Schneider Electric policy is one of continuous technological innovation and the Company therefore reserves the right to amend any data herein without
prior notice. The images shown in this catalogue are for descriptive purposes only. They may therefore differ from specific models which are selected.
Some of the features described may be available only for some models or configurations. Please refer to the specific technical literature for further details.
AQUAFLAIR Cooling portfolio 4 5
Uniflair BRWC
Page 28 - 29
Cooling only
Uniflair BCWC
Page 30 - 31
Water-cooled
and
condenserless
units Heat pumps Uniflair BRWH
Page 28 - 29
Uniflair BRRC
Condenserless Page 32 - 33
Uniflair ERCC
Page 34 - 35
Cooling only
Uniflair ISCC
Page 36 - 37
Uniflair ERCH
Page 34 - 35
Units with
Heat pumps
ducted fans
Uniflair ISCH
Page 36 - 37
Uniflair ERCF
Page 38 - 39
Free-cooling
Uniflair ISCF
Page 40 - 41
Uniflair UTAT
Fan-coil
Units for Page 42- 43
Underfloor Scroll Compressors Screw compressors
comfort
terminal units
applications Uniflair UTCT
Fan unit Oil free compressors Variable speed drive compressors
Page 44 - 45
6 7
Why Uniflair
Efficiency and Reliability Optimized management
The issue of energy continues to play an extremely important role regarding operating costs for modern systems. Management of the whole system allows energy consumption to be optimized and strategies of integrated control to
Uniflair’s range of products makes it possible to guarantee maximum service reliability while cutting energy be implemented which would otherwise not be possible.
consumption to a minimum:
Uniflair ‘s precision air conditioning units, Active Floor modules and chillers can be linked together by a LAN,
maximising the operating parameters and the real needs of the system.
Particular attention has been paid to the management logic which is aimed at reducing the energy requirement by
means of a “tracking logic” for the current thermal load.
Indirect free-cooling High efficiency refrigerants
The temperature of the chilled water varies dynamically in such a way as to minimize compressor consumption and
the use of free-cooling, maintaining the desired temperature within the room.
“Oil-free” centrifugal
Efficiency at partial loads compressors with 7.0
magnetic bearings 25
(tandem) 6.0 EER
20 Chilled water temperature
3.0
10
Inverter driven 2.0
compressors 5
Optimized set-point 1.0
0 0
Min. Load Medium Medium Max Load
Load Load
Uniflair produces the software for its units internally. This enables the company to equip each machine with a “tailor Reduction in sound pollution is one of the most critical factors designers are called on to solve when choosing plant
made” control which manages all aspects of the unit. systems.
Absolute control means: Uniflair chillers offer low-noise solutions with extremely low acoustic impact thanks to:
When a system is used for technological or industrial Direct expansion mode The need to install a stand-by unit can be exploited
processes which operate all year round, it is important to increase the free-cooling capacity.
in terms of energy saving to use solutions which exploit By interconnecting the circuits of the free-cooling units
these conditions. Chillers equipped with free-cooling it is possible to make the water flow through all of the
Free-cooling coil
devices not only reduce energy consumption compared available exchangers therefore further decreasing energy
to traditional systems but also limit CO2 emissions into consumption.
the atmosphere, contributing therefore to reducing global
pump
Free-cooling pump warming. Additional annual energy saving
When the external temperature is low enough, the free- • Compared to traditional Free-cooling: up to 7%
evaporator cooling system produces chilled water using external air depending on the climate
only, significantly reducing energy consumption since it is • Compared to a traditional system: up to 50%
pump
limited to the fans. Mixed Mode
Limits Benefits
• Pumps sized 24/7 to overcome resistance of Free-cooling • Main Pumps sized only to overcome resistance of
coil and the 3-way valve standard evaporator
• 3-way valve low reliability • Extremely reliable free-cooling pump
• No 3-way valve
Glycol-free
• Capacity with in-built free-cooling up to 1450 kW
1400 saving cooling cooling Created for applications where the use of anti-
- 41% freeze solutions are not permitted, this solution,
Energy
1200 thanks to an intermediate heat exchanger,
absorbed MWh 1370445 994434 969760
- 6% Free-cooling coil isolates the principal hydraulic circuit from the
(yearly)
Standard Chiller
Free-cooling
Energy
Careful selection of the intermediate heat
Traditional
pump
saving % 0 38% 41%
exchanger allows the delta T to be limited to
Uniflair
800 (yearly)
