Академический Документы
Профессиональный Документы
Культура Документы
Years
Dearago, whileProfessional,
Hydronic starting out on my own, I bought a twenty-year-old fully
furnished home. Furniture, appliances, lawn equipment, electrical tools, party
lineWelcome
phone, and even
to the a kitchen
2nd edition range with
of idronics a retractable
– Caleffi’s cooktop!
semi-annual design journal for
hydronic professionals.
The house had been owned by a self-reliant engineer who had passed away, but
The 1st edition of idronics was released in January 2007 and distributed to over
not before creating detailed records of how equipment in the house operated.
80,000 people in North America. It focused on the topic hydraulic separation. From
Hethe
kept carefully
feedback maintained
received, files ofwe
it’s evident operating instructions
attained our and service
goal of explaining the records,
benefits
plus
andhandwritten notes on
proper application of nearly everydesign
this modern mechanical device
technique associated
for hydronic with that
systems.
A Technical Journal house. One of those notes even stated that the cranky chainsaw needed “just
1 prime, not 3, before
If you haven’t starting.”
yet received I was
a copy grateful#1,
of idronics foryou
his can
meticulous
do so by records
sending as the
in the
from equipment
attached and appliances
reader response aged and
card, or byrequired maintenance.
registering online at www.caleffi.us. The
Mark Olson
INDEX
1. INTRODUCTION SUMMARY
2. WHAT IS PROPER SYSTEM DOCUMENTATION? APPENDIx A1: CALEFFI COMPONENT
3. TOOLS AVAILABLE FOR DOCUMENTATION SYMBOL LEgEND
4. CREATINg PIPINg SCHEMATICS APPENDIx A2: gENERIC COMPONENT
5. ELECTRICAL SCHEMATICS SYMBOL LEgEND
6. DESCRIPTION OF OPERATION APPENDIx B: SUggESTED SYMBOL LEgEND
7. ADDITIONAL DOCUMENTATION FOR COMMON ELECTRICAL COMPONENTS
8. ExAMPLE SYSTEMS APPENDIx C: CALEFFI RELAY SYMBOL LEgEND
Disclaimer: Caleffi makes no warranty that the information presented in idronics meets the mechanical, electrical or other code requirements applicable within a Mixed Sources
given jurisdiction. The diagrams presented in idronics are conceptual, and do not represent complete schematics for any specific installation. Local codes may Products from well-managed
require differences in design, or safety devices relative to those shown in idronics. It is the responsibility of those adapting any information presented in idronics to forests, controlled sources and
recycled wood or fiber.
verify that such adaptations meet or exceed local code requirements.
Documenting Hydronic Systems
Figure 1-2
3
What lies ahead is several hours of trying to learn what the Unfortunately, scenarios similar to the above occur multiple
original designer or installer had in mind when the system times during each year.
was installed. You are trying to first determine how the
system should operate when everything is normal. Only In today’s market, nearly all manufacturers provide
then can you try to pinpoint what is causing it to not information on the proper installation and servicing of the
operate as expected. components they sell. This information is often shipped
with the product, and usually available online.
The house is getting progressively cooler as time passes
and the system is not delivering heat. You start to wonder However, a hydronic system is a combination of many
if you should make arrangements for temporary electric individual components, and in many cases, a very unique
space heaters in case water pipes in some areas of the combination. There are no manufacturers that currently
building approach freezing temperatures. You wish you sell complete hydronic systems along with associated
had some kind of “road map” that might show you what installation, commissioning and servicing instructions. It
the original installer’s intent was, rather than tracing falls to the designer to select the components needed in
piping circuits, wiring and numerous adjustments to the system, and communicate how those components
several independently operating controls in the system. are to be installed relative to each other. The designer
You are concerned that any control adjustments you also must ensure compatibility between all selected
make without a clear understanding of how the system components. The challenge is to create a stable, efficient
was intended to operate might make the present and reliable system that is often an assembly of several
situation worse. hundred individual components.
IT DOESN’T HAVE TO BE THIS WAY This is a task that some individuals savor, while others
This is obviously not a situation that any HVAC service view it as far less important than maximizing the profit
technician wants to find themselves in. It gives the associated with the installation.
appearance, at least to the owner, that they, and perhaps
the company they work for, are incompetent.
It is also the designer’s responsibility to clearly
communicate how the selected hardware is to be
Although most building owners expect that their installed and properly commissioned. The very best
heating or cooling systems will require service, they system design is of marginal value when it’s only “stored”
don’t understand why any reasonably competent HVAC in the designer’s mind.
service technician should not be able to quickly identify
the problem(s), and fix them. They are used to well-
trained service technicians repairing their vehicles, their The level of detail used in documenting the design can
refrigerator and their computers. make the difference between thousands of dollars’ worth
of hardware that works harmoniously and efficiently as a
complete system, versus an assembly of perfectly good
From the owner’s perspective, why should it be necessary hardware that never achieves it full performance potential,
to spend hours “reconstructing” the original intended creates frequent service calls and repeatedly frustrates all
operation of the system, and only then attempt to restore parties involved.
to this operation? Why should the owner be expected to
pay for that time?
Beyond its use for installation and servicing, good system
documentation adds significant value to the project. It
Such situations can also lead a rapid spread of negative demonstrates knowledge, professionalism, commitment
experience as the owner and his family describe their to proper system installation and operation, and lasting
situation to others. The “take-away” of such conversations value for a purchase that often costs thousands of
will likely be that hydronic heating systems are complex, dollars. Well-prepared documentation sets the heating
expensive, break down and are difficult to service. Such professional who offers it apart from competitors that
conversations can create lasting bad impressions among don’t care enough or know enough to create it.
people who may influence future decisions on heating
systems for other buildings. Consumers obviously have
many choices when it comes to selecting heating and This issue of idronics describes modern methods for
cooling systems, and even minor bad impressions create properly documenting the technical nature of hydronic
legitimate doubts that sway decisions. heating and cooling systems intended for residential and
light commercial installations. This documentation helps
4
ensure proper installation, proper commissioning and 2. WHAT IS PROPER SYSTEM DOCUMENTATION?
efficient serviceability for the system over its full life.
This question is like asking: What is a proper resume?
Beyond technical documentation, consulting engineers What is a proper will? Or what is a proper contract
often have to prepare documents that detail bidding between a heating professional and a client? Opinions
processes, contractual procedures, payment schedules obviously vary on such issues. Likewise, opinions vary
and other legal aspects of the parties involved with on what documentation is insufficient, adequate or even
designing, installing and commissioning the system. superfluous regarding design, installation, commissioning
This documentation varies considerably depending and servicing of a hydronic heating or cooling system.
on the scope of the project and the client (i.e., private
owner, corporate owner or a government agency). Such Experience has shown that problems are more likely to
documentation is not covered in this issue. occur in projects where the documentation lacks sufficient
detail, or is poorly communicated. Such situations have
Figure 1-3 occurred many times across the industry spectrum from
wholesalers and manufacturer’s representatives who
are asked for design assistance, to installers who often
do their own design, to professional engineers hired to
provide sufficient design information for proper installation
and commissioning of a system.
5
responsible to complete the control system will lead to even within these categories designers should provide a
misunderstandings, callbacks, “finger pointing,” or even detailed specification for any hardware that is required for
litigation if the system operates in a manner far different atypical service. Examples include electrical conductors
than what was expected. for use in high-temperature surroundings; fasteners for
securing especially heavy equipment; and specialty
While proper documentation is not a guarantee that such pipe fittings for inserting temperature sensors, dielectric
problems can’t develop, it certainly lowers the chances fittings or vibration-absorbing piping supports.
by reducing the ambiguity of what the final system should
be and how it should operate. In addition to specific hardware, it’s important that
designers also specify any settings or calibrations, such
Figure 2-1 as the rated pressure of a relief valve, or the temperature
setting of the boiler’s high limit controller.
FUNDAMENTAL DOCUMENTATION
The documentation that collectively achieves these
objectives includes:
To gain a better perspective on what constitutes proper • One or more tables that show the desired operating
documentation, it’s important to start with the objective flow rates and temperatures to which the system should
of that documentation. be adjusted when it is commissioned
From the standpoint of design, the objective is to define • Possible use of photos to show examples of the
all non-commodity devices within the system in a manner intended installation of certain devices
that clearly represents the designer’s selections, intended
assembly and desired operating conditions.
The relatively simple question designers should ask
themselves when preparing such documentation is: Can
“Non-commodity devices” refers to hardware such as heat a reasonably competent installer, familiar with the basic
source(s), chillers, circulators, heat exchangers, tanks, principles of hydronics, install this system as intended
piping materials and size, air and dirt separators, mixing and commission it to the desired operating conditions
valves, specialty valves, manifold stations, chimneys, vent using the documentation I have provided?
connectors, temperature sensors and all safety devices.
These are all devices that must be sized and selected to
Designers should not assume that those installing the
fulfill specific performance requirements in the system.
system are familiar with the product selections, or how the
overall system is supposed to operate. This is especially
Commodity items usually include common pipe fittings, true if the design is for anything but a very basic system
wiring hardware and mechanical fasteners. However, using the simplest of controls.
6
From the standpoint of installers, documentation should Piping Schematic
include: Figure 2-2 shows an example of a piping schematic
prepared for a system that uses an air-to-water heat
• Labeling of all major components in the system, pump to provide space heating and partial heating of
including circulators, valves, heat exchangers, mixing domestic water.
devices, controllers, sensors, etc. Be sure the labeling
matches the component abbreviations shown on the A piping schematic shows the relative placement of the
piping and electrical schematic. The labeling should non-commodity devices within a system. It is not a scaled
also be durable and not subject to damage from water drawing, nor does it show the exact physical placement of
or the temperatures likely to be encountered by the the devices within a mechanical room.
components being labeled.
The installer uses the schematic to ensure proper
• A system service log stating the date when the system placement of the devices within the overall system, but
was commissioned; what all initial control settings still has flexibility on the exact physical placement of these
are; and what flows, temperatures and pressures were devices to best suit the available space in the mechanical
measured at locations where the designer has specified room, and ultimately where the piping circuits need to be
intended values for these parameters. This log should routed to reach the heat emitters.
also include a description of the fluid used in the
system, and any chemicals added to that fluid. It should
For example, some of the PEX tubing circuits connecting
be updated to describe any service or adjustment to the
the panel radiators to the manifold station in figure 2-2
system, the exact nature of that work, and the date/time
may be routed downward from the manifold station rather
it was performed. The log should be maintained both
than upward as shown in the schematic. The manifold
onsite, in a labeled binder in the mechanical room, and
station may be mounted at a different elevation compared
offsite where it can be easily referenced.
to where it is shown in the schematic. The expansion tank
may not be installed at an elevation below the bottom of
It is extremely important that any individuals involved with the buffer tank, but it will still be connected to the piping
the system record any changes made to any operational entering the lower right side of the tank.
settings. Examples would include settings on electrical/
electronic controllers; adjustment of mechanical valves
Notice that several major components, such as
for balancing or mixing; adjustments to circulator
the circulators, heat exchanger and temperature
speeds; or changes to settings within devices having
sensors shown in figure 2-2, have been identified with
their own embedded controllers, such as boilers, heat
abbreviations such as P1, P2, S1 and HX1. These
pumps, or other heat sources or chillers.
abbreviations can be used in other documents, such
as an electrical schematic or description of operation.
Any changes should be communicated to all those They allow someone to “cross reference” between these
who have access and authority to make changes to different parts of the documentation package.
settings in the system, including the owner, installer,
commissioning agent, designer, or those performing
In many cases, the abbreviations are selected by the designer.
any type of system monitoring. A lead person (typically
For example, a given circulator could have abbreviations
the system designer) should approve any changes to
such as P1, P-1, C1 or C.1. Designers that work for the
system settings before they are made, and maintain
same company should standardize abbreviations so that
accurate records of all such changes. A common tool
all documents produced use a consistent format.
for maintaining such a log would be a spreadsheet file
that can easily be emailed to anyone having access to
the system. It is extremely important that the component abbreviations
used for devices within the same system be consistent
from one document to another, or from one portion of a
Examples of Documentation
drawing to another. Thus, if circulator (P1) provides flow
There are several parts to a complete documentation to the air-to-water heat pump on the piping schematic, it
package. Each will be introduced and briefly discussed. can be properly wired for this task based on the electrical
Later sections will provide additional details on each part. schematic, and its operation can be properly narrated
within the description of operation.
7
Piping schematics can be drawn by hand or using ELECTRICAL SCHEMATIC
many different types of software. The latter approach Another important part of good system documentation is
offers many advantages. an electrical schematic showing all electrically operated
devices within the system, how they are interconnected,
Section 3 will discuss how to make piping schematics and how they are powered. Figure 2-3 is an electrical
in greater detail. schematic that corresponds to the piping schematic
shown in figure 2-2.
Figure 2-2
Thermostatic operator
Towel
warmer
radiator
TRV
panel radiators
PEX tubing
(ETWH)
Manifold pressure
station regulated
circulator
outside (P2)
temperature
(S1)
reset
controller
(HX1)
(S2)
(P3)
(P1)
OUTSIDE
INSIDE
8
An electrical schematic shows the interconnection of symbols to the left of these circulators represent normally
electrically operated devices within the system. It is not open relay contacts. The normally open relay contact
a scale drawing, nor does it show the exact physical within each rung must close to transfer line voltage to
location of electrical devices when they are installed. its associated circulator and turn it on. When the relay
contact is open, no voltage is present at the circulator
The right-side portion of the electrical schematic in figure and it is off.
2-3 is drawn as a “ladder diagram.” The vertical lines
near the top represent the two conductors required for The lower rung on the line voltage portion of the ladder
line voltage: (120 VAC) on the left, and neutral on the represents the primary winding of a transformer. This
right. The main switch (MS) must be closed for 120 VAC transformer establishes a dividing point in the ladder
voltage to be present below the switch. diagram. All rungs above the transformer, including the
transformer’s primary winding, operate at line voltage.
