flow ratio alarm (FAL) is sounded. If the ratio continues
To minimize coking, steam is usually supplied in a ratio of to fall below approximately 2.7:1, the feed gas is shut off by
3.5:1 by weight, relative to feed gas. Special precautions must closing the valve (HV-1).
PAH
Methane
PIC M
2 AR
1
TI PT
2
AT
1
Pressure
compensated
FIC S
1 HV TI
1 2
TI
1 Catalyst
Hydrocarbon
feed gas (TYP) tubes
FAL FC S/D
Preheat
FT FSL I coil
1 1
2.7:1
FFC FAL
2
FT 3:1
2 Furnace
Superheated HV
steam 1
FO
FV HIC
2 FC I
1
HV (TYP
3 HV for 3)
S/D—shut down 2
Fuel gas
system PAL
Figure 8.27c 1
FIG. 8.27v
Reforming furnace process controls by manipulating the steam flow in ratio to the hydrocarbon feed.
and upon the residence time in the pyrolysis coils. Therefore, adjusted to guarantee that all coils will coke at an almost equal
the distribution of furnace products is dependent upon the rate.
degree of firing and upon the temperature profile in the fur- The steam flow controllers (FIC-7 is shown as typical for
nace. Effluent from the furnace is quickly quenched to pre- all three) regulate the steam flow to match the total flow of
vent recombination of products into undesirable polymers. hydrocarbon feed, controlled by FIC-4. The temperature con-
troller (TIC-4) sets the firing controls by adjusting the total
heat input to the process and brings the effluent temperature
Process Controls The important variables to be controlled to the desired value.
in order to obtain the desired effluent product distribution are The temperature indicator points (TI-1 through TI-6, as
hydrocarbon feed flow, steam flow, coil temperatures, and well as the tube skin temperature sensors) are monitored by
firebox temperature. The firing controls discussed in connec- the process operator to maintain a certain furnace temperature
tion with the previously discussed furnaces are also applica- profile and, hence, a certain product distribution in the fur-
ble here. nace effluent. The temperature relationships are accomplished
As shown in Figure 8.27x, the charge to the cracking by manually trimming burners at the required places in the
furnace is determined by the flow controls on each of the firebox.
individual passes rather than by total flow control. It is impor- In order to determine whether the desired product spec-
tant to keep the flow through the coils constant, because ifications are being met, an analyzer is installed in the furnace
coking causes a gradual build-up in the pressure drop through effluent (AT-1). This analyzer is usually a chromatograph,
the coils and reduces both the flow and the heat transfer. though mass spectrometers could also be used, if the speed
If the feed distribution were left purely to hydraulic split- of response of this analysis was critical. This analyzer mea-
ting, the coking would start in one coil and reduce the flow sures most of those components in the effluent stream that
through that coil, which in turn would cause overheating of that are lighter than butane.
coil, producing even more coking. Eventually, the flow would This analysis is a difficult one, primarily because of the
be reduced to such a low rate that the overheating of the coil sample handling requirements. The sample has a high water
would cause its melting and rupture. The individual flow control content, and the water must be condensed and removed
valves serve to introduce variable pressure drops, which are before the sample entrs the analyzer. The sample also has a
Pass balancing
algorithm
TI’s
FX TI
4 6
TAH
HIC
1 TI
1 Chromatograph
I FAL FI FT
1 1 1 AI
1
FIC
4 FO TAH
HIC TI AT
2 2 1
FT I FAL FI FT
2 2 2 To quench
system
FO FO TAH TT TI
HIC 4 5
Hydrocarbon TI
3 3
I FAL FI FT
feed from 3 3
3 TAH
preheat
coil TIC To firing
4 controls
FO TI
Note 1. Each coil has
FIC FO several tube
7 Note 1.
skin thermocouples,
Typical hot spots are alarmed.
for all FT
three (3) 7
Dilution
steam
FIG. 8.27x
Pyrolysis furnace process controls.
Furnace
In response, the operator can increase the set point of the
Furnace appropriate feed flow controller, thus forcing more fluid
Feed effluent through the hot tube, thereby hoping to bring the temperature
down. If this does not alleviate the condition, the operator
FT TRC
4 1
has no alternative but to shut down the firing.