Free-cooling pump only 2°C, reducing therefore the energy drops
600 Annual saving € €0 - € 41361 - € 44075 which are intrinsic to this system.
Uniflair LRAC-LRAH
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
LRAC-LRAH 06/12
Air-cooled water chillers and heat pumps with axial fans for outdoor installations 12 ERAC - ERAH 13
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERAC-ERAH 06/12
Air cooled modulating water chillers and heat pumps for outdoor installation 14 ISAC - ISAH 15
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISAC-ISAH 06/12
Air-cooled water chillers and heat pumps with axial fans for outdoor installations 16 ARAC - ARAH 17
R407C
conditions: water temperature
Cooling capacity: 120 ÷ 260 kW ARAC / ARAH MODELS 0644A 0744A 0964A 1084A 1204A
12/7°C; external temperature
Heating capacity: 129 ÷ 285 kW Power supply V/ph/Hz 400 / 3 + N / 50
35°C; R407C refrigerant
Circuits / compressors nr. 2/4 2/4 2/4 2/4 2/4
Available versions 2. With pump group
Fans / poles nr. 2/6 3/6 3/6 4/6 4/6
- standard Evaporator type nr. x mod 1 x Shell &Tube 3. Measured in free field
- modulating condensation control Cooling only (ARAC) conditions, coil side, direction
- low-noise factor Q=2, at 10 mt. from the
Cooling capacity (1) kW 135 165 190 230 260
unit (at nominal conditions)
Refrigerant R-407C Absorbed power (1) kW 49 54 73 84 95
Heat pump (ARAH) 4. Data refer to nominal
Scroll Compressors conditions: water temperature
Heating capacity (4) kW 141 179 220 255 285
40/45°C, external temperature
Absorbed power (4) kW 41 64 79 84 85
7°C dry bulb, 6°C wet bulb;
Noise pressure level min/max (3) dB(A) 50 / 57 51 / 58 51 / 58 52 / 59 52 / 59 R407C refrigerant
Low noise version
5. Data refer to nominal
Cooling capacity (1) kW 128 158 180 219 245 conditions: recovery water
Absorbed power (1) kW 52 56 78 88 102 temperature 40/45°C; chilled
Noise pressure level (3) dB(A) 47 48 48 50 50 water temperature 12/7°C;
Standard Features - advanced defrost function (only for ARAH) Partial heat recovery (option) external temperature 35°C;
• Self-supporting frame in galvanised steel (colour - integrated LAN card for local network connection of Exchanger type nr. plate / 2 R407C refrigerant
RAL7037) with panels finished in epoxy powders a group of chillers (up to 10 units with 1or 2 units in Thermal heat recovery (5) kW 48 53 75 76 86 6. Data refer to empty unit
• Four hermetic Scroll compressors with internal thermal stand-by) Water flow l/h 8256 9116 12900 13072 14792
protection and anti-vibration supports • Moreover, the microprocessor control system permits: Total heat recovery (option)
• Two refrigerant circuits conforming to EC norms - an overlapped management of units as a single chiller Exchanger type nr. Shell &Tube / 2
(PED 97/23/CE) in copper tubes mainly including: filter (up to 10) Thermal heat recovery (5) kW 178 207 278 318 350
dryer, flow indicator, thermostatic valves with external - management of double set-point and selection Water flow l/h 30616 35600 47816 54696 60200
equalisation, high and low pressure switches and high - free-contact for general alarm and 2 addressable alarms Dimensions and weight
and low pressure transducer management Height mm 1618 2140 2140 2140 2140
• Compressor crankcase heaters (*) - remote ON-OFF switch Depth mm 3807 4542 4542 5242 5242
• Exchange of the cycle on the refrigerant side with 4-way - abilit y to interface with Modbus protocol directly on Width mm 1193 1344 1344 1344 1344
reversing valve (only for ARAH) RS485 serial card Weight (without hydronic kit) (6) kg 1271 1754 2001 2182 2290
• Shell & tube water/refrigerant heat exchanger with - ability to interface with main external communication Weight (with water tank and 2 pumps) kg 1554 2058 2321 2537 2648
two independent cooling side circuits and one hydraulic protocols: Bacnet, Lonworks, Metasys, TCP/IP and
circuit: the heat exchanger is insulated with closed-cell SNMP
expanded neoprene
• Heat exchanger coil with aluminium fins and (*) Standard only for ARAH
mechanically-expanded copper tubes
• Water flow pressure switch Construction Options supervision system or to interface with external BMS
• Sickle-blade axial fans, statically and dynamically • Standard version with modulating condensation control • Condensing coil cataphoresis treatment
