Вы находитесь на странице: 1из 3

SUPERMARKET – MEP REQUIREMENTS (AJMAN)

1) Area - 1265 m² + 1000m² (Future).


2) Fire Water Tank Capacity - 300x 30 min = 35m³.
3) Pump Capacity - 300 GPM @ 4.5 bar.
4) Pump Room size - 8 x 6 x 3m height.
5) Potable Water - 2265m² x 1 gal = 2265 Gallons.
6) Water Tank Capacity - 35 + 11 = 46 m³.
7) Water Tank Size - 2.5 x 8 x 2.7 water level + 0.3m free board.
8) Holding Tank Capacity - 11 x 0.8 x 7 = 62m³.
9) Holding Tank Size - 4.5 x 5 x 3m depth.
(3m - Water Level)).

For Fire Fighting Sprinkler and Hose reel are required.

Electrical:

1) Transformer Capacity - 400 KW, 500 KVA.


2) Transformer Room - 6 x 5 m².
3) LV Room - 3.5 x 5 m².
4) Telephone - 3 x 4 m².
SUPERMARKET – MEP REQUIREMENTS (FUJAIRAH)

1) Built Area - 3788 m².


2) Plot Area - 6426 m²
3) Pump Capacity - 1500GPM x 60 min @ 11 bar.
4) Fire Water Tank Capacity - 341 m³.
5) Potable Water - 18 m³.
6) Total Tank Capacity - 341 + 18 = 359 m³.
7) Tank Size - 14.1m x 8m x 3.2m + 0.3m free board
8) Pump Room size - 10m x 8m x 3.5m depth.
9) Drainage Holding Tank Capacity - 100m³.
10) Drainage Holding Tank size - 6.75m x 5m x 3m depth.
(3m –Water level)

For Fire Fighting Sprinkler, Fire Hose reel, Wet riser, Landing Valve and Fire Hydrant are
required.

Electrical:

1) Transformer Capacity - 800 KW, 1000 KVA.


2) Transformer Room - 6 x 5 m².
3) LV Room - 3.5 x 5 m².
4) Telephone - 3 x 4 m².
SUPERMARKET – MEP REQUIREMENTS (Umm Al Quwain)

1) Built Area - 2273 m². + 1000m² = 3273 m².


2) Future - 1000 m²
3) Plot Area - 32,000 m²
4) Pump Capacity - 1000GPM x 60 min
5) Fire Tank Capacity - 228 m³.
6) Potable Water - 15 m³.
7) Total Tank Volume - 228 + 15 = 243 m³
8) Tank Size - 14.1m x 8m x 3.3m depth + 0.3m free board.
9) Pump Room size - 10m x 8m x 3.5m.
10) Drainage Holding Tank Capacity - 15 m³ x 0.8m x 7m = 84 m³
For 7 days
11) Holding Tank Size - 5.6m x 5m x 3m depth.
(3m water level)

For Fire Fighting - Sprinkler, Fire Hose reel, Wet riser, and Landing Valve are required.

Electrical:

1) Transformer Capacity - 400 KW, 500 KVA.


2) Transformer Room - 6 x 5 m².
3) LV Room - 3.5 x 5 m².
4) Telephone - 3 x 4 m².