Failure of instrument air will result in failing all the
SP Burner Set control valves open, as in Figure 8.27x. The feed valves and
headers point
FR PIC PIC
the steam valves open on air failure to continue the flow
4 1 2 HV through the furnace coils and, thereby, to prevent overheating
1 Fuel
FC FC FC gas
and possible rupture of the coils.
FSL PV Push PV
4 FT
1 button 2 8
HS
PSL ADVANCED CONTROLS
FAL
1 S 1
4
Fuel shutdown FR PAL
HY 1 Advanced furnace controls include feedforward control
1 8
Instrument based on feed rate, cross-limiting firing (Figure 8.6rr in
air Section 8.6), coil balancing (Figure 8.21r in Section 8.21),
Fuel
shutdown and optimization. Implementation of these control strategies
is normally aided by expert system software, distributed
FIG. 8.27y control systems, single or dual loop programmable control-
Pyrolysis furnace firing controls. lers, or dedicated microprocessor-based devices can also
perform this type of control to a limited extent. An example
of each type of control is presented in the next paragraphs.
large amount of entrained coke and tars, which likewise must Control systems can include any combination of these
be eliminated (scrubbed out). advanced techniques.
ature controller (TIC-1) providing the set point for the fuel A/D
flow controller (FIC-1). When the feed flow to the furnace PDT A/D
TI
changes (this flow is an independent variable in this system), FV 20
20
2
there is a need to change the rate of fuel firing.
The feedforward loop includes the feed flow transmitter FT
(FT-1), which detects the change in feed flow rate, and this 2 D/A Furnace
2 A/D
rate is multiplied by a constant in FY-1. This constant relates A/D FV
TI 21
2 21
to the heating value of the fuel gas, and if a BTU analyzer 3
(AT-1) is used, the correction can be automatically obtained. FT
This multiplying block sets the relationship between a change A/D
3
D/A A/D
in feed flow rate and the required corresponding change in 1 3 TI 22 A/D
A/D FV 22 30
fuel header pressure. This is an empirically determined value 3 4
and can be field-adjusted. FT AT
1 30
FT
Dynamics may be included (dead time, lead/lags) if war- 4
Furnace
D/A effluent
ranted (this topic is discussed in full detail in Section 2.9 in 4
Feed A/D
Chapter 2). The response of the furnace to an increase in firing 4
gas TI A/D
rate is often too slow, and therefore such controls are useful 30 30
Legend
only when responding to step changes in feed flow rate.
The modified signal from FY-1 is then summed (FY-2) A/D −Indicates computer input
with the signal from the temperature controller output,
D/A − ,, ,, output
thereby setting a new fuel gas flow rate via FIC-2. In effect,
advance information is fed forward through FY-1 to the firing
FIG. 8.27bb
controller (FIC-2), indicating that a change in process load
The I/O requirements of a digitally controlled pyrolysis furnace.
will require a change in firing rate shortly and that the firing
rate, therefore, should begin to change.
Without the feedforward leg of the loop (FY-1 and FY-2), this ratio changes with time. Thus, TRC-1 acts in the feed-
the required change in firing rate would take place much later, back path as a slow trim-controller, keeping the controlled
after the temperature controller (TRC-1) detects an error in variable at a desired value.
the controlled variable (the effluent temperature of the fur-
nace). If a constant ratio existed between feed flow and fuel Coil Balancing Control
gas flow, the temperature controller would not even be nec-
essary, but with changing ambient and process conditions, One of the main considerations in a multipass furnace control
is the proper splitting of feed among the parallel passes
through the furnace. In a large ethylene plant, six to eight
Fuel gas identical cracking furnaces may be present, each with from
header To 10 to 20 parallel coils. Maintaining proper flow splits in these
burners coils is a formidable task if done manually.
Fuel The objective is to maximize furnace energy utilization
Surge- PT
gas no.1 per unit of feed flow. In general, heat transfer efficiency is
mix 1
drum highest when the percentage of vaporization measurements
Fuel FT in all the coils are equal. However, without a measurement
1 PIC
gas no.2
High Low 1
Set of percentage of vaporization, the best that can be done is
FR FT limit limit point equalization of all the individual coil outlet temperatures.