balanced with safety protection grilles (internal and • Low noise version with modulating condensation control • R134a Refrigerant (*)
external) protection grade IP54 through special algorithm and sound-proofing of • Condensing version (*)
• Condensation pressure control switch ON-OFF compressor housing • Electronic expansion valve (*)
• Electric panel conforming to EC (Directive 2006/95/EC • Version for production of glycol water mixture at low
and Directive EMC 2004/108/EC) with anti-condensation temperatures down to - 10 °C (ARAC) (*) on request
heater (*), auxiliary circuit, general cut-off switch, • Partial / total condensation heat recovery
magneto-thermal protection cutoff switches • Integrated hydronic system with 1 or 2 pumps (1 + 1 Options
• Sequence phase control standby), expansion vessel, safety valves, water tank Units can be supplied with the following construction
• Microprocessor control system UPC1m including: • Water tank equipped with pump for primary circuit options:
- local user terminal mP20 II visible on unit with panel management • Remote user terminal mP20 II (up to 200 metres) for:
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ARAC-ARAH 06/12
Air-cooled water chillers with axial fans for outdoor installation 18 BREC 19
Uniflair BREC
Cooling capacity (2) kW 392 495 560 592 721 793 909 1020,9 1163
Absorbed power (2) kW 119,2 158,4 173,1 188,4 237,0 258,4 294,7 322,6 362,5
E.E.R. 3,92 3,13 3,23 3,14 3,05 3,07 3,09 3,16 3,21
E.S.E.E.R 4,23 4,31 4,28 4,26 4,38 4,60 4,72 4,40 4,59
Standard Features - Refrigerant charge monitoring I.P.L.V. 4,78 4,91 4,85 4,89 5,00 5,20 5,55 5,05 5,40
• Self-supporting frame in galvanized steel with panels - Monitoring of the absorbed current and checking of Noise pressure levels
finished in epoxy powders (colour RAL7037) possible malfunctions Low noise version (3) 61,0 61,1 61,2 60,1 60,9 62,4 62,6 63,1 63,6
• Two semi-hermetic double screw compressors with - Advanced anti-freeze protection on evaporator Ultra low noise version (3) 55,0 55,2 55,6 54,8 55,0 57,5 57,6 58,0 58,4
internal thermal protection, discharge shut-off valve, oil - Integrated LAN card for local network connection of a Dimensions
heaters and antivibration supports group of chillers Height mm 2525 2525 2525 2525 2525 2525 2525 2525 2525
• Two refrigerant circuits conforming to EC norms (PED - Integrated clock card Length mm 4931 4931 6357 6357 6357 8890 8890 10320 10320
97/23/EC) in copper tubes including: filter dryer, flow - Rotation of pump group setting functioning and start of Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200
indicator, electronic expansion valve managed by the pump in stand-by in the event of pump breakdown
Uniflair control system, valve on the liquid line, pressure • Microprocessor control system in addition allows:
switches, transducers and manometers of high and low - Management of double set-point from remote control
pressure - Limiting of absorbed current on pre-set value or external
• High efficiency shell & tube single passage evaporator. signal
The heat exchanger is insulated with UV-resistant closed- - Rapid “Quick Start” procedure to reach total cooling
cell expanded neoprene capacity within 3 minutes
• Air side exchange coils with aluminium fins and internally - Free-contact for general alarm and 2 for addressable
grooved copper tubes alarms
• Water flow differential pressure switch - Remote ON-OFF switch
• Acousti-composite fans: Sickle-blade axial fans, - Ability to interface with Modbus protocol directly on Construction Options • Coil manifolds protection panels
statically and dynamically balanced, made from RS485 serial card • Double power supply with automatic integrated • Condensing coil cataphoresis or pre-painting treatment (*)
composite materials for high efficiency and low acoustic - Ability to interface with main external communication management on the active line
impact, with safety protection grilles protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP • Fans with electronic commutation motors (EC) (*) on request
• Modulating condensation control with fan speed and SNMP • Power phase correction capacitors