Any horizontal “rung” connected across these two All rungs below the transformer, including its secondary
vertical lines represents a portion of the electrical system winding, operate at lower (a.k.a. “secondary”) voltage.
that connects across line voltage. In this system, the two Many HVAC control systems have transformers that
circulators identified as (P2) and (P3) are shown in the produce a secondary voltage of approximately 24 VAC.
line voltage portion of the ladder diagram. The device
The two smaller portions of the
drawing, seen at the left, show wiring
Figure 2-3 for a specific make and model of
heat pump, and specific wiring for a
240 VAC / 30 amp
tankless electric water heater. These
L1 L2 N L1 N two devices are supplied by their
120 VAC / 15 amp
own dedicated electrical circuits, and
main
(HPD) switch
thus not part of the ladder diagram.
(MS) However, they are part of the overall
control system. The relay contacts
designated as (RH1-1) and (RH1-2),
(HP) are wired to specific terminals in the
L
(P1) heat pump, and contacts associated
N
(RH2-1)
(P2) with relay coil (RH2) are seen in the
Solstice
Extreme
ladder diagram. The labeling is the
heat pump only indication of the relationship
between the coil and contacts of
17
18
15
16
(Rdhw-1)
(P3)
a given relay, and thus is critically
important. The coil and all contacts of
(RH1-2 NC)
transformer
(RH1-1)
120/24 VAC
a given relay are physically part of the
24 VAC same device, but they are often shown
outdoor reset controller separately in the ladder diagram to
(ODR) keep it graphically simple. A relay
R C
wired in parallel electric tankless
(S1) (RH1) coil would have an abbreviation such
with contactor water heater
(ETWH) (S2) as (R1), and its associated contacts
coil (240 VAC)
(Rdhw) would have abbreviations such as
master thermostat R1-1, R1-2, R1-3, etc.
(T1) (RH2)
9
Some components, such as the heat exchanger (HX1) target temperature to the measured temperature at the
seen in the piping schematic, do not appear in the tank sensor (S2). If the measured temperature is a few
electrical schematic because they are not electrically degrees below the target temperature, the contacts in
operated devices. Still, their abbreviations can be used in the outdoor reset controller (ORC) close. This passes
another portion of the system documentation called the 24 VAC to relay coil (RH1). Contact (RH1-1) closes and
description of operation. (RH1-2 NC) opens to turn on the air-to-water heat pump
in heating mode. Circulator (P1) is turned on by an
Section 4 will cover electrical schematics in more detail. internal relay in the heat pump.
10
Figure 2-4
COMPONENT SCHEDULES When radiant floor heating is used, each tubing circuit
The most common way to call out the makes and models should be drawn, measured and labeled on the floor
of specific components on mechanical system plans plan. A table should be constructed listing all the tubing
is through use of a “schedule.” Examples of hydronic circuits by a unique designation and giving the length of
system components for which often include: each circuit. Figure 2-5 shows an example.
Total: 899'
ancillary information such as
pipe size, flange requirements,
function, electrical data,
R
dimensions, heat output, flue
size, etc. Circuit 3: 263+10=273'
PANTRY
CLOSET
KITCHEN
D BATH
MASTER
WOOD
BEDROOM
separate plan sheet.
LIVING
11
When panel radiators, fin-tube baseboard, fan-coil leaving flexibility to make slight adjustments to the
convectors or other pre-built heat emitters are used, routing as needed to avoid unforeseen details such as
they should be shown on a scale floor plan and structural headers, steel beams or other mechanical/
identified. The approximate routing path of tubing that plumbing hardware that may already be placed when
supplies each heat emitter can also be shown. This the hydronic piping is installed. Figure 2-6 shows an
gives the installer a guideline for pipe routing, while example.
Figure 2-6
2 circuit manifold station in
mechanical room
12
3. TOOLS AVAILABLE FOR DOCUMENTATION Figure 3-1a
SKETCHINg
For decades, schematics for heating and cooling systems
were created by hand, usually on a drafting board
or graph paper. Although more time consuming than
present-day software-based drawings, these documents
accomplished their purpose, even in situations where
complex systems were involved.
13
able to create sketches or drawings that simply can’t be • It requires access to some means of reproducing
replicated by hand. the original drawing into “blue line” prints that can be
physically mailed to those involved in the project.
Regardless of the sketching/drawing tool used, designers
need to continually practice and refine their ability to quickly • Errors or changes to the design require erasing and
create sketches as a starting point for communicating redrawing, which can be time consuming and messy.
technical ideas. Major changes often require a completely new drawing.
Figure 3-2
Souce: http://www.geekpac.org/page/5/
14
CAD SOFTWARE use the software on one or more computers, and for a
The time from 1980 through the end of the 20th century specific time (typically a month or a year). The software
was one of transition for many professionals who is accessed through a web browser such as Safari®,
produced drawings on a daily basis. The transition was Firefox®, or Google Chrome®. The user interacts with
away from traditional manual drafting to computer- the software essentially the same way as if it were
based drawing. Computer-aided drafting (CAD) quickly running on their personal computer. This approach offers
became the standard for 2-dimensional drawing in the advantages of broad compatibility across different
most engineering and architectural offices. It offered operating systems, such as Windows®, MAC OS, and
significantly increased productivity, instant deletion Linux. It also offers easy software updates, remote
of unwanted drawing details, ability to make multiple access to drawing files on a variety of Internet-enabled
iterations of a basic concept to refine the design devices, and cloud-based backup of drawing files.
(without constantly having to erase objects, or redraw
the same details over and over), ease of passing Examples of browser-based drawing software include:
drawings between multiple people, and digital storage
(rather than paper-based storage).
Software name website
When it was first introduced, CAD software was
expensive and often unaffordable by smaller firms or SmartDraw Cloud https://www.smartdraw.com
those who only needed to create occasional drawings.
Many hours of training were required to become HydroSketch www.hydronicpros.com
proficient with early-generation CAD software. Top-
end computers with specialized graphic cards, math
coprocessors, lots of memory and large hard drives
were also required for early-generation CAD software Figure 3-4 shows an example of a piping schematic
to operate to its full potential. Once the drawing was created with HydroSketch.
created, it still needed to be transferred to paper using
expensive peripherals such as multiple pen plotters. At
the time, very few small businesses, such as heating Figure 3-4
contractors or small engineering firms, could afford the
software, hardware and training necessary to implement
CAD-based drawing into their workflow.
15
Figure 3-5
Figure 3-5 shows an example of LoopCAD® software that monitor at the new zoom level, but always retaining its
is used for automatically creating circuit layout drawings exact mathematical definition. When the view shown on
for hydronic radiant panel systems. the monitor running a vector-based drawing program is
zoomed in, the object, or portions of the object being
viewed, retains a crisp and precise appearance. Lines
VECTOR-BASED vs. PIxEL-BASED DRAWINg joined at their end point remain precisely joined at those
SOFTWARE points regardless of the level of zoom. Nearly all CAD
There are hundreds of computer graphic software software uses vector-based drawing.
packages available. They can be loosely categorized as
either vector-based or pixel-based.
Because the objects created in vector-based software
are mathematically defined, the software can quickly
Vector-based software creates drawing objects that determine geometric properties such as the center of a
are mathematically defined and maintained within circle or rectangle, or, for example, find a point that is
the software. For example, a simple line segment is exactly 1/5 of the length of a line from its endpoint. The
a drawing object having a precise beginning and end precise geometry used in vector-based drawing allows
coordinate. The precise mathematical definition of this operations such as precisely rotating an object, drawing a
line object is used by the computer to draw it on the line at a precise angle or instantly determining the area of
monitor based on the current zoom level being viewed. If a complex shape. Such operations, although often hidden
the zoom level is changed, the mathematical description beneath the surface of the software’s user interface, allow
of the line object allows it to be instantly redrawn on the vector-based drawing software to provide precision far
16
Figure 3-6a when applied to drawings. The primary limitation is that
pixel-based graphics appear to become “grainy” when
the view is zoomed in. That’s because there are only
so many pixels to represent the image. Zooming into a
view reduces the number of visible pixels, and thus what
might appear to be smooth contours or precisely shaped
objects at normal resolution become less precise.
17
Figure 3-8 Many manufacturers of equipment for building systems,
including Caleffi North America, offer BIM files for of
their products. These files can be downloaded into BIM
software, such as the Autodesk Revit® package, and
then placed within the mechanical or plumbing systems
in the building. An example of a 3-dimensional BIM model
of a Caleffi hydraulic separator is shown in figure 3-8.
Figure 3-10b
1.2.20 Conventional boiler with zone circuits and zone DHW production
18
These drawings are offered as guidelines
Figure 3-11 for installers. They show what is
considered good practice for application
of Caleffi hardware, as well as other
components. However, it is impossible
to know the exact circumstances in
which these drawings might be applied,
or the specific code requirements at the
location where a system based on these
drawing may be installed. Those using
these drawings must determine any
specific requirements related to a given
installation, or the code requirements
at the installation site, and make any
necessary modifications to the system
configurations shown in these drawings.
19
4. CREATING PIPING SCHEMATICS These symbols can be organized into a symbol legend,
such as shown in figure 4-1.
Piping schematics are used to show the relative
placement of components within an overall hydronic Having the symbols ready to go greatly speeds the
system. A typical hydronic system schematic would drawing process. It allows designers to focus on the
show all heat sources and all heat emitters in the system. system, rather than be distracted when the need for a
It would also show all non-commodity components, new component symbol arises.
such as circulators, air separators, dirt separators, buffer
tanks, heat exchangers, expansion tanks, make-up water Those using CAD software to create schematics can
assemblies, mixing valves, zone valves, flow meters and either create their own symbol library using that software,
temperature sensors. or purchase a library of pre-drawn symbols in a file format
that can be imported by their CAD software.
Piping schematics are useful for design, installation and
servicing of hydronic systems. An advantage of creating one’s own schematic
symbol library is that the component symbols can
Designers can quickly conceptualize a system, and look exactly the way the person creating them desires.
perhaps create multiple variations of the system using The drawing process can also take full advantage of
piping schematics. The arrangement of components the capabilities of the CAD system that will eventually
within a piping schematic defines one or more piping be used to manipulate these symbols into a complete
circuits in the system. Designers may then analyze the piping schematic. Such capabilities include options
required thermal and hydraulic performance of these for colors, gradients, pre-drawn pipe threads or
circuits, and select hardware that allows each circuit, as fastener details, choices for line width and patterns,
well as the overall system, to perform as required. text options and more. Once they are created, the
symbols can be duplicated as many times as needed.
Installers use piping schematics to guide them during This creates a distinctive and consistent appearance
installation. Although the schematic does not show the between schematics coming from the same designer,
exact placement of a component within a mechanical room, or the same firm. The schematic symbol library can
it does show how they must be placed relative to each also be expanded over time as new devices become
other. Experienced installers develop skill in placing the available.
components in a neat and efficient manner, while keeping
them in the proper relative positions shown on the schematic. The main disadvantage of creating a symbol library is
that it requires time and effort. Many hours of drawing
Piping schematics are also very helpful in troubleshooting time are needed to create an extensive symbol library
systems. They provide a fast way to communicate the in which the symbols are well detailed, such as those
overall system layout, especially for those not already shown in figure 4-1. If the person making the schematic
familiar with the system, and without having to trace is not skilled in using the CAD software, or if the projects
down numerous piping circuits to determine the extent for which the schematics are needed require immediate
of the system. results, commercially available symbol libraries can be
purchased.
SCHEMATIC SYMBOLS
The degree of detail shown on a schematic symbol
Piping schematics are drawn by placing symbols that
can vary. The symbol could be a highly simplified
represent various components onto a drawing “canvas”
representation of the component and look completely
(e.g., paper or the drawing space seen on the display
generic, or it could have close resemblance to a specific
while using CAD software).
product. Figure 4-2 shows some examples of schematic
symbols representing a micro-bubble air separator.
Since CAD-based drawing represents the state-of-the-art
approach to schematic drawing, the discussion that follows
The very simple/generic symbol on the far left is usable,
will assume that CAD-based drawing is being used.
but lacks visual interest. Without already knowing that
it was drawn to represent an air separator, or being
Whenever possible, the piping symbols used in schematics familiar with the general shape of such a device, it is
should be drawn before work begins on a schematic. not evident what this symbol represents (e.g., maybe
20
Figure 4-1
3-way motorized
circulator mixing valve DISCAL central
air separators
backflow
spring-loaded
VENT
preventer
gate valve check valve
pressure-
reducing distribution
globe valves purging valve valve station
cap metered
thermoelectric ThermoCon
balancing thermostatic
zone valve buffer
valve radiator valve
(2 way) tanks (4 sizes)
dual isolation
diaphragm-type valve for
brazed-
expansion tank panel radiators
plate
heat differential
exchanger pressure
bypass valve
DIRTCAL
panel radiator dirt
with dual
isolation valve separators
Comp.
DIRTMAG
dirt
separators Hydro
SEP4
Separator
heating mode
reversible HydroCal
water-to-water Separator
heat pump
DISCALDIRT DISCALDIRTMAG
reversing conventional boiler HydroCal
valve air & dirt air & dirt
Separator
separator separator
evaporator
condenser
FLOCAL DISCALDIRT
balancing air & dirt mixing units
TXV valve separator (2 configurations)
QuickSetter
balancing solar
valve w/ circulation
flowmeter station
motorized
ball valve
(2 way)
Modulating / condensing boiler
high-temperature high-
solar air vent temperature
ThermoBloc™
solar
high-temperature expansion
shut-off valve for tank
wood-fired boiler solar air vent
indirect water heater (with trim)
21
When drawing schematic symbols, keep in mind that they
Figure 4-2 are usually shown as small objects, especially when an
entire system schematic is printed to standard 8.5 x 11-inch
paper. An excessively high level of detail on the symbol,
especially for small components, may be lost when the
symbols are viewed on screen, or printed on devices that
may not have the high resolution to show all details.