1 2 (BTU/lbm) setter setter
Digital control of the total furnace circulation is imple-
FR HIC HIC
F2 2 6 7 mented by feedback manipulation of all furnace coil flow
XR
Total 1 rates. Figure 8.27bb shows an older computer control system.
F1 < > Hr
heating value FY FY Here, the total feed flow (A/D-1) and the individual coil flows
analog 6 7 (A/D-2, -3, -4, etc.) are monitored by the DCS system, which
computer
calculates the proper valve settings based on these flows. The
H1 H2 proper valve openings are sent by the DCS system (through
Heating Heating F1H1 + F2H2 the digital-to-analog converters (D/A-2, -3, -4, etc.), and the
value value Hr =
F1 + F2 valves divide the total feed flow properly.
gas no.1 gas no.2
(dial setting) (dial setting) The total feed flow rate sets the total charge to the furnace.
Each coil flow rate set point is calculated as the total furnace
FIG. 8.27aa flow (minus the flow of all nonautomated coils), divided by
Header pressure set by heating value of fuel mixture. the number of coils that are automatically controlled. This
allows for coil balancing of at least a portion of the furnace, are “off-normal” alarms on feed flow, “off-normal” alarms
if some of the coils cannot be placed under automatic control on effluent temperatures, alarms to signal excessive pressure
due to defective instrumentation. drops across coils, high coil-metal temperatures, and other
After start-up, the total flow will be divided equally scanning functions.
among the passes, but as time progresses, coke builds up at
different rates in the individual coils, causing outlet temper- Cross-Limiting Firing
atures to vary from coil to coil. This control system keeps
the coil effluent temperatures the same (within some toler- A cross-limiting firing control technique ensures that air is
ance) by adjusting the flows of the feeds through each coil. always in excess of the amount required to fully combust the
The DCS system does this by taking the effluent coil tem- fuel. This avoids hazardous (fuel-rich) combustible mixtures
perature information (A/D-20, -21, -22, etc.), comparing in the firebox. When an increase in firing rate is needed,
them with the desired temperatures, and modifying the “feed- cross-limiting firing controls first increase the airflow, and
splitting” computation to correct for deviations. The results the fuel flow only after that. When a decrease in firing rate
of the computation are sent out to reposition the feed valves is desired, the strategy reduces fuel flow before reducing the
(FV-2, FV-3, FV-4, etc.). airflow. This is performed through a combination of high-
Changes to the furnace charge rate are normally ramped, and low-select modules and dynamic exponential lag mod-
and their speed of change is limited to avoid rapid upsets in ules. A control block diagram of the cross-limiting firing
the furnace. Limit constraints, including a differential flow circuit is shown in Figure 8.27cc.
limit between each coil and the average coil flow, are normally The success of the cross-limiting firing is predicated on
included in the overall control algorithm to maintain safe flow being able to measure or infer the air and fuel flow rates (see
rates in all coils, in order to prevent excessive coking or devel- Table 8.6d in Section 8.6 for sensors). If the airflow is con-
opment of hot spots in the furnace. trolled only by damper position, this flow rate must be inter-
Many additional optimization functions can be per- polated from the damper position. Also, fuel is often not
formed using much of the same input data. Some of these metered, but only controlled by a pressure controller, so the
Effluent
TIC-1 AIC-1
temperature Air/fuel ratio
A M Air/fuel A M
Excess O2 ratio
FT3 FT3/BTU
+
Dynamics + Σ
Volumetric
feed flow ⋅ N
D
SG BTU
Optional Feed heat value
FY-2
BTU
Low sel
Minimum
fuel value BTU TY-1
N
BTU/FT3 D
Fuel Hi sel PY-1
heat value FT3/BTU
BTU/FT3 FT3 BTU BTU
(from analysis) BTU
⋅ LAG Hi sel ⋅ FY-1
TY-2
LAG
FT3
Air flow
FT3
Limits Set point Limits Set point
R L R L
FIG. 8.27cc
Cross-limiting firing control block diagram.