regulation • Economizer (increase in both capacity and E.E.R.) Options
• Electrical panel conforming to EC Norms (Directive • Operation possible with external temperature upto 50°C The units can be supplied with the following external
2006/95/EC and EMC 2004/108/EC, IP54) with general at full load accessories:
cut-off switch, electic bars distribution for power supply, • Low external temperature: unit works down to -20°C • Remote user terminal mP20 II (up to 200 metres with
acquisition of absorbed current, maximum internal • Ultra-low noise version with sound-proof casing and shielded cable) for:
temperature control, magnetothermal cut-off switch on mufflers for the compressors - Entering of commands
the fans and auxiliaries, fuses for the compressors • Production of glycol water mixture at low temperatures - Display unit status of alarms
• Sequence phase, minimum and maximum power supply (down to -10°C) • Spring anti-vibration kit
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BREC 06/12
Air-cooled modulating water chillers with axial fans for outdoor installation 20 BCEC 21
Uniflair BCEC
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCEC 06/12
Air-cooled water chillers with axial fans and free-cooling system 22 ERAF 23
Uniflair ERAF
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERAF 06/12
Air-cooled modulating water chillers with axial fans and free-cooling system 24 ISAF 25
Uniflair ISAF
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISAF 06/12
Air-cooled water chillers with free-cooling system 26 ARAf 27
Uniflair ARAf
R407C
conditions: water temperature
Cooling capacity: 130 ÷ 280 kW ARAF MODEL 0644A 0744A 0964A 1084A 1204A
10/15°C; external temperature
Power supply V/ph/Hz 400 / 3 / 50
Available versions 35°C; glycol 20%; R407C
Circuits / compressors nr. 2/4 2/4 2/4 2/4 2/4 refrigerant
- standard with modulating condensation control Fans nr. 2 3 3 4 4
2. With pump group
- low noise Condensing coil/free-cooling coil nr. 1+1/1+1
Evaporator nr. x mod 1 x Shell & Tube 3. Measured in free field
Refrigerant R-407C conditions, coil side, direction
Scroll Compressors Basic version
factor Q=2, at 10 mt. from the
Cooling capacity (1) kW 144 177 203 245 276
unit (at nominal conditions)
Absorbed power (1) kW 52 57 78 90 103
4. Data refer to nominal
Cooling capacity in free-cooling (4) kW 85 146 152 196 202
conditions: inlet water
Absorbed power in free-cooling (4) kW 6,3 8,4 7,9 9,9 10,0
temperature 15°C; external
Noise pressure level (3) dB(A) 47 48 48 50 50 temperature 5°C; glycol 20%
Low noise version
5. Data refer to nominal
Cooling capacity (1) kW 133 167 188 228 252 conditions: recovery water
Absorbed power (1) kW 58 62 86 98 114 temperature 40/45°C; chilled
Cooling capacity in free-cooling (4) kW 70 123 127 163 166 water temperature 10/15°C;
Standard Features - advanced anti-freeze protection on evaporator Absorbed power in free-cooling (4) kW 5,1 6,5 6,0 7,4 7,6 external temperature 35°C;
• Exclusive free-cooling Uniflair system completely - integrated LAN card for local network connection of a Noise pressure level (3) dB(A) 47 48 48 50 50 glycol 20%; R407C refrigerant
managed by the microprocessor control group of chillers (up to 10 units with 1or 2 units in Partial heat recovery (option) 6. Data refer to empty unit
• Self-supporting frame in galvanised steel (colour stand-by) Exchanger type nr. plate / 2
RAL7037) with panels varnished with epoxy powders • Moreover, the microprocessor control system permits: Thermal heat recovery (5) kW 48 53 75 76 86
• Modulating condensation control with automatic - an overlapped management of units as a single chiller Water flow l/h 8256 9116 12900 13072 14792
regulation of fans speed (up to 10) Dimensions and weight
• Four hermetic Scroll compressors with incorporated - management of double set-point and selection Height mm 1618 2140 2140 2140 2140
thermal protection, with anti-vibration supports and - free-contact for general alarm and 2 addressable alarms Depth mm 3807 4542 4542 5242 5242
crankcase heaters management Width mm 1193 1344 1344 1344 1344
• Shell & tube evaporator insulated with closed-cell - remote ON-OFF switch Weight (only with free-cooling pump) (6) Kg 1451 2164 2411 2682 2790