The schematic symbol at the far right is drawn with Schematic symbols for components should also be
detailing and color to resemble a Discal air separator from drawn in approximate proportion to their physical size.
Caleffi. It includes additional detail, such as the label. For example, an air separator for a 1.25” pipe should not
be the same size as a typical cast iron boiler. The symbol
Figure 4-3
22
for a thermal storage tank would be significantly larger binds them together as if they were a single object.
than the symbol for a 2” ball valve. That new object can then be moved, rotated, duplicated
or scaled like any other drawing object. If the grouped
Figure 4-3 shows a photo of some hydronic components object needs to be modified, it can be “ungrouped” using
assembled as part of a system. It also shows a schematic a different command in the CAD software. Grouping and
representation of these components. Note that the size ungrouping is a very powerful technique for expediting
of the schematic symbols is approximately in proportion schematic drawings, which are characterized by repetitive
to the size of the actual components. This lends clarity to use of symbols.
the schematic.
Figure 4-4
DRAWING TECHNIQUES
Once a schematic symbol legend is created,
it can be used to make a piping schematic.
The exact process used varies from one CAD
system to another. Some CAD systems have
a library feature where each symbol can be
selected from a scrolling list or a floating
symbol palette by name, or by clicking on an
icon resembling that symbol. In other CAD
systems, the person making the schematic
may choose to bring the entire symbol
legend, such as shown in figure 4-1, into the
drawing space and select symbols from that
grouping as needed. In this case, it’s best to VENT
23
Figure 4-5
There are many ways to assemble component symbols a major component such as a heat source, attach one or
to create a complete piping schematic. Opinions vary more line segments to the outlet connection that would
on the “best” approach, which in many cases is highly represent piping, add another component such as an air
dependent on the software being used. separator, add another line segment representing more
piping, and so forth. While this method is somewhat
One method is to “build” the schematic similar to how intuitive, it isn’t necessarily the most productive
the actual components would be assembled. Start with approach, because the line segments are “broken” at
24
Figure 4-6
desired
appearance
Fewer line segments. Components are on a drawing layer
above the line so they can be placed "on top" of line, and
cover up the line. Easy to move components along line
without having to repair line.
OK
preferred
each component. If a component has to be moved, even is drawn or placed on layer 2. If layer 2 is selected to
slightly, the lines connected to it also have to be modified be on top of layer 1, the circulator symbol on layer 2 will
to provide a visually unbroken path. cover up the portion of the line segment on layer 1, which
it overlaps. The concept is similar to placing a sticker on
A preferred approach is to use a feature found in most a sheet of paper. The sticker covers up the paper beneath
CAD software called “layers.” Think of a layer as the it. If the sticker is moved, the area of paper that was
digital equivalent of a thin, transparent sheet having the covered becomes visible.
overall size of the drawing. A drawing can have many
layers, perhaps over 100 if needed. These layers can be Schematic symbols with a non-transparent (100%
“stacked” on top of each other, and their stacking order opacity) color, and placed on a layer above the lines, will
easily changed. simply mask over the portion of the line under them. This
allows the symbol to be easily moved along the line, if
Assume an object, such as a line segment, is drawn on necessary, without having to later repair any gap in the
layer 1. Then another object, such as a circulator symbol line. These two methods are compared in figure 4-6.
25
Whenever possible, piping schematics should be drawn • The width of lines should correspond to pipe size. The
from left to right, based on the flow of heat through the larger pipe sizes in the system should be represented by
system. For example, if a boiler is the heat source, its wider lines in the piping schematic, and vice versa.
preferred location is on the left side of the schematic.
Other components through which heat passes would • Use a “fillet” (e.g., a circular arc) at locations where
then be placed to the right of the boiler. The heat piping changes direction. This “softens” the appearance
emitters, where heat leaves the system, would ideally of the schematic and makes it more closely resemble the
be shown near the right side of the schematic. More assembled piping.
complex schematics, especially those that show many
heat emitters, may require those emitters to be shown
above or below other components. • Minimize locations where piping crosses over other
piping. When piping has to crossover other piping,
include a semicircular “bridge” to clearly indicate the
Several other guidelines apply when creating piping crossover (rather than a possible joining of the pipes
schematics: where they cross).
• Whenever possible, lines that represent piping should • Minimize changes in direction in lines between any
be drawn horizontally and vertically. Avoid angled lines two points on the schematic. Unnecessary changes in
whenever possible. If an angled line needs to be drawn, direction add complexity to the schematic, making it
limit it to a 45º angle. harder to understand.
Figure 4-7
change in pipe size
indicated by change
in line width
VENT
26
• Keep the visual density of the drawing consistent (e.g., schematic or in a schedule (i.e., a circulator schedule, or
don’t crowd components tightly together in one area, a valve schedule) should be labeled.
while spreading them significantly farther apart in other
areas of the schematic.) There is no widely accepted standard for labeling,
but there may be a standard established within a
• Always keep some white space around individual company so that all drawings are consistently labeled.
components. Don’t place symbols so that they overlap Figure 4-8 shows a piping schematic with component
or touch each other, unless they will be physically joined abbreviations shown in a different color from those
when installed. An example of the latter would be two used elsewhere in the drawing.
circulators joined in a close-coupled series arrangement.
The circulators are labeled as (P1), (P2), etc. The
• Always keep some space between components and temperature sensors are labelled as (S1), (S2), etc.
changes in the direction of lines. An outdoor reset controller is labelled as (ORC). Many
of the labeled components will be referenced in the
• Whenever possible, make use of color to help identify electrical schematic and the description of operation.
the relative temperature of the piping during normal
system operation. Use red to indicate piping that carries Finally, it is important to include a piping symbol legend
“hot” fluid, and blue, purple, or lighter shades of red to with any piping schematic. On larger drawings, the legend
indicate piping carrying “cooler” fluid. This helps the can be placed in a corner of the drawing sheet on which
person looking at the schematic understand what should the piping schematic appears. When the schematic is
be occurring during normal operation. distributed on a smaller sheet, a symbol legend, such
as shown in figure 4-1, can be included as a separate
These guidelines are shown in the piping schematic of sheet. The symbol legend should show all symbols that
figure 4-7. are used in the schematic. It can also include symbols
that are not used in the schematic. In many cases, the
symbol legend can be the same for all piping schematics
Once the all the symbols have been placed in the produced by a given designer or firm.
schematic, it’s time to add labels. In general, any
component that might be referred to in the electrical
Figure 4-8
outdoor
temperature
(S2) sensor
OUTSIDE
INSIDE
zone (T1-T8)
thermostats
outdoor pressure
(ORC) reset regulated
controller variable
speed
(R1) circulator
manifold
valve
actuators
(P3) (VA1-VA8)
antifreeze
protected
zoned radiant ceiling panels
circuit (S1)
(HX1)
(P1) (P2)
make-up water
(ET2)
27
5. ELECTRICAL SCHEMATICS prevents an electrical signal from passing a given point
in the circuit. A closed contact allows the signal to pass
All modern hydronic heating and cooling systems use through. In the context of the controls for hydronic
electrical components. Many use multiple circulators, systems, switches are considered to be manually
multiple controllers, and also have an assortment of other operated devices.
electrically driven devices such as zone valves, low water
cutoffs, motorized mixing valves or flow switches. This RELAYS
electrically powered hardware requires proper selection, Relays are electrically operated switches. They can
proper installation wiring and proper adjustment. be operated from a remote location by a low voltage
Preparing an electrical schematic for the system is and low current electrical signal. They consist of two
essential in accomplishing these requirements. basic subassemblies: the coil and the contacts. Other
parts include a spring, pendulum and terminals. These
The purpose of an electrical schematic is to show how the components and the basic operation of a relay are
electrically powered devices in the system are powered illustrated in figure 5-1.
and interconnected. The devices that are typically shown
in an electrical schematic include switches, relays,
circulators, zones valves, motorized mixing valves, flow Figure 5-1
spring enclosure
switches and “embedded controllers.” The latter refers to
pivot
devices such as mixing valve controllers, outdoor reset coil
controllers or multi-zone relay centers. These devices pendulum
have pre-built self-contained circuits that allow them to wire
provide specific functions. Many of these controllers also normally closed!
require specific adjustment to settings or DIP switches. contact (N.C.)
These controllers can only provide their intended
functions if they are properly interconnected with other
electrical devices in the system and properly set.
coil!
terminals
Designing an electrical control subsystem for hydronic common terminal
heating and cooling requires a basic knowledge of line normall closed terminal
normally open!
contact (N.O.)
voltage and low voltage circuits. The most commonly used normally open terminal common contact
line voltages in residential and light commercial systems
are 120 VAC and 240 VAC single phase. The most common
low voltage is 24 VAC. However, some controllers also
"Normal" mode: No
require use of 0-10 VDC and 4-20 milliamp circuits. voltage is applied to
coil (terminals A and
B). Spring holds
Many of the control functions needed in hydronic systems pendulum so the
are “on/off” switching. For example, a zone valve is common contact
touches the normally
powered on, often by 24 VAC, to open it. When power closed contact. Current
is removed, the valve closes using an internal spring. can ßow from terminal
1 to terminal 2.
Zone circulators are turned on and off by applying or
removing 120 VAC power. Many boilers and heat pumps
are turned on and off by a switch or relay contact closure. 1 2 3 A B
Because switching is so commonly used, it’s imperative
for designers to understand the terminology, and basic Energized mode:
logic used for selecting and applying switches and relays. Voltage is applied to
coil (terminals A and
This knowledge is repeated applied when constructing B). Pendulum pivots
electrical schematics. toward coil. The
common contact
touches the normally
SWITCHES open contact.
Current can ßow
All switches have one or more contacts. These contacts from terminal 1 to
must be either open or closed. There is no intermediate terminal 3.
position between open or closed. An open contact 1 2 3 A B
28
The spring holds the contacts in their “normal” position. the schematic symbols for switches and relays having the
The word “normal” implies that the coil of the relay is same number of poles and throws.
not powered. When the proper voltage is applied to
the coil, and current flows through it, the coil creates Many of the electrical schematics used for documenting
an electromagnetic field. This field creates a force that hydronic heating and cooling systems use these symbols.
pulls the “common” contact, which is attached to the
pendulum, from its “normal” position to its other position. Although the coil and contacts associated with a relay are
This movement slightly extends the spring inside the relay. all contained in the same physical device, they are often
In most relays, this action takes only a few milliseconds. A
click can be heard as the contacts move from one position
to the other. When voltage is removed from the coil, the Figure 5-2
magnetic field collapses, and the spring pulls the contacts
back to their de-energized (e.g., “normal”) position. contact designation switch contacts relay contacts
!
Relay contacts are classified as normally open (N.O.), or Single Pole
normally closed (N.C.). A normally open contact will not Single Throw! pole 1 pole 1
!
allow an electrical signal to pass through while the coil SPST
of the relay is off. A normally closed contact will allow an
electrical current to pass through when the coil is off.
!
Double Pole pole 1 pole 1
The coil in a relay is designed to operate at a specific Single Throw!
voltage. In heating systems, the most common coil ! pole 2 pole 1
DPST
voltage is 24 VAC. Relays with coil voltages of 12, 120,
and 240 VAC are also available, and occasionally used in
HVAC systems. Relays with coils designed to operate on
! pole 1 pole 1
DC voltages are also available, although less commonly Triple Pole
used in HVAC control systems. Single Throw! pole 2 pole 2
! pole 3 pole 3
3PST
POLES & THROWS
Switches and relays are classified based on their poles !
and throws. Single Pole pole 1
Double Throw! pole 1
!
The number of poles is the number of independent and SPDT
simultaneous electrical paths through the switch or relay.
Most of the switches and relays used in heating control
systems have one, two, or three poles. They are often ! pole 1
Double Pole
designated as single pole (SP), double pole (DP), or triple Double Throw!
pole 1
pole 2 pole 3
29
shown in different parts of an electrical schematic. This is Normally open contacts are more common in the types
done to simplify the schematic. There are often multiple of electrical schematics used to document hydronic
relay coils and multiple relay contacts in the electrical systems. To ensure that a normally closed contact is not
schematic. All the relay coils have the same schematic mistaken for a normally open contact, it is good practice
symbol. Likewise, all the normally open contacts to add the letters NC at the end of the label. For example,
have the same schematic symbol, and all the normally (R1-1 NC) in figure 5-3 implies relay coil (R1), pole #1, and
closed contacts have the same symbol. The only way to the normally closed contact.
determine which contacts are associated with a given
coil is by labeling. Such labeling is simple, but it must be HARD-WIRED LOgIC
consistent. For example, the coil of a given relay might be
One way to create operating logic for a control system
labeled (R1). If the relay only has one contact, that contact
is by connecting switch contacts, or relay contacts, in
could be labeled as (R1-1). If the relay had two contacts,
series, parallel, or combinations of series and parallel.
they could be labeled as (R1-1) and (R1-2). If it had 3
Figure 5-4 shows basic series and parallel arrangements.
contacts, they could be labeled as (R1-1), (R1-2), and
(R1-3). If the contacts in the relay are double throw (e.g.,
each contact has a common terminal, a normally open Contacts in series represent an “AND” decision. For
terminal, and a normally closed terminal), the labeling can an electrical signal to reach a driven device, all series-
be more detailed. For example, (R1-2 NC) would mean connected contacts must be closed simultaneously.
that the relay coil is (R1), the pole on that relay is 2, and
the specific contact being referenced is the normally
closed contact of pole 2. Figure 5-4
Figure 5-3
contacts in PARALLEL driven!