header pressure must be converted into an approximation of These firing rates may be printed out as instructions to
flow rate. Such indirect methods of flow approximations are the operator or used to automatically manipulate the fuel
highly inaccurate and should no longer be used. valves, or fuel flow controller set points, thereby changing
The cross-limiting firing system described in Figure 8.27cc the heat flow pattern throughout the furnace and thus con-
works in the following manner: When the effluent tempera- trolling the cracking operation.
ture controller (TIC-1) calls for additional heat to be supplied
by the furnace, the output of the controller increases. After Model-Based Control
feedforward adjustment, this signal goes to both a high- and
a low-signal selector (TY-1 and TY-2). Process models can relate the control variables of the radiant
At the high-signal selector, this rising signal will be coil to operational parameters. Information on furnace oper-
greater than the signal representing current fuel flow (pres- ation includes hydrocarbon flow rate, steam-to-hydrocarbon
sure). The high select (TY-2) will thus call for increased heat ratio, coil outlet temperatures and pressure, severity of crack-
by increasing its output, and this increased signal will be ing, and fouling parameters. These parameters are used to
multiplied by the current air/fuel ratio in FY-1. The output develop interrelationships between independent and depen-
from this multiplier (FY-1) goes to the set point of the airflow dent variables.
controller (FIC-1). Therefore, the result of an increase in the Matrix calculations can be performed to change the
output of TIC-1 is an immediate increase in the airflow con- manipulated variables so that the controlled variables are held
troller set point. at their set points. General-purpose computing modules are
At the low select (TY-1), the increasing TIC-1 output signal used to run these models and optimizers. For in-depth cov-
will not be chosen because it is greater than the signal supplied erage of a variety of model-based control approaches, refer
by the air/fuel ratio FY-2. The airflow measurement signal is to Sections 2.13 to 2.18 in Chapter 2.
sent through a lag block and is divided by the air/fuel ratio Two common applications of model-based control will
set point in FY-2, which produces the second input to the be briefly discussed below.
low selector. The immediate increase in air, which followed
the rise in TIC-1 output, is thus lagged with a first-order lag Coil Outlet Temperature (COT) Matrix The individual COTs
block prior to the low select (TY-1), resulting in a gradual can be simultaneously controlled by solving an interaction
increase in fuel. Therefore, an increase in the firing rate (TIC-1 matrix that relates the change in each coil temperature to the
output) results in a fast increase in air and a slow increase in change in valve openings of the wall burners. The matrix coef-
fuel flow. ficients determine the gains associated with each COT-firing
When the firing demand drops due to a drop in the feed zone pair.
flow or in the temperature controller output, the reduced Knowledge of furnace geometry and experimental data is
signal is sent to both the high and low selector modules (TY- employed to define the matrix. If the matrix accounts for only
1 and TY-2). The dropping signal is immediately passed the steady-state character of the process, the dynamic nature
through by the low selector (TY-1), resulting in an immediate must be handled by feedback trimming of the COT controllers.
decrease in the fuel flow set point. It may be necessary to remove the excess degrees of
However, at the high selector (TY-2), the decreased signal freedom that result from having more wall burners than COT
is blocked, because the lag element keeps the apparent flow measurements. This can often be accomplished by interpo-
of fuel higher. The result is a slow (first-order lagged) reduc- lating the desired wall burner valve positions on the basis of
tion in the flow of air. A change in the output of the excess the outputs of adjacent COT controllers.
air (or O2) controller (AIC-1) goes through the low selector Provisions should be made to disable controllers whose
on the fuel flow (TY-1) in a similar manner. The output of the thermocouples have failed (burned out). The proper installa-
controller (AIC-1) is the air/fuel ratio setting for the furnace, tion of tube surface-detecting thermocouples is shown in
which is multiplied by the signal from the high selector in Figure 8.27dd.
FY-1. Therefore, the air/fuel ratio directly affects the airflow set Because of the harsh service, COT thermocouple (T/C)
point. This same air/fuel ratio is the divisor at the airflow in failure is a routine incident that the control strategy must
FY-2. The output of FY-2 is the second input to the low selector handle. To detect the thermocouple burnout, it is necessary
TY-1, which selects the fuel oil flow set point. to detect the loop resistance of the installed thermocouple
(Figure 8.27ee).