expanded neoprene - ability to interface with Modbus protocol directly on Weight (water tank, 2 + f.c. pump) (6) Kg 1734 2468 2731 3037 3148
• Condensing and free-cooling coils with aluminium fins RS485 serial card
and mechanically expanded copper tubes - ability to interface with main external communication
• Condensing coil protection filters and grilles protocols: Bacnet, Lonworks, Metasys, TCP/IP and
• Axial fans, statically and dynamically balanced, with SNMP
sickleblades and with safety protection grilles
• Two independent refrigerant circuits conforming to
EC norms (PED 97/23/EC directive) in copper tubing
including: filter dryer, flow indicator, thermostatic valves
with external equalization, high & low pressure switches
and high pressure transducers
• Free-cooling pump regulated by microprocessor control
• Electric panel conforming to EC norms (2006/95/EC Construction Options • Electronic expansion valve (*)
directive and EMC 2004/108/EC directive) complete with • Low noise version with modulating condensation control • Intelligent free-cooling (*)
anti-condensation heater, auxiliary circuit, general cut-off through special algorithm and sound-proofing of
switch, magneto-thermal protection cut-off switches for compressor housing (*) on request
compressors, fans and auxiliaries • Partial condensation heat recovery
• Sequence phase control • Integrated hydronic system with 1 or 2 pumps (1 + 1 Options
• Water flow differential pressure switch stand-by), expansion vessel, safety valve, water tank Units can be supplied with the following construction
• Microprocessor control system UPC1m including: • High and low pressure gauges options:
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ARAF 06/12
Air-cooled water chillers with axial fans and free-cooling system 28 BREF 29
Uniflair BREF
Standard Features - local user terminal with external accessibility Absorbed power (2) kW 124,0 165,5 184,0 197,0 251,0 275 315 350 400
• Exclusive Uniflair free-cooling system completely - outlet chilled water temperature regulation by means of E.E.R. (2) 3,35 3,12 3,21 3,19 3,04 3,12 3,04 3,1 3,08
managed by the microprocessor control an exclusive PID algorithm Cooling capacity
kW 260 312 352 356 423 510 602 711 726
• Self-supporting frame in galvanized steel with panels - electronic expansion valve managed by the control in free-cooling (3)
finished in epoxy powders (colour RAL7037) system Absorbed power
kW 16,9 17,7 24,2 24,5 25,8 28,5 29,4 38,2 38,6
• Two semi-hermetic double screw compressors with - advanced control of cooling capacity by automatic set- in free-cooling (3)
internal thermal protection, discharge shut-off valve, oil point sensitivity regulation E.E.R. in free-cooling (3) 15,42 17,63 14,54 14,56 16,44 17,9 20,5 18,6 18,8
heaters and antivibration supports - refrigerant charge monitoring Noise pressure levels
• Two refrigerant circuits conforming to EC norms (PED - monitoring of the absorbed current and checking of Low noise version (4) dB(A) 61,0 61,1 61,2 60,1 60,9 62,4 62,6 63,1 63,6
97/23/EC) in copper tubes including: filter dryer, flow possible malfunctions Ultra low noise version (4) dB(A) 55,0 55,2 55,6 54,8 55,0 57,5 57,6 58,0 58,4
indicator, electronic expansion valve managed by the - advanced anti-freeze protection on evaporator Dimensions
control system, electrovalve on the liquid line, pressure - integrated LAN card for local network connection of a Height mm 2525 2525 2525 2525 2525 2525 2525 2525 2525
switches, transducers and manometers of high and low group of chillers Length mm 4931 4931 6357 6357 6357 8890 8890 10320 10320
pressure - integrated clock card Width mm 2200 2200 2200 2200 2200 2200 2200 2200 2200
• Possibility of operation with external temperatures down - rotation of pump group setting functioning and start of
to -25°C pump in stand-by in the event of pump breakdown
• High efficiency shell & tube single passage evaporator. • Microprocessor control system in addition allows:
Construction Options • Condensing and free-cooling coil cataphoresis or
The heat exchanger is insulated with UV-resistant closed- - management of double set-point from remote control
• Double power supply with automatic integrated prepainting treatment (*)