1 7 4 device
(R1-1 NC) pole #1
(R1-2)
2 8 5
pole #2
(R1-3)
3 9 6
pole #3
30
Contacts in parallel represent an “OR” decision. If any Ladder diagrams have two sections: the line voltage
one or more of the contacts are closed, the electrical section at the top, and the low voltage section at the
signal passes through the group of contacts to operate bottom. A step-down transformer separates the two
the driven device. sections. The primary winding of the transformer is
connected to line voltage in the upper portion of the
When switch contacts, relay contacts and contacts within diagram. The secondary winding of the transformer
embedded controllers are physically wired together in a supplies power to the lower portion of the diagram.
given manner, they create hard-wired logic. Such logic In North America, most heating and cooling systems
determines exactly how the control system functions in operate with a secondary voltage of 24 VAC.
each of its operating modes. Some operating modes are
planned occurrences, while others may be fail-safe modes An example of a simple ladder diagram is shown in
in the event a given component does not respond properly. figure 5-5. The vertical lines can be thought of as sides
of an imaginary ladder. Any horizontal line connected
between the two sides is called a “rung.” A rung
LADDER DIAGRAMS connected across the line voltage section is exposed
A ladder diagram is the preferred method for documenting to 120 VAC. A rung connected across the low voltage
the electrical interconnection of devices used in a section is usually exposed to 24 VAC. The overall
hydronic heating or cooling system. They can then be ladder diagram is constructed by adding the rungs
used for design, installation and troubleshooting. necessary to create the desired operating modes of the
system, and show how all the devices
necessary for those modes are to be
Figure 5-5 connected. The vertical lines of the
ladder can be extended as necessary
line voltage down neutral down right to accommodate all required rungs.
left side of ladder side of ladder
thermostat low voltage rung Notice that the coil and contacts of the
(switch) (T1)
same relay appear in different sections
of the ladder diagram. When more than
one relay is present in the diagram, it’s
relay coil
(R1)
critically important to use consistent
24 VAC (typical) labeling to know which relay contacts
are associated with a given relay coil.
31
It is also common to show a main
Figure 5-6 switch at the top of the ladder.
When open, the main switch
prevents any electrical signal
L1 L2 L1 N
from passing downward into the
120 VAC ladder diagram, and thus would
main totally prevent any electrical
switch components shown in the
(MS)
ladder diagram from operating.
For systems powered by 120
VAC, the main switch would be
installed in the live lead (e.g., the
left vertical line of the ladder).
heat distribution For systems supplied by 240
pump circulator
(R1-1) VAC, a double pole main switch
would be used to open both live
R W (P3) leads simultaneously.
HP - HX
circulator
(R2-1)
More complex ladder diagrams
(P1) are developed by placing
HX - tank
circulator schematic symbols for
(R2-2) additional components into
the diagram. Some of these
(P2)
components might be simple
transformer switches or relays, others might
120/24 VAC
(FS1) be special purpose “embedded
24 VAC
controllers” that provide very
specific control functions, such
thermostat
(T1) as temperature setpoint control,
(VA1)
thermostat differential temperature control
M
& valve actuator or outdoor reset control. An
example of a ladder diagram with
thermostat
several rungs and an embedded
(T2) (VA2) controller (labelled as ORC,
thermostat
for outdoor reset controller) is
& valve actuator
M
32
outdoor
Figure 5-7 temperature
sensor
(S2)
OUTSIDE
INSIDE
zone (T1-T8)
thermostats
outdoor pressure
(ORC) reset regulated
controller variable
speed
(R1) circulator
manifold
valve
actuators
(P3) (VA1-VA8)
antifreeze
protected
zoned radiant ceiling panels
circuit (S1)
(HX1)
(P1) (P2)
make-up water
(ET2)
associate specific contacts with the relay coil that Notice that the electrically driven components on the
operates them. For example, relay coil (R1) operates piping schematic have corresponding designations on
relay contact (R1-1), and relay coil (R2) operates contacts the ladder diagram. This makes it easy to cross reference
(R2-1) and (R2-2). The number after the dash indicates between the two diagrams when examining the operating
the pole number of the relay contact. For example, R2-1 logic, or troubleshooting the installed system.
designates pole #1 on relay (R2), and R2-2 designates
pole #2 on the same relay. Such designations are multi-ZonE rElaY CEntErS
critically important when interpreting the operating logic Some controllers provide all the circuitry and logic
associated with the ladder diagram. necessary to operate simple hydronic systems. One
example is a multi-zone relay center such as shown in
The single embedded controller in figure 5-6 is identified figure 5-8.
as (ORC), which stands for outdoor reset control. It’s
shown as a simple box with four terminals and two
attached sensors. This is a simplified rendering that only Multi-zone relay centers are a commonly used controller
shows the terminals relevant to this particular application. in multi-zone hydronic systems using either zone
A fully detailed symbol for the embedded controller could circulators or zone valves. In basic applications, all the
be used, but it will add to drawing complexity. circuitry and operating logic required to operate the
system is contained in the multi-zone relay center, the
zone thermostats and the heat source. In such cases,
The ladder diagram in figure 5-6 is also shortened
it is usually not necessary to draw a ladder diagram for
by omitting some redundant detailing for the zone
the system. Instead, the components that are controlled
thermostats and valve actuators, and inserting break
by the multi-zone relay center can be shown directly
lines with a note: “Zones 4,5,6,7,8 wired same as zones
connected to it, as shown in figure 5-9.
1,2,3.” This is done to conserve vertical space without
omitting unique details.
There are times when multi-zone relay centers will only
There are also some notes on the right side of the ladder be a part of an overall control system that includes
making reference to specific functions or hardware other embedded controllers and perhaps other relays or
associated with a rung. These are optional. switches. In such cases, the multi-zone relay center can
be treated as an embedded controller. Figure 5-10 shows
Figure 5-7 shows the piping schematic of the system an example.
associated with the ladder diagram shown in figure 5-6.
33
Figure 5-8
ZONE 1 R W C R W C R W C R W C R W C R W C D P POWER
AUX X X E/S T T COM T T COM T T COM T T COM T T COM T T COM COMMS
T-STAT 1 T-STAT 2 T-STAT 3 T-STAT 4 T-STAT 5 T-STAT 6
ZONE1
MASTER SLAVE
ZONE2
PRIORITY ON OFF
REMOTE ENABLE ON OFF
ZONE3
TRANSFORMER EXERCISE ON OFF
POST PURGE ZONE#1 ON OFF
ZSR106 ZONE4
6 Zone ZONE5
ZONE6
OFF
ON
Figure 5-9
space heating thermostats
DHW
aquastat
AQ1 T2 T3 T4 T5 T6
boiler AUX X X
ZONE 1 R W C R W C R W C R W C R W C R W C D P POWER
E/S COMMS
high limit T T COM T T COM T T COM T T COM T T COM T T COM
T-STAT 1 T-STAT 2 T-STAT 3 T-STAT 4 T-STAT 5 T-STAT 6
controller ZONE1
MASTER SLAVE
ZONE2
PRIORITY ON OFF
REMOTE ENABLE ON OFF
BS ZONE3
TRANSFORMER EXERCISE ON OFF
N
T T ZSR106 ZONE4
6 Zone
G ZONE5
boiler
MS
L N G
P2 P4 P6
20A / 120 VAC
circuit
P1 P3 P5
34
240 VAC
Figure 5-10 40 amp
L1 L2 L1 N
120 VAC / 20 amp
main
switch
(MS)
DHW
circulator
electric (R2-1)
(ETWH)
tankless
(P3)
water boiler
heater boiler
boiler
enable boiler to HX1
switch circulator
(P2)
ZV1
heat dump
zone valve
transformer
120/24 VAC
(X1)
24 VAC mixing
valve
(S1)
sensors
(S2)
(MV1)
ZONE 1
AUX X X
R W C R W C R W C R W C D P
E/S T T COM T T COM T T COM T T COM COMMS
T-STAT 1 T-STAT 2 T-STAT 3 T-STAT 4
POWER
ZONE 1
MASTER SLAVE
PUMP EXERCISE ON OFF ZONE 2
PRIORITY ON OFF priority off ZONE 3
AUX ON OFF
ZVR104
STATUS DURING 4 Zone
ZONE #1 DEMAND T-SAT VALVE
OFF
OFF
CALL OPEN
ON
ON
(P4)
35
Figure 5-11
36
• Specify the voltage and ampacity of the circuit that 6. Description of operation
supplies power to the control system. This should be
noted at the top of the ladder diagram. Piping and electrical schematics show the relative
placement of piping and electrical components.
• Always try to align similar components that appear However, they don’t “explain” exactly how the system
on multiple rungs. Examples include relay coils, relay should work once these components are assembled.
contacts, thermostats and circulators. Alignment As such, schematics alone are not sufficient to properly
improves the appearance of the drawing. document a hydronic heating or cooling system. Another
document, called the “Description of Operation” should
• Always indicate the secondary voltage of the transformer. be developed to provide this explanation.
• Show manually-operated switches in their open position. A description of operation is useful in several ways. First,
it forces the designer to be sure they fully understand
how the system operates, and that it is fully documented
• Always label devices in the ladder with abbreviations in the piping and electrical schematics. It also helps the
that can be cross-referenced to the piping schematic and designer spot any inconsistencies or missing details,
description of operation. especially in regards to how the system is controlled.
For example, when a description of operation is
• Always use a dot to indicate an electrical bond at a “T” written, and it describes when circulators (P1, P2, and
connection. P3) should operate, but the piping schematic shows
four circulators (P1, P2, P3, P4), it is obvious that the
description of operation is not complete, or perhaps the
necessary details for operating circulator (P4) have not
been included in the electrical schematic.
37
garage heating, pool heating, or descriptions of specialized From this point, the description of operation just continues
hardware such as a pellet-fired boiler or solar thermal to explain what happens next. For example, the next
collector subsystem, especially when that specialized sentence might say: Relay contact (R1-1) closes, passing
hardware includes an embedded controller. 120 VAC to circulator (P1). The next sentence might say:
Relay contact (R1-2) closes to complete a circuit between
The description of operation for each mode should begin the (TT) terminals of the boiler high limit controller, enabling
with an explanation of what “calls” for that mode to the boiler to operate.
commence. For example: upon a call for space heating
from thermostat (T1), 24 VAC is passed to relay coil (R1). In Notice that each sentence contains references to
this case, space heating is initiated when the contacts in specifically identified components, such as (T1), (P1), (R1-
thermostat (T1) close — a very common way, but not the 1), and (R1-2). These designations appear in the electrical
only way, of initiating heat input to a space. This sentence schematic, and in the case of circulator (P1), also in
describes the first and second actions that take place in the piping schematic. This cross-referencing allows the
this mode operation. The first action is the call for heat by person reading the description of operation to quickly
thermostat (T1), and the second action is 24 VAC being reference both the piping and electrical schematics, and to
applied to the coil of relay (R1). better understand what is accomplished by each control
(P4) (P5)
outdoor
3/4" piping
supply water
temperature (TEK261) temperature sensor
sensor
1.5" piping
(P2) (TEK156)
closely
1" piping spaced zone returns
2"size short header
tees
(keep tee as close to tank
(S4)
as possible)
(P3)
1.5" piping
(S3)
pellet boiler
PRV "ON" sensor (LWCO2)
press ga. (S5) 2nd tapping
air vent down from top
1" piping
(LWCO1)
210 gallon
(MV1)
thermal storage tank
swing
check
(P1)
make up water
38
Figure 6-2 240/120 VAC,
20amp
L2 L1 N
(PBD)
L N
120 VAC / 20 amp
main
(LWCO1)
switch
(MS) (LWCO2)
(OBD)
(S5) (S6)
(X1)
OIL BOILER
PELLET
24 VAC T T C1 C2 N L
BOILER
2-stage outdoor
Set high limit
reset controller
(P1) controller to 180 ºF
(TEK 261)
(MV1)
5 6
(P3)
boiler demand
1 2
11 12
thermostats
boiler stage 2 (S1)
(T1) (T2)
9 10
(S2)
boiler stage 1
multi-zone (P2)
(X X)
relay center
L N L N 3 4 (S3)
(S4)
2 1
(MZRC)
(TEK156)
(P5) ∆T controller
(P4)
zone circulators
action being described. It is very important to make 2. Can a service technician with a basic knowledge of
frequent references to specifically identified components hydronics, but who has no previous experience with the
when writing a description of operation. Likewise, it is system, understand how that system should operate?
very important to consistently and accurately label these
components in any schematic where they appear. Figure 6-1 is a piping schematic for a specific system in
which a pellet boiler and associated thermal storage tank
Keep in mind that there is no single description of are being added as the primary heat source, while the
operation that is “right,” while all other variations on that existing oil-fired boiler is retained for supplemental heating.
description are “wrong.” Different designers will inevitably
word their descriptions of operation differently. That’s Notice the abbreviations for components such as
fine. The two questions by which to judge the suitability circulators, mixing valve, and sensors.
of a description of operation are:
Figure 6-2 shows the electrical schematic for this system.
1. Is it sufficiently detailed that an installer with a basic
knowledge of hydronics can assemble and commission
the system as intended? The following is a description of operation for this system.
