GLICERIA M.

PEREZ, MASEP
Structural Engineer

NAME OF PROJECT PROPOSED RETROFITTING OF TWO-STOREY WAREHOUSE


DESIGNED BY DATE
SHEET NO. 1
CHECKED BY DATE
BEAM-TO-BEAM/COLUMN-TO-COLUMN

BEAM ID SB-1 SECTION W 14x43

1.0 SECTION PROPERTIES 4.0 BEAM ANALYSIS


DEPTH, d 346.96 mm Fy 248.00 MPa
tw 7.75 mm E 200,000.00 GPa
BASE, bf 203.07 mm 4.1 FLEXURAL STRESS
tf 13.46 mm fb = M
Sx 1027.00 x10³ mm³ Sx
Ix 178.00 x10⁶ mm⁴ fb = 139.99 MPa
W 64.00 kg/m Fb = 0.60Fy
Fb = 149.00 MPa
2.0 DESIGN LOADS PASSED!

wt
4.2 SHEAR
fv = V
L A SHEAR
A B V= w tL
(UDL)
2
2.1 DEAD LOADS AT FLOOR, DL fv = 35.64 MPa
SLAB t = 0.125 m 3.00 kPa Fv = 0.4Fy
FLOOR TOPPING 1.20 kPa Fv = 99.20 MPa
CEILING 0.24 kPa PASSED!
∑DL = 4.44 kPa
4.3 DEFLECTION
2.2 LIVE LOADS, LL 6.00 kPa y all = L
(Floor Beam, DL+LL)
240
3.0 LOAD AND MOMENT CALCULATION yall = 25.00 mm
TRIBUTARY WIDTH 3.00 m y act = 5w t L ⁴
BEAM LENGTH, L 6.00 m 384EI
yact = 15.14 mm
w LL+DL = (DL + LL) (TRIBUTARY WIDTH) PASSED!
wLL+DL = 31.32 kN/m
wb = 0.63 kN/m
wt = 31.95 kN/m
M = w uL ²
(UDL)
8
M= 143.77 kN-m
GLICERIA M. PEREZ, MASEP
Structural Engineer

NAME OF PROJECT PROPOSED RETROFITTING OF TWO-STOREY WAREHOUSE


DESIGNED BY DATE
SHEET NO. 2
CHECKED BY DATE
BEAM-TO-BEAM/COLUMN-TO-COLUMN

BEAM ID SB-2 SECTION W 14x26

1.0 SECTION PROPERTIES 4.0 BEAM ANALYSIS


DEPTH, d 353.31 mm Fy 248.00 MPa
tw 6.48 mm E 200,000.00 GPa
BASE, bf 127.64 mm 4.1 FLEXURAL STRESS
tf 10.67 mm fb = M
Sx 578.00 x10³ mm³ Sx
Ix 102.00 x10⁶ mm⁴ fb = 246.82 MPa
W 39.00 kg/m Fb = 0.60Fy
Fb = 149.00 MPa
2.0 DESIGN LOADS FAILED!

wt
4.2 SHEAR
fv = V
L A SHEAR
A B V= w tL
(UDL)
2
2.1 DEAD LOADS AT FLOOR, DL fv = 41.54 MPa
SLAB t = 0.125 m 3.00 kPa Fv = 0.4Fy
FLOOR TOPPING 1.20 kPa Fv = 99.20 MPa
CEILING 0.24 kPa PASSED!
∑DL = 4.44 kPa
4.3 DEFLECTION
2.2 LIVE LOADS, LL 6.00 kPa y all = L
(Floor Beam, DL+LL)
240
3.0 LOAD AND MOMENT CALCULATION yall = 25.00 mm
TRIBUTARY WIDTH 3.00 m y act = 5w t L ⁴
BEAM LENGTH, L 6.00 m 384EI
yact = 26.22 mm
w LL+DL = (DL + LL) (TRIBUTARY WIDTH) FAILED!
wLL+DL = 31.32 kN/m
wb = 0.38 kN/m RETROFIT BEAM!
wt = 31.70 kN/m
M = w uL ²
(UDL)
8
M= 142.66 kN-m
GLICERIA M. PEREZ, MASEP
Structural Engineer

NAME OF PROJECT PROPOSED RETROFITTING OF TWO-STOREY WAREHOUSE


DESIGNED BY DATE
SHEET NO. 3
CHECKED BY DATE
BEAM-TO-BEAM/COLUMN-TO-COLUMN

BEAM ID SB-2 SECTION W 14x26

1.0 RETROFITTED SECTION PROPERTIES 2.0 LOAD AND MOMENT CALCULATION


wLL+DL = 31.32 kN/m
wb = 0.54 kN/m
wt = 31.86 kN/m

M= 143.35 kN-m

3.0 BEAM ANALYSIS


3.1 FLEXURAL STRESS
Fb = 149.00 MPa
fb t,c = M c t,c
1.1 PLATE PROPERTIES Ix
THICKNESS 10.00 mm fbt = 129.83 MPa
WIDTH 200.00 mm PASSED!
W 78.50 kg/m² fbc = 177.97 MPa
1.2 BUILT-UP SECTION PROPERTIES FAILED!
SECTION AREA, A (mm²) yb
W 14X26 4875.00 186.66 3.2 SHEAR
PLATE AT THE WEB (2 SETS) 2000.00 186.66 Fv = 99.20 MPa
PLATE AT THE FLANGE (1 SET) 2000.00 5.00 fv = VQ
TOTAL AREA, AT 10875.00 Ixb
yb = distance from centroid to the bottom of the built-up section Q = static moment of area above or below N.A.
LOCATION OF N.A. FROM THE FARTHEST TENSION FIBER, ct fv = 12.49 MPa
A T c t = ∑A(y b ) PASSED!
ct = 153.25 mm
LOCATION OF N.A. FROM THE FARTHEST COMPRESSION FIBER, cc 3.3 DEFLECTION
cc = 210.06 mm yall = 25.00 mm
SECTION Ix (x10⁶ mm⁴) d² (mm²) yact = 15.89 mm
W 14X26 102.00 1116.08 PASSED!
PLATE AT THE WEB (2 SETS) 6.67 1116.08
PLATE AT THE FLANGE (1 SET) 0.02 21977.23
TOTAL Ix 115.35
d = distance from centroid to the N.A. of the built-up section
= yb - ct
Ix = ∑I + ∑Ad²
Ix = 169.21 x10⁶ mm⁴