cell expanded neoprene - limiting of absorbed current on pre-set value or external
management on the active line
• Air side exchange coils with aluminium fins and internally signal
• Fans with electronic commutation motors (EC) (*) on request
grooved copper tubes - rapid “Quick Start” procedure to reach total cooling
• Power phase correction capacitors
• Water flow differential pressure switch capacity within 3 minutes
• Economizer (permits an increase in both capacity and Options
• Acousti-composite fans: Sickle-blade axial fans, - free-contact for general alarm and 2 for addressable
E.E.R.) The units can be supplied with the following external
statically and dynamically balanced, made from alarms
• Operation possible with external temperature up to accessories:
composite materials for high efficiency and low acoustic - remote ON-OFF switch
50°C at full load • Remote user terminal mP20 II (up to 200 metres with
impact, with safety protection grilles - ability to interface with Modbus protocol directly on
• Ultra-low noise version with sound-proof casing and shielded cable) for:
• Modulating condensation control with fan speed RS485 serial card
mufflers for the compressors - entering of commands
regulation - ability to interface with main external communication
• Intelligent Free-cooling for an increase in efficiency with - display unit status of alarms
• Electrical panel conforming to EC Norms (Directive protocols: Bacnet, Lonworks, Trend, Metasys, TCP/IP
unit in stand-by • Spring anti-vibration kit
2006/95/EC and EMC 2004/108/EC, IP54) with general and SNMP
• Glycol-free version • Flanged type hydraulic connection
cut-off switch, power supply electic bars distribution,
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BREF 06/12
Air-cooled modulating water chillers with axial fans and free-cooling system 30 BCEF 31
Uniflair BCEF
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCEF 06/12
Water cooled water chiller and heat pump 32 BRWC - BRWH 33
Cooling capacity (1) kW 330 389 430 476 544 631 712 830 954 1077 1204 2. Data refer to nominal
Refrigerant R-134a
Absorbed power (1) kW 71,8 82,2 96,9 100,2 116,6 131,5 146,0 172,8 196,3 225,9 249,0 conditions: Evaporator in/
Double screw compressors
I.P.L.V. (3) 5,10 5,52 5,00 5,52 5,88 5,50 5,68 5,63 6,03 5,50 5,63 out water temperature:
12/7°C; Condenser in/out
E.S.E.E.R (4) 4,78 5,11 4,67 5,11 5,35 5,08 5,26 5,15 5,45 5,03 5,20
water temperature: 40/45°C;
Heat pump (BRWH)
condenser fouling coefficient:
Heating capacity (2) kW 377 440 494 541 627 715 806 938 1091 1216 1368 0,000043 m²°C/W; evaporator
Noise levels fouling coefficient: 0,000043
Noise pressure level m²°C/W; R134a refrigerant
73,5 73,7 73,8 78,0 79,5 79,7 79,6 77,3 75,3 76,3 78,4
basic version (5) 3. Integrated Partial Load
Standard Features - double set-point management with contact selection Noise pressure level Value: based on ARI conditions
64,0 63,9 64,6 68,5 69,6 68,7 72,4 69,3 69,1 71,8 72,5
• Self-supporting frame in galvanised steel with panels - general alarm contact and 2 addressable alarms LN version (5)
4. European Seasonal Energy
finished in epoxy powders (colour RAL7037) - ON-OFF remote control Dimensions
Efficiency Ratio
• Two semi-hermetic double screw compressors with - ability to interface with Modbus protocol directly on Height mm 2050 2050 2050 2050 2050 2060 2060 2295 2295 2295 2295
5. Measured in free field with
internal thermal protection, oil heaters and anti-vibration RS485 serial card Length mm 3660 3660 3660 3800 3800 4070 4070 4130 4130 4130 4130
Q=2 directionality factor, at a
supports - ability to interface with main external communication Depth mm 860 860 860 860 860 860 860 1485 1485 1485 1485 distance of 1 mt. from the unit
• Two refrigerant circuits conforming to EC standards protocols: Bacnet, Lonworks, Metasys, TCP/IP and Width with heat
mm 1680 1680 1680 1680 1680 1755 1755 1660 1660 1660 1660 6. Data refer to basic versions
(PED 97/23/CE) in copper tubing including: filter dryer, SNMP recovery
without load
liquid sight glass, electronic expansion valve, discharge Weight (6) kg 2815 2865 2930 3649 3707 3747 3818 5360 5481 5638 5719
shut-off valve, pressure gauges, pressure switches and
high and low pressure transducers
• Shell & Tube evaporator insulated with closed-cell