39
DESCRIPTION OF OPERATION: The oil-fired boiler continues to operate along with
SYSTEM POWER: The control system, oil-fired boiler, circulator (P2) until and unless the return water
and all circulators other than (P1) are powered by a 120 temperature measured at sensor (S4) increases to within
VAC/20-amp dedicated circuit. The pellet-fired boiler, 2ºF below the temperature at the upper thermal storage
circulator (P1), and motorized mixing valve (MV1) are tank header, measured at sensor (S3). If this 2ºF differential
powered by a dedicated 240/120 VAC/20-amp circuit. occurs, the contact in the (TEK156) opens, turning off
circulator (P2) to prevent heat from the oil-fired boiler
PELLET BOILER OPERATION: The pellet boiler is from being inadvertently added to thermal storage. When
enabled to operate on its own internal controller whenever the temperature at sensor (S3) increases due to pellet
the pellet boiler disconnect (PBD) is closed, and water boiler operation so that it is again 5ºF or more above the
is detected by the low water cutoff (LWCO1). The pellet return water temperature at (S4), circulator (P2) will again
boiler fires whenever the upper tank temperature sensor be turned on to move heat from thermal storage into the
(S5) drops to 150ºF or less. It continues to fire until the distribution system. As long as the second stage contacts
lower tank sensor (S6) reaches 175ºF. This operation in the (TEK261) controller are closed, the oil-fired boiler
continues 24/7, and is completely under the control of will continue to fire, whether or not the thermal storage tank
the pellet boiler, and not dependent on the status of any circulator (P2) is operating. This coordinated operation of
heating zone. The pellet boiler turns on circulator (P1), the heat sources continues as long as a demand for heat
and manages operation of the 3-way motorized anti- from either zone thermostat (T1) or (T2) is present, or until
condensation mixing valve (MV1). the supply water temperature at sensor (S1) climbs to
5ºF above the current target supply temperature, at which
SPACE HEATING: When either zone thermostat (T1) or time both first and second stage contacts on the (TEK261)
(T2) calls for heating, the associated zone circulator (P4) open, turning off circulator (P2), the oil-fired boiler and
or (P5) is turned on by the multi-zone relay center (MZRC), circulator (P3).
and the isolated relay contact (X X) in the multi-zone
relay center closes. The closed (X X) contact passes 24
VAC to the “boiler demand” terminal (#1) of the (TEK261)
controller. When the (TEK261) receives the 24 VAC boiler
demand, it boots up and measures the current outdoor
temperature at sensor (S2). It uses this temperature, along
with its settings, to calculate the current target water
temperature at the supply sensor (S1). It then compares
the measured temperature at sensor (S1) to the calculated
target temperature. If the measured temperature at (S1)
is 5ºF or more below the calculated target temperature,
the first stage contacts in the (TEK261) close. This passes
120 VAC to the normally open contact in the (TEK156)
differential temperature controller. If the temperature at the
upper header of the thermal storage tank, measured by
sensor (S3), is at least 5ºF above the temperature on the
return side of the distribution system, measured by sensor
(S4), the normally open contact in the (TEK156) closes to
supply 120 VAC to circulator (P2). Circulator (P2) moves
heated water from the upper thermal storage tank header,
and the pellet-fired boiler if it is operating, to the closely
spaced tees in the distribution system.
40
7. ADDITIONAL DOCUMENTATION is shown in figure 7-2, along with the corresponding circuit
layout drawing.
The previous three sections have discussed the need for a
piping schematic, an electrical schematic and a description Some CAD programs have built-in features for creating
of operation as the primary means of documenting the schedules. Another option is to use spreadsheet
design of a hydronic system. This section discusses software to quickly build the table, and if necessary,
additional means of conveying information related to perform edits to that table as the design is developed.
design, installation and future servicing of hydronic Once the schedule is finalized, it can be copied and
systems. These include: pasted into the CAD drawing file as a JPEG, PDF, or
other compatible file format.
• Component schedules
• General drawing notes gENERAL DRAWINg NOTES
• Drawings for specific installation details Due to space limitations, it’s usually not possible to
• Photos of intended installation details show all the information on how the system should be
installed directly on the piping or electrical schematics.
• System service log
On some projects, this additional information is presented
• System binder as detailed specifications, following the CSI (Construction
Specifications Institute) Master Format. However, on
COMPONENT SCHEDULES smaller projects this information can be conveyed using
The term “schedule,” as used in the context of general drawing notes that describe expected details that
documentation, refers to a listing of individual devices that often occur at many locations within the system. The text
all fit into a category. For example, a circulator schedule below is an example of general drawing notes applying to
would be a listing of all circulators in the system. Each the hydronic piping in a specific system.
circulator would be identified by the same abbreviation
it has in the piping schematic, electrical schematic and gENERAL PIPINg NOTES:
description of operation. An example of a circulator 1. All rigid tubing used for space-heating circuits shall be
schedule is shown in figure 7-1. type M copper soldered with 50/50 solder.
2. All copper tubing used for potable water shall be type L
In addition to the abbreviation used to identify the joined with non-lead solder.
circulator, and the specific make and model, the 3. All tubing in the mechanical room shall be supported on
circulator schedule can list supporting information Unistrut® or equivalent channel/clamp system.
such as the type of flanges to be used, the motor speed 4. Do not mount any electrical hardware below servicable
setting, if the circulator is to have an internal check piping components, including valves or circulators.
valve, the voltage the circulator operates at, and the 5. Provide brass isolation flanges with integral ball valves
amperage required at full load. on all circulators.
6. Provide a minimum of 10 pipe diameters of straight pipe
The purpose of a schedule is to list information that is too on the inlet side of all circulators.
lengthy or detailed to be listed near a component on the 7. Provide a minimum of 10 pipe diameters of straight pipe
piping or electrical schematics. upstream of all check valves.
8. Provide a minimum of 10 pipe diameters of straight pipe
upstream of all flow meters or balancing valves.
Other schedules can be developed for groups of similar 9. Zone valves shall be Caleffi 3/4” CxC, normally closed,
components, such as circuit-balancing valves, heat 24 VAC, 4-wire.
emitters or radiant panel circuits. An example of the latter
Figure 7-1
CIRCULATOR SCHEDULE:
Circulator Circulator Location Circulator model circulator trim notes
P1 earth loop circulator Grundfos UPS26-150 (speed 3) 1.25” webstone isolation flanges remove internal check valve if present
P2 heat pump to buffer tank Grundfos alpha in UPS 15-58 FC speed 3 mode 1” webstone isolation flanges circulator must have internal check valve
P3 future cooling circulator NOT CURRENTLY SPECIFIED N/A N/A
P4 boiler circulator Grundfos alpha in UPS 15-58 FC speed 3 mode 1.25” webstone isolation flanges circulator must have internal check valve
P5 House heating circulator Grundfos alpha in auto adapt ∆P mode 1.25” webstone isolation flanges remove circulator check valve if present
P6 solar drainback circulator Taco 009 VS Solar (drainback) 3/4” webstone isolation flanges circulator must have internal check valve
P7 garage floor heating Grundfos alpha in UPS 15-58 FC speed 3 mode 1” webstone isolation flanges e circulator must have internal check valve
P8 DHW recirculation pump Grundfos UP10-16BN5 1/2” FPT connection use 1/2” ball valve on each port
41
Figure 7-2
11. All system piping (other than on the earth loop of 13. Route PVC condensate drainage piping from the
the heat pump) shall be pressure tested and washed boiler to the condensate neutralizing station, then to the
using Rhomar Hydro-Solv 9100 solution (as per Rhomar floor drain.
instructions). System shall then be thoroughly flushed 14. Wipe all solder joints and clean all residual flux from the
and filled with clean water. exterior of piping and fittings using detergent and water.
12. All system water shall be demineralized to a level of 15. Insulate all domestic hot water piping with 1/2” wall
10-30 PPM total dissolved solids. thickness closed-cell foam insulation.
42
General drawing notes can be developed to whatever
Figure 7-3
level of detail is deemed necessary. In most cases,
EARTH LOOP general drawing notes should cover the installation
details for:
CROSSECTION
Þnish grade • System piping and piping insulation
• System wiring
• Combustion appliance venting and air supply
• Specialty installation details such as earth loops for
geothermal heat pumps, or collector mounting for solar
backÞll thermal collectors.
with dozer 5 feet
or loader
DRAWINgS FOR SPECIFIC INSTALLATION DETAILS:
Some systems require specific installation details that
are easier to communicate using a drawing or a photo,
rather than through notes. As an example, figure 7-3
shows a specific installation detail, represented as a
2 feet
cross sectional drawing, for a horizontal earth loop to be
used in a specific geothermal heat pump system.
1.5 ft. 1.5 ft.
1" DR-11 Figure 7-4 shows a mounting detail for a solar thermal
3 ft. PE3608 tubing
collector, along with two photos that further illustrate
sand shown around piping
(may not be needed if soil is how the mounting hardware is to be installed.
not sharp or rocky)
nominal 500 ft of trench required Figure 7-5 shows the cross section of an “above-floor”
(use 1000 ft tubing coils to eliminate tube & plate radiant panel installation.
need for pipe fusion)
Figure 7-4
COLLECTOR MOUNTING
43
Figure 7-5
carpet, tile, or vinyl ßooring
3/8" cover sheet (plywood / cement brd.)
construction adhesive
aluminum heat transfer plate
sleeper
staples, one side only
tube heat transfer plate
hardwood ßoor nailed directly over plates slight gap (side opposite staples) tube
plywood sleeper
construction adhesive
subßoor
6" thick kraft-faced Þberglass batt insulation 6" thick kraft-faced Þberglass batt insulation
44
Figure 7-6 use router guided by template to form return bends
typical 6" x 24" aluminum heat transfer plate shown
maintain minimum 1/4" gap between plates
nailed down wood ßooring 3/4" plywood end sleeper
route tube through shallow hole in subßooring
tubing pressed down into groove in plates
plywood sleepers
maintain tubing at least 4" away from any walls
3/8" cover sheet when ceramic, vinyl, or carpet ßooring is used
Þnish ßooring
Figure 7-7
• The date when a service or
adjustment was made
• The person and associated
company who performed the
service or adjustment
• A description of the issue to
be resolved by the service or
adjustment
• A description of exactly what
was done
• A space for any additional
comments
45
A system service log can also be maintained as a as well as interpret fault codes or other specific settings
spreadsheet file. Such a file should be periodically for the more complex system components, such as the
updated based on new information that was written into boiler, heat pump, chiller or electronic controllers.
the system service log on the site.
Given that much of the documentation will be created
There is also specialized software available that enables a using software, it’s also a good idea to create a digital
service technician to enter the information using a laptop, archive of all documentation. This archive should include
tablet or smartphone while onsite. That information can PDF files of the installation and operating (I/O) manual for
then be quickly moved to a master service file maintained all major equipment. These files are readily available from
at the company doing service work. most manufacturer’s websites. This digital information
should be stored on site, on a CD or preferably on a USB
SYSTEM BINDER thumb drive. It should also be stored of-site for quick
reference when necessary.
After creating good documentation, it’s important to make
it immediately available to those who may be servicing the
system. A common approach is to prepare a system binder Information that is handwritten into the system service log
that contains the piping and electrical schematics, the should be periodically scanned, digitally photographed,
description of operation, installation details and photos, or manually entered into a spreadsheet version of the
and the system service log. It can also contain submittal system service log, and included in the digital archive.
sheets, installation manuals, or technical literature for the
major components in the system. This documentation
should be printed, ideally in color, and neatly placed in a
3-ring binder. The cover of the binder should provide the
contact information for the installing contractor, as well as
other heating professionals involved with the project. The
binder should be housed in a clear plastic wall pocket,
mounted in a location where it’s readily visible to service
personnel, as shown in figure 7-8
46
8. EXAMPLE SYSTEMS DESCRIPTION OF OPERATION
SYSTEM POWER: The boiler and multi-zone relay
This section gives examples of six hydronic systems that center (ZVR106) are both supplied by a 120 VAC/15-amp
provide space heating, domestic water heating, and in one dedicated circuit.The (ZVR106) receives power whenever
case, hydronic cooling. These systems range from simple the main switch (MS) is closed. The boiler receives power
to relatively complex in terms of the components involved. when the main switch (MS) and the boiler service switch
Each system is documented using a piping schematic, (BSS) are closed, and the low water cutoff (LWCO) detects
electrical schematic and description of operation. water present at its location in the system.
Some of these systems require specialized embedded SPACE HEATING MODE: Upon a call for space heating
controllers for functions such as operating a motorized from any of the five thermostats (T2-T6), the associated
mixing valve, or maintaining the temperature of a buffer zone valves (ZV2- ZV6) are powered on by 24 VAC
tank. A specific and appropriate controller is assumed supplied from the (ZVR106). When any powered zone
in the documentation for these systems. However, in valve reaches its fully open position, an end switch within
many cases, several other available controllers could be that valve’s actuator closes. This end switch closure
used, with only minor variations in the schematics and signals the (ZVR106) that circulator (P1) can operate.
descriptions of operation. The (ZVR106) passes 120 VAC to the system pump
terminals to activate circulator (P1). Circulator (P1) is a
variable-speed pressure-regulated circulator that has
EXAMPLE SYSTEM #1
been set for the differential pressure required when all
Figure 8-1a shows the piping schematic for a relatively five space-heating zones are operating simultaneously. It
simple multiple zone hydronic “combi-system” that serves will automatically adjust its speed as the number of active
five zones of space heating and also provides domestic zone circuits changes. All calls for space heating from
hot water using an indirect water heater. This system also any of the five zone thermostats also causes the isolated
uses a variable-speed pressure-regulated circulator that (X X) contact on the (ZVR106) to close. The (X X) contact
automatically adjusts speed based on the number of active completes a circuit through the space-heating demand
zone valves. terminals on the boiler reset controller (BRC).This enables
the boiler to fire under the control of the (BRC), which
The electrical schematic for this system is shown in figure measures the outdoor temperature at sensor (S1), and
8-1b. uses this temperature along with it settings to calculate
a target supply water temperature for the boiler. The
In this system, all coordination of the zone valves and (BRC) also measures the water temperature inside the
system pump is handled by the circuitry and settings of the boiler at sensor (S2) and compares it to the calculated
Caleffi ZVR106 multi-zone relay center. The boiler
is managed by an outdoor reset controller, which
Figure 8-1a
is assumed to be external to the boiler.