Severity Control Dual or companion thermocouples can be connected to
multiplexers and can be used to validate the COT measure-
Using the ethylene cracking furnace in Figure 8.27bb as an ments. When a COT controller is placed in manual, its output
example, an analyzer measuring the effluent stream compo- is forced to be equal to the average output of the COT con-
sition (AT-30) also sends its measurement signal to the com- trollers that are still controlling the process (the average of
puter, where it is compared with the desired composition. those controllers that are not in manual).
Based on the difference between the two, the desired degree In this way, temperature control for the failed coil is still
of fuel firing in various furnace zones can be computed. maintained to some extent, and responses are made to
Boiler
tube
Furnace
wall
FIG. 8.27dd
The expansion loop allows for thermal expansion in furnace applications.
disturbances that are affecting all the coils. This approach rate in a matrix format. Outputs to local controllers or valves
has proven to be an effective solution whenever thermocou- are then adjusted all at once.
ples are to be replaced on-line.
The use of a matrix algorithm alone does not necessarily
guarantee an even firing pattern, because there is no feedback CONCLUSIONS
component in this strategy to correct for errors in the matrix
model. Over time, as the effects of coking, air register adjust- The furnaces and control systems discussed in this section
ments, and burner fouling are better understood in a particular are representative of a wide spectrum of furnaces throughout
installation and when they are better quantified, solutions can the process industry. The strategies are valid whether imple-
be implemented by shifting the duty requirements between mented by older analog instrumentation or by more sophis-
the firing zones in such a way as to equalize the bias station ticated DCS or PLC systems.
positions. The control systems that were described in this section
did not cover the specifics of advanced process control. For
Optimizers Optimizers are used to calculate the required the subjects of optimization and modeling, the reader is
charge rates and the severity of cracking of ethylene furnaces, referred to Sections 2.7 to 2.20, and for relative gain calcu-
based upon financial or contractual criteria. The model-based lations or for decoupling of interactions to Sections 2.25 and
program then simultaneously manipulates several indepen- 2.37 in Chapter 2. It should also be noted that the sections
dent variables to achieve these dependent control points. describing boiler controls (Section 8.6) and distillation con-
The model solves simultaneous polynomial equations trols (Sections 8.19 to 8.21) should also be studied, because
relating severity to charge rate, steam-to-hydrocarbon ratio, there is a fair amount of overlap between these unit operations
furnace effluent temperature, excess oxygen, and coil fouling and furnace controls.
With the expansion of industrial facilities and with the
use of larger furnace units on the one hand and with the
increased availability of advanced process control (APC) on
T1
the other hand, the use of more advanced and model-based
controls should be considered, while taking full advantage
of the basic controls described in this section, to obtain more
efficient and more profitable furnace operation.
Ts T1
40CFR Part 60, “New Source Performance Standard” (sec- Gilchrist, J. D., Fuels, Furnaces, and Refractories, New York: Pergamon
tion for oil refineries) Press, 1977.
Gruhn, P. and Cheddie, H., “Safety Shutdown Systems–Design, Analysis,
40CFR Part 61, “National Emissions Standards for Hazard- and Justification,” 2001.
ous Pollutants” Harrison, T. J., “Microcomputer in Industrial Control: An Introduction,”
IEC 61508, “Functional Safety – Safety Related Systems” Research Triangle Park, NC: Instrument Society of America, 1978.
ISA TR84.02-2002, “Fault Tree Analysis” Hugo, A., “Limitations of Model Predictive Controllers,” Hydrocarbon
Proc., January 2000, p. 86.
NFPA 85-2004, “Boiler and Combustion Systems Hazard
Hurowitz, S., Anderson, J., Duvall, M., and Riggs, J. B., “Distillation
Code” Control Configuration Selection,” submitted to J. Process Control,
OSHA 40CFR1910.119, “Process Safety Management” March 2004.