expanded neoprene
• Shell & Tube condenser
• Water flow differential pressure switch for the evaporator
and condensers
• Electric panel conforming to EC standards (2006/95/EC
and EMC 2004/108/EC directives) with maximum internal
temperature control, auxiliary transformer, auxiliary general
cut off switch, fuses for compressors, cut off switches
• Phase sequence and min / max voltage control
• UPC1m microprocessor control system including:
- mP20II local user terminal visible externally and
accessible through a door panel Construction Options
- chilled water / hot discharge water temperature • Low noise version with sound proofed housing for the (*) on request
regulation compressors (**) available only for 1402A, 2002A, 2202A, 3202A,
- advanced start-up management with 8 partialization • Low external temperature version with anti- 3602A models
steps with automatic set-point regulation and condensation heater for the electrical panel and heaters
compressor rotation with FIFO logic (run time counter, for the evaporator and condensers Options
inrush counter and counter threshold for programmed • Condensers for sea water (*) • Pressostatic valve with integrated control for control
maintenance) • High condensation temperature version (**) software
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BRWC-BRWH 06/12
Water-cooled modulating water chillers for indoor installation 34 BCWC 35
Uniflair BCWC
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BCWC 06/12
Condenserless chiller with remote condenser 36 BRRC 37
Uniflair BRRC
(*) on request
(**) available only for 1402A, 2002A, 2022A, 3202A,
3602A models
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
BRRC 06/12
Air-cooled water chillers and heat pumps with backward curved blade fans 38 ERCC - ERCH 39
C.O.P. (2) 3,29 3,29 3,40 3,32 3,30 n.a. 3,30 n.a. 3,26 n.a. 5. European Seasonal Energy
Standard Features - Production of chilled water to -15°C Noise pressure level (4) dB(A) 67,5 67,6 67,5 69,1 69,1 69,1 71,2 71,2 72,5 72,5 Efficiency Ratio
• Self supporting frame in galvanised steel with panels - Anti-freeze protection ERCC - EC Fans 6. Data refer to an empty unit
varnished with epoxy powders (colour RAL7037) - Compressor timing and protection Cooling capacity (1) kW 48 57 66 76 84 85 97 97 113 113 without pump and water tank
• Access panel to the unit equipped with handles and fast - Compressor rotation based on FIFO logic Absorbed power (1) kW 16,7 20,4 22,8 26,2 30,0 30,0 34,5 34,5 40,6 40,6
screws - Pump rotation on a timed basis for equal operation and E.E.R. (2) 2,85 2,78 2,89 2,91 2,81 2,82 2,82 2,81 2,80 2,80
• Two hermetic scroll compressors with internal thermal startup of the stand-by pump (with alarm signal) in the E.S.E.E.R. (5) 4,02 4,23 4,42 4,28 4,27 4,13 4,41 4,21 4,40 4,39
protection, anti-vibration supports and crankcase heaters event of a breakdown ERCH - EC Fans
(ERCH and low ambient temperature versions) - Display of compressor operating hours Heating capacity (3) kW 56 65 76 87 97 n.a. 113 n.a. 131 n.a.
• Single refrigerant circuit (*) conforming to EC Directives - Alarm code signal Absorbed power (3) kW 17,1 20,3 22,2 26,6 30,1 n.a. 33,7 n.a. 40,7 n.a.
(PED 97/23/CE) in copper tubing including filter dryer, - General alarm with clean signal contact C.O.P. (2) 3,25 3,23 3,41 3,29 3,22 n.a. 3,36 n.a. 3,22 n.a.
liquid sight glass, dual flow thermostatic valve with - ON-OFF remote contact Noise pressure level (4) dB(A) 65,2 65,3 65,3 66,8 66,8 66,8 69,9 69,9 71,2 71,2
external equalisation, high and low pressure switches and Dimensions and weights
high pressure transducers Height mm 1836 1836 1836 1836 1836 1836 2146 2146 2146 2146
• Environmentally friendly R410A Refrigerant Depth mm 1190 1190 1190 1190 1190 1190 1190 1190 1190 1190
Top Level Options
• Water side brazed plate heat exchanger in stainless Width mm 2006 2006 2798 2798 2798 2798 3067 3067 3067 3067
• Electronic expansion valve directly controlled by the
steel insulated with closed cell expanded polyurethane Weight ERCC basic (6) kg 773 778 921 957 963 974 1197 1196 1232 1232
unit microprocessor control
• Water flow differential pressure switch Weight ERCH basic (6) kg 797 802 951 987 994 n.a. 1241 n.a. 1276 n.a.
