Академический Документы
Профессиональный Документы
Культура Документы
quantities of heat
The boiling point of a liquid can be changed by
Indoor air can be too cold, too hot, too wet, too dry,
too drafty, and too still.
These conditions are changed by treating the air.
Cold air is heated, hot air is cooled, moisture is
added to dry air, moisture is removed from damp
air, and fans are used to create and maintain an
adequate air movement.
Each of these air treatments is accomplished in the
air-conditioning air cycle.
Air – Conditioning Air Cycle
The main purpose is to provide a surface over which air from the
room can flow. It also provides a passage through which the
refrigerant flows.
The combination of warm air flowing over the cold refrigerant
causes the air to lose heat and the refrigerant to gain heat.
Although the temperature of the refrigerant does not change, the
heat picked up from the air needed to vaporize the liquid
refrigerant at the same temperature and then the refrigerant is
heated.
By supplying a cool surface to the air, the cooling coil serves as a
heat transfer device. Heat is transferred from the air to the coil
surface, and then to the refrigerant in the coil. In effect, heat is
transferred from the air to the refrigerant through the coil (heat
transfer) surface.
Compressor
The compressor serves two purposes. First, it draws the
refrigerant from the cooling coil and forces it into the
condenser. Secondly, the compressor increases the pressure
of the refrigerant.
The compressor increases the pressure of the refrigerant and
also increase the refrigerant vapor temperature (discharge).
As a result, it is easier for the condenser to do its job.
To find the heat that flows through the building surface by conduction,
the U-factor is multiplied by the surface area in square feet. This
product is then multiplied by the difference in temperature between
the indoor air and the out- door air. The resulting value is the total heat
flow; Q. Q is expressed in Btu per hour of conducted heat flow.
The position of the building with relation to the sun is a factor that
does not change the total heat load, but which can be put to
practical use.
For example, figures 5.11 through 5.14 illustrate the possible
placement of the glass areas of a building with respect to the sun.
The resulting solar heat load and the time relationships are also
shown. For these figures, it is assumed that there is equal glass area
in each wall of the building and the midsummer conditions apply.
Since the sun rises in the east, the solar load through the glass in the
east wall is greatest in the morning, figure 5.11. By noon, the solar
load in the east is somewhat reduced and its effects are now greater
through the glass in the south wall, figure 5.12.
By mid afternoon, the solar heat reaches its greatest intensity; it is
now felt through the glass in the west wall, figure 5.13. The north
wall, of course, is exposed to the less intense late afternoon and
early evening sun; thus, the load through the glass on the north side is
about 1070 of the load on the east or west, figure 5.14.
Building Orientation
The information given in figures 5.11 through 5.14 is important in its
application to practical situations where the effects of the solar load are a
factor. For example, if a building used for a retail business has a large glass
surface facing toward the east and the remaining walls have only small
glass areas, it is possible to reduce the initial cost of the air-conditioning
equipment by 25%.
To reduce the initial cost of the system, the equipment is selected not to
handle the highest load (the solar load through the glass on the east side),
but rather to handle the next-to-highest load (such as the afternoon solar
load on the west wall).
Although the solar heat in the afternoon is even more intense than the
morning solar heat, the west wall of the building in this example has a
limited glass area. There-fore, it is reasonable to expect a smaller solar
load through the west wall. Since the maximum load to be handled is less,
smaller equipment can be selected. Thus, the owner must accept slightly
warmer building temperatures in the morning hours when customers are
likely to be infrequent. The morning temperatures are warmer because the
equipment selected can handle only the maximum midafternoon building
load. The equipment is not large enough to handle the total morning load.
Building Orientation
Walls and Roofs
Heat from the sun enters a building through the walls and
roof at a much slower rate than it does through glass, figure
5.15. As the solar heat penetrates the surface skin of the
building, some of the heat enters the building material and
some is reflected to the atmosphere. The heat absorption
process is continuous and the amount of solar heat entering
the building material penetrates deeper until it reaches the
inside surface. If the sun were stationary so that it could shine
continuously in one location with the same intensity,
approximately seven hours would be required for the heat to
reach to the interior surface of a 12-in. thick brick wall.