(ZV2)
(ZV3)
(ZV4)
(ZV5)
(ZV6)
VENT
(P1)SYSTEM
pump
Given that these controllers collectively provide
all the operating logic for the system, it is not
(ZV1)
necessary to create a ladder diagram. However,
it is still necessary to show how these controllers
are powered and interconnected. The electrical
schematic in figure 8-1b provides sufficient
documentation to do this. It shows that both (BRC)
the boiler and multi-zone relay center are (MV1)
powered by a common circuit. It shows the main
power switch (MS), the boiler service switch
(AQ1)
(BSS), and the low water cutoff (LWCO). It also
shows the interconnection of the controllers, all DHW
aquastat
thermostats, the DHW aquastat, the zone valves
and the system circulator. All components are low ßow resistance boiler
labeled so that they can be referenced in the
piping schematic and description of operation. indirect DHW tank
47
Figure 8-1b
15A / 120 VAC
circuit
outdoor
temperature
sensor (S1)
(MS)
(LWCO)
(BSS)
boiler reset (S2)
controller
(BRC)
space
heating DHW
boiler
(P1)
(ZV1) (ZV2) (ZV3) (ZV4) (ZV5) (ZV6)
target temperature. If the measured temperature is 5ºF DOMESTIC WATER HEATINg MODE: A call for
(adjustable) or more below the target temperature, the domestic water heating occurs when the normally open
(BRC) turns on the boiler’s burner. The burner continues contact in the tank aquastat (AQ1) closes, based on
to fire until the measured temperature of the water leaving the temperature setting of the aquastat. This closure
the boiler climbs to 5ºF (adjustable) or more above the is sensed by the (T-STAT 1) terminals in the multi-zone
current target temperature, or until all calls for heat from all relay center (ZVR106). The (ZVR106) closes a set of
space-heating thermostats (T2-T6) are satisfied. isolated contacts (Zone 1 E/S), which completes a circuit
48
Figure 8-2a manifold station 1
manifold station 2
P2
AH1
MV2
P3
P4
P6
HL1
MV4 MV3
P1
AQ1 MV1
P5
VENT
AH2
through the DHW demand terminals in the (BRC). The (ZVR106) priority = ON
boiler is now enabled to operate in setpoint mode (e.g., (ZVR106) Aux during priority = OFF
targeting a fixed upper temperature limit regardless of (ZVR106) Status during zone #1 demand/secondary
outdoor temperature). Zone valve (ZV1) is powered on. pump = OFF
When (ZV1) reaches its fully open position, its internal
(ZVR106) Status during zone #1 demand/system pump = ON
end switch closes. This is sensed by (ZRV106), which
responds by turning on the system circulator (P1). (AQ1) aquastat = 145ºF
(MV1) domestic hot water delivery temperature = 120ºF
Domestic water heating is treated as a priority load. When
a call for domestic water heating occurs, all other zones EXAMPLE SYSTEM #2
valves (ZV2-ZV6) are temporarily turned off for up to 60 The system in figure 8-2a provides space heating using air-
minutes, assuming the tank aquastat (AQ1) continues to handlers and radiant panels. The air handlers operate with a
call for domestic water heating. If 60 minutes elapses and supply water temperature of 170ºF at design load. The radiant
aquastat (AQ1) is still calling for domestic water heating, panel manifold stations operate at supply water temperatures
zone valve (ZV1) is turned off, and any space heating of 105ºF and 110ºF. The space-heating loads are all served
zones that are calling for heat are allowed to operate. through a Caleffi HydroLink. The low-temperature loads are
This operating mode continues until all space-heating supplied through Caleffi HydroMixer blocks with integrated
zone thermostats (T2-T6) that were calling for space thermostatic mixing valves. The conventional gas-fired
heating when priority operation of (ZV1) began are boiler is protected against low-temperature return water by
satisfied. Only then can (ZV1) reopen, assuming (AQ1) is a high-flow capacity thermostatic mixing valve. Domestic
still calling for domestic water heating. The thermostatic water heating is treated as a priority load.
mixing valve (MV1) is set to 120ºF to limit domestic hot
water delivery temperature. The electrical schematic for example system #2 is shown
in figure 8-2b.
CONTROLLER/VALVE SETTINGS:
(BRC) high limit = 180ºF (domestic water heating mode) As was true with example system #1, all the operating
(BRC) reset ratio = 1.5 logic for this system is contained within the multi-zone
(BRC) min. supply temperature = 140ºF relay center (ZSR106) and the boiler reset controller
(ZVR106) master/slave = master (BRC). Therefore, the electrical schematic is shown in the
same manner as for example system #1, showing power
(ZVR106) pump exercise = OFF
49
SPACE-HEATINg MODE: Upon a
Figure 8-2b
call for space heating from any of
20A / 120 VAC
circuit the four thermostats (T2-T5), the
outdoor
temperature
sensor S1
associated zone circulators (P2-P5)
MS
LWCO
are powered on by 120 VAC. The
BSS (ZSR106) also turns on circulator
boiler reset
controller
S2 (P6) to create flow between the
BRC boiler and the HydroLink.
space
heating DHW The lower temperature radiant
panel loads are supplied through
boiler
HydroMixer blocks attached to the
HydroLink. A thermostatic mixing
valve in each of the two HydroMixer
space heating thermostats
blocks modulates to maintain a
AQ1
T2 T3 T4 T5
preset supply water temperature to
each radiant panel manifold station.
50
DOMESTIC WATER HEATING MODE: A call for domestic The thermostatic mixing valve (MV4) is set to 120ºF to limit
water heating occurs when the normally open contact in domestic hot water delivery temperature.
the tank aquastat (AQ1) closes, based on the aquastat’s
set temperature. This closure is sensed by the (T-STAT 1) CONTROLLER/MIXING VALVE SETTINGS:
terminals in the (ZSR106). The (ZSR106) closes a set of
(BRC) high limit = 180ºF (domestic water heating mode)
isolated contacts (Zone 1 E/S) which completes a circuit
through the DHW demand terminals in the (BRC). The (BRC) reset ratio = 1.5
boiler is now enabled to operate in setpoint mode (e.g., (BRC) min. supply temperature = 140ºF
targeting a fixed upper temperature limit regardless of (ZSR106) master/slave = master
outdoor temperature). Circulator (P1) is also turned on. (ZSR106) priority = ON
(ZSR106) remote enable = OFF
Domestic water heating is treated as a priority load. When (ZSR106) exercise = ON
a call for domestic water heating occurs, all other zones (ZSR106) post purge zone #1 = OFF
circulators (P2-P6) are temporarily turned off for up to 60
(AQ1) aquastat = 145ºF, differential = 10ºF
minutes, assuming the tank aquastat (AQ1) continues to
call for domestic water heating. If 60 minutes elapse and (MV1) boiler inlet temperature protection setting = 130ºF
aquastat (AQ1) is still calling for domestic water heating, (MV2) supply water to manifold station 1 setting = 105ºF
circulator (P1) is turned off, and any zones that are (MV3) supply water to manifold station 2 = 115ºF
currently calling for heat are allowed to operate.This mode (MV4) DHW anti-scald setting = 120ºF
continues until all space-heating thermostats (T2-T5) that
were calling for heating when priority operation of (P1)
EXAMPLE SYSTEM #3
began are satisfied. Only then can circulator (P1) restart,
assuming (AQ1) is still calling for domestic water heating. The system shown in figure 8-3a is supplied by a mod/
con boiler, which can be called to operate in either space-
outdoor S3
Figure 8-3a temperature TRV TRV
sensor
TRV
mod/con boiler
TRV
TRV
TRV
MV2
P1
P2
P4
AQ1
main floor
manifold
S4
station
ThermoCon
buffer tank
T3
MV1
S1
outdoor
temperature basement
sensor P3 manifold
S2 station
51
Figure 8-3b 20A / 120 VAC
S3 outdoor
temperature
circuit sensor
buffer tank S4
MS temperature
LWCO sensor
BSS
mod/con
boiler
(B1)
WWSD
P1 DHW
AQ1 T3
ZSR103
3 Zone
120/24 VAC
(X1) 40 VA
P2 P3 transformer
outdoor
temperature
(R1) sensor
P4 (R1-1) (S1)
(S2) supply
temperature
sensor
(MV1)
heating mode (in which it uses its own internal reset control controller/actuator. Domestic hot water is supplied as a
logic), or setpoint temperature mode, where it seeks a priority load by an indirect water heater.
fixed high limit temperature. Space heating is supplied to
the main floor area of the building by panel radiators, and The electrical schematic for this system is shown in figure
to the basement by radiant floor panels. The latter requires 8-3b.
a significant lower supply water temperature, which is
created by a motorized mixing valve with a combined
52
DESCRIPTION OF OPERATION at sensor (S1), and uses this temperature along with its
SYSTEM POWER: The boiler and multi-zone relay settings to calculate a target supply water temperature
center (ZSR103) are both supplied by a 120 VAC/20-amp for the basement floor-heating circuits. It measures the
dedicated circuit.The (ZSR103) receives power whenever temperature of the supply water at sensor (S2) and
the main switch (MS) is closed. The boiler receives power compares it to the calculated target temperature. If the
when the main switch (MS) and boiler service switch measured temperature is below the target temperature,
(BSS) are closed, and the low water cutoff (LWCO) detects the actuator/controller rotates the shaft of mixing valve
water present at its location in the system. (MV1) to increase supply water temperature, and vice
versa. The boiler will respond to the temperature change
at sensor (S4) in the buffer tank, and fire as necessary
SPACE-HEATING MODE: When power is available to
to provide ample heated water to mixing valve (MV1).
it, the mod/con boiler continuously measures outside
When thermostat (T3) is satisfied, circulator (P3) and the
temperature at sensor (S3). When the outdoor temperature
motorized mixing valve (MV1) are turned off.
is below the warm weather shutdown (WWSD) setting, the
boiler closes an internal contact to send 120 VAC to the
remote enable terminals on the (ZSR103). With remote DOMESTIC WATER HEATING MODE: A call for domestic
enable powered, the (ZSR103) can operate the space- water heating occurs when the normally open contact
heating zones as necessary. 120 VAC from the remote in the tank aquastat (AQ1) closes, based on its setting
enable circuit is also sent to relay coil (R1). Relay contact and current tank temperature. This closure is sensed by
(R1-1) closes to provide 120 VAC to circulator (P4). The the (T-STAT 1) terminals in the multi-zone relay center
boiler fires its burner and turns on circulator (P1). The (ZSR103). The (ZSR103) closes a set of isolated contacts
boiler monitors the temperature of the water in the buffer (Zone 1 E/S), which completes a circuit through the DHW
tank at sensor (S4). It continues to fire until the temperature demand terminals in the boiler, enabling it to operate in
at sensor (S4) in the buffer tank is slightly above a target setpoint mode (e.g., targeting a fixed upper temperature
temperature the boiler has calculated based on its internal limit regardless of outdoor temperature). Circulator (P2) is
reset logic and settings, as well as the current outdoor powered on.
temperature.
Domestic water heating is treated as a priority load. When
PANEL RADIATOR HEATING: This system is designed a call for domestic water heating occurs, circulator (P1) is
so that areas of the building served by the panel radiators turned off by the boiler, and circulator (P3) is temporarily
will automatically have heated water available to those turned off by the (ZSR103) for up to 60 minutes, assuming
panel radiators whenever the boiler is not in warm weather the tank aquastat (AQ1) continues to call for domestic
shutdown mode. Circulator (P4) is on whenever the boiler water heating. Circulator (P4) remains on to deliver heat
is not in warm weather shutdown. (P4) is a variable- from the buffer tank to the panel radiators while priority
speed pressure-regulated circulator that has been set to domestic water heating takes place. If 60 minutes elapse
the differential pressure required when the thermostatic and aquastat (AQ1) is still calling for domestic water
radiator valves (TRV) on all the panel radiators are fully heating, circulator (P2) is turned off until zone thermostat
open. Heated water will flow from the buffer tank to each (T3) is satisfied. Only then can circulator (P2) restart,
panel radiator on which the (TRV) is partially or fully open. assuming (AQ1) is still calling for domestic water heating.
The speed of circulator (P4) will automatically increase The thermostatic mixing valve (MV2) is set to 120ºF to limit
or decrease based on maintaining a constant preset domestic hot water delivery temperature.
differential pressure, regardless of how many thermostatic
radiator valves are partially or fully open. If all thermostatic
radiator valves are fully closed, circulator (P4) will reduce CONTROLLER/MIXING VALVE SETTINGS:
speed to a minimum “sleep mode” level, and await the
Boiler high limit (during setpoint operation) = 180ºF
opening of one or more thermostatic radiator valves, at
which time it will increase speed as necessary. Boiler reset ratio (during space heating) = 1.0
Boiler warm weather shutdown = 55ºF (outdoor temperature)
BASEMENT HEATING: When thermostat (T3) calls for Boiler minimum water temperature (during space heating)
heating, the (ZSR103) controller turns on circulator (P3) = 100ºF at WWSD = 55ºF
and transformer (X1). Transformer (X1) supplies 24 VAC to (ZSR103) master/slave = master
the combined controller/actuator of the 3-way motorized (ZSR103) priority = ON
mixing valve (MV1). When it is powered on by the 24 VAC, (ZSR103) remote enable = ON
this controller/actuator measures outdoor temperature
53
Figure 8-4a AH3
BV3
ZVC3
AH2
BV2
HM1
ZVC2
MV1 AH1
HM2
BV1
ZVC1
outdoor HM3
temperature
electric water heater sensor S2
ZVH1
ZVH3
ZVH2
P4
P5 P3
ORC temperature
S1
sensor
P1 S3
SP1
P2
heat pump
80 gallon
ThermoCon
buffer tank
VENT
earth
loop
manifold
54
Although the air handlers are configured for
Figure 8-4b chilled-water cooling, the owner has asked for
120 VAC
20 AMP
the ability to operate each air handler in “fan-
G N L1
240 VAC
30 AMP only” mode, while the system is in either heating
L1 L2 N G
cool
cool
circulator
heat
T3 RC
RH
W
During cooling mode, the heat pump operates to
G
Y
R4
maintain the water temperature in the buffer tank
between 45 and 60ºF.
ELECTRICAL SCHEMATIC
The electrical schematic for the system is shown
in figure 8-4b. It is a hybrid drawing that uses
P3 some elements of ladder diagrams, as well as
ZVH1 ZVH2 ZVH3 point-to-point wiring between the multi-zone
relay centers and other controllers.