• Single suction back ward cur ved fans with
• Free-cooling air side exchange coil with aluminium fins
electronically commutated motor (EC)
and mechanically-expanded copper tubes
• Evolved UpCO1m control for:
• Refrigerant side cycle inversion with 4-way inversion
- Discharge water temperature regulation
valve (ERCH)
- Management of the electronic thermostatic valve
• Single suction backward curved blade centrifugal fans.
- Monitoring of the refrigerant load
The external tri-phase rotary electric motor is directly
- Self-adjustment of the set-point regulation
coupled and has an IP54 Class F equipped with internal Construction Options • Evaporator, water tank and pump group anti-freeze
- Evolved defrost operation management (ERCH)
thermal protection (klixon). The fan impeller is • Ultra low noise version by means of sound-proofing the heaters
- Integrated LAN card
dynamically and statically balanced and the cushions are compressors • Modification of the set point by external 0-10V signal
- Compatibility with the most common external BMS
sealed and lubricated for life • Partial / total condensation heat recovery • EC fans
and with the Modbus protocol using only a RS485
• Modulating condensation control based on the • Integrated hydraulic module with one or two pumps (1
card
condensation pressure + 1 stand-by) with heat-protected circulation, expansion Options
• Electrical panel conforming to EC Directives vessel and safety valve • Remote user terminal
(2006/95/EC and EMC 2004/108/EC) protection grade • Internal water tank • Clock card
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERCC-ERCH 06/12
Air-cooled modulating water chillers and heat pumps with backward curved blade fans 40 ISCC - ISCH 41
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISCC-ISCH 06/12
Air-cooled water chillers with backward curved fans and free-cooling system 42 ERCF 43
Uniflair ERCF
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ERCF 06/12
Air-cooled modulating water chillers and heat pumps with backward curved blade fans and free-cooling system 44 ISCF 45
Uniflair ISCF
E.E.R. in free-cooling (4) 9,5 8,6 9,1 4. Data refer to total absorbed
Noise pressure level (5) dB(A) 67,6 69,1 72,5 power (fans and free-cooling
Dimensions and weights pump)
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
ISCF 06/12
Fan coil cassette units for underfloor installations 46 UTAT 47
Uniflair UTAT
stabilised to UV rays, statically and dynamically balanced • LCD display with intuitive symbols 490
on two levels • Selection of the value to display (temperature, set-point,
• 230V/1/50Hz winding induction motor with constantly offset compared with common set-point)
inserted condenser. Class B insulation. Declared to • Selective key block (limited functions for offices,
conform with electromagnetic compatibility (according to hotels...)
2004/108 /EC, CE92/31, CE93/68 Directives) and low • Signalling of coded alarms and faults
voltage directives (Section 10, Directive 2006/95/EC), • ON-OFF timer functions
IP44 protection level. Three rotation speeds. • Economy-sleep function
Electrical Panel Air-filter around
• CE Directive electrical panel (Directives 2006/95/EC and • Manual or automatic operation cold/hot water coil
EMC 2004/108/EC) with unit control card equipped with
incorporated relays
• Thermoformed plastic condensation collection tray
• Cleanable filter in self-extinguishing material Inlet water 1/2” Electrical
supplied with galvanised plate hooks F GAS connection
• 230V/1/50Hz Power supply 522
230
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com
UTAT 06/12
Underfloor air distribution module 48 UTCT 49
Uniflair UTCT
265
IN/OUT pLan user terminal
operation:
BMS
- automatic regulation based on ambient temperature (*) (*) on Master unit only
and room set point (defined with the TUL or by the (**) acquired from remote user terminal (TUL) or from the
BMS); unit air inlet temperature probe.
518
- manual selection of fan regulation (10 speeds) (***) defined by the remote user terminal (TUL) or by the
- manual selection of motorized air damper (10 positions) BMS system
• 230V/1ph/50-60Hz power supply 151,5 199,5 159,5
780
Schneider Electric Uniflair SpA Viale della Tecnica, 2 35026 Conselve (PD) Italy Telephone: +39 049 5388211 schneider-electric.com uniflair.com