Figure 5.16 is a comparison of the heat gain through equal
areas of roof surface, wall surface, and glass. This graph
clearly shows that the solar heat penetrates glass with much
greater ease than it does non-transparent materials of
greater thickness.
Walls and Roofs
Infiltration
When estimating the heat load, indoor heat sources must be considered also.
These sources include people, lights, appliances, and motors.
People are a source of both sensible heat and latent heat, figure 5.17. The
heat produced by a person depends upon the energy that is being exerted.
A person at rest causes less heat than a person being very active. For
example, a person sitting quietly produces about 1/7 as much heat as a
person who is bowling.
All lights give off heat. The heat emitted by incandescent bulbs is directly
related to the wattage of the bulbs. The heat produced by fluorescent
lamps is approximately 25% greater than that expected from the rated
wattage. This heat increase is due to the additional electricity required by
the ballast. The heat load from all types of lights varies according to the
usage.
Motors, appliances, and office machines are additional sources of indoor
heat. This heat load is a direct function of the energy that is used. Motor
heat generally is based on the horsepower rating, but varies according to
usage and to the starting and stopping characteristics of the motor. Heat
from appliances and office machines is directly related to the fuel or energy
consumed. Again, the actual load from these items is affected by usage.
Storage
Every structure can absorb and retain heat.
In some cases, the heating effect may not be felt until after sunset. Thus, the interior as
well as the inside surface of the wall or roof contains heat. In addition, all objects in the
building (such as furniture and floors) contain heat. If this heat is present when the air-
conditioning equipment is shut down at night, a percentage of the heat is retained. This
heat becomes part of the heat load present when the equipment starts again in the
morning.
This portion of the start-up load can be decreased by operating the air-conditioning
equipment during the night or during the early morning hours before the building is
occupied. Since a solar heat load is not a factor during these periods, the total building
heat load is considerably below the load that the equipment is capable of handling.
Therefore, it is possible to reduce the temperature of the walls, roof, and objects in the
building to the point at which they are no longer a heat load. These surfaces can be
cooled until they become a source of stored cooling capacity. This stored capacity can then
be used to offset part of the solar heat load during the morning and the load that results
when the building is again occupied.
This principle of stored cooling capacity can be applied to smaller commercial and
residential installations whenever the total heat load is below the maximum capacity of the
cooling equipment. However, care must be taken to prevent the temperature from
becoming too cold for comfort if the building is occupied.
Storage
The stored cooling capacity can be used to reduce the size of the air-
conditioning equipment. Figure 5.18 shows that the equipment capacity can
be smaller than that required to handle the maximum load if the stored
cooling capacity is used. The storage principle can be applied to any
comfort installation in which the maximum load is present for less than two to
three hours. It is not recommended where a change in temperature is critical.
Zoning
In air conditioning, a zone is an area in a building that is set apart from other
areas, usually by partitioning. Zoning makes it possible to handle load
conditions in the various areas on an individual space or zone basis. Zoning
usually results in a lower equipment operating cost; non zoning usually results in
a lower initial equipment cost.
If different loads occur in different parts of a building, or if different
temperatures are required in different parts of a building, zoning may be
required. If zoning is to be used, the load estimate is usually based on the use
of one central equipment (heating and cooling) installation rather than separate
installations for each zone. Separate installations cost more. In addition, the use
of separate installations requires a greater total cooling capacity because each
installation must be able to handle the maximum load for its zone.
Figure 5.19 shows one possible arrangement of zones within a building. In this
case, the building is divided into four zones: north, south, east, and west.
Assume that the maximum loads are as follows: the north zone, 5 tons; the south
zone, 5 tons; the east zone, 10 tons; and the west zone, 12 tons. Thus, the total
cooling capacity required when each zone is handled separately is
5+5+10+12 or 32 tons, figure 5.19 (B). If the same zones are handled by a
central system, the maximum cooling capacity required equals the maximum
building load at any given time of the day.
Zoning
All of the zones do not experience the full solar load at the same time. As a result,
the maximum loads of the zones do not occur at the same time. Therefore, the
amount of cooling to be supplied at any given time must be just large enough to
handle the zone experiencing the maximum load plus the load in the remaining
zones. In most instances, at least one of the other zones is not at its peak load.