DESCRIPTION OF OPERATION
SYSTEM POWER: The control system receives
power from a 120 VAC/20-amp circuit whenever
ZVR103 (C)
the main switch (MS) is closed. This circuit
COOLING powers all controls, circulators (P3) and (P4), all
three air handlers, thermostats and relays. The
heat pump receives power from a dedicated
240/120 VAC/30-amp circuit whenever the heat
pump disconnect (HPD) switch is closed. The
P4
heat pump circuit also powers circulators (P1)
ZVC1 ZVC2 ZVC3 and (P2).
55
MODE SELECTION: The mode selection switch (MSS) If the mode selection switch is set for heating, and the fan
is a 3-pole double throw manual switch. It must be set to selector switch on any thermostat is set to “ON,” 24 VAC is
“HEAT” for heating mode operation, or “COOL” for cooling present on the (G) terminal of that thermostat. This 24 VAC
mode operation. If the (MSS) is set to OFF, the system is passed to the coil of a relay (R2, R3, R4), depending on
will not operate in either heating or cooling mode, and all which thermostat is set to “ON” fan. The associated relay
controllers are powered down. contact (R2-1, R3-1, or R4-1) closes to pass 120 VAC to the
blower of the associated air handler. If the thermostat is set
SPACE-HEATING MODE: The mode selection switch for“AUTO”fan, the blower will only run when the thermostat is
(MSS) must be set for heating. This passes 120 VAC to calling for heat. If the thermostat fan switch is set to“ON,”the
the [ZVR103(H)] multi-zone relay center. It also passes blower in the associated air handler will run continuously.
24 VAC from transformer (X1) to the (X X) contacts on The three relay coils (R2, R3, R4) are powered by the
the [ZVR103(H)] controller. 24 VAC is provided from the transformer in the [ZVR103(H)] controller.The common side
[ZVR103(H)] transformer to the (RH) terminals on all three of the 24 VAC circuit through relay coils (R2, R3, R4) passes
thermostats (T1, T2, T3). When any of these thermostats through the mode selection switch (MSS) to the 24 VAC
call for heating, 24 VAC is passed to the (W) terminal of common terminal on the [ZVR103(H)] controller.
the thermostat. The 24 VAC is then passed back to the
thermostat input terminals on the [(ZVR103(H)] controller, COOLING MODE: The mode selection switch (MSS) must
and the associated zone valve (ZVH1, ZVH2, ZVH3) be set for cooling. This passes 120 VAC to the [ZVR103(C)]
is powered on. When the powered zone valves reach multi-zone relay center controller. It also passes 24 VAC from
their fully open position, their internal end switch closes, transformer (X1) to the (X X) contacts on the [ZVR103(C)]
which signals the [ZVR103(H)] to turn on circulator (P3). controller. It also passes 24 VAC from the [ZVR103(C)]
Circulator (P3) is a variable-speed pressure-regulated controller transformer to the (RC) terminals on all three
circulator. It is set to the differential pressure required thermostats (T1,T2,T3). When any of the thermostats call for
when all three heating zones are operating simultaneously. cooling, the associated zone valve (ZVC1, ZVC2, ZVC3) is
Circulator (P3) will automatically adjust its speed as the powered on by the [ZVR103(C)] controller. When the zone
three heating zone valves open and close. The (X X) valves reach their fully open position, their internal end
contact in the [ZVR103(H)] controller also closes when switch closes, which signals the [ZVR103(C)] to turn on
any thermostat calls for heating. This passes 24 VAC from circulator (P4). Circulator (P4) is a variable-speed pressure-
transformer (X1) to the outdoor reset controller (ORC). regulated circulator. It should be set to the differential
The (ORC) measures the current outdoor temperature pressure required when all three cooling zones are
at sensor (S2), and uses this temperature along with its operating simultaneously. Circulator (P4) will automatically
settings to calculate the target water temperature for the adjust its speed as the three cooling zone valves open and
buffer tank, measured at sensor (S1). If the measured close. The (X X) contact in the [ZVR103(C)] controller also
temperature at (S1) is 5ºF or more below the calculated closes when any thermostat calls for cooling.This passes 24
target temperature, the (ORC) closes it contacts, which VAC from transformer (X1) to the setpoint controller (SPC).
completes a circuit between the (R) and (Y) terminals of The (SPC) is set to close its contacts if the temperature at
the heat pump, turning it on in heating mode. The heat sensor (S3) in the buffer tank reaches or exceeds 60ºF. Its
pump passes 120 VAC to circulators (P1) and (P2) to contacts open if the temperature at sensor (S3) drops to or
provide flow through the earth loop, as well as between below 45ºF. A closed contact in (SPC) passes 24 VAC to the
the heat pump and the buffer tank. Provided that a heating coil of relay (R1) and terminal (O) of the heat pump. Relay
call remains active from one or more of the thermostats contact (R1-1) closes to pass 24 VAC from the (R) terminal
(T1, T2, T3), the heat pump continues to operate until of the heat pump to the (Y) terminal of the heat pump. This
the temperature at sensor (S1) is 5ºF above the target turns on the heat pump in cooling mode. The heat pump
temperature, at which point the heat pump turns off, and passes 120 VAC to circulators (P1) and (P2) to provide flow
so do circulators (P1) and (P2). through the earth loop, as well as between the heat pump
and the buffer tank.
AIR HANDLER OPERATION (DURING HEATING MODE):
The air handlers are primarily for cooling. However, they AIR HANDLER OPERATION (DURING COOLING
can be used to circulate air through the building in either MODE): If the mode selection switch is set for cooling,
heating or cooling mode. If the air handlers are operated and the fan switch on any thermostat is set to “ON,” 24 VAC
when the mode selection switch (MSS) is set to heating, is present on the (G) terminal of the thermostat. This 24
there will be no heated or cooled water passing through VAC is passed to the coil of a relay (R2, R3, R4, depending
their coils. In heating mode, they are only for air circulation. on which thermostat has the fan switch set to ON). The
56
associated relay contact (R2-1, R3-1, or R4-1) closes to EXAMPLE SYSTEM #5
pass 120 VAC to the blower of the associated air handler. The system shown in figure 8-5a combines a 2-stage
If the fan switch on the thermostat is set to “AUTO” mode, air-to-water heat pump with an auxiliary mod/con boiler.
the blowers will only run when the associated thermostat It provides zoned space heating through individually
is calling for cooling. If the fan switch on the thermostat controlled panel radiators. It provides cooling through a
is set to “ON,” the blower in the associated air handler will single chilled-water air handler. It also provides domestic
run continuously. The three relay coils (R2, R3, R4) are hot water, using heat from both the heat pump and the
powered by the transformer in the [ZVR103(C)] controller. auxiliary boiler.
The common side of the 24 VAC circuit through relay coils
(R2, R3, R4) passes through the mode selection switch
To protect the heat pump, as well as much of the
(MSS) to the common terminal on the [ZVR103(C)]
remaining portion of the system, from freezing, all space-
controller.
heating and cooling portions of the system operate with
a 30% solution of inhibited propylene glycol antifreeze.
DOMESTIC WATER HEATING MODE: The heat pump This eliminates the need for a heat exchanger between
contains a desuperheater heat exchanger and small the outdoor heat pump and the remainder of the system.
bronze circulator (P5), which runs whenever the heat
pump is operating in either heating or cooling mode.
Figure 8-5b shows the electrical wiring schematic for the
Heat from the hot refrigerant gas leaving the compressor
system.
passes through the desuperheater and transfers heat
to domestic water drawn from the lower portion of the
electric water heater. This water absorbs heat from the DESCRIPTION OF OPERATION
desuperheater and flows back to the dip tube connection SYSTEM POWER: Electrical power to operate the
on the water heater. This provides a portion of the controllers; circulators (P2), (P3), (P4) and (P5); and the
domestic water heating load. The electric element in the auxiliary boiler is provided by a 120 VAC/20-amp dedicated
upper portion of the tank provides supplementary water circuit. Power to operate the air-to-water heat pump and
heating. An anti-scald thermostatic mixing valve (MV1) is circulator (P1) is provided by a 240/120 VAC/40-amp
set to 120ºF to limit the hot water temperature delivered dedicated circuit.
to the plumbing system.
SPACE-HEATING MODE: The main switch (MS) and heat
CONTROLLER/MIXING VALVE SETTINGS: pump disconnect switch (HPDS) must be closed, and the
ZVR103 (H) master/slave = MASTER mode selection switch (MSS) must be set to heat. This
ZVR103 (H) pump exercise = OFF passes 24 VAC to the RH terminal of the master thermostat
(T1). When the master thermostat (T1) calls for heating, 24
ZVR103 (H) priority = OFF
VAC is passed to the (W) terminal of the thermostat, which
ZVR103 (H)Aux on during priority = OFF energizes the coil of relay (RH2). Relay contact (RH2-
1) closes, passing 120 VAC to circulator (P2). Circulator
ZVR103 (C) master/slave = MASTER (P2) is a variable-speed pressure-regulated circulator set
ZVR103 (C) pump exercise = OFF for constant differential pressure mode. It automatically
ZVR103 (C) priority = OFF adjusts speed as the thermostatic radiator valves on the
panel radiators open, close or modulate flow through their
ZVR103 (C) Aux on during priority = OFF
respective panels.
57
towel
warmer
Figure 8-5a radiator air vent
thermostatic radiator valves
air vent
TRV
dual isolation valve
mod/con boiler
2-stage
PEX, or temperature
variable
PEX-AL-PEX tubing setpoint controller
speed (SPH)
circulator (P2)
isolation and
flushing valves
for potable side
of HX
manifold P&T
station
temp. (MV1)
(P3)
(HX1)
DHW
sensor
(S1)
(FS1)
OUTSIDE
INSIDE
diverter (P4)
valve N.C.
A
AB
(DV1)
B
N.O.
(P1) spring-
loaded
check 80 gallon ThermoCon
2 stage valves buffer tank
air-to-water heat pump
(AH1)
single zone
air handler
for
(P5) cooling
(SPC)
(S1)
25 gallon ThermoCon
buffer tank (CWBT)
(P1), and turns on in heating mode. The heat pump’s of DV1). The heat pump and these associated devices
internal controls determine if one or both stages are active. continue to operate as described until sensor (S1) climbs
Diverter valve (DV1) directs the flow of heated antifreeze to 125ºF, or if the master thermostat (T1) stops calling for
solution from the heat pump to the upper header of the heat. Note, the heat pump’s internal controller must be set
buffer tank (e.g., flow passes from the AB port to the A port to a high limit temperature of at least 130ºF.
58
COOLINg MODE: The main switch
Figure 8-5b (MS) and heat pump disconnect switch
240 VAC L1 N
(HPDS) must be closed, and the mode
120 VAC selection switch (MSS) must be set
heat pump L1 L2 N
disconnect main to cool. This passes 24 VAC to the RC
switch switch
(HPDS) (MS) terminal of the master thermostat. If the
master thermostat is set for cooling, and
calls for cooling, 24 VAC is passed to its
(Y) terminal. From the (Y) terminal, 24
(RH2-1)
L (HP) (P2) VAC energizes the coil of relay (RC) and
(P1) N the cooling setpoint controller (SPC). A
Solstice (Rdhw-1) (P4) normally open set of contacts (RC-1)
heat pump close to pass 120 VAC to the air handler
(AH1) turning it and circulator (P5) on.
43 44 5 6
(P5) If the temperature at sensor (S2) in
the chilled-water buffer tank is 60ºF or
(RC-1) (AH1) higher, the contacts in the (SPC) close
(RH1-2 NC)
(MSS)
off off MODE: Whenever there is a demand
for domestic hot water of 0.6 gpm or
RC
more, flow switch (FS1) closes. This
RH (RH2)
W passes 24 VAC to energize the coil
G
(RC) of relay (Rdhw). Contact (Rdhw-1)
Y
closes to pass 120 VAC to circulator
(T1) master
thermostat (SPC) (P4). Heated fluid flows from the upper
(S2) R C portion of the buffer tank through the
sensor
primary side of heat exchanger (HX),
and transfers heat to the cold domestic
water flowing through the secondary
side of the heat exchanger (HX). When
the demand for domestic hot water
If the temperature at sensor (S1) drops to 110ºF, the stage
drops to 0.4 gpm or less, flow switch (FS1) opens. This
2 contacts in the (SPH) controller close. This completes
turns off relay (Rdhw) and circulator (P4). All domestic hot
a circuit across the (T T) terminals in the auxiliary boiler,
water leaving the system passes through a thermostatic
enabling it to turn on circulator (P3) and fire its burner.
mixing valve (MV1) to limit the water temperature to the
The boiler and circulator (P3) remain on until sensor (S1)
distribution system.
reaches a temperature of 130ºF, at which point the boiler
is turned off.
59
When the mode selection switch is set to cooling, the SPH stage 2 contacts close at 110ºF, open at 130ºF
stage 1 contacts of the (SPH) controller do not provide any Heat pump internal high limit (heating mode) = 130ºF
control action. However, the stage 2 contacts of the (SPH) Heat pump internal high limit differential (heat mode) = 10ºF
controller still operate the auxiliary boiler to maintain the
Heat pump internal low limit (cooling mode) = 40ºF
temperature at sensor (S1) in the buffer tank between 110
and 130ºF.This provides heat for domestic water when the Heat pump internal low limit differential (cooling mode) = 15ºF
heat pump is in cooling mode. Thermostat (T1) setting = 70ºF heating, 75ºF cooling
Thermostat (T1) fan setting = ON
CONTROLLER/MIxINg VALVE SETTINgS: TRV initial settings = 3
SPH, stage 1 contacts close at 115ºF, open at 125ºF Mixing valve (MV1) = 115ºF
Figure 8-6a
MV1
spring checks
supply & return
1" piping
AQ1
3/4" piping
baseboard circuits
supply water (P4)
outdoor temperature sensor
temperature (T261)
(P5)
(P6)
sensor
3-speed circulator (S2) (S1)
with check valve (T156)
1.5" copper
(P2)
closely
1" piping spaced
tees
2"size short headers (upper & lower)
(keep tee as close to tank (S4)
as possible)
1" piping
1.5" piping
outdoor
temperature (T256)
sensor (S3)
pellet boiler
(S7) PRV "ON" sensor
press ga. (S5) 2nd tapping
air vent down from top
(P3)
1" piping
(LWCO1) (LWCO2)
swing (OBHL)
check (T150)
(P1)
expansion
tank
make up water
60
120 VAC / 20 amp
Figure 8-6b G L 120 VAC / 20 amp N L2 N G
(MS)
main switch
(PBD)
(LWCO1)
(X1)
PELLET
120/24 VAC, 40 VA
BOILER
(T261)
C1 C2
2-stage reset controller T T
5 6
(R1-1)
boiler demand
1 2
(P1)
setpoint demand
3 4
(S1)
supply sensor 11 12
boiler stage 1
(OBD)
3 4
T2 T3 (S3)
AQ1 (S4)
(P2)
(LWCO2)
2 1
(T156)
∆T controller OIL BOILER
contacts closed if (S3)≥(S4)+5 ºF
contacts open if (S3)≤(S4)+2 ºF C1 C2
T T
5 6 (R1)
temperature
(R1-2)
setpoint controller
(T150)
2 1
3 4 (S6)
contact closed If (S3) ≤ 165 ºF
P5 contact open if (S3) ≥ 175 ºF
P4 P6
61
no longer make a net heat contribution to the distribution off. A portion of the flow can also pass to the load through
system, and will stop any further circulation through the circulator (P2) if it is operating.
thermal storage tank under those conditions.
