DC Power System
Product Description
ZTE CORPORATION
No. 55, Hi-tech Road South, ShenZhen, P.R.China
Postcode: 518057
Tel: +86-755-26771900
Fax: +86-755-26770801
URL: http://support.zte.com.cn
E-mail: support@zte.com.cn
LEGAL INFORMATION
Copyright © 2014 ZTE CORPORATION.
The contents of this document are protected by copyright laws and international treaties. Any reproduction or
distribution of this document or any portion of this document, in any form by any means, without the prior written
consent of ZTE CORPORATION is prohibited. Additionally, the contents of this document are protected by
contractual confidentiality obligations.
All company, brand and product names are trade or service marks, or registered trade or service marks, of ZTE
CORPORATION or of their respective owners.
This document is provided “as is”, and all express, implied, or statutory warranties, representations or conditions
are disclaimed, including without limitation any implied warranty of merchantability, fitness for a particular purpose,
title or non-infringement. ZTE CORPORATION and its licensors shall not be liable for damages resulting from the
use of or reliance on the information contained herein.
ZTE CORPORATION or its licensors may have current or pending intellectual property rights or applications
covering the subject matter of this document. Except as expressly provided in any written license between ZTE
CORPORATION and its licensee, the user of this document shall not acquire any license to the subject matter
herein.
ZTE CORPORATION reserves the right to upgrade or make technical change to this product without further notice.
Users may visit the ZTE technical support website http://support.zte.com.cn to inquire for related information.
The ultimate right to interpret this product resides in ZTE CORPORATION.
Revision History
II
Intended Audience
This manual is intended for:
l Planning engineers
l Maintenance engineers
Chapter/Appendix Summary
3, ZXD1500 (V4.0) Rectifier Describes the input features, output features, over-temperature
Specifications protection and fan speed control of the ZXD1500 (V4.0) rectifier.
A, Alarm List Describes the alarm name, and the default alarm level and
output relays.
B, Electrical Connection Diagram Provides the electrical connection diagram of the ZXDU58
B121 (V2.0R01M05).
Typeface Meaning
II
• Unit: mm
1-1
Item Description
1-2
Item Description
1-3
Safety Standards
The ZXDU58 B121 (V2.0R01M05) system is in compliance with the IEC/UL/EN 60950
safety standards.
Other Standards
The ZXDU58 B121 (V2.0R01M05) system is also in compliance with the following
standards:
l The Restriction of Hazardous Substances (RoHS) directive (2002/95/EC) of the
European Union.
l This device complies with Part 15 of the FCC Rules. Operation is subject to the
following two conditions: (1) This device may not cause harmful interference. (2)
This device must accept any interference received, including interference that may
cause undesired operations.
1-4
2-1
1 AC/DC distribution unit Provide AC and DC power distribution. For the further
details, refer to 2.2 AC/DC Distribution Components.
2 Centralized Supervision Unit Collects the power device operation data and manages
(CSU) the power device. For the further details, refer to 2.4
Centralized Supervision Unit.
3 ZXD1500 (V4.0) rectifiers Converts AC power to DC power. For the further details,
refer to 2.3 ZXD1500 Rectifier.
AC Output - -
2-2
AC SPD AC surge protection Provides surge protection for the AC input power.
device
Battery Input Battery input circuit Controls the connection and disconnection of a
breakers battery circuit.
Appearance
For the appearance of a ZXD1500 (V4.0) rectifier, see Figure 2-3.
2-3
Indicators
The indicators indicate the working state of the rectifier. For a description of the status of
these indicators, refer to Table 2-3.
CL Current limit Lit (yellow) Current limit has occurred (the rectifier output
current has reached the current limit).
Note:
When the rectifier is in sleep mode, only the IN indicator is lit.
2-4
27 AC input N Neutral
28 AC input L Live
Functions
l Collects the operational data and monitors the operation of the system.
l Provides alarm and necessary protection if the system is operating abnormally.
2-5
l Sends data to the background Supervision Center (SC) and receives the commands
from the SC. In this way, the system can be monitored remotely.
Structure
For the CSU structure, see Figure 2-5.
Indicators
The indicators indicate the current operational status of the CSU. For a description of the
CSU indicators, refer to Table 2-5.
Buttons
l The RST button is used to restart the CSU.
l Users can perform querying and setting operations through the buttons laid on the
front panel of the CSU. For the function description of the buttons, refer to Table 2-6.
Button Function
2-6
Button Function
Interface Description
2-7
Interface Description
Communication Interfaces
X13 Input relay 1 and 2 The four input relays can be customized by the user for alarm
input.
X14 Input relay 3 and 4
The default alarm status of the input relays in the CSU are
“close”.
X15 Output relay for CSU This output relay is reserved for CSU fault.
fault
X16 Output relay 1 l The output relays 1 to 5 correspond to the software codes
A1 to A5 in the CSU.
X17 Output relay 2
l For the default output relays for the alarms, refer to the
X18 Output relay 3
Alarm List.
X19 Output relay 4 l Users can customize these output relays for alarm output.
2-8
≤ 80 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.
≥ 300 V The post-DC/DC conversion circuit and the pre-PFC circuit stop working.
3-1
3-2
The radiator temperature may keep increasing when the fan is faulty or it is working at
full speed. Therefore, a negative temperature coefficient thermistor is used to prevent the
rectifier from being damaged due to over-temperature. The over-temperature protection
is as follows:
l When the temperature exceeds the temperature protection threshold, the post-DC/DC
conversion circuit stops working.
l When the temperature is below the temperature protection threshold, the post-DC/DC
conversion circuit starts to work.
3-3
3-4
AC Related
4 AC Power Off Major A2 The mains supply is cut off and there is no
standby AC input available.
9 AC Current Over Minor A2 The AC input current is higher than the preset
maximum AC current.
SMR Related
A-1
16 Bat Under-Vol Major A4 The battery voltage is lower than BatVol Min.
18 1st Shut-down Major A4 When the battery voltage is lower than 1-Shut
Vol., the secondary loads are shut down.
19 2nd Shut-down Major A4 When the battery voltage is lower than 2-Shut
Vol., all the loads are shut down.
Environmental Related
A-2
33 Door Magnet Alm Minor A5 The door with door magnet switch is opened.
A-3
A-4
B-1
MTBF
- Mean Time Between Failures
PC
- Personal Computer
PE
- Protective Earth
PFC
- Power Factor Correction
RoHS
- Restriction of Hazardous Substances
SIB
- Signal Interface Board
SPD
- Surge Protection Device