Zoning
ventilation
Conduction
During the heating season,
heat is lost in a manner similar
to the way in which some heat
is gained during the cooling
season. That is, heat is lost by
conduction through walls and
roofs, glass areas, basement
floors, and foundations, figures
5.21 and 5.22.
The total heat lost, therefore,
consists of losses by conduction
through materials and by
filtration through cracks and
open doors.
Figure 5.22: Conduction takes place through
glass, floor, and foundations
Conduction
The amount of heat lost is affected by the materials used in
construction and by the difference in temperature between the indoor
air and the outdoor air. The U-factor rate of heat flow is used to
determine the total heat quantity Q that is lost through the materials.
In a heating operation, however, the temperature difference between
the inside and outside air is usually quite large. As a result, the
transfer of heat by conduction is usually greater than that of a
cooling operation. For example, the average temperature difference
for cooling may be 10 to 20 degrees; for heating, this difference is
in the range of 30 to 70 degrees.
Heat is also lost through floor on ground level (slab construction) and
through floors and walls below the ground level (basement area),
figure 5.23. There is usually a greater heat loss from the outer
areas of slab floors on ground level than through basement floors
and walls that are below the ground level. This difference in heat loss
is due to the difference in temperature between surface ground and
the ground below the surface. The surface ground temperature varies
with the air temperature.
Conduction
This temperature variation
decreases almost
uniformly as the depth
below the ground surface
increases. At
approximately eight feet,
the ground temperature
remains relatively constant
since the surface
temperature has little
effect. At this depth, the
temperature may be a
minimum of 45°F.
Ventilation
Heat loss also occurs because heat is required to
increase the temperature of the air used for
ventilation. A better term for this heat is perhaps
the source of the heat load, rather than heat loss.
The heat used to increase the ventilation air
temperature is not actually lost since it enters the
heated space. However, this heat is an additional
requirement (heat load) since the cold ventilation air
must be heated.
Body Heat loss
The human body creates heat when it metabolizes (oxidizes) food. This body
heat is continually lost to its cooler surroundings. The factor that determines
whether one feels hot or cold is the rate of body heat loss. When the rate of
heat loss is within certain limits, a comfortable feeling ensues. If the rate of
heat loss is too great, cold is felt; if the rate is too low, one feels hot.
The processes by which the body loses heat to surrounding are: convection,
radiation, and evaporation.
In convection, the air immediately around the body receives heat from the
body. The warmed air continually moves away, by rising naturally through
the cooler air around it, or by being blown away, and is replaced by more
air which in turn receives heat.
In radiation, body heat is transmitted through space directly to nearby
objects (e.g. walls) which are at a lower temperature than the body; this is
why it can be uncomfortable to sit near a window or wall in cold weather,
even in a warm room. However, heating sources that are warmer then the
body can radiate heat towards the body, creating a feeling of warmth even
at a low surrounding air temperature; this is why one feels warm in front of
a fire even on a cold day.
Body Heat loss
The body is also cooled by evaporation: water on
the skin (perspiration), which has absorbed heat
from the body, evaporates into the surrounding air,
taking the heat with it. The rate of body heat loss is
affected by five conditions:
Air Temperature
Air Humidity.
Air Motion.
Temperature of surrounding Objects.
Clothing.
Body Heat loss
The system designer and operator can control comfort primarily by
adjusting three of these conditions: temperatures, humidity, and air
motion. How are they adjusted to improve comfort?
The indoor air temperatures may be raised to decrease body heat
loss (winter) or lowered to increase body heat loss (summer) by
convection. Humidity may be raised to decrease body heat loss
(winter) and lowered to increase body heat loss (summer) by
evaporation.
Air motion may be raised to increase body heat loss (summer) and
lowered to decrease body heat loss (winter) by convection.
Occupants of the building, of course, have some personal control over
their own comfort. For instance, they can control the amount of
clothing that they wear, they can use local fans to increase convection
and evaporative heat loss, and they can even stay away from cold
walls and windows to keep warmer in winter.
5. Types of Air Conditioning System
And its Unit.
Window Unit
Central Systems
Window Unit