SPACE-HEATING DELIVERY: If the main switch is closed,
The electrical wiring diagram for this system is shown in 120 VAC is delivered to power up the (T261) controller
figure 8-6b. and the (ZSR103) controller. 24 VAC is provided on the
secondary winding of transformer (X1).
Description of Operation If either space-heating thermostat (T2) or (T3) call for
SYSTEM POWER: The control system and circulators heat, the multi-zone relay center (ZSR103) turns on
(P2, P4, P5, P6) are powered by a 120 VAC/20-amp circuit the associated zone circulators (P5) or (P6). The (X X)
passing through the main switch (MS). The pellet boiler is contacts in the (ZSR103) close to pass 24 VAC to the
powered by a dedicated 120 VAC/20-amp circuit passing boiler demand terminals (1 & 2) of the (T261) 2-stage
through disconnect (PBD). Low water cutoff (LWCO1) must reset controller. The (T261) measures the current outdoor
detect water present for 120 VAC to reach the pellet boiler. temperature at sensor (S2), and calculates a target supply
The oil-fired boiler is power by a dedicated 120VAC/15- water temperature based on the outdoor temperature and
amp dedicated circuit passing through disconnect (OBD). its settings. It then measures the supply water temperature
Low water cutoff (LWCO2) must detect water present for at sensor (S1). If the supply water temperature at sensor
120 VAC to reach the oil boiler. (S1) is slightly below the calculated target temperature,
the stage 1 contacts in the (T261) close. This passes 120
PELLET BOILER OPERATION: The main switch (MS) VAC to the normally open contacts in the (T156) differential
must be closed.The pellet boiler enable switch (SW1) must temperature controller. If the temperature measured at the
also be closed. The pellet boiler disconnect (PBD) must upper tank header sensor (S3) is at least 5ºF above the
be closed, and the low water cutoff (LWCO1) must detect temperature at the return side of the distribution system
water present. 24 VAC is passed from transformer (X1) to measured at sensor (S4), the contacts in the (T156) close to
outdoor reset controller (T256). The (T256) measures the pass 120 VAC to circulator (P2). However, if the temperature
current outdoor temperature at sensor (S7) and calculates at (S3) drops to 2ºF or less above the temperature at
the minimum target temperature in the upper portion of the (S4), the contacts in the (T156) open, turning off circulator
thermal storage tank as measured by sensor (S5). When (P2). This prevents heat derived from the oil boiler from
the temperature at (S5) drops 2ºF below the calculated inadvertently entering the thermal storage tank.
target temperature, the contacts in the (T256) close. This
energizes the coil of relay (R1). Relay contact (R1-1) If the temperature at sensor (S1) does not rise to approach
closes across the external demand terminals of the pellet the calculated target temperature within a short time, the
boiler, enabling it to fire and turn on circulator (P1), which stage 2 contacts in the (T261) close. This completes a
is contained within the loading unit (LU). Relay contact circuit through the (T T) terminals on the oil-fired boiler’s
(R1-2) also closes, providing a second path for 24 VAC to high limit controller. If the oil-fired boiler disconnect (OBD)
reach relay coil (R1). 24 VAC also passes to the temperature is closed, and the low water cutoff (LWCO2) detects water
setpoint controller (T150), which monitors the temperature present, and if the water temperature in the oil boiler is
of sensor (S6) in the lower portion of the thermal storage slightly below 180ºF, the boiler’s high limit controller will
tank. If the temperature at (S6) is below 165ºF, the contacts turn on circulator (P3) and fire the burner. Heated water
in (T150) will be closed, providing an alternate path for 24 from the oil boiler is delivered to the closely spaced tees
VAC to reach relay coil (R1). The contacts in the (T256) in the distribution system. Note: Heat from the upper
will open when the temperature at sensor (S5) climbs to header of the thermal storage tank is still being delivered
2ºF above the calculated minimum target temperature. to the closely spaced tees by circulator (P2), unless
However, because the contacts in (T150) are still closed, 24 the temperature at (S3) drops to within 2ºF above the
VAC continues to power relay coil (R1) through contact (R1- temperature at (S4).
2), and the pellet boiler remains on until the temperature at
lower tank sensor (S6) reaches 175ºF. The pellet boiler is DOMESTIC WATER HEATING MODE: When the
protected against flue gas condensation by a thermostatic temperature at aquastat (AQ1) on the indirect domestic
mixing valve within loading unit (LU). water heater drops below its setpoint, the (ZSR103)
controller turns on circulator (P4), and because domestic
Hot water from the pellet boiler is delivered to the upper water heating is a priority load, it temporarily turns off
tank header, where sensor (S3) is located. This hot water circulators (P5) and (P6) if they are operating. 24 VAC from
passes into the thermal storage tank if circulator (P2) is transformer (X1) passes though the (zone 1/EX) terminals
62
of the (ZSR103) and provides a setpoint demand to the ZSR103 master/slave = master
(T261) controller at terminals (3 & 4). The (T261) targets a ZSR103 priority = ON
fixed (e.g., non-outdoor temperature dependent) supply ZSR103 remote enable = OFF
water temperature at sensor (S1). If the temperature at ZSR103 exercise = ON
sensor (S1) does not rise to approach this temperature ZSR103 post purge on zone 1 = OFF
within a short time, the stage 2 contacts in the (T261)
controller close. This completes a circuit through the (T OBHL = 180ºF
T) terminals on the oil boiler’s high limit controller. If the OBHL differential = 8ºF
oil-fired boiler disconnect (OBD) is closed, and the low MV1 = 115ºF
water cutoff (LWCO2) detects water present, and if the
water temperature in the oil boiler is slightly below 180ºF,
the boiler’s high limit controller will turn on circulator (P3)
and fire the burner. Heated water from the oil-fired boiler
SUMMARY:
is delivered to the closely spaced tees in the distribution
All hydronic heating and cooling systems should be
system, from where it will be routed through the coil of the
properly documented. This helps ensure proper design
indirect water heater by circulator (P4).Thermostatic mixing
and installation, and provides a higher probability that the
valve (MV1) is set to 115ºF to protect against scalding.
system can be serviced over its full service life.
SETTINGS:
T261 terminal unit # = 4 (fin-tube convector) Quality documentation also conveys professionalism and
T261 design water supply temperature (BOIL DSGN) = 170ºF competence to prospective clients.
T261 boiler indoor temperature (BOIL INDR) = 60ºF
T261 outdoor design temperature (OUTDR DSGN) = 0ºF This issue of idronics has addressed several forms of
T261 boiler minimum temperature (BOIL MIN) = 130ºF documentation, with emphasis on piping schematics,
T261 boiler max temperature (BOIL MAX) = 170ºF electrical schematics and description of operation. Other
T261 setpoint demand temperature = 160ºF possible documentation includes a tubing layout plan for
T261 boiler differential = 10ºF radiant panel systems, circulator and valve schedules,
T261 Fire delay of 30 seconds and a heat emitter or chiller water terminal unit placement
T261 advanced/installer DIP Switch = Advanced drawing.
T261 rotate/off DIP switch = OFF
T261 ºC/ºF = ºF
A wide variety of computer-based drawing software
products are available, many at relatively low cost to aid in
T256 terminal unit # = 4 (fin-tube convector)
creating documentation drawings. Word processors and
T226 design water supply temperature = 170ºF
spreadsheets are widely available for creating descriptions
T256 occupied room temperature = 70ºF
of operation and schedules.
T256 outdoor design temperature = 0ºF
T256 boiler minimum target temperature = 100ºF
T256 differential = 4ºF Caleffi offer several tools that can assist designers and
T256 boiler max temperature = 180ºF installers with proper documentation. These include the
T256 warm weather shutdown = 65ºF Caleffi schematic library, Z-one wiring guide, and BIM
T256 ºC/ºF = ºF object files.
63
APPENDIX A1: Caleffi component symbol legend
APPENDIX A: PIPING SYmBOL LEGEND
CALEFFI COMPONENTS
3-way
thermostatic mixing valve
DIRTCAL
dirt
separators
pressure-
distribution
reducing
station
valve
(3/4")
backflow
preventer
HYDROFILL
multi-zone controls
differential
pressure
bypass valve
zone valve
ThermoCon buffer tank
(2 way)
zone valve
single zone control (3 way)
thermoelectric
zone valve
(2 way)
Hydro
Separator
Hydro
Separator
variable orifice motorized
balancing ball valve
valve (2 way)
Hydro
Separator
FLOWCAL motorized
balancing ball valve
valve (3 way)
FLOWCAL
balancing
valve
solar
thermostatic
circulation
radiator valve
station
fixed orifice
balancing
valve thermostatic
radiator valve
dual isolation
SEP4 valve for
SEP4
QuickSetter panel radiators
SEP4
balancing
valve w/
high-temperature
flowmeter
solar 3-way thermostatic
high-temperature mixing valve
solar DISCAL
air separators
HydroBlock isolar
mixing units
differential
high-temperature temperature
boiler
protection solar pressure controller
valve
relief valve
high-temperature
solar air vent
high-
ThermoBlock temperature
solar
high-temperature
expansion
shut-off valve for
tank
solar air vent
Hydrolink (4 configurations)
symbols are in Visio library @ www.caleffi.com
64 81
APPENDIX A2: Generic component symbol legend
APPENDIX A: PIPING SYmBOL LEGEND
GENERIC COMPONENTS
3-way motorized
circulator mixing valve
blower compressor
filter
circulator w/ 4-way motorized
mixing valve
coil reversing!
valve
union
evaporator
circulator w/
internal check valve
evaporator
condenser
swing check valve comp. RV
TXV
spring-loaded
gate valve check valve water-to-air
TXV
heat pump
(in heating mode) water-to-water
globe valves purging valve heat pump
(in heating mode)
ball valve blower
pressure gauge
filter
compressor
primary/secondary
fitting
pressure coil
relief
valve
reversing!
condenser
hose bib valve
drain valve pressure &
temperature comp.
TXV RV
relief valve
condenser
evaporator
diverter tee
water-to-air
cap metered
balancing heat pump
valve (in cooling mode)
TXV
water-to-water
heat pump
diaphragm-type (in cooling mode)
brazed-
expansion tank
plate
heat
exchanger
panel radiator
with dual
isolation valve Modulating tankless water heater
Comp.
reversible
heating mode
water-to-water
heat pump
condenser
TXV
solar collector
Modulating / condensing boiler
indirect water heater (with trim) solar water tank (with electric element)
80
65
APPENDIx B: Suggested symbol legend for common electrical components
normally-open
relay contact Single Pole
circulator
pole pole
Single Throw 1 1
SPST
normally-closed
relay contact
2-wire
pole pole
zone valve Double Pole
Single Throw
1 1
relay coil
pole pole
M 2 1
DPST
heating pole
1
pole
1
thermostat Triple Pole pole pole
Single Throw 2 2
pole pole
3-wire 3PST 3 3
3-wire electronic
heating thermostat 4-wire pole
Double Pole pole 1
zone valve Double Throw 1
end switch M pole
DPDT 2
pole
R W C
2
motor
pole
pole 1
1
Triple Pole
flow switch Double Throw pole
2
pole
3PDT 3
pole pole
2 3
66
APPENDIX C: Symbols legend for ZSR & ZVR electrical relay boxes
ZONE 1
AUX X X
R W C R W C R W C R W C R W C R W C D P
E/S T T COM T T COM T T COM T T COM T T COM T T COM COMMS
T-STAT 1 T-STAT 2 T-STAT 3 T-STAT 4 T-STAT 5 T-STAT 6
POWER
ZONE 1
MASTER SLAVE
PUMP EXERCISE ON OFF ZONE 2
PRIORITY ON OFF
ZONE 3
AUX ON OFF
ZONE 5
ZVR106 ZONE 6
6 Zone
T-SAT VALVE
STATUS DURING
ZONE #1 DEMAND
CALL OPEN
OFF
OFF
ON
ON
ZONE 1 R W C R W C R W C R W C R W C R W C D P
AUX X X E/S T T COM T T COM T T COM T T COM T T COM T T COM COMMS
T-STAT 1 T-STAT 2 T-STAT 3 T-STAT 4 T-STAT 5 T-STAT 6
POWER
MASTER SLAVE
ZONE1
PRIORITY ON OFF
REMOTE ENABLE ON OFF
ZONE2
EXERCISE ON OFF
POST PURGE ZONE#1 ON OFF
ZONE3
TRANSFORMER
ZSR106 ZONE4
6 Zone
ZONE5
ZONE6
R W C
T T COM
PWR
67
10 Years of Educational Excellence
www.caleffi.com
Milwaukee, WI USA