Johnson, R. K., “Modern Approach to Process Heater Control Systems,”
Parkersburg-Marietta ISA Section, Parkersburg, WV, February 8, 1977.
Khalil, E. E., Modelling of Furnaces and Combustors, Tunbridge Wells, UK:
Bibliography
Abacus Press, 1982.
Kostiw, W. B., “How to Instrument Fuel Oil Systems,” Instrumentation
AIChE, “Guidelines for Safe Automation of Chemical Processes,” 1993. Technology, October 1974.
Batur, C., Sharpless, R. B., Duval, W. M. B., Rosenthal, B. N., and Singh, Kralj, F., “Application of the S88 Model in the Control of Continuous
N. B., “Adaptive Temperature Profile Control of a Multizone Crystal Distillation Facilities,” Proceedings of the World Batch Forum, Wood-
Growth Furnace,” Proceedings of the American Society of Mechanical bridge Lake, NJ, April 2003.
Engineers, Dallas, TX, November 1990. Lipták, B. G., “Process Control Trends,” Control, January, March, and May,
Baxley, R. A., “Computer Control of Severity on Ethylene Cracking Fur- 2004.
naces,” Instrumentation Technology, November 1971. Maeda, M. and Nagao, S., “A New Combustion Sensor for Exhaust Gases
Blevins, T. L., McMillan, G. K., Wojsznis, W. K., and Brown, M. W., for Boilers, Furnaces, and Automobile Engines,” Proceedings of the
Advanced Control Unleashed, Research Triangle Park, NC: ISA, ISA/90 International Conference & Exhibition, Vol. 45, Part 1, New
2003. Orleans, LA, October 1990.
Boyle, W. E. and Hoyt, R. R., “Experimental Application of Combustion Marchant, G. R., “Digital Controls for Continuous Copper Smelting,” Instru-
Controls to a Process Heater,” Annual ISA Conference, September ment Technology, June 1978.
13–17, 1948. Normandeau, L. and Bambeck, R. J., “Combustion Control using CO Trim
Calabrese, A. M. and Kreji, L. D., “Safety Instrumentation for Ammonia for Coal- and Gas-Fired Boilers,” Proceedings of the ISA/89 Interna-
Plants,” Chemical Engineering Progress, February 1974. tional Conference & Exhibition, Vol. 44, Part 4, Philadelphia, PA,
Clelland, P. J., “Furnace Implosions: Causes and Cures,” Instrumentation October 1989.
Technology, December 1977. Omata, S., Yamamoto, T., Maruyama, H., and Hotta, M., “Adaptive Control
Dukelow, S. G., “Energy Conservation through Instrumentation,” University of a Furnace Temperature by using a Microcomputer,” Proceedings of
of Houston Energy Conservation Seminar, February 7, 1993. the 28th Society of Instrument and Control Engineers, Tokyo, July
Dukelow, S. G., “Fired Process Heaters,” presented at ISA/CHEMPID, April 1989.
1980. Reed, R. J., Combustion Handbook, 3rd edition, Cleveland, OH: North
Dukelow, S. G., “How Control Improvements Save Process Heater Fuel,” American Mfg. Co., 1986.
1979 Conference on Industrial Energy Conservation Technology. Roffel, B., “Distillation: Instrumentation and Control Systems,” Encyclope-
Edwards, D., “From LR to PC: Recent Developments in Furnace Control dia of Separation Science, London: Academic Press, 2000.
Systems,” Metals and Materials, October 1990. Shinskey, F. G., “Controlling Multivariable Processes,” Research Triangle
Garcia-Borras, T., Manual for Improving Boiler and Furnace Performance, Park, NC: Instrument Society of America, 1981.
Houston, TX: Gulf Publishing Co., 1983. U.K. Health and Safety Executive, “Out of Control: Why Control Systems
Gibbons, C. and Kania, C., “On-Line Optimization for an Ethylene Plant,” Go Wrong and How to Prevent Failure,” 1995.
Proceedings of the ISA/90 International Conference & Exhibition, Vol. Willis, M. J., “Selecting a Distillation Column Control Strategy (A Basic
45, Part 2, New Orleans, LA, October 1990. Guide),” 2000.