{A} WIRE COLOUR IDENTIFICATION (IEC 60204-1)

Sr. No. WIRE COLOUR CIRCUIT Example, wiring draw. 2.1 STV Portugal
1. BLACK (BK) A.C. & D.C. Power 690V AC / 230V AC Power supply behind ACB and behind Main Switch –
circuit 9Q3
2. Yellow (YE) Earth 400 / 230V AC construction power, 230V AC UPS Supply,
300V DC Battery, 690V AC Supply Until mail switch –9Q3
3. Red (RD) A.C. Control Circuit 400 / 230 AC Control Supply
4. Red - White (RDWH) Neutral for A.C. Circuit 230V AC Neutral
5. Blue D.C. Control Circuit 24V DC
6. White – Blue (WH / BU) Neutral For D.C. Circuit Ground of 24V DC Supply
7. Green – Yellow (GN / YE) PE Connection PE Connection
8. Brown Measurement Measurement Wiring
9. Orange Interlock Control
Circuits

Note: - These Colour Schemes shall be used for all IEC standard jobs, wherever customer has not specified his colour scheme.
• These colour schemes as per IEC 60204-1 Which shall be considered for Europe, Asia, India, etc.

PRIMA Automation (I) Pvt. Ltd. – Quality Panel Builder Page 1 of 2


Prima Automation (I) Pvt. Ltd.

{B} WIRE COLOUR IDENTIFICATION (NEC) (REF: NFPA 79, 1997 & 16.1.2 &16.1.3)

Sr. No. WIRE COLOUR DESCRIPTION REMARKS


1. BLACK Ungrounded line ,load and control conductor at line voltage Main Power wire
2. RED AC Conductor less than Line Voltage Control Wire Phase
3. WHITE OR NEUTRAL Ground circuit Conductor Control wire neutral
GRAY
4. YELLOW AC conductor that may remain energize when disconnecting is in OFF Main Incoming wire
Position. Phase.
5. WHITE WITH YELLOW Grounded ac control circuit conductor that remain energized when the Main incoming wire
STRIP disconnecting means is in the OFF position.For additional circuits powered neutral
from different sources that remain energized when the main disconnecting
means is in the OFF position , stripping colors other than GREEN ,
YELLOW OR BLUED shall be used for the unique identification of the
grounded conductor.
6. BLUE DC Conductor at line voltage. D.C + Ve Voltage
7. WHITE WITH BLUE STRIP DC Grounded Conductor D.C - Ve Ground
8. GREEN + YELLOW OR Equipment Grounding Conductor Earthing
GREEN
• These colour schemes are as per NEC 508 Which shall be considered for USA ,Canada etc.